As with all types of electrical equipment, dangerous voltages exist within the equipment
where the Liebert Distribution Monitor (LDM) is installed. For maximum safety, ensure
power is removed and circuit breakers/disconnects are tagged/locked out per all applicable
national, state and local electrical codes prior to working inside equipment.
The area around the equipment must be free of any debris or standing water.
All power and control wiring must be installed by a qualified electrician in accordance with
the NEC and all applicable national, state and local codes.
ONLY qualified service personnel should perform maintenance and/or service on the Liebert
LDM. When performing maintenance and/or service on any component, verify test equipment
is insulated and has been inspected prior to use.
To avoid damage to the circuit boards, personnel handling these components should be
wearing an Electrostatic Discharge strap or other approved protective device.
When replacing or installing a solid core Current Transformer (CT), power must be removed
from equipment to prevent damage to the CT and/or circuit board. If the CT is a split-core
design, follow proper electrical safety procedures.
These safety precautions are to be used in conjunction with NEC and local/state electrical
code.
1
1.0GLOSSARYOF ABBREVIATIONS
The following abbreviations are used in this manual.
BCBBranch Circuit Monitoring Control Board
BCMSBranch Circuit Monitoring System
BMSBuilding Management System
BSMBCMS Sensor Module
DSPDigital Signal Processor
GUIGraphical User Interface
IGMInformation Gathering Module
LDMLiebert Distribution Monitor
LIBLarge Interface Board
OCWCOpenComms Web Card
PBVIPanelboard Voltage Current
PCDPower Conditioning Device
PDUPower Distribution Unit
STPService Terminal Protocol
Glossary of Abbreviations
2
2.0PRODUCT OVERVIEW
The Liebert Distribution Monitor (LDM) monitors the main panelboard circuit breaker and individual
panelboard branch circuit breakers. The measurements are used to report the current and alarm conditions for each breaker. The Liebert LDM utilizes branch circuit sensor modules and individual current transformers (CT) to monitor current. In addition, the Liebert LDM monitors options like
subfeed and output circuit breakers and provides a full array of power parameters and alarms.
The Liebert LDM is available as an option for the Liebert PPC™ Precision Power Center, Liebert
FDC™, Liebert FPC™ and Liebert RDC™ Remote Distribution Cabinet.
Product Overview
The Liebert LDM system can communicate with a Building Management System (BMS) and Liebert
SiteScan
®
Web.
The Liebert LDM consists of a control board, panelboard voltage and current board, power supply
boards and sensor modules and can monitor two 42-pole panelboards and three subfeed breakers.
The Liebert LDM is capable of receiving input from 21-pole current sensor modules; two sensor modules are required to monitor one 42-pole panelboard. The sensor module (BSM) contains twenty-one
50A current transformers (CTs) capsulated in an epoxy-filled plastic enclosure designed to be
mounted next to the panelboard. Sensor modules are designed to work with Square D™ and GE panelboards. If a sensor module CT fails, connections are provided for up to six replacement CTs. The
optional CTs can be attached directly to the load cable feeding the failed CT.
For branch breakers larger than 50A, discrete 100A rated large branch current transformers can be
added. Higher-rated CTs can be used for monitoring optional subfeed circuit breakers. For subfeed
breakers, like main panelboard breakers, the Liebert LDM monitors not only the 3-phase current but
also the ground and neutral current. These subfeed circuit breakers are in addition to the 42 panelboard circuit breakers that can be monitored through the BSM. The Liebert LDM can accommodate
18 individual large current transformers.
If your Liebert power center is supplied with a Square D I-Line
®
panelboard, the Liebert LDM can
also monitor it as well as its output breakers. A large interface board (LIB) replaces the panelboard
voltage and current board and can monitor up to 42 poles. Each LIB can monitor eight 5-wire I-Line
and/or subfeed breakers including ground and neutral current. There can be 1 or 2 LIBs per control
board that can monitor a total of sixteen 5-wire I-Line and/or subfeed breakers.
The Liebert LDM has a Modbus port on the BCB for direct communication with a building management system (BMS). The Liebert LDM can communicate with Liebert SiteScan by using a Liebert
SiteLink™ communication device. A Liebert SiteLink-2E™ is available as an option with the Liebert
LDM and is mounted in the power center. Modbus Registry Summary documentation can be found at:
Click on the link for the Liebert Distribution Monitor (LDM Toolkit). Save the file to a desktop or laptop computer (PC) and extract the contents.
3
3.0MAJOR COMPONENTS
3.1Branch Circuit Monitoring Control Board (BCB)
The BCB is the main processing and storage circuit board of the Liebert LDM. It is a DSP-based logic
controller with internal flash memory and non-volatile memory. The BCB also includes a batterybacked real time clock.
Major Components
One of the power parameters, kilowatt-hours (kWh)
board mains, subfeeds and each branch circuit breaker. A Modbus command is provided to reset all
accumulated power usage.
, data is accumulated on this board for the panel-
4
3.2Panel Board Voltage-Current Board (PBVI)
The PBVI board monitors two panelboards and provides the voltage attenuators for the two panelboard voltages. The two sets of panelboard main breaker CTs are connected to the PBVI board.
Connections for the 18 large branch CTs are located on the PBVI board. The nine CTs on the A side of
the board are normally associated with the A-side voltages for power calculations. The B-side CTs are
normally associated with the B-side voltages. A cross-configuration tool allows changing that association for subfeeds.
Major Components
The 18 large branch CT inputs can also be used to monitor up to three subfeed circuit breakers. This
is configured using the Configuration tool (see 5.5 - Using the Configuration Tool). The CTs from
the B side of the PBVI are cross-configured to the A side so that the three sub-feeds appear within the
A-side panelboard register space. The 18 large branch breakers require CTs with 1A secondary.
WARNING
!
Before connecting a large CT to the PBVI board, note the CT MUST have 1A secondary.
Connecting a 5A secondary type CT will damage the board and the CT.
To ensure the proper current ratio and accuracy, the CTs should be purchased through
Emerson Network Power. See Table 1 for details. Contact your local Emerson Network
Power representative or call Liebert Services at 1-800-LIEBERT (1-800-543-2378).
528461G13-L1 pole 0-100A Branch Breaker CT Kit 100:1——
528415G14-L2 pole 0-100A Branch Breaker CT Kit 100:1——
528415G15-L3 pole 0-100A Branch Breaker CT Kit 100:1——
5
3.3Large Interface Board (LIB)
The LIB provides the voltage attenuators for Square D I-Line panelboard
voltages. The LIB monitors the current for the I-Line panelboard. The
panelboard input CTs are connected to the LIB board. There are 42 CT
inputs provided. The current inputs require the use of 1A secondary CT.
WARNING
!
Before connecting a large CT to the PBVI board, note the CT
MUST have 1A secondary. Connecting a 5A secondary type CT
will damage the board and the CT.
To ensure the proper current ratio and accuracy, the CTs should
be purchased through Emerson Network Power. See Table 1 for
details. Contact your local Emerson Network Power
representative or call Liebert Services at 1-800-LIEBERT
(1-800-543-2378).
There can be up to two LIB boards per control board for a maximum total of sixteen 5-wire output
breakers.
3.4Branch Circuit Monitoring Sensor Module (BSM)
The BSM—more commonly referred to as the CT Module—is packaged in an epoxy-filled plastic
assembly. There are two designs: one for 1" center-to-center GE panelboards and one for 3/4" centerto-center for Square D panelboards. Each contains twenty-one 50A CTs that are rated up to 50A RMS
50/60 Hz.
Major Components
NOTE
The diameter of each CT hole is 0.354" (9mm). Wire diameter and thickness of insulation
cannot be larger than the CT opening.
For the 42-breaker position in-line panel boards, the Square D CT Module is designed to interlock end
to end to maintain alignment between the breaker poles and the CT Module.
3.5Power Supply Assembly (with EMI Filter)
The power supply assembly is 120-240VAC (range +6, -13%) 50/60 Hz input, 24VDC output to provide
logic level power for the BCB.
6
4.0INSTALLATION
WARNING
!
Dangerous voltages exist in power distribution units and power conditioning units. To ensure
maximum safety, all circuits breakers in the panelboard should be removed of power and the
input feeder breaker should be turned off and locked-out in accordance with NEC and local/
state code.
NOTE
Installation of Liebert LDM components or other monitoring devices should be performed by
qualified personnel only.
This section provides instructions for installing and connecting Liebert LDM current transformers. If
service needs to be performed on any Liebert LDM component, contact Emerson Network Power Liebert Services at 1-800-LIEBERT (1-800-543-2378) for assistance.
4.1Installing a BSM (CT Module Assembly)
In most cases the BSM—the CT Module—is factory-installed and no further work is required. If you
need to add a CT Module, it attaches easily to the side of a panelboard to monitor any combination of
1-, 2- and 3-pole circuit breakers.
• For side-by-side panelboards (21 circuits on each side), attach one
CT Module to each side of the panelboard, ensuring that the center of
the CT hole lines up to the branch circuit breaker connection.
• For SqD Inline panelboards (42 circuits in a row), the two CT Modules must be interlocked to monitor 42 inline circuits. Flip the second,
lower CT Module so that the two cutout sections line up, then attach
the screws to secure the CT Modules to the panelboard.
• For GE Inline type panelboards, the two CT Modules fit end to end.
Flip the second, lower CT Module so that the 50-pin ribbon cable connector, mounted on the bottom of the CT Module, lines up with the hole
in the panelboard mounting bracket.
Installation
Install the circuit breakers according to the manufacturer’s documentation.
Route the circuit wire through the center of the CT and attach securely to
the circuit breaker.
4.1.1Connecting Panelboards A and B
The CT Module connects to the BCB via a 50-pin ribbon cable
attached to the back of the CT Module. Route the ribbon cable
and attach to the appropriate connector (see figure at right).
There are four connectors that are labeled for easy identification:
two for Panelboard A (A1 and A2) and two for Panelboard B
(B1 and B2).
• Connect the CT module that will monitor Circuits 1-21 to the
A1 or B1 connector, depending on whether the CT Module is
connected to Panelboard A or B.
• Connect the CT module that will monitor Circuits 22-42 to
the corresponding A2 or B2 connector.
Circuits
Monitored
1-21A1B1
22-42A2B2
To configure branch circuits, see 5.5.12 - Adding a Circuit Breaker.
Panelboard A
Connector
Panelboard B
Connector
7
4.2Installing a Solid-Core Current Transformer
WARNING
!
A solid-core CT cannot be installed on a wire while current is flowing through the wire.
Damage to burden resistor and CT will occur. Power needs to be removed prior to installing
and/or removing any CT. CTs should be installed by qualified electricians only.
The CT for the panelboard main input circuit breaker is hard-wired to the connectors. Removing CT
wires from the connector requires a pin extraction tool. Contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378) for assistance.
Installation
NOTE
When replacing or installing a CT, ensure the replacement CT has a secondary rating of 1A—
for example, 100:1, 200:1 or 500:1. Using a higher-rated CT—for example, 100:5 or 500:5—will
damage the burden resistors on the PBVI board.
Typically the three-phase and neutral wires utilize a CT rating of 100:1, 200:1 or 500:1, while the
ground wire utilizes a CT rating of 100:1.
Route the circuit wire through the core of the CT and wire-tie the CT to the cable. Refer to the manufacturer’s documentation for proper orientation to ensure accurate readings. Generally, CTs have an
arrow, white dot or similar marking to indicate how to position the CT.
For the Liebert LDM, CTs have a white dot that must face the source on the three-phase wires and
must face the load on the neutral and ground wires.
NOTE
When installing CTs for a large branch circuit breaker or subfeed, verify which monitoring
board is installed.
• A PBVI board can support one subfeed per panelboard (if neutral and ground will be
monitored) or up to three subfeeds if neutral and ground are not monitored.
• One LIB can support up to eight output and/or subfeed breakers.
• Two LIB boards are provided to support up to 16 output and/or subfeed breakers.
8
4.3Connecting a Current Transformer to the PBVI Board
If subfeed breakers are ordered with the unit, the phase CTs are installed and wired to the PBVI. The
neutral and ground CTs are also factory-supplied and wired to the PBVI board.
Since the CTs must be installed on the subfeed breaker’s neutral and ground cables, they cannot be
installed in the factory. They are located in the bottom of the unit in front of the transformer.
CTs have an arrow, white dot or similar marking that depicts how to position the CT on the cable to
ensure accurate readings. The arrow, white dot or similar marking must face the load when installing
the CT on the ground and neutral cable. Route the neutral and ground cable through the core of the
CTs and wire-tie the CT to the cable.
If subfeed breakers are installed in the field, up to five CTs may be installed to monitor a subfeed
breaker (three phases, neutral and ground). The neutral and ground CTs may be omitted if monitoring of neutral and ground is not required.
On large branch circuit breakers, ground and neutral is not monitored.
There are two 18-pin terminal blocks on the PBVI for large branch circuit breakers and/or subfeeds—
one for Panelboard A and one for Panelboard B.
The circuit board is marked with a triangle to indicate Pin 1.
• Pin 1 should be used for the white wire of CT1 (Phase A)
• The black wire should be connected to Pin 2.
• The same pattern will follow for the remaining CTs.
After all CTs are installed, use the Configuration tool to label and set alarm parameters. To configure
the Liebert LDM, see 5.5.11 - Add or Delete a Circuit Breaker.
If the Power Distribution Center is supplied with optional isolated ground, the isolated ground circuit
can be monitored by the Liebert LDM.
• Connect the isolated ground CT to Pins 17 and 18 on the two 18-pin terminal blocks on the PBVI.
• Connect the isolated ground CT white wire to Pin 17 and the CT black wire to Pin 18.
▼
Installation
CTs for the
three phases
CT for neutral
and ground
Five CT
connection
Refer to the following example and Table 2 for wiring configuration details.
Example: When installing a subfeed breaker where the three phases, neutral and ground will be
monitored, the CTs should be wired as follows:
PinWiring
1Phase A CTWhite wire
2Phase A CTBlack wire
3Phase B CTWhite wire
4Phase B CTBlack wire
5Phase C CTWhite wire
6Phase C CTBlack wire
7Neutral CTWhite wire
8Neutral CTBlack wire
9Ground CTWhite wire
10Ground CTBlack wire
If neutral and ground will not be monitored, Pins 7-10 may be used instead for a second subfeed
(Phase A and Phase B CTs).
9
4.4CT Table for PBVI Board
Table 2 shows the configuration of large branch circuit breakers and their CT assignments.
Table 2Wiring configuration of large branch circuit breakers
Configuration 1: Four Modules
Connector P3 (A)Pins
Wire Color WBWBWBWBWBWBWBWBWB
CTCT1CT2CT3CT4CT5CT6CT7CT8
Connector P4 (B)Pins
Wire Color WBWBWBWBWBWBWBWBWB
CTCT10CT11CT12CT13CT14CT15CT16CT17
Configuration 2: Two Modules With Large Branch Breaker CTs
Connector P3 (A)Pins
Wire Color WBWBWBWBWBWBWBWBWB
CTLB1LB2LB3LB4LB5LB6LB7LB8
Connector P4 (B)Pins
Wire Color WBWBWBWBWBWBWBWBWB
CTLB10LB11LB12LB13LB14LB15LB16LB17
▼
123456789101112131415161718
▼
123456789101112131415161718
▼
123456789101112131415161718
▼
123456789101112131415161718
Installation
CT9
or IG
CT18
or IG
LB9
or IG
LB18
or IG
Configuration 3: Four Modules With Two 5-Wire Subfeed Breaker CTs
▼
Connector P3 (A)Pins
123456789101112131415161718
Wire ColorWBWBWBWBWB
CTLB1LB2LB3LB4LB5IG
PhaseA1B1C1N1G1
▼
Connector P4 (B)Pins
123456789101112131415161718
Wire ColorWBWBWBWBWB
CTLB6LB7LB8LB9LB10IG
PhaseA2B2C2N2G2
Configuration 4: Four Modules With Three 5-Wire Subfeed Breaker CTs
4.5Connecting a Current Transformer to the LIB Board
LIB can monitor eight 5-wire output/subfeed breakers. Two LIB boards are provided to support up to
16 output and/or subfeed breakers. If subfeed breakers are ordered with the unit, the phase CTs are
installed and wired to the LIB. The neutral and ground CTs are also factory-supplied and wired to the
LIB.
Since the CTs must be installed on the subfeed breaker’s neutral and ground cables, they cannot be
installed in the factory. They are located in the bottom of the unit in front of the transformer.
CTs have an arrow, white dot or similar marking that depicts how to position the CT to ensure accurate readings. The arrow, white dot or similar marking must face the load when installing the CT on
the ground and neutral cable. Route the neutral and ground cable through the core of the CTs and
wire-tie the CT to the cable.
If subfeed breakers are installed in the field, up to five CTs may be installed to monitor a subfeed
breaker (three phases, neutral and ground). The neutral and ground CTs may be omitted if monitoring of neutral and ground is not required.
The designators on the LIB are different from those on the PBVI board.
• CT1 (Phase A white wire) begins on TB1 CT1+ and the black wire connects to CT1-.
• The Ground CT for the first subfeed/output circuit breaker connects to TB4 CT35.
Installation
Four CTs
(three phases
and neutral)
Ground CT
Refer to the example below and Tables 3 and 4 for wiring configuration details.
Example: The above pictures show how to install CTs for a subfeed or I-Line output circuit breaker
with neutral and ground being monitoring. The CTs should be wired as follows:
First BreakerSecond Breaker
CT1+Phase A CTWhite wireCT5+Phase A CTWhite wire
CT1-Phase A CTBlack wireCT5-Phase A CTBlack wire
CT2+Phase B CTWhite wireCT6+Phase B CTWhite wire
CT2-Phase B CTBlack wireCT6-Phase B CTBlack wire
CT3+Phase C CTWhite wireCT7+Phase C CTWhite wire
CT3-Phase C CTBlack wireCT7-Phase C CTBlack wire
CT4+Neutral CTWhite wireCT8+Neutral CTWhite wire
CT4-Neutral CTBlack wireCT8-Neutral CTBlack wire
CT35+Ground CTWhite wireCT36+Ground CTWhite wire
CT35-Ground CTBlack wireCT36-Ground CTBlack wire
If more output or subfeed CTs need to be installed, continue in the same pattern shown above.
• Connect the Phase A CT for the second breaker on CT5 (white wire to CT5+, black to CT5-).
• Connect the Ground CT for the second breaker to CT36 (white wire to CT36+, black to CT36-).
• Continue the same pattern until all CT connections are used or there are no more output or subfeed CTs to add.
12
4.6CT Table for LIB
Tables 3 and 4 show the CT assignments for 10 output breaker CTs and three subfeed breaker CTs
with neutral and ground being monitored.
Table 3Wiring configuration for LIB 1
Pins181716151413121110987654321
Connector
TB1
Connector
TB2
Connector
TB3
Wire ColorBWBWBWBWBWBWBWBWBW
CTCT9CT8CT7CT6CT5CT4CT3CT2CT1
PhaseA3N2C2B2A2N1C1B1A1
Pins181716151413121110987654321
Wire ColorBWBWBWBWBWBWBWBWBW
CTCT18CT17CT16CT15CT14CT13CT12CT11CT10
PhaseB5A5N4C4B4A4N3C3B3
Pins181716151413121110987654321
Wire ColorBWBWBWBWBWBWBWBWBW
CTCT27CT26CT25CT24CT23CT22CT21CT20CT19
PhaseC7B7A7N6C6B6A6N5C5
-+-+-+-+-+-+-+-+-+
-+-+-+-+-+-+-+-+-+
-+-+-+-+-+-+-+-+-+
Installation
Connector
TB4
Connector
TB5
W = White
B = Black
Pins181716151413121110987654321
-+-+-+-+-+-+-+-+-+
Wire ColorBWBWBWBWBWBWBW
CTCT2CT1NONENONECT32CT31CT30CT29CT28
PhaseG2G1N8C8B8A8N7
Pins121110987654321
-+-+-+-+-+-+
Wire ColorBWBWBWBWBWBW
CTCT8CT7CT6CT5CT4CT3
PhaseG8G7G6G5G4G3
A = A Phase
B = B Phase
C = C Phase
N = Neutral
G = Ground
13
Table 4Wiring configuration for LIB2
Pins18 17 16151413121110987654321
Connector
TB1
Connector
TB2
Connector
TB3
Wire ColorB W B W B W B W B WBWBWBWBW
CTCT41CT40CT39CT38CT37CT36CT35CT34CT33
PhaseA11N10C10B10A10N9C9B9A9
Pins18 17 16151413121110987654321
Wire ColorB W B W B W B W B WBWBWBWBW
CTCT50CT49CT48CT47CT46CT45CT44CT43CT42
PhaseB13A13N12C12B12A12N11C11B11
Pins18 17 16151413121110987654321
Wire ColorB W B W B W B W B WBWBWBWBW
CTNONENONENONENONENONENONENONECT52CT51
PhaseN13C13
- + - + - + - + - +-+-+-+-+
- + - + - + - + - +-+-+-+-+
- + - + - + - + - +-+-+-+-+
Installation
Connector
TB4
Connector
TB5
W = White
B = Black
Pins18 17 16151413121110987654321
- + - + - + - + - +-+-+-+-+
Wire ColorB W B WB WBWBWBWBW
CTCT10CT9NONENONENONENONENONENONENONE
PhaseG10G9
Pins121110987654321
- + -+-+-+-+-+
Wire ColorB W BWBWBWBWBW
CTNONENONENONECT13CT12CT11
PhaseG13G12G11
A = A Phase
B = B Phase
C = C Phase
N = Neutral
G = Ground
14
Operation
5.0OPERATION
The Liebert LDM is a factory-installed option to provide monitoring of the main breaker, branch circuit breakers and subfeed breakers. It may be installed in the Liebert PPC Precision Power Center,
Liebert FDC, Liebert FPC and Liebert RDC Remote Distribution Cabinet.
Software available on Liebert’s Web site (see 5.3 - Downloading the Software) can be installed on a
desktop or laptop computer (PC) to monitor status and configure breaker parameters and alarm setpoints. These monitoring and configuration functions are described in 5.4 - Using the Monitor Tool
and 5.5 - Using the Configuration Tool.
The Liebert LDM monitors and displays the parameters listed in Table 5.
Table 5Parameters monitored for breakers
Displayed and monitored for each:
Panelboard
Parameters
Voltage—✔——
Line-to-line—✔——
Line-to-neutral—✔——
Phase Current✔✔✔✔
Neutral Current—✔✔✔
Ground Current—✔✔✔
kVA—✔✔✔
kW✔✔✔✔
kW-Hours✔✔✔✔
Percent Load✔✔✔✔
Power Factor—✔✔✔
Crest Factor—✔✔✔
Voltage Total Harmonic Distortion (THD)—✔✔✔
Current Total Harmonic Distortion (THD)—✔✔✔
branch
circuit breaker
Panelboard main
circuit breaker and
SqD I-Line panelboard
SqD I-Line
panelboard
circuit breaker
Subfeed
circuit
breaker
Circuit identification and status of each breaker are also displayed. Parameters are updated every
500msec.
15
Operation
5.1Alarms
The Liebert LDM constantly monitors configured parameters for normal values. When the unit
detects an alarm condition, it annunciates and displays alarm messages via the Monitor program (see
5.4 - Using the Monitor Tool).
Alarms must be manually reset after the alarm condition has been corrected and may be reset
through Modbus.
To facilitate troubleshooting:
• All alarms are stored in non-volatile memory to protect against erasure by a power outage.
• Alarms are saved in an event log. The event log stores up to 128 events using a first-in, first-out
format (FIFO).
All alarm thresholds for monitored parameters are adjustable by using the Configuration tool to
match site requirements (see 5.5 - Using the Configuration Tool).
Table 6 shows the types of alarms for the various types of breakers, along with a description, factory
default setpoints and allowable range for each.
Table 6Alarm conditions and factory setpoints
AlarmDescriptionDefault settingRange
Branch Breakers
• Overcurrent WarningCurrent exceeds 75% of breaker amps15A0-75%
• Overcurrent AlarmCurrent exceeds 80% of breaker amps16A10-80%
0%, which
• Low Current AlarmMinimum current level of a branch breaker
Panelboard Main Breaker and SqD I-Line Panelboard
• Phase Overcurrent WarningCurrent exceeds 75% of breaker amps170A0-75%
• Phase Overcurrent AlarmCurrent exceeds 80% of breaker amps180A10-80%
• Neutral Overcurrent AlarmCurrent exceeds 95% of breaker amps214A10-200%
Summary AlarmDetects and annunciates upon occurrence of any alarm——
Panelboard Summary Alarm
At least one of the line-to-line voltages exceeds +6% of
nominal
At least one of the line-to-line or line-to-neutral voltages
falls below -13% of nominal
Detects and annunciates upon occurrence of branch or
panelboard main breaker alarm
disables
the alarm
—0-50%
—0-50%
0%, which
disables
the alarm
——
0-70%
0-70%
16
5.2Communication
5.2.1LDM Setup Port Connection
Use the LDM Setup port to download and use the software from Liebert’s Web site for monitoring,
configuration and firmware upgrades (see 5.3 - Downloading the Software). This port is not a terminal interface.
To connect to the LDM Setup port:
• Connect one end of a standard DB9 (female-female) null modem cable to a desktop or laptop computer (PC).
• Connect the other end of the cable to the LDM Setup port on the Liebert LDM, as shown below.
NOTE
The images above are intended for illustration only. The location of the external port may vary.
Operation
5.2.2Modbus Connection
Use the Modbus port for remote communication. The Liebert LDM supports 2- or 4-wire RS-485/422
connection (customer-installed).
To connect to the Modbus port:
• Look for Connector TB1 on the BCB. This is the RS-485 Modbus port.
• Refer to the following figure for proper connection points.
NOTE
The triangle printed on the circuit board depicts Pin 1.
Triangle
indicates
Pin 1
Pin 5 = TX+
Pin 4 = TX-
Pin 3 = TX+/RX+
Pin 2 = RX-/TX-
Pin 1 = Shield
17
5.3Downloading the Software
The Liebert LDM has three software tools for monitoring, configuration and firmware updates:
• Monitoring - see 5.4 - Using the Monitor Tool
• Configuration - see 5.5 - Using the Configuration Tool
• Firmware updates - see 5.6 - Upgrading the Firmware
These programs may be downloaded at no charge or license fee at Liebert’s Web site at:
The software may be updated and changed without any notification. Check the Web site
regularly to ensure the software is up-to-date.
5.4Using the Monitor Tool
The Monitor tool supports service terminal connections through the LDM Setup port. The tool displays the following information:
• Main input voltage and currents
• Total power
• Individual branch circuit breaker currents
•Event log
• System clock (date and time)
• Reset kWh function
Operation
A special registry key may be installed in the PC to enable the auto-zero control option and provide
access to a more in-depth event log. This diagnostic feature is reserved for use by Liebert Services and
Emerson Network Power technical personnel.
5.4.1Starting the Monitor Tool
• If needed, download the latest version of the software (see 5.3 - Downloading the Software).
• Run the executable file Monitor-xx.exe (where xx is the latest version) to start the Monitor tool.
• In the Connect window, select the appropriate COM port, shown below left. The dialog box lists
available ports only. If a port is in use, it does not appear in the list.
•Click Connect.
• The Monitoring main window, below right, opens after communication is established.
COM port
Connect
18
5.4.2Monitor Menu Options
The Monitor window has a menu bar at the top with a drop-down list of options for each menu.
Table 7 summarizes the options available in these menus.
Table 7Monitor menu options
Menu OptionFunction
File Menu
• ExitTerminates the monitoring session and closes the Monitor program.
View Menu
• Event LogsOpens the Event Log window, allowing users to view a list of events for Panel A or Panel B or
system. Events are listed in order of occurrence, starting with the most recent.
• BreakersUpdates the status of all branch breakers for the selected panel in the Breaker Status area.
• SubfeedsUpdates the status of all subfeed breakers for the selected panel in the Breaker Status area.
Dump Menu
• ReadingsDownloads a .csv file with main breaker, branch circuit breaker and subfeed readings. The file
may be viewed with a spreadsheet program such as Microsoft Excel.
• Event LogDownloads a .csv file with the event log stored on the BCB. The file may be viewed with a
spreadsheet program such as Microsoft Excel.
• ConfigurationDownloads a .txt file with the configuration file stored on the BCB. The file includes scaling data,
Panelboard A and B configurations, branch circuit values and CT ratio settings.
Alarms Menu
Choose one of three options—Raw, Filtered or Latched—to specify how alarms are displayed.
Note that alarms sent over Modbus are latched independent of changes performed in the Alarms menu.
• RawThe raw alarm state is the instantaneous state of the alarm. It is not filtered and has no
hysteresis. When Raw is selected, an alarm is active whenever the latest reading exceeds the
setpoint and is cleared as soon as the reading returns to a level within the setpoint range.
• FilteredThe filtered alarm uses the hysteresis interval to suppress transient alarms. A filtered alarm is
cleared after the alarm condition remains cleared for longer than the hysteresis interval.
• LatchedLatched alarms behave like filtered alarms that get stuck on. A latched alarm stays active until
the alarm is manually cleared.
• Clear AllClears all latched alarms for the selected panel. Any alarm condition that is still active is latched
again after the hysteresis interval passes.
Help Menu
• AboutDisplays information about Liebert Distribution Monitoring.
Operation
Menu options
5.4.3Panel Status and Real-Time Clock
The Panel Status area displays:
• The name of the Liebert LDM in the Unit box.
• The currently selected panel in the Panel box.
To choose a different panel, click on the panel name or the A/B button. If the selected panel has
any active alarms, the panel name appears in white text with a red background.
The Real-Time Clock displays the time as stored in the Liebert LDM unit. The time will not display
correctly if the time zone is incorrect in the PC. If the time displayed is incorrect and the problem is
not caused by a time-zone configuration problem:
•Click the Set button to force the real-time clock to synchronize with the time set on the PC.
19
5.4.4Main Breaker Status
The Main Breaker Status area displays RMS current, percent load (PCT), total harmonic distortion
(THD), crest factor (CF), line-to-line voltage (VLL-RMS), line-to-neutral voltage (VLN-RMS), instantaneous power (Power), VA and power factor (PF) for each input phase. If any phase voltage or current is in alarm, the associated field displays white text with a red background.
The metered energy usage for the panel is also displayed in kilowatt hours (kWh), as shown above. To
clear all metering information, click the Reset All kWh button.
CAUTION
!
Exercise care before using the Reset All kWh button, which resets the kWh usage for the
main breaker as well as all branch breakers and subfeed breakers on the panel.
5.4.5Breaker Status
The Breaker Status area displays detailed status for every branch or subfeed breaker on the selected
panel. The information may appear in a table or as icons, depending on the whether the Table or
Icons button is active (see 5.4.6 - Mode Buttons).
Operation
Metered energy usage for the panel
The example below shows the table format with details for each breaker: type and rating, percent
load, individual phase current in amps (I1, I2, I3), power, apparent power (VA), power factor (PF) and
accumulated kilowatt hours (kWh.)
5.4.6Mode Buttons
Mode buttons at the bottom of the Monitor window allow users to download Monitor readings to a file,
toggle the display between branch and subfeed breakers, toggle between table and icon views of
breaker status data and view the Event Log. Additionally, Emerson Network Power technical personnel may control the auto-zero function if the diagnostic registry key is installed.
Table 8Monitor mode buttons
ButtonFunction
DumpConverts the Monitor readings into a spreadsheet format (.csv file format).
Subfeeds/Breakers
Icons/Table
EventsDisplays the Event Log dialog box.
Auto-Zero
(not shown above)
Subfeeds/Breakers
button
Toggles between the subfeed and branch breaker displays. The button label changes
when the display is changed.
Toggles between the tabular and icon views. The button label changes when the display is
changed.
Viewable only if the diagnostic registry key has been installed on the PC. Used by Emerson
Network Power technical personnel for diagnostic purposes only.
Icons/Table
button
20
5.5Using the Configuration Tool
The Configuration tool allows users to set up breakers and view or change their parameters and
alarm setpoints.
NOTE
End users are unable to create a configuration file. Only Emerson Network Power technical
personnel can create a unique configuration file. Please contact your local Emerson Network
Power representative or call Liebert Services at 1-800-LIEBERT (1-800-543-2378) for
assistance.
5.5.1Starting the Configuration Program
Before starting the Configuration tool, make sure you have the most recent version of the software
and decide whether you want to connect to the Liebert LDM or work in offline mode.
Offline mode allows you to run the configuration tool without being connected to the equipment.
(Prior to Version 25—LDM-Config-25—a service terminal connection was required to configure or
monitor the Liebert LDM.)
NOTE
A configuration file is required for Offline Mode. If one is not available, connect to the
equipment locally and save the configuration to disk. See 5.5.4 - Install Configuration Changes in the Unit and 5.5.5 - Save the Configuration File to Disk.
To Connect via COM PortTo Work in Offline Mode
1. If needed, download the latest version of the
software (see 5.3 - Downloading the Software).
2. Connect a PC to the Liebert LDM via the external
DB9 connection. Refer to 5.2.1 - LDM Setup Port Connection.
3. Run the file LDM-Config-xx.exe (where xx is
the version number) to start the Configuration
program.
4. In the Connect window, select the appropriate
COM port from the list of available ports.
5. Click Connect.
Operation
1. If needed, download the latest
version of the software (see 5.3 - Downloading the Software).
2. Run the file LDM-Config-xx.exe
(where xx is the version number) to
start the Configuration program.
3. In the Connect window, click the
Work Offline button, shown below.
4. When prompted for the
configuration file, navigate to the
location of the file.
5. Click Open.
COM port
Proceed to 5.5.2 - Main Configuration Window Overview to begin configuration.
When a local connection to the Liebert LDM can be performed, load the configuration using the
instructions in 5.5.3 - Load a Configuration File from Disk.
21
Work Offline
5.5.2Main Configuration Window Overview
The Configuration window shows breakers graphically in the left pane and associated breaker data at
right. Selecting a breaker in the left pane changes the display of data in the right pane.
Operation
Select Panel
Select View
Unit
Properties
Panel
Properties
Breaker
Properties
Mode
buttons
Table 9 shows the main sections of the window, along with a description and a reference to step-bystep instructions for each.
Table 9Overview of main Configuration window
SectionFunctionFor details, see:
Select PanelToggles the display between Panel A and Panel B.5.5.6 - Select Panel to View
Select ViewToggles between Panel and Auxiliary Breakers.5.5.7 - Select Breakers to View
Unit Properties
Panel Properties
Breaker PropertiesDisplays breaker parameters and alarm setpoints.5.5.10 - Edit the Breaker Properties
Configuration Mode Buttons
• Load from File
• Install to Unit
• Save to File
• Exit NowCloses the Configuration program.—
Displays the name, DIP switch address and
software address of the Liebert LDM unit.
Displays the name of the selected panelboard; also
password setup for security purposes.
Uploads a saved configuration file from the PC to
the Liebert LDM.
This feature may be used to install a backup copy
of a configuration file or set up a new Liebert LDM
installation.
Uploads the current configuration from the PC to
the Liebert LDM after making changes to the
configuration.
This step is required to update the unit with the
latest changes.
Saves a copy of the configuration file to the PC.
This feature is useful when a backup copy of the
configuration file is needed.
5.5.8 - Edit the Liebert LDM Unit
Properties
5.5.9 - Edit the Panel Properties or
Set a Password
5.5.3 - Load a Configuration File
from Disk
5.5.4 - Install Configuration
Changes in the Unit
5.5.5 - Save the Configuration File
to Disk
22
5.5.3Load a Configuration File from Disk
A previously saved configuration file—created
by Emerson Network Power technical personnel or saved from a Liebert LDM unit—may
be transferred from a PC to the Liebert LDM.
This feature allows for quick setup based on
another unit’s configuration or replacing a
configuration file in an existing installation.
To upload the configuration file:
• Click on the Load from File button at
the bottom of the Configuration window.
• In the Open window, navigate to the configuration file, then click Open.
After a short delay, a confirmation message
appears. The Liebert LDM is now updated
with all breaker and subfeed data from the
configuration file that was just loaded.
5.5.4Install Configuration Changes in the Unit
Whenever configuration changes are made using the Configuration program, the changes must be
installed in the Liebert LDM using this step.
Operation
Load from File
To install changes in the unit:
• Click on the Install to Unit button at the bottom
of the Configuration window.
• During the upload, the circuit board will reboot.
Once the rebooting process is complete, the configuration is now active.
NOTE
Always perform this step after making changes to the configuration. Configuration changes are
not stored in the Liebert LDM until the Install to Unit button is clicked.
5.5.5Save the Configuration File to Disk
Saving the configuration file creates a copy of
the current configuration, ensuring a backup
is available in the event of file corruption or
some other problem.
• Click on the Save to File button at the
bottom of the Configuration window.
• In the Save As window:
• Specify the location where you want
to save the file in the Save In box.
• Enter a unique name in the File
Name box.
•Click Save.
Install to Unit
23
Save to File
5.5.6Select Panel to View
Up to two panelboards may be connected to the Liebert LDM (see 4.1.1 - Connecting Panelboards
A and B). Each may be viewed in the Configuration main window.
To switch the view to a different panel:
• In the Select Panel box, click on Panel A for Panelboard A or Panel B for Panelboard B. The
panel name appears in the Panel Name box, as in the following examples.
Operation
Select Panel
Panel Breakers viewAuxiliary Breakers view
Select View
5.5.7Select Breakers to View
For each panelboard, two types of breakers may be configured.
To switch the view, click on a button in the Select View box (shown above):
• Panel Breakers to view circuit breakers installed in the panelboard (see example above left).
• Auxiliary Breakers to view breakers installed outside the panelboard—for example, subfeed
breakers (see example above right).
24
5.5.8Edit the Liebert LDM Unit Properties
The Unit properties box displays the name,
DIP switch address and software address of
the Liebert LDM unit:
• LDM Unit Name - a name assigned to
the Liebert LDM unit.
To make a change, click in the LDM
Unit Name box, click Edit and enter a
name, then click Apply.
• DIP Switch Address - the Modbus
address determined by the Modbus
address DIP switch setting.
The address can be changed by resetting DIP switches on S2 on the BCB.
• Software Address - a software-configured address that overrides the DIP
Switch Address if the DIP switch
address is set to zero.
To make a change, click in the Software
Address box, click Edit and enter a
value, then click Apply.
• When finished, click Install to Unit to
upload the changes to the Liebert
LDM.
Unit
Properties
Install to Unit
(click to save changes
to Liebert LDM)
Operation
Panel
Properties
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
5.5.9Edit the Panel Properties or Set a Password
The Panel properties box displays the name of the selected panelboard, as well as a Password box for
creating a password to protect against unwarranted changes to the configuration:
• Panel Name - the default panelboard names are PANEL A and PANEL B.
To change a name, click in the Panel Name box, click Edit and enter a name, then click Apply.
• Password - a password required for users to make changes to the configuration file.
To create a password:
• Click in the Password box, click Edit and enter a password.
The password may be up 10 characters long and may consist of any combination of numbers,
letters and special characters. The password is not case-sensitive.
•Click Apply.
• When finished, click Install to Unit to upload the changes to the Liebert LDM.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
25
5.5.10 Edit the Breaker Properties
The Breaker Properties box displays the breaker name, rating, other parameters and alarm setpoints.
Select a
Breaker
Breaker
Properties
Edit and
Apply
buttons
Operation
Install to Unit
(click to save
changes to
Liebert LDM)
To view or change parameters and alarm setpoints of a breaker:
• Click on the breaker in the left pane. When selected, the breaker has a yellow outline.
• Refer to the following table to make changes.
ParameterDescriptionTo make a change:
Breaker
Name
Position
Number
of Poles
Breaker
Rating
Phase
Overcurrent
Alarm
Phase
Overcurrent
Warning
Phase
Undercurrent
Alarm
Neutral Current
Alarm
Ground Current
Alarm
The name of the selected breaker. The default
names are BREAKER #01, BREAKER #02, etc.
The location of the selected breaker on the
panelboard.
The number of poles selected when the breaker was
added to the panelboard.
The amperage for which the circuit breaker is rated.
The default is 20A.
Percentage of the breaker rating that triggers an
overcurrent alarm. This value must be higher than
the Phase Overcurrent Warning.
Percentage of the breaker rating that triggers an
overcurrent warning. This value must be lower than
the Phase Overcurrent Warning.
Percentage of the breaker rating that triggers an
undercurrent alarm. The default is 0 (zero). Indicates
no current is flowing through the breaker—either the
breaker has tripped or the equipment has shut down.
Percentage of the breaker that triggers a neutral
current alarm.
Amperage that triggers a ground current alarm.
• Click in the Breaker Name box, click Edit and
enter a name, then click Apply.
(Cannot be edited)
(Cannot be edited)
• Click in the Breaker Rating box, click Edit and
enter a value, then click Apply.
• Click in the Phase Overcurrent Alarm box,
click Edit and enter a value, then click Apply.
• Click in the Phase Overcurrent Warning box,
click Edit and enter a value, then click Apply.
• Click in the Phase Undercurrent box, click Edit
and enter a value, then click Apply.
• Click in the Neutral Current Alarm box, click
Edit and enter a value, then click Apply.
• Click in the Ground Current Alarm box, click
Edit and enter a value, then click Apply.
• When finished, click Install to Unit to upload the changes to the Liebert LDM.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
26
5.5.11 Add or Delete a Circuit Breaker
After moving or removing circuit breakers in the panelboard, use the Configuration tool to add or
delete in the configuration.
Run the configuration program using the steps outlined in 5.5.1 - Starting the Configuration Pro-gram. Once connected, the configuration file that is currently programmed will be displayed.
5.5.12 Adding a Circuit Breaker
NOTE
Check to make sure the location for the new breaker does NOT have a breaker assigned. If it
does, first remove that breaker (see 5.5.14 - Delete a Breaker), then return to this procedure.
An error message appears if you attempt to add a breaker to an assigned position.
• If NOT assigned, a breaker position is shown with a Liebert logo.
• An assigned breaker position appears as a picture of a circuit breaker.
To add a 1-, 2- or 3-pole circuit breaker:
• Run the Configuration program (see 5.5.1 - Starting the Configuration Program).
• If needed, select the panel and breaker view with the new breaker:
• In the Select Panel box, click on Panel A or Panel B.
• In the Select View box, choose Panel Breakers if the new breaker is installed inside the panelboard or Auxiliary Breakers if located outside the panelboard.
Operation
Add
Breaker
Assigned
breaker
positions
Unassigned
breaker
positions
• Right-click on the new breaker position in the left pane. The selected breaker has a yellow outline.
• In the pop-up menu, click on Add Breaker, then on the type of breaker that was installed: One-Pole, Two-Pole or Three-Pole.
• In the Breaker Properties at right, change the breaker’s name, parameters and alarm setpoints as
needed (see 5.5.10 - Edit the Breaker Properties).
• When finished, click Install to Unit to upload the changes to the Liebert LDM.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
27
5.5.13 Adding a Subfeed Breaker
NOTE
Check to make sure the location for the new breaker does NOT have a breaker assigned. If it
does, first remove that breaker (see 5.5.14 - Delete a Breaker), then return to this procedure.
An error message appears if you attempt to add a breaker to an already assigned position.
• If NOT assigned, a subfeed breaker position is shown with three Liebert logos.
• An assigned subfeed breaker position appears as a picture of a 3-pole breaker.
To add a 3-pole subfeed breaker circuit:
• Run the Configuration program (see 5.5.1 - Starting the Configuration Program).
• If needed, select the panel and breaker view with the new breaker:
• In the Select Panel box, click on Panel A or Panel B.
• In the Select View box, choose Panel Breakers if the new breaker is installed inside the panelboard or Auxiliary Breakers if located outside the panelboard.
Panel Breaker ViewAuxiliary Breaker View
Operation
Add
Subfeed
Assigned
breaker
positions
Unassigned
breaker
positions
• Right-click on the new breaker position in the left pane. The selected breaker has a yellow outline.
• In the pop-up menu, click on Add Subfeed.
• In the Add Subfeed window:
• Click on the subfeed—for example, Subfeed #1 or
Subfeed #2—in the Select Subfeed box.
NOTE
The number of available subfeeds is determined by the
interface board selected and whether cross-configuration
is enabled.
• In the Select Size box, choose the rating of the new breaker: 100 Amp, 225 Amp or 400 Amp.
• Click on the Add Subfeed button to return to the main Configuration window.
• In the Breaker Properties box of the Configuration window, change the subfeed breaker’s name,
parameters and alarm setpoints as needed (see 5.5.10 - Edit the Breaker Properties).
• When finished, click Install to Unit to upload the changes to the Liebert LDM.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
28
5.5.14 Delete a Breaker
Removing a breaker from the configuration is required after moving or removing circuit breakers in
the panelboard. This step must be performed before adding a breaker in the same position.
To delete a breaker:
• Run the Configuration program (see 5.5.1 - Starting the Configuration Program).
• If needed, select the panel and breaker view with the breaker to be deleted:
• In the Select Panel box, click on Panel A or Panel B.
• In the Select View box, choose Panel Breakers if the breaker is installed inside the panelboard or Auxiliary Breakers if located outside the panelboard.
Operation
• Right-click on the breaker position in the left pane. The selected breaker has a yellow outline.
• In the pop-up menu, click Delete.
• A confirmation message appears, as shown above. Select Yes to delete the breaker (or No to cancel).
• Repeat as needed to delete other breakers.
• When finished, click Install to Unit to upload the changes to the Liebert LDM.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
29
5.6Upgrading the Firmware
The Flash program is used to upgrade the firmware on a Liebert LDM unit. It uses the service terminal port to erase the old firmware, copy the new firmware and reboot the unit.
NOTE
Updating the firmware will not erase any configuration settings currently installed. No notice
is given to customers when a new firmware version becomes available. Check Liebert’s Web site
periodically for any available updates (see 5.3 - Downloading the Software).
To upgrade the firmware:
1. Make sure the Liebert LDM unit is powered ON.
2. Connect the PC to the Liebert LDM via the external DB9 connection. Refer to 5.2.1 - LDM Setup Port Connection.
3. If needed, download the latest version of the software (see 5.3 - Downloading the Software).
4. Run the file named Flash x.x.x.exe (where x.x.x is the version number).
5. In the Upgrade Firmware window, click the Select Port button.
Operation
6. In the Scan for LDM Units window:
• Select the COM port from the drop-down list—for example, COM1.
• Make sure the Baud Rate is 115200.
•Click the Start Scan button to check for a connection to the unit.
30
Operation
7. If the Liebert LDM unit is detected, a confirmation window appears. Click Yes to continue and
proceed to Step 8.
If the Liebert LDM unit is NOT detected, an error message appears. Click OK to return to the
Upgrade Firmware window. Check to verify the following, then repeat Step 6:
• The correct COM Port is selected and the Baud Rate is 115200.
• A serial cable is properly connected to the unit (see 5.2.1 - LDM Setup Port Connection).
• The Liebert LDM unit is powered ON.
8. In the Open window, locate the firmware file named MAIN-xx.out (where xx is the current
version):
• Browse to the folder where the Flash files are located—the default folder is Flash.
• Select the file you want to download—MAIN-xx.out (where xx is the current version).
•Click the Open button.
31
9. The Upgrade Firmware window appears. Click the Download button to continue.
10. Wait for the firmware upgrade to complete.
• The program erases the old image, than writes the new image, as shown below.
Operation
Progress
Progress
Failed = 0
11. When the new image is loaded, the Flash program restarts the unit. Verify the following:
• In the Summary Status box, the Number of Units should be 0 under Failed.
• In the Detail Status box, Running should appear under Progress—this indicates that the
BCB has been restarted successfully.
12. Click Exit to close the Flash program.
32
6.0SPECIFICATIONS
ELECTRICAL
Voltage120 - 240 VAC (-13% to +6%)
Frequency50 and 60Hz
Control Transformers Rating
(Secondary Winding)
BSM Current0.25A to 50A
CT Accuracy
Minimum Current200mA
ENVIRONMENTAL
Humidity0-95%
Temperature (Non-Operating)-68°F to 158°F (-20°C to 70°C)
Temperature (Operating)32°F to 104°F (0°C to 40°C)
Specifications
1A for Branch Circuits and Subfeeds
5A for Main Input Breaker
2% for 1A to 50A
5% for 0.25A to 1A
33
7.0TROUBLESHOOTING / FAQS
1. How do I obtain the software necessary to monitor and configure the Liebert LDM?
• The software package is available from Liebert’s Web site:
2. What is contained in the downloaded software package?
• The downloaded file from Liebert’s Web site is a zip file that contains:
• the flash program with a walk-through instruction
• the configuration program
• the monitor program
• the latest firmware file (to update the Liebert LDM firmware using the flash program)
3. What should I do if the BMS is reporting an overcurrent alarm?
• Verify the circuit is not actually overloaded.
• Using the Configuration program, verify alarm setpoints and CT ratio is correct.
• If settings are correct, verify that the BMS is operating correctly.
• If the issue still exists, contact Liebert Services at 1-800-LIEBERT (1-800-543-2378) for assistance.
4. I get an error message “Incorrect Schema Version” when I try to run the Monitor tool or
Configuration tool. What should I do?
• Ensure that only one program—either Monitor or Configuration—is running at a time. You
can’t run both programs at the same time.
• Ensure the latest firmware is loaded into the BCB. Please visit Liebert’s Web site for firmware updates. If a firmware upgrade is necessary, refer to 5.6 - Upgrading the Firmware.
• Verify the PC is connected to the LDM Setup port and the cable is fully seated (see 5.2.1 - LDM Setup Port Connection).
• Verify the Liebert LDM unit has power (green LEDs on the BCB will be flashing).
5. How can I make a backup copy of the configuration file?
• Connect to the external LDM Setup port (see 5.2.1 - LDM Setup Port Connection).
• Run the configuration program (see 5.5.1 - Starting the Configuration Program).
• At the bottom of the Configuration window, select Save to File. Navigate to a location on
your PC to store the file (see 5.5.5 - Save the Configuration File to Disk).
Troubleshooting / FAQs
34
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.