Liebert DPN001599 User Manual

Page 1
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
STANDARD FEATURES
TANDEM COMPRESSORS - Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, manual reset high-pressure switch and pump
down low-pressure switch.
REFRIGERATION SYSTEM - Dual R-407C refrigeration circuits each including liquid line filter dryers, refrigerant sight glass with moisture indicator, electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.
PUMPS - Centrifugal type. Uses R-134a.
STANDARD CONTROL PROCESSOR - The standard control system is microprocessor-based with an external LCD numerical display to allow
observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel, which is mounted to the unit. The control system also monitors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
CABINET AND FRAME - Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel and painted using an auto-deposition coating system.
CANBUS ISOLATOR - Electrically isolates external CANBUS from internal CANBUS. Allows for greater total length of external CANBUS cables.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 1/6
REV 12/11 REV 4
Page 2
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
SHIPPED WEIGHT
B
A
Overall
C
Overall
F
Height of Unit
1in
25.4mm
E
D
Unit Base
Unit Base
UNIT DIMENSIONAL DATA
17in
431.8mm
D
2in
50.8mm
FLOOR CUTOUT DIMENSIONS
SHADED AREAS INDICATE A RECOMMENDED
CLEARANCE OF 36in (914mm) BE PROVIDED FOR
5in 127 mm
COMPONENT ACCESS.
RECOMMENDED MINIMUM HOT GAS SUPPLY & LIQUID RETURN PIPING OPENING
MODEL
50/60 HZ
XDC160 74 (1880) 34 (864) 33-1/8 (841) 33 (838) 72 (1829) 78 (1981) 1975 (896) 2109 (957)
* Dimension Does Not Include the Bezel of the Disconnect Switch or iCOM Display.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
DIMENSIONAL DATA inches (mm)
lbs (kg)
A B * C D E F DOM. EXPORT
PAGE 2/6
REV 12/11 REV 4
Page 3
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
MODEL
To First Cooling Module or Bypass Flow Controller **
Install Replaceable Filter Drier Assembly in Liquid Supply Line
22in 559mm
Orientation
21in 533mm
Defined by Installer.*
DIMENSIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
6in 152 mm
23in 584 mm
47in 1194 mm
Return Line From
A
Cooling Units (line is spin closed) (elbow customer provided)
44in
~
1118 mm
3 1/4in 83mm
8in
*
203mm
Liquid Supply Line
B
To Cooling Units
* Allow 8in (204mm) Of Clearance For Filter Replacement. Filter assembly may be positioned horizontally.
** To Ensure All Refrigerant Flow is Filtered, Install the Filter Drier Assembly Between the Discharge Line of the Liebert XDC and the first Bypass Flow Controller or the first Liebert XD Cooling Module.
Hot Gas Refrigerant Lines
C
Liquid Refrigerant Lines
D
UNIT PIPING OUTLET CONNECTION SIZES, inches
A
50/60 HZ
OD CUBOD CUCOD CUDOD CU
XDC160 2-1/8 1-1/8 1-3/8 7/8
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 3/6
REV 12/11 REV 4
Page 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Bypass Flow Control Assembly
Bypass Flow Controller Factory Supplied and Field Installed
Return Main
Ball Valve
Supply Main
Field Supplied and Field Installed
LIEBERT
XD
Field Supplied and Field Installed
COOLING
MODULE
RETURN
RETURN
Flow Direction Must be toward Return Main.
Install Bypass Flow Control Assembly between the Liebert XDC and first Liebert XD Cooling module. See System Design Manual SL-16655 for quantity required.
SUPPLY
Replaceable Filter Drier Assembly
Install Replaceable Filter Drier Assembly in liquid supply line
SUPPLY
LIEBERT XDC
Factory Piping Field Piping
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 4/6
REV 12/11 REV 4
Page 5
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Three phase electric service not provided by Liebert.
Field supplied disconnect switch may not be required, check local codes.
HEAT REJECTION CONNECTION (R-407C Side) Field supplied 24V. Class 1 wiring to interlock heat rejection from pigtails: 70A & 71A - Compressor 1 circuit 70B & 71B - Compressor 2 circuit 70C & 71C - Dual Cool relay (optional)
Three phase electric service not by Liebert.
ELECTRIC CONDUIT KNOCKOUTS On top of electric box. Knockout size 2 in (51 mm)
Factory installed unit disconnect switches
iCOM display
EARTH GROUND CONNECTION Connection terminal for field supplied earth grounding wire.
Electrical handy box factory installed with cover.
THREE PHASE CONNECTION Electric service connection terminals
Factory wired to components on electric panel
Factory installed disconnect switch
EARTH GROUND BAR (50Hz only) Connection terminal with factory ground from each high voltage component
60HZ COMPONENTS SHOWN
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
CANBUS ISOLATOR
ALARM AND WARNING OUTPUT RELAYS Field supplied 24V Class 2 wire for special alarms. (Not to exceed 1.0A @ 24v each.)
REMOTE UNIT SHUTDOWN Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 50VA rating. Use field supplied 24V Class 2 wire.
INTELLISLOTS Two Liebert Intellislots for optional OCWEB-LBDS or OC485-LBDS card.
®
®
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 5/6
REV 12/11 REV 4
Page 6
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Liebert XDC Extra Low Voltage field connection points
TO REMOTE T/H SENSOR A
P67
DO NOT
USE
TO P64 ON ICOM CONTROL BOARD RED ETHER NET CABLE
TO LIEBERT XD COOLING MODULE AND REMOTE T/H SENSOR B
TO OPTIONAL EXTERNAL CONNECTIONS
P64
P67P66
UNIT DISPLAY (REAR VIEW)
FACTORY WIRED TEMPERATURE SENSOR.
TO P66 ON ICOM CONTROL BOARD
TERMINATION PLUG
COMMON WARNING OUTPUT
FOR CONTACTS INDICATING AN ALARM CONDITION. (MAX) 1.0AMP @ 24V
K11NO
TO REMOTE ALARM
CIRCUIT BY OTHERS
INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE N.O. CONTACTS FROM REMOTE ALARM DEVICE AS SHOWN.
N.O. CONTACT BY OTHERS
INPUT: CONDENSATION
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: FAN BREAKER STATUS
1
K11
K11
K11COM
24 50
DETECTION
K11NC
5124
NOTES:
1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).
2. REQUIRES SHIELDED CABLE.
ALARM WHEN CLOSED.
5424
N.O. CONTACTS REQUIRED
COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN ALARM CONDITION. (MAX) 1.0AMP @ 24V
K3
K3
K3COM
K3NO
TO REMOTE ALARM
1
CIRCUIT BY OTHERS
INPUT: REMOTE SHUTDOWN
FOR SHUTDOWN OF CONTROL CIRCUIT, REMOVE JUMPER BETWEEN TERMINALS 37 & 38 AND REPLACE WITH N.C. CONTACT
N.C. CONTACTS BY OTHERS
K3NC
3837
21
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599
PAGE 6/6
REV 12/11 REV 4
Loading...