Liebert DM Series, DME07M1, DME12M1, DME07M2, DME12M2 User Manual

User Manual
Liebert® DM Series Air Conditioner
Precision Cooling For Business-Critical Continuity
New Liebert_DM Series Air Conditioner User Manual
Version
V1.0
Revision date
April 28, 2013
BOM
31012860
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Copyright © 2013 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan Distr i ct 518057, Shenzhen
China Homepage: www.emersonnetworkpower.com.cn E-mail: support@emersonnetwork.com.cn
Contents
Chapter 1 Overview ............................................................................................................................................................ 1
1.1 Model Description ................................................................................................................................................. 1
1.2 Product Introduction .............................................................................................................................................. 1
1.3 Basic Performance Parameters ............................................................................................................................ 1
1.4 Main Components ................................................................................................................................................. 2
1.4.1 Indoor Unit ................................................................................................................................................. 2
1.4.2 Outdoor Unit .............................................................................................................................................. 2
1.5 Options ................................................................................................................................................................. 3
1.5.1 Humidifier .................................................................................................................................................. 3
1.5.2 Heater ........................................................................................................................................................ 3
1.5.3 Remote Monitor ......................................................................................................................................... 3
1.5.4 Energy-Saving Card .................................................................................................................................. 3
1.5.5 Power SPD ................................................................................................................................................ 3
1.6 Ambient Requirements ......................................................................................................................................... 3
1.6.1 Operation Environment .............................................................................................................................. 3
1.6.2 Storage Environment ................................................................................................................................. 4
1.7 Refrigerant Charging Requirement ....................................................................................................................... 4
Chapter 2 Mechanical Installation ....................................................................................................................................... 5
2.1 Unpacking And Inspection .................................................................................................................................... 5
2.2 Installation Notes .................................................................................................................................................. 5
2.3 System Installation Arrangement .......................................................................................................................... 5
2.3.1 General Arrangement ................................................................................................................................ 5
2.3.2 System Installation Illustration ................................................................................................................... 6
2.3.3 Mechanical Parameters ............................................................................................................................. 7
2.4 Installing Indoor Unit ............................................................................................................................................. 8
2.4.1 Equipment Room Requirements ................................................................................................................ 8
2.4.2 Installation Location Requirements ............................................................................................................ 8
2.4.3 Installation Procedure ................................................................................................................................ 9
2.5 Installing Outdoor Unit ........................................................................................................................................ 10
2.5.1 Installation Notes ..................................................................................................................................... 10
2.5.2 Installation Procedure .............................................................................................................................. 10
2.6 Piping for AC Unit ............................................................................................................................................... 11
2.6.1 General Princ iples ................................................................................................................................... 11
2.6.2 Installation Notes Of Connector ............................................................................................................... 12
2.6.3 Required Pipe Connections ..................................................................................................................... 12
2.6.4 Connecting Refrigerant Pipe .................................................................................................................... 12
2.6.5 Connecting Drain Pipe Of Indoor Unit ..................................................................................................... 14
2.6.6 Connecting Humidifier Water Supply Pipe (If Applicable) ........................................................................ 14
2.7 Removing Transportation Fastener And Vibration Absorber ............................................................................... 15
2.8 Adding Refrigerant For Long Pipe System .......................................................................................................... 15
2.9 Check List ........................................................................................................................................................... 16
Chapter 3 Electrical Installation ......................................................................................................................................... 17
3.1 Task Introduction ................................................................................................................................................ 17
3.2 Notes .................................................................................................................................................................. 17
3.3 Connecting Power Cable Of Indoor Unit ............................................................................................................. 17
3.4 Connecting Power Cable Of Outdoor Unit .......................................................................................................... 19
3.5 Connecting Control Cable ................................................................................................................................... 19
3.5.1 Connecting Control Terminals ................................................................................................................. 19
3.5.2 Connecting Monitoring Port Cable ........................................................................................................... 21
3.6 Connecting Energy-Saving Card ......................................................................................................................... 21
3.7 Check list ............................................................................................................................................................ 23
Chapter 4 System Testing ................................................................................................................................................. 24
4.1 Start-Up Inspection ............................................................................................................................................. 24
4.2 Function Testing ................................................................................................................................................. 24
4.2.1 Cooling .................................................................................................................................................... 24
4.2.2 Heating .................................................................................................................................................... 24
4.2.3 Humidifying .............................................................................................................................................. 25
4.2.4 Dehumidifying .......................................................................................................................................... 25
4.2.5 Checking Refrigerant Charge Capacity Of Lee-Temp Outdoor Unit ........................................................ 25
Chapter 5 Micro-Processing Controller ............................................................................................................................. 26
5.1 Feature ............................................................................................................................................................... 26
5.2 Appearance ........................................................................................................................................................ 26
5.3 LCD Screen ........................................................................................................................................................ 26
5.4 Control Buttons ................................................................................................................................................... 27
5.4.1 Function Description ................................................................................................................................ 27
5.4.2 Operation Example .................................................................................................................................. 27
5.5 Control Screen .................................................................................................................................................... 28
5.5.1 ON Screen ............................................................................................................................................... 28
5.5.2 Normal Screen ......................................................................................................................................... 28
5.5.3 Password Screen .................................................................................................................................... 28
5.6 Menu Structure ................................................................................................................................................... 29
5.6.1 Main Menu ............................................................................................................................................... 29
5.6.2 Alarm Menu ............................................................................................................................................. 29
5.6.3 Set Points ................................................................................................................................................ 31
5.6.4 System Status ......................................................................................................................................... 31
5.6.5 System Menu ........................................................................................................................................... 32
5.6.6 Help Menu ............................................................................................................................................... 34
5.6.7 Display Set .............................................................................................................................................. 34
Chapter 6 System Maintenance ........................................................................................................................................ 35
6.1 Electric Inspection ............................................................................................................................................... 35
6.2 Indoor Unit Maintenance ..................................................................................................................................... 35
6.2.1 Filter......................................................................................................................................................... 35
6.2.2 Fan .......................................................................................................................................................... 36
6.2.3 Drain Pipe ................................................................................................................................................ 37
6.2.4 Heater ...................................................................................................................................................... 37
6.2.5 Humidifier ................................................................................................................................................ 37
6.2.6 Power SPD .............................................................................................................................................. 39
6.2.7 Thermal Expansion Valve ........................................................................................................................ 39
6.2.8 High-Pressure Switch And Low-Pressure Switch .................................................................................... 40
6.2.9 Compressor ............................................................................................................................................. 40
6.3 Outdoor Unit Maintenance .................................................................................................................................. 41
6.3.1 Refrigeration System ............................................................................................................................... 41
6.3.2 Air-Cooled Condenser ............................................................................................................................. 41
6.3.3 Low-Temperature Unit Of Lee-Temp Outdoor Unit .................................................................................. 41
6.4 Maintenance Inspection Checklist ....................................................................................................................... 42
Chapter 7 Troubleshooting ................................................................................................................................................ 43
Appendix 1 Menu Structure ............................................................................................................................................... 44
Appendix 2 Parameter Setting Table ................................................................................................................................ 45
Appendix 3 RDU-Cooling Air-Conditioner Single-Unit Manager Software Introduction ..................................................... 47
Chapter 1 Overview 1
New Liebert_DM Series Air Conditioner User Manual
Chapter 1 Overview
This chapter introduces the model description, product introduction, basic performance parameters, main components, options and ambient requirement, and refrigerant charging requirement of the new Liebert_DM series air conditioner (Liebert_D M AC for short).
1.1 Model Description
The model description of the Liebert_DM AC is shown in Figure 1-1.
Client code
1DM E
07
M T
1: Standard; 2: High effici ency
Input power supply. M: 380V-3-ph-50Hz Cooling capacity. 07: 7.5kW; 12: 12.5kW
Liebert_DM series air conditioner
E: indoor unit; C: outdoor unit; L: Lee-Temp outdoor unit
C
C: cooling only; O: with heater; H: with heater and humidifier
Figure 1-1 Model description
1.2 Product Introduction
The Liebert_DM AC is a small precise environment control system, specially designed for cooling the electrical devices. It is applicable to environment control in equipment room and co mput er room. Featuring high reliability, it can maintain a favorable running environment for precise devices such as sensitive devices, industry process devices, communication devices and computers.
The cooling kit is provided as standard and it can precisely control the ambie nt temper ature. The heater and humidifier are provided as options and they can precisely control the ambient humidity. If the AC unit is only used for cooling, the options are not needed.
The Liebert_DM AC prov ides a micro-processing controller that can automatically switch over to the required function (cooling or heating, dehumidifying or humidifying), based on the programmed setpoints and room ambient conditions.
Each Liebert_DM AC consists of an indoor unit and an outdoor unit. Both units are installed on the floor separately.
Indoor unit
The Liebert_DM AC includes units with a cooling capacity of 7.5kW and 12.5kW, which are applicable to power supply of 380V, 3-ph. You can select them according to the actual equipment room conditions.
Outdoor unit
The outdoor unit adopts air cooled mode. It is classified into two models: standard model and Lee-Temp model. The Lee-Temp model can be used at lower temperature (see Table 1-1) than the standard model.
1.3 Basic Performance Parameters
The basic performance parameters of the Lieber t_DM A C are given in Table 1-1.
Table 1-1 Basic performance parameters
Model
Nominal refrigeration
capacity (kW)
PowerkW
Energy efficiency
rate
Heating capacity
[1]
(kW)
Humidification
capacity
[2]
(kg/h)
DME07M**1
7.5
2.5
3.0
3.2
2.5
DME12M**1
12.5
4.15
3.0
3.2
2.5
DME07M**2
7.5
2.34
3.2
3.2
2.5
DME12M**2
12.5
3.9
3.2
3.2
2.5
2 Chapter 1 Overview
New Liebert_DM Series Air Conditioner User Manual
Model
Nominal refrigeration
capacity (kW)
PowerkW
Energy efficiency
rate
Heating capacity
[1]
(kW)
Humidification
capacity
[2]
(kg/h)
Note:
[1]: The heating capacity is only for the models with heating function; [2]: The humidification capacity is only for the models with humidification function
1.4 Main Components
1.4.1 Indoor Unit
The indoor unit consists of evaporator, compressor, fan, micro-processing controller, thermal expansion valve, strainer, filter, heater (optional), humidifier (optional) and surge protective devices (SPD, optional). For option introduction, refer to 1.5 Options.
Evaporator
Adopt a fin-tube heat exchanger with high efficiency. The distributor is designed and verified according to individual model to ensure that the refrigerant is distributed evenly in each loop, improving the efficiency of the heat exchanger to a great extent.
Compressor
Adopt a compressor with high efficiency ratio. It features low vibration, low noise and high reliability.
Fan
Adopt a centrifugal fan with high efficiency and high reliability. It features large airflow, long blowing distance, direct driving and easy maintenance.
Micro-processing controller
Provide a simple-operation user interface with multi-level password protection, self-recovery upon power failure, high-voltage & low-v olt age protection, phase loss protection, automatic phase-sequence switching upon anti-phase and rotate speed control of the outdoor fan. The expert-level fault diagnose system can automatically display current fault information to facilitate equipment maintenance by maintenance personnel.
Thermal expansion valve
Adopt a thermal expansion valve with external equalizer type. It collects temperature and pressure signals at the same time to accurately regulate the refrigerant flow.
Strainer
Filtrate the impurities generated during long-term system operation and ensure normal system operation.
Filter
Adopt nylon filter material with big mesh for Lie bert_DM AC . The filter features compact structure and easy maintenance. It can be washed repeatedly.
1.4.2 Outdoor Unit
The outdoor unit consists of fan and condenser. Other than the above components, the Lee-Temp model also includes a low-temperature unit.
Fan
Adopt axial flow blades with low noise. The single-phase motor with high performance is customized based on the power grid of base stations, so it can work over a wide voltage range with high reliability.
Condenser
Adopt a fin-tube heat exchanger with high heat dissipation and wavy fins. It is free of dust accumulation, and can be easily cleaned and maintained.
Chapter 1 Overview 3
New Liebert_DM Series Air Conditioner User Manual
Low-temperature unit
Make the AC unit operate in cooling mode normally at the lowest outdoor temperature of -34°C.
1.5 Options
1.5.1 Humidifier
The humidifier can add pure water vapor (up to 2.5 kg/hour) into the room to control the indoor humidity within ranges required by devices and computer.
The humidifier consists of a steam canister with automatic flushing control function, inlet tube, drain tube, solenoid valve and steam distributor.
Note
1. The electrode humidifier should be installed and tested in factory.
2. The Liebert_DM AC can control the ambient humidity only after a humidifier is installed.
1.5.2 Heater
A ceramic heater with positive temperature coefficient can be selected. It is safe and reliable. When the surface temperature is too high, it will reduce the heating power to avoid danger caused by over-temperature. A temperature switch is provided on the surface of the heater, and it will cut off the power of the heater when the surface temperature is too high. When the surface temperature decreases to normal, the temperature switch will restore the operation of the heater automatically.
1.5.3 Remote Monitor
The Liebert_DM AC communicates with the host computer through a configured RS485 port and receives the control of the host software. You can also select and configure a monitoring card to realize different monitoring functions. For the descriptions of the host monitoring sof tware RDU-Cooling developed by Emerson, refer to Appendix 3 RDU-Cooling Air-Conditioner Single-Unit Manager Software Introduction.
1.5.4 Energy-Saving Card
The Liebert_DM AC can monitor the maximum room temperature with the energy-saving card located outs ide the unit cabinet. The card is placed in position with high heat load and temperature. Up to four cards can be used for an AC unit. When the temperatures measured by all energy-saving cards are lower than the setpoint in ‘Sleep Mod’ and only indoor fan is running, if the ‘Sleep Mod’ is set to ‘ENAB’, the AC unit will turn off the indoor fan and enter the sleep mode for saving the energy.
1.5.5 Power SPD
The power SPD is used for second level (C level) lightning over-volt age prot e cti on of the AC power. It can be maintained easily and provides status indicating and alarm function.
Note
The humidifier, heater and power SPD should be installed in factory.
1.6 Ambient Requirements
1.6.1 Operation Environme nt
The operation environment requirements are listed in Table 1-2.
4 Chapter 1 Overview
New Liebert_DM Series Air Conditioner User Manual
Table 1-2 Operation environment requirements
Item
Requirements
Installation position
The maximum equivalent horizontal distance between the indoor unit and outdoor unit
[1]
: 50m;
Vertical distance ΔH
[2]
: -5m ΔH 20m
Installation mode
Indoor unit: vertical mode, mounting base 150mm;
outdoor unit: horizontal airflow mode
Ambient temperature
Indoor: 0°C ~ 40°C
Outdoor: standard model, -15°C ~ +45°C; Lee-Temp model, -34°C ~ +45°C
Ambient humidity
30%RH ~ 80%RH
Protection level
Outdoor unit: IPX4
Altitude
< 1000m. Derating is required when the altitude exceeds 1000m
Operation voltage range
380V (-15% ~ +15%), settable according to different environments, the error is 3%
Note:
[1]: For the equivalent lengths of parts, refer to Table 2-4. [2]: The value is positive if the outdoor unit is installed above the indoor unit; negative if the indoor unit is installed above the outdoor unit
1.6.2 Storage Environment
The storage environment requirements are listed in Table 1-3.
Table 1-3 Storage environment requirements
Item
Requirements
Storage environment
Indoor, clean (without dust)
Ambient humidity
5%RH ~ 85%RH
Ambient temperature
-40°C ~ +70°C
Storage time
The total shipment and storage time should not exceed six months. Otherwise, the
performance needs to be re-calibrated
1.7 Refrigerant Charging Requirement
The low quality or counterfeit refrigerant will damage the system severely. Please use the refrigerant approved by Emerson Network Power Co., Ltd. For the system abnormity or damage caused by using other brands of refrigerant, the warranty will be invalid.
See Table 1-4 for the refrigerant brands approved by Emerson Network Power Co., Ltd.
Table 1-4 Approved refrigerant brands
Brand
LOGO
Note
DU PONT
The DU PONT refrigerant adopts
Emerson custom-made package
JUHUA
Chapter 2 Mechanical Installation 5
New Liebert_DM Series Air Conditioner User Manual
Chapter 2 Mechanical Installation
This chapter expounds the mechanical installation of the Lieb ert_DM AC, including unpacking & inspection, installation notes, system ins t a llati on ar rang em ent, installing indoor unit, installing outdoor unit, piping, removing transportation fastener and vibration absorber, adding refrigerant for long pipe system and check list.
2.1 Unpacking And Inspection
Move the product to the place most close to the final installation site and then unpack it. If any part is found missing or damaged, please report to your carrier immediately. If any covert defect is found,
please report to the carrier and the local sales office too. Do not accept a damaged unit.
2.2 Installation Notes
1. The Liebert_DM AC adopts split-floor installation. The indoor unit must be installed on the floor in the equipment room or computer room. The outdoor unit can be installed outdoors or on the floor in other rooms.
2. Before installation, make sure that the installation environment me et s the r equ irem ents (see 1.6 Ambient Requirements) and that the buildi ng should be tra nsf orm ed to accommodate the constructi on wor k such as piping, wiring and ventilation ducts.
3. The installers must strictly follow the design drawings for installation and reserve space for in st al lation and maintenance. The manufacturer’s engineering dimension drawings can serve as a reference.
2.3 System Installation Arrangement
2.3.1 General Arrangement
The system general arrangement diagram is shown in Figure 2-1. The standard pipe sizes are shown in Table 2-1.
Figure 2-1 General arrangement diagram
6 Chapter 2 Mechanical Installation
New Liebert_DM Series Air Conditioner User Manual
Note
1. : Factory piping.
2.
: Field piping (by technicians).
3. *: Check valve and traps are optional and not supplied by Emerson. But they are recommended for normal system operation and easy maintenance. They should be installed on site by technicians.
4. +: Solenoid valve is a part of extended piping kit.
Table 2-1 Standard pipe sizes
Actual cooling capacity
Pipe length (m)
Discharge pipe OD
Liquid pipe OD
Liebert_DM series
7.5kW unit
5
1/2” (12mm)
3/8” (10mm)
12.5kW unit
5
5/8” (16mm)
1/2” (12mm)
2.3.2 System Installation Illustration
All equipment must be installed vertically. The Liebert_DM AC is available in two installation modes: outdoor unit installed higher than indoor unit and indoor unit installed higher than outdoor unit. See Figure 2-2 for details.
Outdoor unit
Floor
Isolataion
floor
Max. 20m
1:200
7.5m
1:200
Insulation material
Trap
Liquid pipe (not be exposed to sun)
Sealed
Protection
tube
Discharge pipe (slope)
Indoor unit
Condensation water drain pipe (to outdoor)
Humidifier canister water supply pipe (to water tap)
Outdoor unit above indoor unit
Min. 5m
1:200
Outdoor unit
Indoor unit
Sealed
Protection tube
Isolation floor
Discharge pipe (slope)
1:200
Condensation water drain pipe (to outdoor)
Floor
Insulation material
Liquid pipe (not be exposed to sun)
Humidifier canister water supply pipe (to water tap)
Indoor unit above outdoor unit
Figure 2-2 Installation illustration
Chapter 2 Mechanical Installation 7
New Liebert_DM Series Air Conditioner User Manual
2.3.3 Mechanical Parameters
Indoor unit
The mechanical parameters of the indoor unit are shown in Figure 2-3 and Table 2-2.
510
385
1750
510
510
600
500
1850
600
600
DME07kW DME12kW
Figure 2-3 Dimensions of indoor unit (unit: mm)
The shadows in Figure 2-3 indicate a reasonable instal lation and service space. The two sides of the unit need air inlet. Enough service space must be reserved for the unit to facilitate maintenance.
The AC unit equipped with a heater should be kept a distance of minimum 150mm from combustible substance. When testing the AC unit, keep the external static pressure below 150Pa lest the air volume becomes too low and the heater becomes too hot.
Outdoor unit
The mechanical parameters of the outdoor unit are shown in Figure 2-4, Figure 2-5 and Table 2-2.
352
787
829
1240
352
787
Figure 2-4 Dimensions of standard outdoor unit (unit: mm)
8 Chapter 2 Mechanical Installation
New Liebert_DM Series Air Conditioner User Manual
352
1037
575
1238
352
1037
575
829
Figure 2-5 Dimensions of Lee-Temp outdoor unit (unit: mm)
Table 2-2 Mechanical parameters of indoor unit and outdoor unit
Model
Cooling capacity (kW)
Dimensions (W × D × H, mm)
Net weight (kg)
Indoor unit
7.5
510 × 385 × 1750
90
12.5
600 × 500 × 1850
145
Outdoor unit
Standard model
7.5
787 × 352 × 829
40
12.5
787 × 352 × 1240
60
Lee-Temp model
7.5
1037 × 352 × 829
53
12.5
1037 × 352 × 1238
95
2.4 Installing Indoor Unit
2.4.1 Equipment Room Requirements
The equipment room requirements are given as follows:
1. The equipment room should be well insulated and have a sealed damp-proof layer. Note
The most important elements for maintaining normal environmental control in the conditioned room are damp proof and heat preservation.
2. The outdoor air should be kept from entering to a minimum. The outside air will add the loads of heating, cooling, humidifying and dehumidifying of the system. It is recommended that the inhalation of outside air be kept below 5% of the total indoor airflow.
3. All the doors and windows should be properly sealed to mi nim iz e the leakag e and the se ams should be as narrow as possible.
2.4.2 Installation Location Requirements
Note
The Liebert_DM AC can generate condensate water. Water leakage can cause damage to other precise equipment nearby. Do not install the AC units in the vicinity of any precision equipment. The installation site must provide drainpipes.
The installation location requirements are given as follows:
1. Try to locate the indoor unit in a capacious floor space to ensure its normal operation.
2. Avoid locating the indoor unit in confined areas that affect the airflow pattern, short en cooling cycles and result in down-draft and air noise.
3. Avoid locating the indoor unit in an alcove or at the extreme end of a long, narrow room.
Chapter 2 Mechanical Installation 9
New Liebert_DM Series Air Conditioner User Manual
4. Avoid locating multiple indoor units close to each other. This can result in crossing air patterns, uneven loads and competing operation.
5. Do not install additional devices (such as smoke detectors) over the cab inet for facilitating rout i ne main ten anc e. Figure 2-6 indicates the installation location of the indoor unit.
Not recommended locati on
location
Recommended
Figure 2-6 Installation location of the indoor unit
2.4.3 Installation Procedur e
1. Secure the mounting base made by yourself on the selected location. The outline and dimensions of the mounting base are shown in Figure 2-7.
510
385
Rubber cushion
(8mm ~ 10mm t hi ckness)
Steel plate (60 60 4)
H > 150
Rubber cushion (8mm thicknes s)
Angle iron (30 30 3) or square tube (25 25
3)
×
×
×
×
×
×
Mounting base of DME07kW indoor unit
600
500
H > 150
Installation hole for
expansion bolt (M6 50)
Rubber cushion
(8mm ~ 10mm t hi ckness)
Steel plate (60 60 4)
Rubber cushion (8mm thicknes s)
Angle iron (30 30 3) or square tube (25 25 2)
×
×
×
×
×
×
×
Mounting base of DME12kW indoor unit
Figure 2-7 Mounting base (unit: mm)
2. Lay a rubber cushion with 8mm ~ 10mm thickness on the mounting base, as shown in Figure 2-7.
3. Place the indoor unit onto the mounting base and secure it.
4. Rotate the grilles to regulate the airflow direction of the indoor unit, and the regulating angle is 45°, as shown in Figure 2-8.
10 Chapter 2 Mechanical Installation
New Liebert_DM Series Air Conditioner User Manual
Grill
The grilles can be rotated following the arrow direction
Figure 2-8 Regulating airflow direction
2.5 Installing Outdoor Unit
2.5.1 Installation Notes
1. Install the outdoor unit in a place which is secure and easy for maintenance. Do not install it on ground-level sites with public access and be away from residential areas.
2. Do not locate it directly in the environment that requires low noise.
3. To ensure heat dissipation effect, locate it in a clean area, which is away from loose dirt and foreign matter to avoid clogging the heat exchanger.
4. Do not locate it in the vicinity of steam, hot air and exhausts.
5. Keep a clearance of more than 450mm between the outdoor unit and the wall, obstruct and adjacent devices.
6. Avoid areas where snow will accumulate at air-inlet side and air-outlet side of the outdoor unit.
7. Prepare a solid base capable of supporting the outdoor unit weight (see Table 2-2). The base should be at least 50mm higher than the surrounding ground and 50mm larger than the dimensions of the outdoor unit base, as shown in Figure 2-11.
2.5.2 Installation Procedur e
1. Place the outdoor unit on the base.
2. Secure the outdoor unit onto the base with expansion bolts. The installation hole sizes of the base are shown in Figure 2-9 and Figure 2-10.