Liebert EIA-485, EIA-232 User Manual

Liebert® SiteTPI-1
LED Indicators
Addressing Rotary Switches
Port 2
Product Specification/Installation Sheet
The Liebert SiteTPI-1 is an ARCnet-ready device intended to interface specifically with a Liebert SiteScan
It is a 32-bit microprocessor-based device designed to monitor third-party equipment via an EIA-485/232 interface.
Logically, the device sits on the ARCnet network, providing the interface to Liebert SiteScan Web. The Liebert SiteTPI-1 converts proprietary equipment data into open protocol data, enabling a single piece of equipment to reside on a BACnet or Modbus network where it can be monitored or controlled by a Critical Management System.
Screw terminal blocks are provided to terminate power, communication and input signal wiring.
Web system.
Module Dimensions and Layout
0.2"
(5.08mm)
2.05"
(52.07mm)
4.1" (104.14mm)
5.2"
(132.08mm)
4.8"
(121.92mm)
0.2" (5.08mm)
1
Power Wiring
CAUTION
!
The Liebert SiteTPI-1 is a Class 2 device (less than 30VAC, 100VA maximum). Take appropriate isolation measures when mounting the Liebert SiteTPI-1 in a control panel where non-Class 2 devices (for example, 120VAC) or wiring are present.
Mounting
Screw the Liebert SiteTPI-1 into an enclosed panel using the mounting holes provided on the cover plate. Be sure to leave about 2" (50mm) on each side for wiring.
Specifications
Power
Dimensions, W x D x H: in. (mm) 4.1 x 1-1/2 x 5.2 (104.14 x 38.1 x 132.08)
Memory 1 MB Flash, 2 MB RAM
Communication
Ports
Baud rates
(protocol dependent)
Environmental Operating Range
Protection Built-in surge and transient protection circuitry
Battery
Fault Detection Hardware watchdog timer
Memory
Regulatory Compliance
Listed FCC Part 15 - Subpart B - Class A
Pending at Publication UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997)
24VAC ±15%, 50-60Hz, 20VA power consumption (single Class 2 source only, 100VA or less)
One 2-wire EIA-485 port
One jumper-configurable EIA-232/EIA-485 (2-wire/4-wire) port
One Rnet port (EIA- 485, 115.2k bps) for communication with a BACview, RS sensors, or WebCTRL
BACnet MS/TP = 9600, 19.2k, 38.4k, and 76.8k
Modbus = 9600, 19.2k, and 38.4k
Rnet = 115.2k
-22° to 150°F (-30-65.5°C); 10 to 95% relative humidity, noncondensing.
For UUKL Smoke Control Systems, 32°F-120.2°F (0°C-49°C); 10-85% relative humidity, non-condensing
Lithium 3V coin cell battery, CR2032, provides a minimum of 10,000 hours of data retention during power failures
1MB Flash memory and 1MB non-volatile battery-backed RAM (does not lose information that was stored before a power failure)
Ordering Information
Quantity Part # Description
SiteTPI-1 One-to-One Third-Party Interface Module
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
© 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-28110_REV01_09-08