Liebert LIQUI-TECT LT300, LIQUI-TECT LT410 Specifications

Product Specification Sheet page 1 11/02 (Rev. 0)
LIQUI-TECT® 410
Point Leak Detection Sensor
Description
The Liqui-tect 410 (LT410) provides a single-point detection of leaks. The point detection sensor has two gold-plated sensing probes to prevent corrosion resistance and to provide accurate readings. The LT410 constantly monitors points for leaks, internal faults and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building management system or external equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:
Placement on Subfloor
Under Cooling Support Equipment
Specifications
Dimensions-Top, Front & Side Views
Wiring Interconnections
Ordering Information
Applications Locations
• Glycol, Chilled Water Cooling
• Humidification Feed Water Piping
• Condensate Pumps and Drains
• Unit and Ceiling Auxiliary Drip Pans
• Overhead Piping Troughs
• Large-Scale Network Control Centers
• Data Centers
• Server Rooms - Closets
• Unattended Remote Shelters
• Mechanical Equipment Rooms
• Sensitive Areas With Overhead Piping
• Industrial Process Control Rooms
* Output connections to external alarm monitoring panels
such as the Liebert contact closure alarm panels
Leak detection zone (directly beneath unit)
To a Liebert
environmental
unit and
an optional*
monitoring
panel
To e x tern al power supply or directly from unit
LT4 10
Liqui-tect 410 Sensor
Power requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.) Dimensions
W x D x H
6.35" x 2.25" x 4.46"
(161.2 mm x 57.2 mm x 113.2 mm) Weight (assembled) 2.0 lbs (0.9 kg) Metal enclosure NEMA 1, IP 30
Environmental Conditions
Operating temperature 50°F to 104°F (10°C to 40°C)
Operating humidity
10% to 95% relative humidity
(non-condensing) Operating altitude 0 to 10,000 ft (0 to 3,048 m)
Output Relays
Contact rating 2 Form-C; 3 A rating at 24 VAC
Agency Listings
UL UL916 C-UL C22.2, No. 205-M1983 CE Yes FCC Compliance 47 CFR, Part 15
Red Wires Orange Wires Yellow Wires
24 V, AC/DC
@0.10A, 50-60 Hz, DC
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Product Number
Quantity Description
LT410 Point Leak Detection Sensor
5.85"
(148.5mm)
TOP VIEW
Form-C relay outputs & power wiring connection
4.46"
(113.2mm)
FRONT VIEW
Adjustable probe height
0.0–0.5" (0.0–12.7mm)
2.25"
(57.2mm)
SIDE VIEW
6.35"
(161.2mm)
Shipping weight: 2 Ibs (0.9 kg) Mounting holes: #8 screws
Power
Power
1-NO
1-NC
1-COM
2-NO
2-NC
2-COM
Gold-plated probes
Height adjustable 0-0.5" (0-12.7mm)
Product Specification Sheet page 2 11/02 (Rev. 0)
Power Wiring
The LT410 is rated for 24 VAC, 50/60 Hz and
0.10 amp.
Figure 1 24V from Liebert environmental units to LT410
Figure 2 24V from transformer to LT410
Wiring to Auxiliary Alarm Panels
The LT410 has two Form-C dry contact alarm out­put contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp.
Figure 3 LT410 to Liebert environmental units
Figure 4 LT410 to Liebert contact monitor panel
Power Wiring
24V from Liebert Environmental Unit to LT460
Liebert Deluxe Sys/3, Challenger, Himod or MM2 (8 Ton)
TB1
T5
(24V)
G5
(Ground)
LT460
TB1
TB1-1
TB1-2
LT460
24V from Transformer to LT460
Liebert MM2 (1 to 5 Ton) LT460
TB1
TB1-1
TB1-2
4
V transformer of ere are no
ted terminal
t
ions)
(24V)
(Ground)
From 24V
transformer*
Red
Red
Red wires
Liebert Mini-Mate2
(1 to 5 ton)
LT410
* Requires a 24V external transformer (there are
no designated terminal connections on the unit)
Liebert Deluxe Sys/3, Challenger, Himod or MM2 (8 Ton)
TB1
T5
(24V)
G5
(Ground)
LT460
TB1
TB1-1
TB1-2
Transformer
LT460
TB1
TB1-1
TB1-2
From 24V transformer
24V from Transformer to LT460
Liebert MM2 (1 to 5 Ton) LT460
TB1
TB1-1
TB1-2
V transformer of ere are no
ted terminal
t
ions)
(24V)
(Ground)
T5 (24V)
Red
Red
G5 (Ground)
Red wiresTB1
Liebert Deluxe System/3,
Challenger, Himod or
Mini-Mate2 (8 ton) LT410
Location of T5 (24V) connection on main controller board of Liebert unit
Transformer
LT460
TB1
TB1-1
TB1-2
From 24V transformer
24V from Transformer to LT460
From 24V
transformer
Red
Red
Red wires
Transformer LT410
LT460 to Liebert Environme ntal Unit
Liebert Deluxe Sys/3, Challenger, Himod or MM2 (8 Ton)
24
(24V)
51
LT460
TB2
TB2-2
(C)
TB2-1
(N.O.)
TB2-3
(N.C.)
Env. Unit
Liebert MM2 (1 to 5 Ton)
TB1-1
(24V)
TB1-2
LT460
TB2
TB2-2
(C)
TB2-1
(N.O.)
TB2-3
(N.C.)
Env. Unit
OR
1-NC
Orange wires
Liebert Deluxe System/3,
Challenger, Himod or
Mini-Mate2 (8 ton)
LT410
Orange wires
Liebert Mini-Mate2
(1 to 5 ton)
LT410
1-COM
1-NO
1-NC
1-COM
1-NO
Environmental
unit
Environmental
unit
24 (24V)
51, 55 or 56
TB1-1 (24V)
TB1-2 or TB1-3
TB2
TB2-2
(C)
TB2-1
(N.O.)
TB2-3
(N.C.)
LT460
Liebert Contact Monitor Panel
Input
Contact
(N.O.)
Alarm P anel
2-NC
2-COM
2-NO
Yellow wires
LT4 10
Alarm panel
Liebert contact monitor
panel
Input
contact
(N.O.)
Loading...