Liebert ITR User Manual

Liebert® Challenger™ ITR
Installation Manual - Nominal Capacities 23 or 33 kW, 50 & 60Hz
Precision Cooling For Business-Critical Continuity™
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 System Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.1 Self Contained Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.2 Chilled Water Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.3 Split Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3.1 Remote Sensor Installation Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4 Equipment Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4.1 Handling With Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.2 Removal of Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.5 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.1 Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7 Balancing the Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.1 Ducted Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.2 Plenum Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.8 Checklist for Completed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.0 AIR-COOLED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1 Condenser Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Fan Speed Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.1 Materials Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4.2 Dehydration/Leak Test and Charging Procedures for R22 (standard) or R407C (Optional) . 18
3.4.3 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5 Lee-Temp/Flood Back Head Pressure Control Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.1 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.2 Materials Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5.3 Dehydration/Leak Test and Charging Procedures for R22 (Standard) or R407C (Optional). 21
3.5.4 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.0 WATER-COOLED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.2 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.3 Water Regulating Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.1 Water Regulating Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.2 Water Regulating Valve Manual Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.3 Testing Valve Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.0 GLYCOL/GLYCOOL-COOLED MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
5.1 Drycooler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
i
5.2 Drycooler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3.3 Pump and Drycooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.4 Glycol Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.5 Filling Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5.1 Preparing the System for Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.5.2 Glycol Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.5.3 Filling the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.6 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7 Glycol Regulating Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7.1 Glycol Regulating Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.7.2 Testing Valve Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.0 CHILLED WATER MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
6.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.0 SPLIT SYSTEM MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1.1 Air-Cooled Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.1.2 Water/Glycol-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2.1 Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2.2 Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.3 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.1 Refrigerant Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.2 Quick Connect Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.4 Outdoor Air-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.5 Centrifugal Air-Cooled Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.5.1 Installing the Indoor Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.5.2 Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.6 Water and Glycol-Cooled Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.1 Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.2 Condenser Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.3 Regulating Valve Adjustment and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.6.4 Glycol Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.0 R407C REFRIGERANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
8.1 Calculating Subcooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ii
FIGURES
Figure 1 Removing Liebert Challenger ITR from skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 2 Cabinet dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 3 Optional floor stand dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Piping connections for air-cooled units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 5 Piping connections for split system fan coil units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 6 Piping connections for water/glycol and GLYCOOL units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 7 Piping connections for chilled water self-contained units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 8 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 9 Air-cooled condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 10 Air-cooled fan speed control general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 11 Air-cooled, Lee-Temp general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 12 Water-cooled general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 13 Johnson Controls valve adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 14 Drycoolers and pump packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 15 Pump packages—expansion tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 16 Glycol general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 17 GLYCOOL general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 18 Chilled water general arrangement - horizontal flow (BR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 19 Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 20 Outdoor air-cooled condensing unit—horizontal air discharge models . . . . . . . . . . . . . . . . . . . . . 43
Figure 21 Outdoor air-cooled condensing unit—top air discharge models . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 22 Electrical field connections, prop fan condensing module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 23 Detail of ceiling hanging bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 24 Centrifugal air-cooled condensing unit dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 25 Centrifugal air-cooled condensing unit dimensional data (con't.) . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 26 Split systems general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 27 Water/glycol-cooled condensing unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 28 Water/glycol-cooled condensing unit (con't.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
iii
TABLES
Table 1 Unit shipping weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 Piping connection size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 3 Air-cooled condenser statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 4 Recommended line sizes — OD copper (inches)* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 5 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 6 Indoor unit refrigerant charge lb (kg) R22 or R407C (per unit serial tag) . . . . . . . . . . . . . . . . . . 17
Table 7 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube. . . . . . . . . . . . . . . . . . . . . . . 17
Table 8 Condenser refrigerant (per serial tag) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 9 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 10 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 11 Room dew point temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 12 Indoor unit glycol volume approximate gallons (liters) max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 13 Volume in standard Type “L” copper piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 14 Ethylene glycol concentrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 15 Mounting hole dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 16 Drycooler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 17 Glycol pump data* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 18 Refrigerant control settings psi (kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 19 Unit refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 20 Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube. . . . . . . . . . . . . . . . . . . . . . . 40
Table 21 Recommended refrigerant lines (R22 or R407C) sizes OD copper . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 22 Line coupling sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 23 Equivalent lengths (feet) for various pipe fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 24 Horizontal air discharge cabinet and floor planning dimensional data. . . . . . . . . . . . . . . . . . . . . 44
Table 25 Horizontal air discharge piping and electrical connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 26 Cabinet and floor planning dimensional data - prop fan condensing modules, top
air discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 27 Piping and electrical connections - top air discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 28 Indoor centrifugal condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 29 Airflow CFM (CMH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 30 Water and glycol-cooled unit connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 31 Water and glycol-cooled condensing unit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 32 R407C pressure/temperature chart for operation and superheat (discharge/hot gas
and suction gas). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 33 R407C pressure/temperature chart for subcooling only (liquid measurements). . . . . . . . . . . . . . 57
iv

1.0 INTRODUCTION

1.1 System Descriptions

Liebert Challenger ITR™ environmental control systems are available in three main system configu­rations:
• self contained system with a scroll compressor in the room unit
• self contained chilled water system
• split system with an evaporator section and a remote condensing unit
All three types are available in horizontal flow configurations. Each model requires three-phase power. Units are available in 208, 230, 460, or 575 V, 60 Hz; and 200, 230 or 380/415 V, 50 Hz.
The following features are included as standard in all room units regardless of the type of system: V-frame coil, infrared humidifier, finned tubular stainless steel electric reheat, 2" filter, individual high voltage fused protection, and fan assembly.
Each configuration can operate with either Advanced Microprocessor Controls (A), or Advanced Microprocessor Controls with Graphics (G). A brief description of each, including operational differ­ences, is listed below. Check model numbers to see what is supplied with your unit.

1.1.1 Self Contained Systems

Air-Cooled Models
Complete refrigeration system including hot gas bypass and crankcase heater with standard con­denser and fan speed control for 95°F (35°C) ambient at sea level.
Introduction
Water-Cooled Models
Compete refrigeration system including hot gas bypass with water/glycol-cooled condenser and two­way water regulating valve with bypass.
Glycol-Cooled Models
The water-cooled model as described above plus pump package and 95°F (35°C) design ambient dry­cooler.
GLYCOOL Models
Complete refrigeration system including hot gas bypass with glycol condenser and three-way water reg­ulating valve plus an integrally piped Econ-O-Coil with three-way modulating control valve.

1.1.2 Chilled Water Models

Chilled Water models include chilled water piping, three-way modulating valve and actuator assembly.

1.1.3 Split Systems

Each Air-Cooled split system consists of an evaporator section and one of the following condensing units.
Prop Fan
Includes scroll compressor, condenser coil, prop fan, high pressure switch, and Lee-Temp head pres­sure control. Unit is designed for outdoor location.
Centrifugal Fan
Includes scroll compressor, condenser coil, centrifugal blower assembly, high pressure switch, head pressure control valve, Lee-Temp receiver and liquid line solenoid valve. Unit must be mounted indoors. Duct flanges are optional.
Water/Glycol Condensing Units
Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit, which includes scroll compressor, coaxial condenser, water regulating valve, and high pressure switch. Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as optional.
Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as described above), a pump package and a 95°F (35°C) design ambient drycooler.
1

2.0 INSTALLATION

!

2.1 Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors. Doors should not be undercut or have grilles in them.
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cool­ing, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept below 5% of the total air circulated in the room and be preconditioned.

2.2 Equipment Inspection

Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme­diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.

2.3 Location Considerations

The Liebert Challenger ITR can sit on top of an accessible elevated flooring system. It may be neces­sary to furnish additional pedestal support below the unit to ensure maximum structural support (see Table 1). A separate floor stand for the unit may be used as support, independent of the elevated floor and installed prior to the flooring system.
Provide approximately 34" (864 mm) service clearance in the front and rear of the unit.
The unit can be installed between equipment racks or at the end of a row of racks. Consideration should be given before installing refrigerant and liquid lines next to, under or above electronic equip­ment. Avoid placing the Liebert Challenger ITR in an alcove. Placing units too close together will reduce the effectiveness of the air distribution.
Installation
NOTE
Locate and remove shipping screw on fan motor base.

2.3.1 Remote Sensor Installation Location

The remote temperature and humidity sensor should be installed in the cold aisle in front of the equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply air needs to reach but still within the unit's area of influence. The sensor should be installed at the highest point that equipment will draw in cooled air.

2.4 Equipment Handling

WARNING
Risk of equipment tipping over. Can cause damage, injury or death. The instructions listed below must be adhered to when handling this unit with or without the
skid. There is the potential for this unit to tip over if handled improperly.
2

2.4.1 Handling With Skid

Remove plywood skirting holding unit and skid in place.
Raise unit with fork lift or similar machine.
• Always keep the Liebert Challenger ITR upright, indoors and protected from damage.
• Do not use the extended rear door frame to lift the unit.
• If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables, avoid­ing pressing on the top edges of the packaging.
• If using a fork lift, make sure that the forks, if adjustable, are spread to the widest allowable dis­tance to still fit under the skid.
NOTICE
Do not attempt to lift the Liebert Challenger ITR with the extended rear door frame. Attempting to do so will damage the unit. Lift the unit only from its main base.
NOTICE
While on the skid, the Liebert Challenger ITR is too tall to fit through a standard height doorway (83 inches or 2108 mm tall). Any attempt to move the unit, while on the skid, through a standard doorway will damage the unit.

2.4.2 Removal of Skid

1. Remove the plywood skirting that keeps the skid and unit in place.
2. Raise the Liebert Challenger ITR off the skid. Liebert recommends using a fork lift (see Figure 1) or similar machine to ensure that the unit is lifted properly.
Installation
NOTE
Lift the Liebert Challenger ITR only from its main base. Do not use the extended rear door frame to lift the unit.
3. Once the unit is raised, the skid can be removed.
Figure 1 Removing Liebert Challenger ITR from skid
Table 1 Unit shipping weights
Domestic Export
Model
BR059E 650 (295) 750 (340) BR060E 650 (295) 750 (340) BR065A 745 (340) 845 (385) BR067A 745 (340) 845 (385) BR070WG 815 (370) 915 (415) BR071WG 815 (370) 915 (415) BM058G 855 (390) 955 (435) BM061G 855 (390) 955 (435) BR101C 660 (300) 760 (345) BR102C 660 (300) 760 (345)
lb (kg) lb (kg) lb (kg) lb (kg)
50Hz Models 60Hz Models
Model
3
Domestic Export
Figure 2 Cabinet dimensions
DPN001523 Pg. 2, Rev. 1
Filter Access by Opening Door
UNIT TOP VIEW
32-1/2" (826mm)
5/8"
(16mm)
9-5/8"
(244mm)
8-1/2"
(216mm)
31-1/2"
(800mm)
1-7/8"
(48mm)
12-1/2"
(318mm)
30-1/2"
(775mm)
30-1/2"
(775mm)
32-1/2"
(826mm)
32-1/2"
(826mm)
1-5/8"
(41mm)
13"
(330mm)
Projection of Display Bezel
Standard Piping Location
45-1/8"
(1147mm)
5-1/2"
(140mm)
15-1/16"
(382mm)
76"
(1930mm)
91-1/16"
(2313mm)
Blower Outlet with 1" (25.4mm) Flange
Shaded area indicates a recommended clearance of 34" (864mm) for component access
Shaded area indicates a recommended clearance of 34" (864mm) for component access
UNIT DIMENSIONAL DATA FRONT VIEW
UNIT DIMENSIONAL DATA REAR VIEW
10-1/4"
(260mm)
7/8" (22.2mm) Flange for Duct or Plenum Connection
43-5/16"
(1100mm)
11- 3/ 4"
(298mm)
Remove Blocker Panel for Air Discharge Left and/or Right Side Panels
Standard Electrical Outlet Location Through Unit
12-5/8"
(321mm)
Discharge Air Opening
Plenum Overhang
Unit Weight
50 Hz Models 60 Hz Models lb. (kg)
BR059E BR060E 649 (294)
BR065A BR067A 744 (337)
BR070WG BR071WG 814 (369)
BR101C BR102C 659 (299)
BM058G BM061G 854 (387)
Installation
4
Figure 3 Optional floor stand dimensions
30-1/2"
(775mm)
30-1/2"
(775mm)
1"
(25.4mm)
See Specification Sheet for height of floor stand ordered.
SL-11897 Pg. 7
Installation
5

2.5 Piping Considerations

Consideration should be given before installing refrigerant and liquid lines next to, under or above electronic equipment.

2.5.1 Drain Line

A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec­tion and pitched a minimum of 1/8" per ft. (11 mm per meter).
NOTE
This line may contain boiling water. Select appropriate drain system materials.
The Challenger ITR comes standard with a condensate pump will require a field-supplied trap downstream from the pump. The drain line must comply with all applicable codes.
Table 2 Piping connection size
Air-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50Hz)
067A (065A) 1/2 7/8
Split System Fan Coil Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
Liquid Line O.D. Copper
L
Liquid Line
L
Installation
Hot Gas Line O.D. Copper
HG
Suction Line
SC
060E (059E) 1/2 O.D. Cu 1-1/8 O.D. Cu
All Units: Connection Sizes—in.
Humidifier Line
O.D. Copper
H
1/4 1/2 OD Cu 1/2
Water/Glycol-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
071WG (070WG) 1-1/8 1-1/8
GLYCOOL Unit Connection Sizes —in.
Model No. BR/BM
60Hz (50 Hz)
061G (058G) 1-1/8 1-1/8
Chilled Water Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
102C (101C) 1-1/8 1-1/8
Condensate
Drain Line
C
Supply Line
S
Supply Line
S
Supply Line
CWS
Condensate Pump Line
O.D. Copper
P
Return Line
Return Line
Return Line
CWR
Hot Water Reheat
O.D. Copper
Supply HWS Return HWR
5/8 5/8
R
R
6
Figure 4 Piping connections for air-cooled units
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return 5/8" OD CU (optional)
Hot Water Supply 5/8" OD CU (optional)
Liquid Refrigerant Line 1/2" OD CU on Models BR067A/BR065A
Humidifier Water Supply Line 1/4" OD CU
Hot Gas Refrigerant Line 7/8" OD CU on Models BR067A/BR065A
Condensate Pump Line 1/2" OD CU
Monitoring Panel
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
DPN001525 REV 0
Installation
7
Figure 5 Piping connections for split system fan coil units
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Supply 5/8" OD CU (optional)
Condensate Pump Line 1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return 5/8" OD CU (optional)
Liquid Refrigerant Line 1/2" OD CU on Models BR060E/BR059E
Humidifier Water Supply Line 1/4" OD CU
Suction Refrigerant Line 1 1/8" OD CU on Models BR060E/BR059E
Monitoring Panel
DPN001534 REV 0
Installation
8
Figure 6 Piping connections for water/glycol and GLYCOOL units
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Supply 5/8" OD CU (optional)
Condensate Pump Line 1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return 5/8" OD CU (optional)
Condenser Supply Line 1-1/8" OD CU on Models BR071WG/BR070WG
Humidifier Water Supply Line 1/4" OD CU
Condenser Return Line 1 1/8" OD CU on Models BR071WG/BR070WG
DPN001528 REV 0
Monitoring Panel
Installation
9
Figure 7 Piping connections for chilled water self-contained units
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return 5/8" OD CU (optional)
Chilled Water Return Line 1-1/8" OD CU
Hot Water Supply 5/8" OD CU (optional)
Humidifier Water Supply Line 1/4" OD CU
Chilled Water Supply Line 1-1/8" OD CU
Condensate Pump Line 1/2" OD CU
Monitoring Panel
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
DPN001531 REV 0
Installation
10

2.6 Electrical Connections

!
757682
83 84 85 88 899192 93 94 95 96
97 1
37C 38C 37B 37 38 24 50 51 55 56
77 78
4
7
2
3
4
5
71
70
15
6
11
13
12
17
16
14
1310
9
8
8
9
1
1
2338B
Terminal Block* (for customer connections)
Electrical Handy Box*
(factory-installed with cover)
DPN001524 REV 0
Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec­trical schematic when making connections.
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the Liebert Chal­lenger ITR in accordance with codes. A factory-supplied, locking disconnect switch is factory-mounted within the unit behind the front door.
WARNING
Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
NOTICE
Three-phase power must be connected to the Liebert Challenger ITR line voltage terminals in the proper sequence so that scroll the compressor rotates in the proper direction.

Figure 8 Electrical connections

Installation
1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).
2. Three phase connection. Electric service connection terminals when factory disconnect switch is supplied.
3. Factory-installed locking disconnect switch.
4. Three-phase electric service not by Liebert.
5. Earth ground connection (50/60Hz). Connection terminal for field-supplied earth grounding wire.
6. Earth ground bar (50Hz only). Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire.
7. Control and monitoring section of electric box.
8. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.
11
Installation
9. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection made by adding normally open contacts between terminals 24 + 50. Optional additional connections available with Advanced or Advanced with Graphics controls and appropriate optional accessories (connections 51, 55, and 56).
10. Liebert SiteScan pair, communication cable (available from Liebert or others) to optional Liebert SiteScan.
11. Remote condensing unit connection. Field-supplied 24V Class 1 wiring to remote condensing unit terminals 1, 2, 3, & 4 from (R2) relay (split system only).
12. Smoke detector alarm connections. Field-supplied 24V Class 1 wiring to remote alarm circuits. Factory-wired contacts from optional smoke detector are #91-comm., #92-NO, and #93-NC.
13. Common alarm connection. Field-supplied 24V Class 1 wiring to common alarm terminals 75 + 76 (and optional 94 + 95, and 96 + 97), which are factory-connected to common alarm relay (R3).
14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: connections provided for remote 24V AC source.
15. Heat rejection connection. Field-supplied 24V Class 1 wiring to interlock heat rejection from pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only and to Glycool relay (R5), Glycool units only).
16. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to connect 24V maximum.
17. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field wiring compartment for remote indication.
®
connection. Terminals 77 (-) and 78 (+) are for connection of a 2-wire, twisted
*Located inside Liebert Challenger ITR on top.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

2.7 Balancing the Air Distribution

2.7.1 Ducted Applications

For ducted applications, the duct work may be attached to the top perimeter of the Liebert Challenger ITR (see Figure 2).
The duct work must allow access to the motors/blowers for maintenance. The duct work must be designed within the capacity of the Liebert Challenger ITR, otherwise air flow and performance will be compromised.

2.7.2 Plenum Installation

A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for its installation ship separately from the Liebert Challenger ITR.
12

2.8 Checklist for Completed Installation

___ 1. Unpack and check received material.
___ 2. Proper clearance for service access has been maintained around the equipment.
___ 3. Equipment is level and mounting fasteners are tight.
___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked,
evacuated and charged (if required).
___ 5. Check piping within the Liebert Challenger ITR and outside of the unit. Remove potential of
rub-through or chaffing.
___ 6. Condensate pump installed.
___ 7. Drain line connected.
___ 8. Water supply line connected to humidifier (if required).
___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if
installed).
___ 10. Ducting completed (if applicable).
___ 11. Filter(s) installed.
___ 12. Line voltage to power wiring matches equipment serial tag.
___ 13. Power wiring connections completed between disconnect switch, evaporator and condensing
unit, including earth ground.
___ 14. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 15. Control wiring connections completed to evaporator and condensing unit.
___ 16. Verify water detection is properly installed around all units (if installed).
___ 17. All wiring connections are tight.
___ 18. Control panel DIP switches set based on customer requirements.
___ 19. Foreign materials have been removed from, in and around all equipment installed (literature,
shipping materials, construction materials, tools, etc.).
___ 20. Fans and blowers rotate freely.
___ 21. Inspect all piping connections for leaks during initial operations. Correct as needed.
___ 22. Verify that a blank start-up sheet has been sent with the unit(s) and is ready to be completed
by the installer.
Installation
13

3.0 AIR-COOLED MODELS

!

3.1 Condenser Location

The air-cooled condenser should be located for maximum security and maintenance accessibility. Avoid ground level sites with public access or areas that contribute to heavy snow or ice accumula­tions. Utilize centrifugal condensers whenever interior building locations must by used. To assure adequate air supply, it is recommended that condensers be located in a clean air area, away from loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located in the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than three feet (1 meter) from a wall, obstruction, or adjacent unit.
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof instal­lation, mount condensers on steel supports in accordance with local codes. To minimize sound and vibration transmission, mount steel supports across load bearing walls. For ground installation, a concrete pad will provide adequate support. Condenser legs have mounting holes for securing the con­denser to the steel supports or concrete pad.

3.2 Electrical Connections

Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec­trical schematic when making connections. Make all wiring and electrical connection in accordance with local and national codes.
WARNING
Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
Air-Cooled Models

3.2.1 Line Voltage

Line voltage electrical service is required for all air-cooled condensers at the location of the condenser. This power supply does not have to be the same voltage as the indoor unit. This separate power source may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and national codes.

3.2.2 Low Voltage

A control interlock between the condenser and the indoor unit is required and is connected between 70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC Class 1 wiring is required.

3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers

Lee-Temp condensers require a separate power supply for the heated receivers. This power supply is connected to the electrical connection box on the end of the receiver.
14
Loading...
+ 44 hidden pages