Guide Specifications for
7.5 - 37 Ton CS/CD/CT Models

1.0 GENERAL

1.1 CS/CD MODELS

The main-frame coolant supply unit shall be a Liebert Model __________________, self-contained, factory assembled system. Provide unit(s) with matching, dual refrigeration systems to provide both primary and redundant sources of chilled water to the main-frame computer system. This system shall be provided such that each chiller module can cool the main-frame computer; the second chiller module serves as a stand-by module.

1.2 CT MODELS

The main-frame coolant supply unit shall be a Liebert Model __________________, self-contained, factory assembled system. Provide unit(s) with matching, dual refrigeration units to provide primary source of chilled water to the main-frame computer system. A third refrigeration module shall be provided to provide redundant cooling capacity.
The packaged coolant supply unit for each model shall have the following built-in components.

1.3 SUBMITTALS

Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical, and Capacity data; Piping and Electrical Connection Drawings.

1.4 WARRANTY

The system shall be provided with a warranty against defects in material and workmanship for a period of one year from the start up date, not to exceed eighteen months from the date of shipment.

1.5 QUALITY ASSURANCE

The specified system shall be factory-tested before shipment. Testing shall include, but shall not be limited to: Quality Control Checks, “Hi-Pot” Test (two times rated voltage plus 1000 volts, per UL requirements), and Metering Calibration Tests. The system shall be designed and manufactured according to world class quality standards. The manufacturer shall be ISO 9001 certified.
(R 3/96) 1
Liebert CSU3000

2.0 PRODUCT

2.1 STANDARD FEATURES / ALL SYSTEMS

2.1.1 Cabinet and Frame Construction

The frame shall be constructed of heliarc-welded tubular steel. It shall be painted using the autophoretic
®
coating process for maximum corrosion protection. The exterior panels shall be insulated with a minimum of 1", 1 1/2 lb. density fiber insulation. All panels shall have captive, 1/4 turn fasteners and shall be removable for service access.
The main unit color shall be ________, and the accent panel color shall be ________. The exterior panels shall be powder coated.

2.1.2 Coolant Piping

The internal coolant piping shall include: isolating valves for each module, an expansion tank, water fill connection, pressurization connection and liquid-level sight glass; a circulating pump which shall provide ______ GPM at ______ feet of water total head; and a discharge check valve to prevent back flow.
The supply and return connections shall be 2 1/8" O.D. copper for connection to RR or ES header assemblies.

2.1.3 High Voltage Electric Panel

Each chiller module shall have a separate, self-contained high voltage electric panel. Each shall include a non-automatic, molded case circuit breaker that can be operated with the panel cover closed. The disconnect shall include a decorative trim to match the exterior trim of the unit. Each electric panel shall include starters, contactors, relays, transformers and dual-element fuses that protect each high-voltage circuit in the system. The electric panel shall be wired with one common electrical line connection.
2.1.4 Solid-State Control System
Each of the solid state control systems shall be powered from separate, non interconnecting 24 volt power sources. Each chiller module control system shall include the following: Start/Stop button, Silence button for the audible alarm; Manual reset circuit breakers; Back-lighted monitor panel (no message is visible until lit.)
The monitor panel shall display operating modes (Pump On, Cooling On) in white and alarm conditions in red. Alarm messages remain lit until the malfunction is corrected but the audible alarm may be silenced. If a second alarm condition occurs, the audible alarm shall sound again. The alarm panel shall activate with the following conditions:
No Water Flow
Low Water Temperature
High Water Temperature
High Compressor Head Pressure
Loss of Power