Liebert Challenger ITR™ environmental control systems are available in three main system configurations:
• self contained system with a scroll compressor in the room unit
• self contained chilled water system
• split system with an evaporator section and a remote condensing unit
All three types are available in horizontal flow configurations. Each model requires three-phase
power. Units are available in 208, 230, 460, or 575 V, 60 Hz; and 200, 230 or 380/415 V, 50 Hz.
The following features are included as standard in all room units regardless of the type of system:
V-frame coil, infrared humidifier, finned tubular stainless steel electric reheat, 2" filter, individual
high voltage fused protection, and fan assembly.
Each configuration can operate with either Advanced Microprocessor Controls (A), or Advanced
Microprocessor Controls with Graphics (G). A brief description of each, including operational differences, is listed below. Check model numbers to see what is supplied with your unit.
1.1.1Self Contained Systems
Air-Cooled Models
Complete refrigeration system including hot gas bypass and crankcase heater with standard condenser and fan speed control for 95°F (35°C) ambient at sea level.
Introduction
Water-Cooled Models
Compete refrigeration system including hot gas bypass with water/glycol-cooled condenser and twoway water regulating valve with bypass.
Glycol-Cooled Models
The water-cooled model as described above plus pump package and 95°F (35°C) design ambient drycooler.
GLYCOOL Models
Complete refrigeration system including hot gas bypass with glycol condenser and three-way water regulating valve plus an integrally piped Econ-O-Coil with three-way modulating control valve.
1.1.2Chilled Water Models
Chilled Water models include chilled water piping, three-way modulating valve and actuator assembly.
1.1.3Split Systems
Each Air-Cooled split system consists of an evaporator section and one of the following condensing units.
Prop Fan
Includes scroll compressor, condenser coil, prop fan, high pressure switch, and Lee-Temp head pressure control. Unit is designed for outdoor location.
Centrifugal Fan
Includes scroll compressor, condenser coil, centrifugal blower assembly, high pressure switch, head
pressure control valve, Lee-Temp receiver and liquid line solenoid valve. Unit must be mounted
indoors. Duct flanges are optional.
Water/Glycol Condensing Units
Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit,
which includes scroll compressor, coaxial condenser, water regulating valve, and high pressure switch.
Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as optional.
Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as
described above), a pump package and a 95°F (35°C) design ambient drycooler.
1
2.0INSTALLATION
!
2.1Room Preparation
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors.
Doors should not be undercut or have grilles in them.
Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cooling, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept
below 5% of the total air circulated in the room and be preconditioned.
2.2Equipment Inspection
Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales
representative.
2.3Location Considerations
The Liebert Challenger ITR can sit on top of an accessible elevated flooring system. It may be necessary to furnish additional pedestal support below the unit to ensure maximum structural support (see
Table 1). A separate floor stand for the unit may be used as support, independent of the elevated floor
and installed prior to the flooring system.
Provide approximately 34" (864 mm) service clearance in the front and rear of the unit.
The unit can be installed between equipment racks or at the end of a row of racks. Consideration
should be given before installing refrigerant and liquid lines next to, under or above electronic equipment. Avoid placing the Liebert Challenger ITR in an alcove. Placing units too close together will
reduce the effectiveness of the air distribution.
Installation
NOTE
Locate and remove shipping screw on fan motor base.
2.3.1Remote Sensor Installation Location
The remote temperature and humidity sensor should be installed in the cold aisle in front of the
equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply
air needs to reach but still within the unit's area of influence. The sensor should be installed at the
highest point that equipment will draw in cooled air.
2.4Equipment Handling
WARNING
Risk of equipment tipping over. Can cause damage, injury or death.
The instructions listed below must be adhered to when handling this unit with or without the
skid. There is the potential for this unit to tip over if handled improperly.
2
2.4.1Handling With Skid
Remove plywood skirting holding
unit and skid in place.
Raise unit with fork lift
or similar machine.
• Always keep the Liebert Challenger ITR upright, indoors and protected from damage.
• Do not use the extended rear door frame to lift the unit.
• If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables, avoiding pressing on the top edges of the packaging.
• If using a fork lift, make sure that the forks, if adjustable, are spread to the widest allowable distance to still fit under the skid.
NOTICE
Do not attempt to lift the Liebert Challenger ITR with the extended rear door frame.
Attempting to do so will damage the unit. Lift the unit only from its main base.
NOTICE
While on the skid, the Liebert Challenger ITR is too tall to fit through a standard height
doorway (83 inches or 2108 mm tall). Any attempt to move the unit, while on the skid,
through a standard doorway will damage the unit.
2.4.2Removal of Skid
1. Remove the plywood skirting that keeps the skid and unit in place.
2. Raise the Liebert Challenger ITR off the skid. Liebert recommends using a fork lift (see Figure 1)
or similar machine to ensure that the unit is lifted properly.
Installation
NOTE
Lift the Liebert Challenger ITR only from its main base. Do not use the extended rear door
frame to lift the unit.
3. Once the unit is raised, the skid can be removed.
Shaded area indicates
a recommended
clearance of 34" (864mm)
for component access
Shaded area indicates a recommended
clearance of 34" (864mm) for component access
UNIT DIMENSIONAL DATA
FRONT VIEW
UNIT DIMENSIONAL DATA
REAR VIEW
10-1/4"
(260mm)
7/8" (22.2mm) Flange for
Duct or Plenum Connection
43-5/16"
(1100mm)
11- 3/ 4"
(298mm)
Remove Blocker Panel
for Air Discharge Left
and/or Right Side Panels
Standard Electrical Outlet
Location Through Unit
12-5/8"
(321mm)
Discharge Air Opening
Plenum Overhang
Unit Weight
50 Hz Models60 Hz Modelslb. (kg)
BR059EBR060E649 (294)
BR065ABR067A744 (337)
BR070WG BR071WG814 (369)
BR101CBR102C659 (299)
BM058GBM061G854 (387)
Installation
4
Figure 3Optional floor stand dimensions
30-1/2"
(775mm)
30-1/2"
(775mm)
1"
(25.4mm)
See Specification Sheet
for height of floor stand ordered.
SL-11897
Pg. 7
Installation
5
2.5Piping Considerations
Consideration should be given before installing refrigerant and liquid lines next to, under or above
electronic equipment.
2.5.1Drain Line
A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate
drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will
not be exposed to freezing temperatures. The drain should be at least the full size of the drain connection and pitched a minimum of 1/8" per ft. (11 mm per meter).
NOTE
This line may contain boiling water. Select appropriate drain system materials.
The Challenger ITR comes standard with a condensate pump will require a field-supplied trap
downstream from the pump. The drain line must comply with all applicable codes.
Table 2Piping connection size
Air-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50Hz)
067A (065A)1/27/8
Split System Fan Coil Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
Liquid Line O.D. Copper
L
Liquid Line
L
Installation
Hot Gas Line O.D. Copper
HG
Suction Line
SC
060E (059E)1/2 O.D. Cu1-1/8 O.D. Cu
All Units: Connection Sizes—in.
Humidifier Line
O.D. Copper
H
1/41/2 OD Cu1/2
Water/Glycol-Cooled Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
071WG (070WG)1-1/81-1/8
GLYCOOL Unit Connection Sizes —in.
Model No. BR/BM
60Hz (50 Hz)
061G (058G)1-1/81-1/8
Chilled Water Unit Connection Sizes—in.
Model No. BR/BM
60Hz (50 Hz)
102C (101C)1-1/81-1/8
Condensate
Drain Line
C
Supply Line
S
Supply Line
S
Supply Line
CWS
Condensate Pump Line
O.D. Copper
P
Return Line
Return Line
Return Line
CWR
Hot Water Reheat
O.D. Copper
Supply HWSReturn HWR
5/85/8
R
R
6
Figure 4Piping connections for air-cooled units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Return
5/8" OD CU (optional)
Hot Water Supply
5/8" OD CU (optional)
Liquid Refrigerant Line
1/2" OD CU on Models BR067A/BR065A
Humidifier Water
Supply Line 1/4" OD CU
Hot Gas Refrigerant Line
7/8" OD CU on Models
BR067A/BR065A
Condensate Pump
Line 1/2" OD CU
Monitoring Panel
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
DPN001525
REV 0
Installation
7
Figure 5Piping connections for split system fan coil units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Supply
5/8" OD CU (optional)
Condensate Pump Line
1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return
5/8" OD CU (optional)
Liquid Refrigerant Line
1/2" OD CU on Models
BR060E/BR059E
Humidifier Water Supply Line
1/4" OD CU
Suction Refrigerant Line
1 1/8" OD CU on
Models BR060E/BR059E
Monitoring Panel
DPN001534
REV 0
Installation
8
Figure 6Piping connections for water/glycol and GLYCOOL units
Piping outlet locations through the
plenum are the same as the unit.
See below for descriptions and
connection sizes.
Hot Water Supply
5/8" OD CU (optional)
Condensate Pump Line
1/2" OD CU
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
Hot Water Return
5/8" OD CU (optional)
Condenser Supply Line
1-1/8" OD CU on
Models BR071WG/BR070WG
Humidifier Water Supply Line
1/4" OD CU
Condenser Return Line
1 1/8" OD CU on
Models BR071WG/BR070WG
DPN001528
REV 0
Monitoring Panel
Installation
9
Figure 7Piping connections for chilled water self-contained units
Piping outlet locations through
the plenum are the same as the
unit. See below for descriptions
and connection sizes.
Hot Water Return
5/8" OD CU (optional)
Chilled Water Return Line
1-1/8" OD CU
Hot Water Supply
5/8" OD CU (optional)
Humidifier Water Supply
Line 1/4" OD CU
Chilled Water Supply Line
1-1/8" OD CU
Condensate Pump Line
1/2" OD CU
Monitoring Panel
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
DPN001531
REV 0
Installation
10
2.6Electrical Connections
!
757682
83 84 85 88 899192 93 94 95 96
97 1
37C 38C 37B37 3824 50 51 55 56
77 78
4
7
2
3
4
5
71
70
15
6
11
13
12
17
16
14
1310
9
8
8
9
1
1
2338B
Terminal Block*
(for customer connections)
Electrical Handy Box*
(factory-installed with cover)
DPN001524
REV 0
Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or
200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes.
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections.
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the Liebert Challenger ITR in accordance with codes. A factory-supplied, locking disconnect switch is factory-mounted
within the unit behind the front door.
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
NOTICE
Three-phase power must be connected to the Liebert Challenger ITR line voltage terminals in
the proper sequence so that scroll the compressor rotates in the proper direction.
Figure 8Electrical connections
Installation
1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).
2. Three phase connection. Electric service connection terminals when factory disconnect switch
is supplied.
6. Earth ground bar (50Hz only). Connection terminals with factory ground from each high
voltage component for field supplied earth grounding wire.
7. Control and monitoring section of electric box.
8. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally
closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two
additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace
existing jumper for appropriate pair as done for 37 & 38.
11
Installation
9. Special alarm connections. Field-supplied 24V Class 1 wiring for special alarm. Connection
made by adding normally open contacts between terminals 24 + 50. Optional additional
connections available with Advanced or Advanced with Graphics controls and appropriate
optional accessories (connections 51, 55, and 56).
10. Liebert SiteScan
pair, communication cable (available from Liebert or others) to optional Liebert SiteScan.
11. Remote condensing unit connection. Field-supplied 24V Class 1 wiring to remote condensing
unit terminals 1, 2, 3, & 4 from (R2) relay (split system only).
12. Smoke detector alarm connections. Field-supplied 24V Class 1 wiring to remote alarm circuits.
Factory-wired contacts from optional smoke detector are #91-comm., #92-NO, and #93-NC.
13. Common alarm connection. Field-supplied 24V Class 1 wiring to common alarm terminals 75 + 76
(and optional 94 + 95, and 96 + 97), which are factory-connected to common alarm relay (R3).
14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier:
connections provided for remote 24V AC source.
15. Heat rejection connection. Field-supplied 24V Class 1 wiring to interlock heat rejection from
pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only
and to Glycool relay (R5), Glycool units only).
16. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field
wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to
connect 24V maximum.
17. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field
wiring compartment for remote indication.
®
connection. Terminals 77 (-) and 78 (+) are for connection of a 2-wire, twisted
*Located inside Liebert Challenger ITR on top.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
2.7Balancing the Air Distribution
2.7.1Ducted Applications
For ducted applications, the duct work may be attached to the top perimeter of the Liebert Challenger
ITR (see Figure 2).
The duct work must allow access to the motors/blowers for maintenance. The duct work must be
designed within the capacity of the Liebert Challenger ITR, otherwise air flow and performance will
be compromised.
2.7.2Plenum Installation
A solid plenum or plenum with discharge grille(s) may be installed. The plenum and instructions for
its installation ship separately from the Liebert Challenger ITR.
12
2.8Checklist for Completed Installation
___ 1. Unpack and check received material.
___ 2. Proper clearance for service access has been maintained around the equipment.
___ 3. Equipment is level and mounting fasteners are tight.
___ 4. Piping completed to refrigerant or coolant loop (if required). Piping has been leak checked,
evacuated and charged (if required).
___ 5. Check piping within the Liebert Challenger ITR and outside of the unit. Remove potential of
rub-through or chaffing.
___ 6. Condensate pump installed.
___ 7. Drain line connected.
___ 8. Water supply line connected to humidifier (if required).
___ 9. Field provided pan with drain installed under all ceiling mounted fluid condensing units (if
installed).
___ 10. Ducting completed (if applicable).
___ 11. Filter(s) installed.
___ 12. Line voltage to power wiring matches equipment serial tag.
___ 13. Power wiring connections completed between disconnect switch, evaporator and condensing
unit, including earth ground.
___ 14. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 15. Control wiring connections completed to evaporator and condensing unit.
___ 16. Verify water detection is properly installed around all units (if installed).
___ 17. All wiring connections are tight.
___ 18. Control panel DIP switches set based on customer requirements.
___ 19. Foreign materials have been removed from, in and around all equipment installed (literature,
shipping materials, construction materials, tools, etc.).
___ 20. Fans and blowers rotate freely.
___ 21. Inspect all piping connections for leaks during initial operations. Correct as needed.
___ 22. Verify that a blank start-up sheet has been sent with the unit(s) and is ready to be completed
by the installer.
Installation
13
3.0AIR-COOLED MODELS
!
3.1Condenser Location
The air-cooled condenser should be located for maximum security and maintenance accessibility.
Avoid ground level sites with public access or areas that contribute to heavy snow or ice accumulations. Utilize centrifugal condensers whenever interior building locations must by used. To assure
adequate air supply, it is recommended that condensers be located in a clean air area, away from
loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located in
the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than
three feet (1 meter) from a wall, obstruction, or adjacent unit.
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof installation, mount condensers on steel supports in accordance with local codes. To minimize sound and
vibration transmission, mount steel supports across load bearing walls. For ground installation, a
concrete pad will provide adequate support. Condenser legs have mounting holes for securing the condenser to the steel supports or concrete pad.
3.2Electrical Connections
Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections. Make all wiring and electrical connection in accordance
with local and national codes.
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter
to make sure power is turned off before making any electrical connections.
Air-Cooled Models
3.2.1Line Voltage
Line voltage electrical service is required for all air-cooled condensers at the location of the condenser.
This power supply does not have to be the same voltage as the indoor unit. This separate power source
may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be
factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and
national codes.
3.2.2Low Voltage
A control interlock between the condenser and the indoor unit is required and is connected between
70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC
Class 1 wiring is required.
3.2.3Lee-Temp/Flood Back Head Pressure Control Condensers
Lee-Temp condensers require a separate power supply for the heated receivers. This power supply is
connected to the electrical connection box on the end of the receiver.
14
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.