Liebert CSU 3000 User Manual

CSU3000 Chiller Designed
Keeping Business in Business
For Siemens Magnetom Harmony /Symphony
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow, year round.
• Factory-tested, piped, wired, and charged for hassle-free start-up and operation.
• Local service and parts for quick and knowledgeable maintenance and service
• Optional switch-over to alternate water source provides redundant continuous operation.
• Standard product ETL/CSA Certified.
• ISO 9000 Certified Company.
Magnetom Harmony/Symphony Specifications
Fluid Specified Water/Glycol
Max Heat Dissipation—BTUH (kW) 102,390
Fluid Temperature Range—°F (°C) 43-54 (6-12)
Fluid Flow Rate—GPM (l/m) 13 (50)
Fluid Pressure Drop—PSI (kPa) 21.8 (150)
Process Fluid Chiller Specifications
Model Number CS135A
Fluid Circulated Water
Net Cooling Capacity—BTUH (kW) 116,000 (34)
Leaving Fluid Temperature—°F (°C) 45 (7.2)
Fluid Flow Rate—GPM (l/m) 24 (91)
Harmony/ Symphony Pressure Drop—PSI (kPa) 21.8 (150)
Chiller Pressure Drop—PSI (kPa) 11.7 (81)
Pump Total Head—PSI (kPa) 56.3 (388)
Pump HP (kW) 3 (2.2)
CSU3000 Chiller Designed For Siemens Magnetom Harmony/Symphony 1
PROJECTION OF DISPLAY BEZEL 5/8" (16mm)
FACTORY SUPPLIED DISCONNECT SWITCH, ONE (1) PER MODULE
72"
(1829mm)
33"
(838mm)
r
e
v
O
n
o
i
s
n
e
m
i
D
l
l
a
74"
(1880mm)
O
v
e
r
a
l
l
D
i
m
e
n
s
i
o
n
PCR 3000 DISPLAY
SHADED AREAS INDICATE A RECOMMENDED CLEARANCE OF 34" (864mm) BE PROVIDED FOR COMPONENT ACCESS. FOR RECOMMENDED MINIMUM CLEARANCE REFER TO THE INSTALLATION MANUAL.
72"
(1829mm)
Unit Base
(787mm)
Unit Base
UNIT DIMENSIONAL DATA
* This application requires the chiller modules and storage tank to be mounted in a "CT" sized frame.
Standard Features
• Indoor chiller with outdoor air-cooled condenser
• Electronic controls and monitor
• Semi-hermetic compressor
• Hot gas bypass capacity control
• Circulating pump
• Manual shut-off valves
• Flow switch and check-valve
Required Special Options
• SFA E4968-1, 110 gallon internal storage tank
• SFA E6351-4, Electronic thermostats with auto­matic cylinder unloader controls
• SFA E5226-1, 3 hp pump
• SFA #E5818-3, Freezestat Change to allow for 45°F water temperature 15% glycol solution is required to prevent icing
• Non-locking disconnect switch
• Water- and glycol-cooled models available
Optional Features Available
• Refrigerant gauges and reservoir heaters
• Alternate water source (AWS) module
• Stainless steel circulating pump
• UPS pump connection
• Separate pump power connection
• Locking disconnect switch
• Remote monitoring panel
31"
1"
(25.4mm)
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Phone: 800.877.9222 Fax: 614.841.6022
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco Italy Phone: 39.049.9719.111 Fax: 39.049.5841257
Liebert Web Site—http://www.liebert.com
SL - 16560 (07/00)
23/F Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong Phone: 852.2.572.2201 Fax: 852.2.572.1182
©2000 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or regisered trademarks of their respective owners.