Liebert CRH204, CRH008, CRH011, CRH014, CRH016 Service Manual

...
R [004-032]
HIGH PERFORMANCE AIR COOLED CHILLER
SERVICE MANUAL
English
Cod. 273044
Rev. 25.05.2005
Issued by T.D.Service
Caution
S the manual is retained for the entire service life of the machine; S the user reads the manual carefully before carrying out any operations on the machine; S the machine is used exclusively for the purpose for which it is intended; incorrect use of the machine shall release the
manufacturer from any liability.
This manual has been prepared to enable the end ---user to carry out only those operations that can be done with the panels closed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified person­nel. Each machine is equipped with an electric isolating device which allows the operator to work in conditions of safety. This device must always be used to eliminate risks during maintenance (electric shocks, scalds, automatic restarting, moving parts and remote control). The panel key supplied with the unit must be kept by the person responsible for maintenance.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, read the identification labels affixed to the outside and inside of the unit.
IMPORTANT: This manual may be subject to modification; for complete and up --- to --- date information the user should

Index

1-- Introduction 1...............................................................................
1.1 --- Foreword 1....................................................................................
1.2 --- Responsibility 1................................................................................
1.3 --- Inspection 1...................................................................................
1.4 --- General description 1............................................................................
2 -- Preliminary Operations 1....................................................................
2.1 --- Operating limits 1...............................................................................
2.2 --- Sound pressure levels 2.........................................................................
2.3 --- Transport 2....................................................................................
2.4 --- Foundations 2..................................................................................
2.5 --- Service area 2..................................................................................
3 -- Installation 2................................................................................
3.1 --- Aeraulic connections 2..........................................................................
3.2 --- Hydraulic connections 2.........................................................................
3.3 --- Connection of the safety valve discharge 3.........................................................
3.4 --- Electrical connections 4..........................................................................
4 -- Start--Up and Operation 5...................................................................
4.1 --- Initial check 5..................................................................................
4.2 --- First start ---up (or after a long stop) 5...............................................................
4.3 --- Starting and stopping 5..........................................................................
4.4 --- Chillers serving special plants 5...................................................................
4.5 --- Freecooling 5..................................................................................
4.6 - -- Microprocessor control 5.........................................................................
5 -- Refrigerant and Oil Charge 5.................................................................
5.1 --- Refrigerant charge 5............................................................................
5.2 --- Oil charge 6...................................................................................
6 -- Safety Devices Settings 6....................................................................
6.1 --- Setting thermostatic expansion valve 7.............................................................
7 -- Maintenance 7..............................................................................
7.1 --- Spare parts 7..................................................................................
7.2 --- Dismantling the unit 7...........................................................................
8 -- Options and Accessories 8...................................................................
8.1 --- Pump set 8....................................................................................
8.2 --- Water chiller with partial heat recovery (20%) 8......................................................
8.3 --- Water chiller with total heat recovery (100%) 8.......................................................
8.4 --- Hydraulic circuit accessories 8....................................................................
8.5 --- Water chiller with inertia tank 9....................................................................
always consult the manual supplied with the machine.
Ta b l e s 10.........................................................................................
Drawings 20......................................................................................
Circuits 35........................................................................................
1 --- Introduction
C
1.1 --- Foreword
This handbook is aimed at enabling both the installer and the op­erator to carry out the correct installation, operation and mainte­nance of the refrigerating machine, without damaging it or caus­ing injuries to the relevant staff. The handbook is thus an aid for the qualified staff in the arrange­ment of the specific equipment for the correct installation, opera­tion and maintenance in compliance with the local regulations in force.
The MATRIX R water chillers can be identified as follows:
RH004
Cooling C apacity “kW”
Nominal cooling capacity / 10
Compressor: H Hermetic Scroll
Version: R Radial
Execution: C Chiller S Superchiller
1.2 --- Responsibility
Liebert Hiross accepts no present or future responsibility for damage to persons, things or to the machine itself due to opera­tors’ negligence, failing to comply with the installation, operation and maintenance instructions of this handbook, failed applica­tion of the safety norms in force for the system and the qualified staff charged with the operation and maintenance.
1 . 3 --- I n s p e c t i o n
All units are fully assembled and wired in the manufacturing plant. Before shipment they are charged with the necessary quantities of refrigerant and oil and then tested at the operating conditions normally required by the customer. The machine’s hydraulic circuit is equipped with drain plugs and open vent valves; the free ---cooling coils are supplied dry to avoid possible problems due to frostin the storage period. Immediately inspect the machine carefully on delivery to check for damage during transportation or missing components; possible claims must be made immediately to the carrier and the factory or its representa­tive.
1 . 4 --- G e n e r a l d e s c r i p t i o n
MATRIX R units with air ---cooled condensers have been de­signed and manufactured for producing chilled water. They are also available in versions with a built -- -in freecooling module, in versions with heat recovery for simultaneous heating of thermal circuit water, with a pump assembly installed on the machine and/or inertial buffer tank inside the machine; the chill­ing units can be equipped with several options indicated in the price list. The ”MATRIX R” product line has been designed utilising the state---of---the---art techniques available nowadays in the indus­try, and includes all the components necessary for automatic and efficient operation.
The Matrix R units are specifically designed for indoor installa­tion (protected from weather agents), for the connection with
ducts of condensation air in machine intake (if present) and outlet.
Each unit is completely factory assembled; after evacuation, the necessary quantity of refrigerant is added to the refrigerant cir­cuit(s) and the unit is tested. All the unitsare equipped with one or two independent refrigerat­ing circuits, each one composed of: an air --- cooled condenser, a hermetic Scroll compressor and a braze---welded plate evapo­rator. The components of the liquid line are the charging valves, filters - --dryers, solenoid valve, shut--- off valve, moisture indicator and thermostatic expansion valve. The hydraulic circuit -- - with max. working pressure 5 bar --- is made up on mod. 004---016 of hydraulic lines both in steel and flexible EPDM rubber, connected by fittings and threaded joints, on mod. 017 --- 032 of carbon steel pipes connected with grooved---end (Victaulic) fittings and couplingsand include also a flow switch (optional) and, in the freecooling versions, chilled water coils and a three - --way valve.
The hermetic scroll compressors are complete with the following protection/safety devices: oil heater (if necessary), electronic protection monitoring the temperature of the motor windings and the direction of rotation (the latter may be enclosed in the electronics of the compressor or external, depending on the model).
Fans are radial type, with aluminum reverse curved blades and structure, statically and dynamically balanced, directly coupled to a motor with external rotor. It is always available the fan speed controlwhich normally is achieved through an adjuster with con­tinuous speed modulation. By simply modifying the parameters(of the Microfacemicropro­cessor control), limiting the fan max. rotation speed, it is possible to change the useful air static pressure (equal to the difference of the static pressure between the delivery and suction ducts connected with the unit).
The ”MATRIX R” water chillers are controlled by the ”MICROFA­CE” microprocessor, managing all the unit operating conditions. The user can change and/or modify the operating parameters through the display keyboard installed on the electrical panel. The electrical control board is equipped with all the safety and operating devices required for reliable operation. The compres­sor motors are equipped with protection on all three phases and are started by three --- pole contactors.
2 --- Preliminary Operations
2.1 --- Operating limits
The units can operate within the indicated operating limits (see Tab. 6). These limits apply to new machines, subject to correct installation and maintenance.
S Ambient air minimum temperature: ---25ûC for Superchiller,
--- 1 0 ûC for Chiller (either Triac or EC fan);
S Maximum outdoor air temperature is in relation to each mod-
el, as indicated in Tab. 6. In any case outdoor temperatures aver 45ûC are not admitted; such limits are determined by electrical and electronic components fitted on units;
S Maximum water flow allowed: depending on the pressure
drop corresponding to the required thermal difference (usu­ally not lower than 3.5ûC --- 4 ûC);
S Minimum allowed water flow: compatible with a sufficient
evaporation temperature, to avoid the intervention of the safety devices (to be evaluated for a thermal difference not higher than 8ûC);
S Temperature range of the water exiting the evaporator: 4ûC
--- 1 5 ûC;
S Maximum temperature of the water entering the unit: 20ûC;
higher temperatures are allowed only at the system start--­up and not during normal operation;
S Maximum glycol concentration: 50% (35% with the optional
pump assembly installed on the machine);
1
S Minimum allowed glycol concentration: depending on the
minimum temperature of the ambient air expected at the installation site (see Tab. a);
S Maximum difference of air side pressure (between the one
in the delivery duct and the one, possibly negative, in the coil suction) equal to the max. one indicated in Tab. 9 next to the max. signal = 10 V set on the microprocessor;
S Maximum pressure of the hydraulic circuit: 5 bar; S Voltage range for the electric supply: 400 V
phase difference: 3%; tolerance on frequency: 1%.
Storage conditions: ---20ûC ÷ 45ûCforallMATRIXRmodels.
+
/
10%; max.
---
2.2 --- Sound pressure levels
The Tab. 7 shows the noise data for the units in standard config­uration (without pumps), operating continuously and measured at 1 m from the coil side unit, with ducted air delivery and 50 Pa of useful static pressure, in free field conditions. The highest noise levels are detected for higher useful static pressures of the air.
Note: Avoid positioning in areas with possible reverberation of the sound waves; acoustically insulate both the delivery and the in­take ducts (if installed); failure to do this can adversely effect the noise levels.
2 . 3 --- T r a n s p o r t
S Handle the unit by lifting it with a crane from above; S The lifting holes are positioned in the frame’s base (when lift-
ing, use spreader bars to protect the sides, see Fig. 3, Fig. 4 and Fig. 5).
Note: Place the lifting tubes in the holes in the base indicated by ”LIFT HERE”. Lock the ends of the tubes with the locking pins and splits pins as shown in Fig. 3 and Fig. 5. As an alternative (on mod. 004 --- 016 only), shackles/hooks (optional) fastened at the base ends can be used as a lifting system: in this case the lifting point must be on the vertical line passing through the machine’s centre of gravity (as indicated in Fig. 4) to prevent any load im­balance. The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the units, the capacity of the lift­ing gear and ropes and the condition and suitability of the afore­mentioned equipment.
2.4 --- Foundations
S The unit must be placed on a level surface which will support
its weight.
S If necessary, position the unit on suitable anti---vibration sup-
ports that can be supplied as an option (in rubber or spring --­type). Refer to the manual ”Installation of the spring anti --­vibration supports” for their correct positioning.
S When positioned, level the unit. Note:
For weight distribution see Fig. 6 and Fig. 7. Note:
The weights and their distribution refer to standard units without options; if the pump assembly, or other options are installed on the machine, add the weights of the installed accessories to those of the standard units (see Tab. 8).
2.5 --- Service area
S In order to allow free air flow or to enable the ducting installa-
tion and maintenance of the unit, a minimum area must be left free of obstructions around the unit (see Fig. 1 and Fig. 2).
S Avoid recirculation of hot air between the outlet and the out-
door intake of the air conveyed in the ducts, otherwise the unit performance may be impaired or the standard oper­ation can be interrupted.
3 --- Installation
3.1 --- Aeraulic connections
The Matrix R units are arranged with connection flanges for the air intake and delivery ducts; if the units are ordered with metal filters to protect the condensing coils, the connection flanges for theintakesideductingarenotsupplied,asthereisnoductto enable the cleaning of such filter.
Connect the ducts fitting flexible joints to prevent transmitting vibrations and to compensate thermal expansion. Check if the holes on the walls --- where the intake and delivery ducts are fitted --- are protected by suitable anti---rain grilles (equipped with pre --- filter like the intake ones) to avoid water or dust to enter in the chiller.
All fans are adjusted at the same speed, so that it is not necess­ary to install overpressure dampers next to each fan discharge. The units are supplied with a setting in the microprocessor for the max. fan speed of 50 Pa useful pressure; set the max. speed according to the features required by the installation (see Tab . 9) .
The units are supplied with the condensation air discharge up­wards; during the installation, it is possible to change the posi­tion of the air discharge opening (with right or left horizontal direction) by simply inverting the position of the drilled panel withtheclosedoneoftherequiredside(seesizedrawings).
3.1.1 -- External air temperature probe installation
Install the external air temperature probe (shipped inside the electric panel), at the end of the air intake duct. The bulb must be positioned as much outside as possible but must not be exposed to direct sunlight or weather agents such as rain or snow. The unit operation could be jeopardized if these precautions are not applied.
If the intake side duct is not present, fasten the probe in the room so that it can correctly detect the external temperature of the coil intake outer air without being influenced by other external factors (sun rays, rain or snow, other heat or radiation sources, etc.).
3.2 --- Hydraulic connections
3.2.1 -- Hydraulic circuit construction (Fig. a)
The piping must be connected to the chiller. Construct a chilled water circuit as described below, see Fig. a:
1) Place shut---off valves within the circuit to allow servicing;
2) Install a pump system suitable for the flow rate required at a pressure head equal to the sum of all the pressure drops (see project data). Matrix R chillers can be equipped, upon request, with pumps having performance as indicated in Tab. 8;
3) Install manometers at the chiller inlet/outlet;
4) Install thermometers at the chiller inlet/outlet;
5) Connect the pipes to the chiller by flexible joints to avoid transmitting vibrations and to balance the thermal expan­sion; proceed in the same way even if the pump set is out­side the chiller;
6) It is useful to include a water pressure switch to give an early warning of low water pressure;
7) Place a mesh filter at the inlets of the pump and water chiller (Can be supplied as an optional accessory --- Not fitted);
8) Install, at the highest points in the circuit, apparatus which allows the bleeding of air and possibly the filling of glycol;
9) Place a drain valve at the lowest point in the circuit and im­mediately at the outlet of the water chiller;
10) Install a water filling set including the following: a) filling water meter; b) manometer; c) non---return valve; d) air separator; e) removable supply tube, which must be disconnected
after each charge/top ---up;
2
11) For maximum protection ensure that all tubing exposed to low outdoor temperatures is fitted with anti ---freeze heaters and insulated using closed cell synthetic rubber (elasto­mer);
12) The circuit must include an expansion vessel (with safety valve) of suitable capacity;
13) Connect the lines avoiding stresses on the machine inner parts.
Note: If the water chiller is complete with an expansion vessel (sup­plied as an option), check if the capacity is enough, and install a second vessel in the circuit, if required (see par. 8.4). Follow the indications in Fig. c for the correct sizing.
Note: The whole circuit must contain a water volume suitable for the capacity of the installed chiller. Check if the inertial capacity giv­en by the sum of the hydraulic volume inside the machine (in­cluding the volume of the optional interna tank, if fitted) and the system volume is sufficient, or possibly install a tank in the circuit. Follow the indications in Fig. b for the correct sizing.
Note: The hydraulic circuit must ensure a constant water supply to the evaporator in every operating condition. Otherwise, the com­pressors may be damaged by repeated returns of liquid refriger­ant on their suction.
Note: The water flow switch is a compulsory safety component that must be installed and correctly wired to the Matrix R chillers, otherwise the guarantee will be invalidated. It is installed, as standard, on units with the optional on --- board pump set, and is available as a option for units without pumps on board: in the latter case the flow switch, if not installed on the machine, can be installed on the hydraulic circuit by the installer, butitiscompulsorythatitiswiredtotheelectricpanelterminal board, as indicated on the wiring diagram.
3.2.2 -- Addition of water and ethylene glycol
Very important: Add water and ethylene glycol to the circuit with a % depending
on the minimum temperature of the outside air expected at the installation site. Do not exceed the nominal operating pressure of the circuit’s components.
Notes:
S To avoid stratification run the circulation pump for at least 30
minutes after adding any glycol.
S After adding water to the hydraulic circuit always discon-
nect the water supply coming from the sanitary supply;
this avoids the danger of glycol entering the sanitary water system.
S After any topping --- up of the water check the concentration
and add glycol if necessary.
3.2.3 -- Water--gly col mixture
Water---glycol mixtures are used as the thermal carrier fluid in very cold climates or with temperatures below zero degrees cen­tigrade. Determine the ethylene glycol % which must be added to the water, with the assistance of T ab. a.
Tab.a--Ethyleneglycoltobeaddedtowater(%in
weight of total mixture)
Ethylene glycol
(% in weight)
Freezing tempera-
(*)
ture, ûC
Mixture density at
(*)
20ûC
,kg/l
(*) Values are for Shell antifreeze 402. For different brands, check
manufacturer’s data.
For the chiller internal water volume refer to Tab. 1. If the optional buffer tank is installed on the machine, add the tank hydraulic volume.
ALWAYS CHARGE THE HYDRAULIC CIRCUIT WITH THE RE­QUIRED GLYCOL % NECESSARY FOR THE MINIMUM AMBI­ENT TEMPERATURE AT THE INSTALLATION SITE. FAILING TO COMPLY WITH THIS INSTRUCTION SHALL INVALIDATE THE UNIT WARRANTY.
0 10 20 30 40 50
0 --- 4 . 4 --- 9 . 9 --- 1 6 . 6 --- 2 5 . 2 --- 3 7 . 2
--- 1.017 1.033 1.048 1.064 1.080
3.3 --- Connection of the safety valve dis­charge
Safety valves are installed on the high pressure side of the refrig­eration circuit(s): the discharge of these valves must be con­veyed outside through a suitable pipe, having a diameter of at least that of the valve outlet, without burdening the valve body. Convey the discharge to areas where the jet cannot harm people and the surrounding environment.
Fig. a --Ideal chilled water circuit
disconnect af-
ter charge
10e
10d10c10b10a
12
flow
9
Vpt
Ta n k
1 1327436
5
T T
CHILLER
5 5 9
USER
11
3
4
8
11
Fig. b --Inertia tank sizing
The total optimum hydraulic volume of the system where the Matrix R chiller is installed can be calculated by the following formula:
43 x Rt
V =
where:
--- V=minimum required total water volume expressed in litres
--- Rt=refrigeration capacity expressed in kW
--- Xd=differential band set on the control and expressed in degrees centigrade
Please note that the sum of the hydraulic volume of the Matrix R chiller (Vm) plus the volume of the hydraulic circuit connected to it (Vpc) must be greater than, or equal to the minimum required total water volume (V). If this condi­tion is not satisfied, it is necessary to install an inertia tank (Vpt, as indicated in the Fig. a) with a volume at least equal to the following value: Vpt=V ---Vm---Vpc
Fig. c --Sizing of the expansion vessel
The total volume of the expansion vessel is calculated with the following formula:
Xd
C x e
V =
1 --
Pi Pf
where:
-- - C=quantity of water inside the system expressed in litres
-- - e=water expansion coefficient, with water at 10ûC as a reference
-- - Pi=absolute pressure of initial charging, equivalent to the vessel pre --- charge pressure (typical value
2.5 bara)
-- - Pf=absolute final tolerated pressure, lower than the operating pressure of the safety valve calibration pressure (typical value 4.0 bara).
Use the values of the water expansion coefficient indicated in the table below:
H2OT[°C] Density [kg/m3] Expansion coefficient “e”
10 999.6 --- --- ---
20 997.9 0.0017
30 995.6 0.0040
40 992.2 0.0075
50 988.1 0.0116
3.4 --- Electrical connections
1) Before proceeding with the electrical connections, ensure that:
S all electrical components are undamaged; S allterminalscrewsaretight; S the supply voltage and frequency are in accordance with
the rating (with tolerance in accordance with IEC 8--- 6 norms, March 1990)
S the allowed phase to phase variability is 3% maximum
(see Fig. d). Variability in excess of 3% invalidates the guarantee.
2) Supply cable connections (see Tab. 5):
S Connect the cable to the supply terminals. S Use appropriately sized 3--- pole cable. An earth wire
must also be connected.
S After having opened the passagein the framework (pre ---
punched knock ---outs) for the supply line entry, restore the original degree of protection using suitable accesso­ries for the wiring and junction boxes.
Fig. d --Example of calculating phase
to phase variability
1) The 400 V supply has the following variability:
RS = 388 V ST = 401 V RT = 402 V
2) The average voltage is:
388 + 401 + 402
3
3) The maximum deviation from the average is:
402 --- 397 = 5 V
4) Thephasetophasevariabilityis:
5
x 100 = 1. 26 (acceptable)
397
= 397
RS T
4
Note: The power supply should never be disconnected, except when performing maintenance. Operate (open) the main switch before carrying out any mainte­nance work on electrical components.
Note: It is forbidden to work on the electrical components without using insulating platforms, and in the presence of water or fog or mist.
Note: The supply to the externalpump assembly must be made before starting the chiller and must be kept on as long as the chiller is in use. Incorrect operation will cause the unit to lock ---out be­cause of the internal protections (flow switch intervention).
Note: The compressors are equipped with an electronic protectionde­vice blocking their start if the phase sequence is not correct, or stopping their operation if a thermal relay intervenes. This device is essential for the integrity of the mechanical and electrical com­ponents of the compressors. Reset the standard functions by isolating this device and removing the causes of the lock---out.
Note: The chillers are equipped with their own microprocessor control adjustment. The use of the remote ON ---OFF input (located in the electric panel terminal board) as a system temperature con­trol element is forbidden.
7) During the unit start---up an inlet water temperature
higher than 20ûC is allowed. Under standard operating conditions check that the limits indicated in paragraph
2.1 are not exceeded.
8) Check the correct operation of the control and safety de­vices.
9) Check the outlet temperature of the chilled water (check if the set--- point set on the controller is reached).
10) Check the compressor oil level.
11) With the compressor at full load, check there are no bubbles visible in the frefrigerant sight glass. If there are any, charge the unit according to par. 5.
4.3 --- Starting and stopping
ALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEEN PREHEATED. FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THE CRANKCASE HEATER (IF ANY).
S Start the unit setting the Microprocessor switch ON. S Stop the unit setting the Microprocessor switch OFF. S In case of long stops, turn the machine off using the Micro-
processor switch OFF. In this case the compressor crankcase heaters (if any) re­main powered.
S For seasonal shutdown of the unit operate the main switch
locatedon the main electrical power supply. This will discon­nect the compressor crankcase heaters.
4 --- S t a r t --- U p a n d O p e r a t i o n
4.1 --- Initial check
1) Check all water connections.
2) Open the shut---off valve on the liquid line.
3) Ensure that the intake pressure is higher than 4.0 bar; if this is not the case, prolong pre --- heating of the compressor (if possible) and check that the refrigerant shut --- off valve is properly sealed, see Fig. 12, Fig. 13, Fig. 14, Fig. 15, Fig. 16 and Fig. 17.
4) Open all isolating valves and/or water ball valves.
5) In case of climates with temperatures below zero degrees C, make sure the chilled water circuit is filled with the correct concentration of water/glycol.
6) Bleed all air out of the chilled water circuit.
7) Verify the water flow rate and its direction.
8) Ensure that the thermal load is sufficient for start---up.
Caution: The ambient air temperature probe must be positioned in the shade and protected against the weather.
4 . 2 --- F i r s t s t a r t --- u p
(or after a long stop)
Operate as follows:
1) At least 8 hours before the start ---up, power the crank-
case heaters (if any, see point 4) by setting the main iso­lator switch ON. Make sure the auxiliary circuit has b een powered and check the operation (a fault due to an in­correct procedure will invalidate the compressor guar­antee).
2) Open the valves of the refrigeration circuit that had been closed before the initial check.
3) Check the machinery supplying the thermal load connected with the unit and start the system pump(s).
4) MAKE SURE THE COMPRESSOR OIL HAS BEEN HEATED FOR AT LEAST 8 HOURS; start the unit only then. In the units not equipped with crankcase heaters (Chillers for sum­mer operation only, without modulating fan speed control), the start must be carried out in the warm season only (exter­nal T > 15ûC), and thus oil pre---heating is not necessary.
5) Make sure the fans rotate in the correct direction (anticlock­wise): check the electrical connections, if necessary .
6) Make sure the pumps rotate in the correct direction.
4.4 --- Chillers serving special plants
The units are capable of cooling a water ---glycol mixture to tem­peratures close to 0ûC without the need for significant modifica­tions. In the case of modification, the set values of the safety and control components must also be changed. This can be carried out in the factory (at the time of testing) or at the time of installa­tion, only by qualified and authorised personnel.
4 . 5 --- F r e e c o o l i n g
The “freecooling” is a system of pre ---cooling and/or cooling the water/glycol mixture using ambient air when the latter is at a tem­perature below the return mixture temperature. If the outside temperature is sufficiently low to dissipate the entire heat load, the refrigeration compressors automatically switch off, and the mixture’s temperature is controlled by the fan speed adjust­ment. If the mixture temperature is too high for freecooling, the com­pressors will operate as long as necessary to ensure the correct water/glycol mixture temperature.
4.6 --- Microprocessor control
Consult the ”Microface and Hiromatic” Service Manual.
5 --- R e f r i g e r a n t a n d O i l C h a r g e
All work on pipes or components of the refrigerating circuit un­der pressure must be exclusively carried out by qualified staff, competent in such works.
5 . 1 --- R e f r i g e r a n t c h a r g e
WHILST REPAIRING THE REFRIGERATING CIRCUIT RE­COVER ALL THE REFRIGERANT IN A CONTAINER: DO NOT ALLOW IT TO ESCAPE. NEVER USE THE COMPRESSOR FOR THE SYSTEM VACUUM (THIS INVALIDATES THE WARRANTY).
S The unit is delivered charged according to the Tab. 2. Warning for the refrigerant charge:
S Ensure there are no refrigerant leaks. S Check the refrigerant type in the refrigeration circuit: a unit
originally charged by the manufacturer with R407C cannot be charged with R22 and vice versa; possibly apply to the Technical Support Department.
5
S Charge with the compressor in operation, connecting the
cylinder with the charge connector after the thermostatic ex­pansion valve. Flush the connection pipe between the cylinder and the charging point; tighten the seal joint and then start charging the unit. It is imperative that the cylinder is weighed both be­fore and after the operation.
S For the units with R407C the refrigerant charge must be
made exclusively with liquid refrigerant.
S Charge the unit until the bubbles in the sight glass have dis-
appeared and the working conditions of the entire refrigera­tion circuit have returned to normal (sub---cooling and su­perheating within the limits indicated below).
S Measure the superheating as follows:
1) Detect the temperature on the suction line, close to the bulb of the thermostatic expansion valve, using a contact thermometer.
2) Connect a pressure gauge (by max. a 30 --- cm pipe) with the Schraeder connection and read the corresponding saturated evaporating temperature.
3) The superheating is the difference between the two readings.
4) For the units with R407C refer to the pressure gauge scale indicated with the initials D.P. (Dew Point)
S Verify that the superheating is 5ûC --- 8 ûC. S Measure the sub---cooling as follows:
1) Detect the temperature on the liquid line using a contact thermometer.
2) Connect a pressure gauge (by max. a 30 --- cm pipe) with the Schraeder connection on the liquid line and read the corresponding saturated condensing temperature.
3) The sub --- cooling is the difference between the two read­ings.
4) For the units with R407C refer to the pressure gauge scale indicated with the initials B.P. (Bubble Point)
S Verify that at the condenser outlet, sub --- cooling is 3ûC ---
5ûC.
IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY. An excess of refrigerant causes an increase in sub --- cooling and
consequent operating difficulties in the hot season; a shortage of charge generates an increase in superheating and possible compressor stoppages. Whenever work is carried out on the unit, ensure afterwards that the working conditions are correct, checking sub---cooling and superheating.
5 . 2 --- O i l c h a r g e
Contact the TechnicalSupport Department for the specifications of the oil to be used for topping up; the oil changes according to thetypeofusedrefrigerant.
NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIP­ING COMPLETELY BEFORE CHANGING THE TYPE OF OIL USED.
TOP ---UPS OF UP TO 20---30% OF THE TOTAL AMOUNT OF OIL CONTAINED IN THE COMPRESSOR CRANKCASE ARE PERMITTED; FOR LARGER PERCENTAGES CONTACT THE TECHNICAL SUPPORT DEPARTMENT.
5.2.1 -- Procedure for oil topping--up
If there has been any loss of oil then this must be topped up as follows:
1) T ake a clean, dry, transparent container (with volume cal­ibrations) and fill it with at least twice the amount of oil re­quired.
2) Isolate the compressor by closing the cock on the liquid line.
3) Connect to the fittings on the compressor body (Schraeder valves) and empty it of refrigerant until atmospheric pres­sure (1 bar) is reached.
4) Using a pipe, connect the oil containerto the oil service fitting on the lower part of the compressor.
5) Open the oil service cock, lifting the container, so that the oil flows by gravity.
6) Charge the required quantity of oil (make sure the tube al­ways remains below the oil level in the container).
7) Stop the oil flow by closing the oil service fitting, open the shut---off cock on the refrigerating circuit and restore the drained refrigerant charge.
6 --- Safety Devices Settings
The water chiller has already been tested and set up by the manufacturer. The following setting values are suggested in the field.
COMPONENT SETTING NOTES
diff.set
Operation with R407C/R22 (standard factory setting):
Low pressure switch (LP)
High pressure switch (HP)
START : 3.6 bar DIFF. : 0.8 bar STOP : 2.8 bar
Operation with R407C/R22 (standard factory setting):
STOP : 26 bar START : 20 bar DIFF. : 6 bar (fixed)
The settings for the safety valves installed on the machine are indicated below:
MODELS SETTINGS SAFETY VALVE
004 ---204 --- 206 --- 207 --- 008 28 bar
006 ---007 --- 011 --- 014 --- 016
017 ---020 --- 023 --- 025 --- 028 ---030 --- 032
29 bar
reset
0.2
5
bar
HP side
1.5
0.5
bar
6
6.1 --- Setting thermostatic expansion valve
THIS OPERATION MUST BE PERFORMED BY AN EXPERI­ENCED REFRIGERATION TECHNICIAN. Before beginning this adjustment be sure that the refrigerant
charge is correct, checking the the sub --- cooling (3ûC---5ûC, as
specified in par. 5.1). The valve has already been factory--- set and should be reset when the superheating is not between 5ûC --- 8 ûC, as follows:
1) Important:
Ensure that the instructions in par.5.1 have been carried out.
2) Allow the compressor to operate for 15 mins.
3) Measure the superheating as follows:
a) Connect a manometer to the Schraeder connection lo-
cated on the evaporator outlet tube, and read the mano­metric temperature on the scale for the refrigerant used (for the units with R407C refer to the pressure gauge scale indicated with the initials D.P. = Dew Point).
b) Using a contact thermometer, measure the temperature
on the tube coming out of the evaporator, next to the socket used for the manometer.
7 --- Maintenance
The Maintenance Programme below must be carried out by a qualified technician, preferably working under a maintenance contract.
Before any intervention on the unit or accessing the inner com­ponents (removing the outer panels), always ensure the ma­chine is switched off. If the panels are removed (fans compart­ment) wait for the fan(s) to come to a complete stop before accessing the compartment; if the front panels are removed (on mod. 004 ---016) or the front lower panels (on mod. 017 --- 032), pay special attention when working near the compressor upper part and the discharge line: they are very hot; possibly wait for them to cool. Be very careful when operating close to the finned coils, as the fins are very sharp. Do not remove the fan protection grille before electrically isolating the whole machine. Do not in­sert foreign matter through the fan protection grille. After the maintenance interventions, always close the unit with the suit­able panels, fastened by the tightening system.
c) The superheating is the difference between the two
readings (b ---a).
4) The superheating must be 5ûC---8ûC; if not, set the expan-
sion valve as follows: a) Remove the protective cover; b) Turn the adjustment screw to return to the optimum val-
ues, tightening it in a clockwise direction to increase the superheating, or slackening it to reduce the superheat-
ing. c) Wait about 10 minutes; d) Measure the superheating and repeat the operation if
necessary.
N.B: If the superheating is too low, there is a risk of poor lubrication
and consequent breakage of the compressor as a result of pres­sure shock. If the superheating is too high the output of the system is limited and the compressor overheats.
7.1 --- Spare parts
The use of original spare parts is recommended. When placing an order refer to the ”Component List” enclosed with the machine and quote the unit model no. and serial no.
7.2 --- Dismantling the unit
The machine has been designed and built to ensure continuous operation. The working life of some of the main components, such as the fans and the compressors, depends on the maintenance that they receive. If the unit has to be dismantled, the job must be done by skilled refrigeration technicians. The refrigerant and the lubricating oil in the circuit must be dis­posedofinconformitywiththelawsinforceinyourcountry.
Maintenance programme -- Monthly check
S Check that the fan motor rotates freely without any abnormal noise, and ensure that the
FANS
CONDENSER AND AIR FILTER
CONTROL S Check that the control equipment, LEDs and display are operating correctly.
ELECTRICAL CIRCUIT
REFRIGERATION CIRCUIT
CHILLED WATER CIRCUIT
bearings are not running hot.
S Also check the current absorption.
S Check the conditions of the filters (if they are supplied); if necessary clean them (including
the electrical panel ventilation filter).
S Check the condenser coils and clean if necessary with compressed air or soft brushes.
S Check the electrical supply on all phases. S Ensure that all electrical connections are tight.
S Check the condensing and the evaporating pressures (to be done by a refrigeration techni-
cian).
S Check the compressor’s current absorption, the delivery temperature and possible unusual
noises.
S Check the refrigerant charge by means of the sight glass. S Check that the safety devices operate correctly.
S Check the correct operation of the thermostatic valve (superheating between 5ûC --- 8ûC). S Check that the oil level indicated by the compressor sight glass is higher than the min. value.
S Ensure that there are no water leaks. S Bleed any air out of the hydraulic circuit using the bleed valves. S Verify that the water flow rate is correct. S Check the inlet --- outlet liquid temperature and pressure. S Check the correct operation of the three---way valve (Versions with free---cooling only). S Check if the system is charged with the specified glycol percentage and that no ice has
formed in the hydraulic circuit.
S Check the evaporator cleanliness.
7
8 --- O p t i o n s a n d A c c e s s o r i e s
8 . 1 --- P u m p s e t
On mod. 004 --- 016 the centrifugal pump units are direct driven, with close-- -coupled motors and a single shaft; the induction mo­tor has 2 poles with IP 54 protection and class F insulation.
The materials used for the pump main components are: S Pump body in plastic material PA 6.6 (cast iron in all high
pressure freecooling versions and on model 016 in the Chil­ler high head pressure version and Superchiller standard head pressure version);
S Impeller in in plastic material PPO (stainless steel in all high
pressure freecooling versions and on model 016 in the Chil­ler high head pressure version and Superchiller standard head pressure version);
S Stainless steel shaft; S Graphite impregnated ceramic mechanical seal (EPDM in
all high pressure freecooling versions and on model 016 in the Chiller high head pressure version and Superchiller standard head pressure version), suitable for the use of mix­tures containing ethylene glycol.
The pump units have been chosen and sized to operate within specific limits, namely:
S Water / ethylene glycol mixtures up to 65% / 35% by weight; S Temperatures of the standard pumped fluid not lower than
4°C.
The hydraulic circuitincludes,for each pump, a suctionshut---off valve and a delivery check valve if two pumps are installed, or suction and delivery shut---off valves if a single pump is installed.
On mod. 017 --- 032 the centrifugal pump units are direct driven, with close-- -coupled motors and a single shaft; the induction mo­tor has 2 poles with IP 55 protection and class F insulation.
Pump casings and impellers are in cast iron EN -- -GJL 200, shafts are in stainless steel, the shaft seal is a unbalanced, mechanical shaft seal with dimensions according to DIN 24 960 and assem­bly length according to EN 12 756, brass neck ring permits ideal conditions for the use of water mixtures containing ethylene gly­col. The pump housing, the motor stool and the motor stator housing are electrocoated.
The pump units have been chosen and sized to operate within specific limits, namely:
S Water / ethylene glycol mixtures up to 65% / 35% by weight; S Temperatures of the standard pumped fluid not lower than
4°C.
The motor stool forms connection between the pump housing and the motor, and is equipped with a manual air vent screw for venting of the pump housing and the shaft seal chamber. It is very important to carry out this operation as the circulation of liq­uid through the duct of the air vent screw ensures lubrication and cooling of the shaft seal.
Between the outlets of the two chambers and the discharge flange, twin --- head pumps have a non --- return flap valve in EPDM rubber. The flap is opened by the flow of the pumped liq­uid and cuts off the port of the idle pump chamber.
In the electrical panel there are, for all the models of pumps, au­tomatic circuit breakers for each pump; the microprocessor con­trol manages the operating rotation between the two pumps and start---up of the stand ---by pump if the primary pump fails.
For the technical features of the pumps and the hydraulic sche­matic see Tab. 8, Fig. 18, Fig. 19, Fig. 20, Fig. 21, Fig. 21 and Fig. 22.
8.2 --- Water chiller with partial heat recovery (20%)
This option enables the recovery of up to 20% of the heat normal­ly rejected by the condensers. The system does not require any adjustment and is made up of plate heat exchangers installed on each circuit before the condenser. The exchangers are pro-
tected by a suitable anti --- frost heater that operates when the sy­stem is stopped. It is recommended that a safety valve be installedin the hydraulic circuit to avoid hazards due to overpres­sures, if there is no water flow through the recuperator.
The water temperature at the recuperator inlet (in stable operat­ing conditions) must be in the range of 25ûC --- 45 ûC, with an out­let differential of between 3.5ûC --- 8 ûC.
8.3 --- Water chiller with total heat recovery (100%)
All heat discharged by the unit to the condenser is recovered. The system includes an additional refrigerating circuit made up of a three --- way solenoid valve, supplying --- in case of hot water demand --- a plate exchanger, usually by --- passed and sized so as to discharge all condensing heat (also installed before the finned air condenser in series with it); a check valve, a liquid re­ceiver at the exit of the finned air condenser working as storage for the needed additional refrigerant charge (see refrigerating scheme). The recuperator is insulated with closed cell polyure­thane and is equipped with heaters activated when the recuper­ator is deactivated to prevent frost in winter with the system stopped or not perfectly drained. The operation in total recovery mode is enabled by an external contact. The Microface control will simultaneously suit the fan speed changing the fan speed setpoint differently from the stan­dard operation without recovery (practically slowing the fans down till they switch off); anyway , the operation in recovery mode is enabled also without load at the users. Indeed, if the us­ers do not demand heat, the water flowing to the condenser reaches a temperature that does not enable the total condensa­tion of the compressed gas, and the remaining portion of the phase change can thus take place in finned coil without inter­rupting the recovery process through the intervention of the ma­chine safety devices. If the plate exchanger is supplied with too cold water, or if the sy­stem is not preset by the installation technician with a three or two---way proportional adjustment valve for the exchanger by­pass (indispensable for cold starts, see following “Recom­mended hydraulic circuit” ), the condensing pressure tends to decrease too much; a prolonged condition of low condensing temperature below the safety threshold leads the Microface mi­croprocessor control to disable the heat recovery, protecting the system from any possible malfunctioning.
Fig. e -- Recommended hydraulic circuit
Heat recovery users
Heat recovery exchanger
8.4 --- Hydraulic circuit accessories
Made up of an expansion vessel (pre --- charged at 1.5 bar, max. operating pressure 10 bar) and a safety valve, set at 5 bar. Their position in the hydraulic circuit is illustrated in Fig. 18, Fig. 19, Fig. 20, Fig. 21, Fig. 21 and Fig. 22.
S Expansion vessel volume:
-- - 8 litres for all 004 ---016 units,
-- - 12 litres for all 017 ---032 units.
It is recommended that the total required expansion vessel ca­pacity is always checked, depending on the unit’s internal hy­draulicvolume(withthevolumeofthebuffertank,ifinstalled), the user circuit volume, the glycol percentage in the mixture, and the expected maximum temperature variation of the mixture.
The water flow switch is a compulsory device protecting the unit. It is installed, as standard, on units with the optional on --- board pump set, and is available as a option for units without pumps
8
on board: in the latter case the flow switch, if not installed on the machine, must be installed on the hydraulic circuit by the install­er and wired to the electric panel terminal board, as indicated on the wiring diagram.
8.5--- Waterchillerwithinertiatank
The machine can be supplied complete with a buffer tank; it per­forms the inertial stabilizer function, for better compressor op­eration, summed up in the following two points:
S it reduces the frequency of the compressor peaks, which is
higher the lower the system thermal inertia, improving their performance;
S it naturally eliminates the operational problems caused by
sudden load variations (shown by variations of the chilled water temperature).
The buffer tank is supplied insulated, with a drain valve, vent valve and connection for immersion electric heaters; maximum operating pressure 6 bar.
Builtincarbonsteelandcoatedwithanti---condensationinsula­tion. It can be installed in all MATRIX R 004 --- 016 versions inside the coil compartment, while on mod. 017 - --032 it is installed in­side a cabinet which can be supplied either already connected to the unit (mechanically and hydraulically jointed to it) or loose (completely separate from the unit).
Mod. 004 ---006 --- 007 technical data
S Internal volume: 200 litres S Net weight: 110 kg S Working weight: 310 kg
Mod. 008 ---011 --- 014 ---016 technical data
S Internal volume: 400 litres S Net weight: 140 kg S Working weight: 540 kg
Mod. 204 ---206 --- 207 technical data
S Internal volume: 160 litres S Net weight: 100 kg S Working weight: 260 kg
Mod. 017 ---032 technical data
S Internal volume: 1000 litres S Net weight: 400 kg S Working weight: 1400 kg
9
Tab. 1 --- Internal hydraulic volume
Model Unit volume
004 8 004 37
006 9 006 38
007 14 007 75
204 10 204 39
CRH
CRH 025 45 SRH 025 158
(*) Add the tank’s volume for the units with optional buffer tank
206 10
207 18
008 24 008 97
011 27 011 101
014 38 014 146
016 46 016 156
017 37 017 129
020 37 020 129
023 45 023 158
028 51 028 186
030 60 030 195
032 60 032 195
(*)
[l] Model Unit volume
SRH
206 40
207 79
(*)
[l]
Tab. 2 --- R 407C refrigerant and oil charge
CRH 004--016
Models 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [kg] 12.6 7.5 13.9 7.7 23.7 12.9 12.9 14.5 19.9 20.8
Oil charge (each circuit) [lt] 6.2 8.0 8.0 3.25 3.25 3.3 6.2 8.0 8.0 8.0
CRH 017--032
Models 017 020 023 025 028 030 032
Refrigerant charge (each circuit) [kg] 21.0 21.6 30.7 30.8 36.8 39.4 39.5
Oil charge (each circuit) [lt] 12.4 14.2 16.0 16.0 16.0 16.0 16.0
SRH 004--016
Models 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [kg] 12.6 7.5 13.9 7.7 23.7 12.9 12.9 14.5 19.9 20.8
Oil charge (each circuit) [lt] 6.2 8.0 8.0 3.25 3.25 3.3 6.2 8.0 8.0 8.0
SRH 017--032
Models: 017 020 023 025 028 030 032
Refrigerant charge (each circuit) [kg] 21.0 21.6 30.7 30.8 36.8 39.4 39.5
Oil charge (each circuit) [lt] 12.4 14.2 16.0 16.0 16.0 16.0 16.0
10
Ta b . 3 --- CR H / S R H 0 0 4 --- 0 3 2 --- P a r t i a l h e a t r e c o v e r y ( 2 0 % )
CRH/SRH 004--016
Model
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: outdoor temperature 35ûC, water inlet/outlet 12/7ûC (Chiller versions), glycol mixture 30% inlet/outlet 15/10ûC (SuperChiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
004 204
10,8 14,8 18,2 21,6 29,6 36,4 44,3
0,516 0,707 0,870 1,032 1,414 1,739 2,117
8 11 14 8 11 14 21
1” 1” 1” 11/4” 11/4” 11/4” 11/4”
CRH/SRH 017--032
Model 017 020 023 025 028 030 032
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: outdoor temperature 35ûC, water inlet/outlet 12/7ûC (Chiller versions), glycol mixture 30% inlet/outlet 15/10ûC (SuperChiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
40 48 56 62 68 79 86
1.91 2.29 2.68 2.96 3.25 3.77 4.11
15 20 16 19 16 17 20
006 206
007 207
008 011 014 016
2”
Tab. 4 --- CRH/SRH 004 ---032 --- Total heat recovery (100%)
CRH/SRH 004--016
Model
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: water inlet/outlet 12/7ûC (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
004 204
53 74 91 105 144 177 223
2,53 3,54 4,35 5,02 6,88 8,46 10,65
60 70 80 60 70 80 90
2” 2” 2” 21/2” 21/2” 21/2” 21/2”
CRH/SRH 017--032
Model 017 020 023 025 028 030 032
Heating capacity
Water flow
Water pressure drop
Water connections
Working conditions: water inlet/outlet 12/7ûC (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.
kW
l/s
kPa
B S P --- T
212 238 290 320 357 412 453
10.13 11.37 13.86 15.29 17.06 19.68 21.64
52 65 71 82 83 85 99
006 206
007 207
DN 80 --- 3”
008 011 014 016
11
Tab. 5 --- Electrical characteristics
CRH 004--016 -- R 407C
Size 004 204 006 206 007 207 008 011 014 016
Power supply --- 400 V / 3 Ph / 50 Hz
(1)
OA FLA LRA Compressors power input Compressors nominal current
(1)
(1)
Compressor max. current Fans power input
Fans max. power input Fans max. current
SHC std. head pressure pump model (Opt.) Std. head pressure pump motor nom. power Std. head pressure pump motor max. power Std. head pressure pump max. current SHC high head pressure pump model (Opt.) FHE high head pressure pump model (Opt.) High head pressure pump motor nom. power High head pressure pump motor max. power High h ead pressure pump max. current
Electrical cable section (min.) mm216 16 25 25 35 35 35 50 70 95
(1) Outdoor air temperature 35ûC ; water inlet/outlet temperature 12/7ûC.
Nominal air flow and 50 Pa available air static pressure.
A A A
kW
A A
kW
kW
A
--­kW kW
A
---
--­kW kW
A
31 43
183
13.2 23 35
2.9
32 46
125
13.2 24 19
2.9
40 58
223
19.3 32 50
3.3
12 --- 129
0.75
1.08
1.85
12 --- 136
---
1.1
1.44
2.67
42 66
167
19.0 34 29
3.3
48 77
278
24.1 40 69
3.1
50 72
185
24.6 42 32
3.1
4.9
8.2
12 --- 136
62 86
226
26.3 46 35
5.8
1.1
1.44
2.67
20---128
---
1.5
1.92
3.90
80 116 281
38.6 64 50
6.8
20 --- 128
1.5
1.92
3.90
20 --- 134
1.85
2.45
4.61
99 163 364
43.6 74 69
10.1
20---134
---
40---160/40
123 169 417
59.4 98 72
10.2
1.85
2.45
4.61
---
4.0
4.0
8.50
CRH 017--032 -- R 407C
Size 017 020 023 025 028 030 032
Power supply --- 400 V / 3 Ph / 50 Hz
(1)
OA FLA LRA Compressors power input Compressors nominal current
(1)
(1)
Compressor max. current Fans power input
Fans max. power input Fans max. current
SHC std. head pressure pump model (Opt.) Std. head pressure pump motor power Std. head pressure pump max. current High head pressure pump model (Opt.) High head pressure pump motor power High h ead pressure pump max. current
Electrical cable section (min.) mm
(1) Outdoor air temperature 35ûC ; water inlet/outlet temperature 12/7ûC.
Nominal air flow and 50 Pa available air static pressure.
A A A
kW
A A
kW
kW
A
---
kW
A
---
kW
A
125 165 305
57.3 100
35
9.7
135 195 360
64.9 110
50
9.7
163 233 398
77.7 130
50
13.1
183 271 472
90.1 150
69
13.1
4.9
8.2
65 --- 190/2
2.2
4.45
65 --- 260/2
4.0
8.00
2
70 95 120 150 185 185 185
65 --- 230/2
3.0
5.95
65 --- 260/2
4.0
8.00
199 317 518
94.5 158
69
16.5
225 323 571
111.7 184
72
16.5
65 --- 260/2
4.0
8.00
65 --- 340/2
5.5
11.20
245 329 577
124.8 204
72
18.1
12
SRH 004--016 -- R 407C
Size 004 204 006 206 007 207 008 011 014 016
Power supply --- 400 V / 3 Ph / 50 Hz
(1)
OA FLA LRA Compressors power input Compressors nominal current
(1)
(1)
Compressor max. current Fans power input
Fans max. power input Fans max. current
SHC std. head pressure pump model (Opt.) FHE std. head pressure pump model (Opt.) Std. head pressure pump motor nom. power Std. head pressure pump motor max. power Std. head pressure pump max. current SHC high head pressure pump model (Opt.) High head pressure pump motor nom. power High head pressure pump motor max. power High h ead pressure pump max. current
kW
kW
kW
kW kW
kW
A A A
A A
A
---
---
A
---
A
32 43
183
13.4 24 35
3.2
12 --- 136
---
1.1
1.44
2.67
32---160/30
3.0
6.50
32 46
125
13.4 24 19
3.2
41 58
223
19.8 33 50
3.8
42 66
167
19.4 34 29
3.8
49
50
77
72
278
185
24.8
25.0
41
42
69
32
3.3
3.3
20 --- 128
---
1.5
1.92
3.90
32 --- 160/30
3.0
6.50
4.9
8.2
64 86
226
26.7 48 35
6.5
82 116 281
39.6 66 50
7.6
20 --- 134
---
1.85
2.45
4.61
40---160/40
4.0
8.50
101 163 364
44.5 76 69
11.4
40---160/40
40---200/75
Electrical cable section (min.) mm216 16 25 25 35 35 35 50 70 95
(1) Outdoor air temperature 35ûC; 30% glycol water mixture; water inlet/outlet temperature 15/10ûC.
Nominal air flow and 50 Pa available air static pressure.
SRH 017--032 -- R 407C
Size 017 020 023 025 028 030 032
Power supply --- 400 V / 3 Ph / 50 Hz
(1)
OA FLA LRA Compressors power input Compressors nominal current
(1)
(1)
Compressor max. current Fans power input
Fans max. power input Fans max. current
Std. head pressure pump model (Opt.) Std. head pressure pump motor power Std. head pressure pump max. current High head pressure pump model (Opt.) High head pressure pump motor power High h ead pressure pump max. current
Electrical cable section (min.) mm
(1) Outdoor air temperature 35ûC; 30% glycol water mixture; water inlet/outlet temperature 15/10ûC.
Nominal air flow and 50 Pa available air static pressure.
kW
kW
kW
kW
kW
A
127
A
165
A
305
58.5
A
102
A
35
10.8
137 195 360
66.5 112
50
10.8
165 233 398
79.7 132
50
14.6
185 271 472
92.5 152
69
14.6
203 317 518
96.9 162
69
18.3
4.9
A
---
65 --- 260/2
4.0
A
---
8.00
65 --- 340/2
5.5
A
2
11.20
70 95 120 150 185 185 185
8.2
65 --- 340/2
5.5
11.20
65 --- 410/2
7.5
15.20
229 323 571
114.8 188
72
18.3
65 --- 410/2
7.5
15.20
65 --- 460/2
11.0
21.40
249 329 577
128.1 208
72
20.3
125 169 417
60.8 100
72
11.4
---
4.0
4.0
8.50
7.5
15.50
Nominal power supply = 400 V; 3 Ph; 50 Hz
Nominal power supply tolerance = 400 V ±10 %
Max. voltage unbalance = 3 %
The cables have to be sized in compliance with local standards and according to the type and characteristics of installation. Suggested cables sectionare referred to PVC insulation with a max. working temperature of 70 ûC and an ambient temperature of 30 ûC.
13
Tab. 6 --- Operating limits
CRH 004--016 -- R 407C
Size 004 006 007 204 206 207 008 011 014 016
Working Ra nge
Max. outdoor air temperature
Safety Device Settings
High pressure switch High pressure safety valve Low pressure switch
(1)
With nominal air flow; water flow outlet at 7û C ; full load
CRH 017--032 -- R 407C
Size 017 020 023 025 028 030 032
Working Ra nge
Max. outdoor air temperature
Safety Device Settings
High pressure switch High pressure safety valve Low pressure switch
(1)
With nominal air flow; water flow outlet at 7û C ; full load
(1)
ûC 45 45 42 42 42 42 45 43 45 42
Barg Barg Barg
(1)
ûC 42.5 40.5 42.5 40.5 43.0 40.0 39.5
Barg Barg Barg
26.0
28.0 / 29.0
2.8
26.0
29.0
2.8
SRH 004--016 -- R 407C
Size 004 006 007 204 206 207 008 011 014 016
Working Ra nge
Max. outdoor air temperature
(2)
ûC 45.0 45.0 41.5 41.5 41.0 41.0 45.0 42.0 45.0 41.0
Safety Device Settings
High pressure switch High pressure safety valve Low pressure switch
(2)
With nominal air flow; 30% mixture flow outlet at 10ûC ; full load
Barg Barg Barg
SRH 017--032 -- R 407C
Size 017 020 023 025 028 030 032
Working Ra nge
Max. outdoor air temperature
Safety Device Settings
High pressure switch High pressure safety valve Low pressure switch
(2)
With nominal air flow; 30% mixture flow outlet at 10ûC ; full load
(2)
ûC 41.5 39.5 41.5 39.5 42.0 39.0 38.5
Barg Barg Barg
26.0
28.0 / 29.0
2.8
26.0
29.0
2.8
14
Ta b . 7 --- No i s e l e v e l s
Model
s
Model
s
The following table indicates the overall sound pressure level at full load conditions, measured 1m from the unit, coil side, with ducted air discharge (50 Pa static pressure), with an outdoor temperature of 35 ûC and referred to free field conditions.
Tota l
Models
sound level
[dB(A)]
CRH / SRH 004 --- 204 70 CRH / SRH 017 74.5
CRH / SRH 006 --- 206 73 CRH / SRH 020 74.5
CRH / SRH 007 --- 207 74 CRH / SRH 023 75
CRH / SRH 008 71.5 CRH / SRH 025 75
CRH / SRH 011 74.5 CRH / SRH 028 76
CRH / SRH 014 75.5 CRH / SRH 030 76
CRH / SRH 016 75.5 CRH / SRH 032 78
Tab. 8 --- Pump set characteristics (opt.)
2 pole pump set, standard head pressure (data refers to each pump)
Models 004 204 006 206 007 207 008 011 014 016
Water flow
CRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
kPa
Nr.
---
kW
dB(A)
kg
6.79 6.79 8.86 8.73 10.94 11.11 13.41 17.53 22.78 28.00
127 156 122 146 104 127 141 142 88 78
1 2
12---129 12---136 20 --- 128 20 --- 134
0.75 1.1 1.5 1.85
10.4 12.7 13.8 15.4
Tota l
Models
sound level
[dB(A)]
58 63 65
2 pole pump set, high head pressure (data refers to each pump)
Models 004 204 006 206 007 207 008 011 014 016
Water flow
CRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
kPa
Nr.
---
kW
dB(A)
kg
6.79 6.79 8.86 8.73 10.94 11.11 13.41 17.53 22.78 28.00
169 198 163 187 145 168 167 191 145 173
1 2
12---136 20---128 20 --- 134 40---160/40
1.1 1.5 1.85 4
58 63 65 70
12.7 13.8 15.4 42
2 pole pump set, standard head pressure (data refers to each pump)
Models 017 020 023 025 028 030 032
Water flow
CRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
26.93 29.26 35.67 38.38 44.20 50.71 55.23
kPa
119 107 136 123 145 111 73
Nr.
---
65---190 / 2 65-- -230 / 2 65---260 / 2
kW
dB(A)
kg
2.2 3 4
60 59 63
57.9 / 116.4 69.3 / 139.2 74.3 / 149.2
1/2
15
2 pole pump set, high head pressure (data refers to each pump)
Models 017 020 023 025 028 030 032
Water flow
CRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
26.93 29.26 35.67 38.38 44.20 50.71 55.23
kPa
197 187 182 170 230 204 173
Nr.
---
kW
dB(A)
kg
65---260 / 2 65 --- 340 / 2
4 6
74.3 / 149.2 89.2 / 178.9
2 pole pump set, standard head pressure (data refers to each pump)
Models 004 204 006 206 007 207 008 011 014 016
30% glycol/water mixture flow
SRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
kPa
Nr.
---
kW
dB(A)
kg
7.83 7.83 10.26 10.08 12.58 12.64 15.45 20.12 26.24 31.92
98 142 62 100 93 128 96 91 50 79
1 2
12---136 20---128 20 --- 134 40---160/40
1.1 1.5 1.85 4
58 63 65 70
12.7 13.8 15.4 42
1/2
63
2 pole pump set, high head pressure (data refers to each pump)
Models 004 204 006 206 007 207 008 011 014 016
30% glycol/water mixture flow
SRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
kPa
Nr.
---
kW
dB(A)
kg
7.83 7.83 10.26 10.08 12.58 12.64 15.45 20.12 26.24 31.92
233 277 183 221 199 234 197 170 138 223
1 2
32---160/30 40---160/40 40 --- 200/75
2 pole pump set, standard head pressure (data refers to each pump)
Models 017 020 023 025 028 030 032
30% glycol/water mixture flow
SRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
31.06 33.49 41.26 43.98 51.08 58.3 63.27
kPa
kW
dB(A)
77 51 118 92 103 146 94
Nr.
---
65---260 / 2 65--- 340 / 2 65---410 / 2
4 5.5 7.5
63 63 68
kg
74.3 / 149.2 89.2 / 178.9 91.1 / 182.7
3 4 7.5
66 70 74
35 42 64
1/2
2 pole pump set, high head pressure (data refers to each pump)
Models 017 020 023 025 028 030 032
30% glycol/water mixture flow
SRH
Available head pressure
Pump quantity
Pump rotor model
Nominal motor power
Noise level
(*)
Pump weight
(*) According to ISO 3744
m3/h
31.06 33.49 41.26 43.98 51.08 58.3 63.27
kPa
157 133 207 183 190 205 159
Nr.
---
65---340 / 2 65--- 410 / 2 65---460 / 2
kW
dB(A)
kg
5.5 7.5 11
63 68 65
89.2 / 178.9 91.1 / 182.7 149.4 / 306.4
16
1/2
Tab. 9 --- Fan performances and settings
Standard air flow [12000 m3/h], 3 Ph fan + TRIAC
Models: CRH 004 --- 204 --- 008
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 004 --- 204 --- 008
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Standard air flow [12000 m3/h], EC fan
Models: CRH 004 --- 204 --- 008
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 004 --- 204 --- 008
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
50
5.0 1034 2860
87
50
5.3 1081 3210
88
50
8.2 1041 1560
86
50
8.6 1099 1910
87
100
5.2 1066 3090
88
100
5.5 1113 3430
88
100
8.5 1080 1790
100
8.9 1135 2140
87
88
150
5.4 1097 3320
88
150
5.7 1143 3620
89
150
8.8 1117 2030
87
150
9.2 1172 2390
88
200
5.6 1128 3530
88
200
5.9 1173 3810
89
200
9.1 1153 2270
88
200
9.5 1208 2650
88
250
5.8 1158 3720
89
250
6.1 1204 4010
89
250
9.4 1190 2520
88
250
9.8 1242 2910
89
300
6.0 1189 3910
89
300
6.5 1236 4170
90
300
9.6 1225 2780
89
290
10.0 1270 3120
89
350
6.3 1220 4090
89
350
6.9 1268 4330
90
350
9.9 1259 3040
89
400
6.7 1252 4250
90
400
7.6 1298 4510
91
370
10.0 1270 3120
89
450
7.2 1283 4420
90
450
8.6 1328 4680
91
500
7.9 1313 4600
91
490
10.0 1351 4810
91
550
9.5 1343 4760
91
570
10.0 1352 4810
91
Standard air flow [14000 m3/h], 3 Ph fan + TRIAC
Models: CRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Standard air flow [14000 m3/h], EC fan
Models: CRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 006 --- 206 --- 011 --- 014 --- 016
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
50
5.6 1162 3320
91
50
6.1 1215 3760
92
50
9.1 1165 2100
90
50
9.7 1232 2610
91
100
5.8 1189 3550
91
100
6.4 1243 3970
92
100
9.4 1200 2360
90
100
9.9 1264 2880
91
150
6.1 1216 3770
92
150
6.9 1273 4160
92
150
9.7 1233 2620
91
112
10.0 1271 2940
91
200
6.4 1245 3980
92
200
7.5 1301 4360
92
210
10.0 1271 2940
91
250
6.9 1274 4170
92
250
8.3 1328 4550
93
300
7.5 1302 4360
92
298
10.0 1355 4740
93
350
8.4 1329 4560
93
395
10.0 1354 4740
93
Unit performances are referred to sea level conditions.
17
Standard air flow [15000 m3/h], 3 Ph fan + TRIAC
Models: CRH 007 --- 207
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 007 --- 207
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Standard air flow [15000 m3/h], EC fan
Models: CRH 007 --- 207
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 007 --- 207
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
50
5.5 1179 3140
93
50
5.7 1197 3300
93
50
9.2 1169 1950
91
50
9.4 1193 2130
91
100
5.8 1205 3380
93
100
6.0 1223 3540
93
100
9.4 1204 2210
91
100
9.6 1226 2390
92
150
6.1 1232 3610
93
150
6.3 1250 3770
93
150
9.7 1236 2480
92
150
9.9 1258 2660
92
200
6.4 1259 3830
93
200
6.8 1278 3980
93
206
10.0 1272 2780
92
172
10.0 1272 2780
92
250
6.9 1287 4040
93
250
7.4 1305 4180
93
300
7.6 1313 4250
93
300
8.1 1331 4380
94
350
8.6 1339 4450
94
354
10.0 1360 4620
94
388
10.0 1360 4620
94
Standard air flow [13250 m3/h], 3 Ph fan + TRIAC
Models: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Standard air flow [13250 m3/h], EC fan
Models: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
50
5.4 1123 3230
90
50
5.8 1172 3600
90
50
8.9 1129 1960
89
50
9.4 1190 2390
89
100
5.6 1151 3440
90
100
6.0 1200 3810
91
100
9.1 1164 2200
89
100
9.6 1224 2650
90
150
5.8 1179 3660
90
150
6.3 1229 4010
91
150
9.4 1199 2460
90
150
9.9 1257 2920
90
200
6.1 1208 3870
91
200
6.8 1260 4190
91
200
9.7 1233 2720
90
170
10.0 1271 3030
90
250
6.4 1237 4060
91
250
7.3 1289 4380
91
258
10.0 1271 3030
90
300
6.9 1268 4240
91
300
7.9 1317 4570
92
350
7.5 1296 4430
92
350
9.6 1346 4750
92
400
8.3 1325 4620
92
360
10.0 1352 4790
92
448
10.0 1352 4790
92
Unit performances are referred to sea level conditions.
18
Standard air flow [14500 m3/h], 3 Ph fan + TRIAC
Models: CRH 032
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Models: SRH 032
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
Pa
V
Rpm
W
dB(A)
Standard air flow [14500 m3/h], EC fan
Models: CRH 032
Useful static pressure Max. f an speed signal Fan speed Absorbed unitary power Fan discharge sound power [PWL]
Pa
V
Rpm
W
dB(A)
50
6.0 1216 3620
92
50
6.8 1272 4050
93
50
9.6 1225 2470
91
100
6.3 1243 3850
92
100
7.3 1300 4250
93
100
9.9 1257 2740
91
150
6.8 1272 4050
93
150
8.0 1326 4450
93
124
10.0 1272 2870
91
200
7.3 1299 4250
93
200
9.8 1354 4660
93
250
8.0 1325 4450
93
206
10.0 1357 4690
94
300
9.7 1353 4660
93
308
10.0 1357 4690
94
Unit performances are referred to sea level conditions.
19
F i g . 1 --- S e r v i c e a r e a s C R H / S R H 0 0 4 --- 0 1 6 ( t o p v i e w )
500 (with duct)
1500 (without duct)
Ordinary maintenance area
Extraordinary maintenance area
1000
1000 1000 (*)
AIR
Notes:
Minimum distance between 2 units from condensing coil side = 2 m (*) 1500 mm (with 160 -- - 200 Lt Tank); 2500 mm (with 400 Lt T ank)
F i g . 2 --- S e r v i c e a r e a s C R H / S R H 0 1 7 --- 0 3 2 ( t o p v i e w )
AIR
Ordinary maintenance area
Extraordinary maintenance area
1500
1000 1000
Notes:
Minimum distance between 2 units from condensing coil side = 3 m
20
Fig. 3 --- Lifting instructions with tubes CRH/SRH 004---016
PROTECTION PLANK
RIGID STRUTS (POSSIBILY STEEL)
PART. “ A ”
LIFTING SYSTEM WITH TUBES
BELT OR CHORD
PART. “ A ”
PART. “A”
BLOCKING PEG (NOT SUPPLIED)
LIFTING TUBE (NOT SUPPLIED) (BASE HOLES Ø45)
SPLIT PIN (NOT SUPPLIED)
N.B: Place the lifting tubes in the holes in the base indicated by the words “LIFT HERE”. Lock the ends of the tubes in position with
the locking pins and split pins as shown above “A”. The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the lifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitable for the load to be moved, so as not to damage the structure.
Lifting
Models
CRH / SRH 004 - 204 - 006 - 206
CRH / SRH 007 - 207 - 008 - 011
CRH / SRH 014 - 016
21
“L”
(mm)
2006 1.7 ' 3.5 ' 8.5
3006 1.7 ' 4.5 ' 8.5
4006 1.7 ' 4.5 ' 8.5
“A”
(m)
“B”
(m)
“C”
(m)
Fig. 4 --- Lifting instructions with straight shackle CRH/SRH 004---016
L
N.B.: LIFT IN THE BARICENTRE LINE “G” OF THE UNIT
”G”
”A1”
”A2”
”L”
PART. “ A ”
LIFTING SYSTEM WITH STRAIGHT SHACKLE
”G”
”Yg”
”Xg”
STRAIGHT SHACKLE Ø 14 (UNI 1947) “A” TYPE
PART. “A”
(OPTIONAL)
N.B: The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the
lifting gear and ropes and the condition and suitability of the aforementioned equipment.
ift the unit with a speed suitable for the load to be moved, so as not to damage the structure.
Lifting
Models
CRH / SRH 004 - 204 - 006 - 206
CRH / SRH 007 - 207 - 008 - 011
CRH / SRH 014 - 016
“L”
(mm)
2006 ' 5.5
3006 ' 6.5
4006 ' 6.5
“A1 + A 2”
(m)
22
B a r i c e n t r e “ G ” --- CR H / S R H 0 0 4 --- 0 1 6
odels
Model
s
M
CRH 004
CRH 204
CRH 006
CRH 206
CRH 007
CRH 207
CRH 008
CRH 011
CRH 014
CRH 016
SRH 004
SRH 204
SRH 006
SRH 206
SRH 007
SRH 207
SRH 008
SRH 011
SRH 014
SRH 016
Unit baricentre position “G” --- (without water)
Without tank With tank
“Xg”
(m)
0.83 0.58 0.89 0.58
0.79 0.62
0.80 0.56 0.86 0.56
0.78 0.62
1.22 0.59 1.32 0.59
1.18 0.64
1.17 0.63 1.25 0.63
1.10 0.63 1.18 0.62
1.50 0.64 1.62 0.63
1.45 0.63 1.57 0.63
0.86 0.60 0.92 0.60
0.82 0.64
0.83 0.58 0.89 0.59
0.82 0.64
1.27 0.63 1.36 0.62
1.23 0.67
1.22 0.66 1.30 0.65
1.16 0.65 1.23 0.65
1.58 0.67 1.68 0.66
1.53 0.67 1.64 0.66
“Yg”
(m)
“Xg”
(m)
Not available
Not available
Not available
Not available
Not available
Not available
“Yg”
(m)
23
Fig. 5 --- Lifting instructions with tubes CRH/SRH 017---032
PROTECTION PLANK
RIGID STRUTS (POSSIBILY STEEL)
BELTOR CHORD
BLOCKING PEG (NOT SUPPLIED)
SPLIT PIN (NOT SUPPLIED)
LIFTING TUBE (NOT SUPPLIED) (BASE HOLES Ø56)
N.B: Place the lifting tubes in the holes in the base indicated by the words “LIFT HERE”. Lock the ends of the tubes in position with
the locking pins and split pins as shown above “A”. The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of the lifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitable for the load to be moved, so as not to damage the structure.
Lifting
Models
CRH 017 - 020 - 023 - 025 - 028 - 030 - 032
SRH 017 - 020 - 023 - 025 - 028 - 030 - 032
“A”
(m)
1.0 ' 5.5 ' 9.0
“B”
(m)
“C”
(m)
24
Fig. 6 --- Support positions and loads (Note: weights refer to standard units)
CRH/SRH 004 - 016
”A”
17116117
34112734
W1
d=14
120 120
”D” ”E” ”D”
W2 W3 W4 W5
FOOT PRINT
W9W8W7W6
”B”
”C” ”C”
W10
D i m e n s i o n s --- C R H / S R H 0 0 4 --- 0 1 6
Dimensions (mm) A B C D E
Model Size
CRH SRH
CRH SRH
CRH SRH
004 --- 204 --- 006 --- 206 004 --- 204 --- 006 --- 206
007 --- 207 --- 008 --- 011 007 --- 207 --- 008 --- 011
014 --- 016 014 --- 016
2000 1760 --- --- ---
3000 --- 1380 --- ---
4000 --- --- 1160 1440
1195
W e i g h t d i s t r i b u t i o n --- C R H / S R H 0 0 4 --- 0 1 6
Weight distribution (kg) W1 W2 W3 W4 W5 W6 W7 W8 W9 W10
Model Size
CRH 004 221 --- --- --- 1 5 1 2 4 1 --- --- --- 1 6 5
204 276 --- --- --- 1 7 3 2 6 2 --- --- --- 1 6 4
006 238 --- --- --- 1 5 1 2 7 6 --- --- --- 1 7 6
206 283 --- --- --- 1 7 4 2 6 9 --- --- --- 1 6 5
007 240 --- 137 --- 137 246 --- 140 --- 140
207 288 --- 152 --- 152 253 --- 134 --- 134
008 314 --- 164 --- 164 285 --- 149 --- 149
011 369 --- 169 --- 169 338 --- 155 --- 155
014 299 299 - -- 136 136 265 265 --- 121 121
016 320 320 - -- 136 136 285 285 --- 121 121
SRH 004 254 --- --- --- 193 241 --- --- --- 183
204 308 --- --- --- 2 1 5 2 6 2 --- --- --- 1 8 2
006 271 --- --- --- 1 9 2 2 7 5 --- --- --- 1 9 5
206 316 --- --- --- 2 1 6 2 6 8 --- --- --- 1 8 4
007 280 --- 186 --- 186 241 --- 161 --- 161
207 328 --- 203 --- 203 248 --- 154 --- 154
008 361 --- 222 --- 222 278 --- 171 --- 171
011 419 --- 227 --- 227 329 --- 178 --- 178
014 356 356 - -- 198 198 265 265 --- 148 148
016 378 378 --- 197 197 284 284 --- 148 148
25
Weight distribution with tank --- CRH/SRH 004 --- 016
Weight distribution (kg) W1 W2 W3 W4 W5 W6 W7 W8 W9 W10
Model Size
CRH 004 271 --- --- --- 2 5 7 2 8 8 --- --- --- 2 7 2
204 Not available
006 289 --- --- --- 2 5 5 3 2 2 --- --- --- 2 8 5
206 Not available
007 230 --- 219 --- 219 235 --- 223 --- 223
207 Not available
008 334 --- 289 --- 289 312 --- 270 --- 270
011 389 --- 294 --- 294 365 --- 277 --- 277
014 310 310 - -- 260 260 283 283 --- 238 238
016 331 331 - -- 259 259 304 304 --- 238 238
SRH 004 301 --- --- --- 300 290 --- --- --- 289
204 Not available
006 320 --- --- --- 2 9 8 3 2 3 --- --- --- 3 0 2
206 Not available
007 267 --- 267 --- 273 237 --- 237 --- 243
207 Not available
008 375 --- 350 --- 350 311 --- 290 --- 290
011 433 --- 354 --- 354 362 --- 297 --- 297
014 362 362 - -- 326 326 289 289 --- 259 259
016 385 385 --- 325 325 308 308 --- 260 260
26
Fig. 7 --- Support positions and loads (Note: weights refer to standard units)
CRH/SRH 017 - 032
1000
1201060120
”A”
60118060
WT1
TANK
MOUNTED
(OPTION)
WT2
125 875
(supply not mounted on unit)
1201060120
125
Ta n k
1000
WA
FOOT PRINT
d=20
750
W1 W2 W3
W5
WB
WDWC
125
WA = WB = 406 kg WC = WD = 299 kg
FOOT PRINT
d=20
W6 W7
125
”B” 1500 ”B” 125
D i m e n s i o n s --- C R H / S R H 0 1 7 --- 0 3 2
Dimensions (mm) A B
Model Size
CRH / SRH 017 --- 020 3750 1000
CRH / SRH 023 --- 025 4750 1500
CRH / SRH 028 --- 030 --- 032 5750 2000
W e i g h t d i s t r i b u t i o n --- C R H / S R H 0 1 7 --- 0 3 2
1180601300
60
Weight distribution (kg) W1 W2 W3 W4 W5 W6 W7 W8
Model Size
CRH 017 196 196 233 233 261 261 310 310
020 203 203 250 250 274 274 337 337
023 240 240 327 327 312 312 427 427
025 240 240 327 327 312 312 427 427
028 273 273 382 382 345 345 482 482
030 281 281 383 383 368 368 502 502
032 280 280 393 393 371 371 520 520
SRH 017 252 252 283 283 293 293 328 328
020 259 259 300 300 306 306 355 355
023 305 305 395 395 348 348 450 450
025 305 305 395 395 348 348 450 450
028 351 351 463 463 385 385 508 508
030 359 359 471 471 402 402 528 528
032 358 358 482 482 405 405 545 545
Weight distribution with tank --- CRH/SRH 017 --- 032
Weight distribution (kg) WT1 W1 W2 W3 W4 WT2 W5 W6 W7 W8
Model Size
CRH 017 443 443 261 261 261 462 462 273 273 273
020 440 440 279 279 279 467 467 296 296 296
023 447 447 351 351 351 477 477 374 374 374
025 447 447 351 351 351 477 477 374 374 374
028 460 460 400 400 400 489 489 425 425 425
030 464 464 403 403 403 508 508 441 441 441
032 460 460 412 412 412 507 507 455 455 455
SRH 017 478 478 309 309 309 467 467 302 302 302
020 475 475 326 326 326 473 473 325 325 325
023 486 486 413 413 413 482 482 410 410 410
025 486 486 413 413 413 482 482 410 410 410
028 507 507 475 475 475 496 496 464 464 464
030 508 508 485 485 485 505 505 483 483 483
032 504 504 494 494 494 505 505 496 496 496
W4
1300
W8
27
Fig. 8 --- Rubber anti---vibration support + 1000 liters tank
t
a
Rubber support dimensions Rubber support installation
A
G
S
CF
P
L
B
F
Access hole for support fixing
Single support code
Code
270327 82 35 M10 11.0 110 60 128 2
270326 108 50 M16 16.5 160 83 190 5
A
(mm)B(mm)P(mm)F(mm)CF(mm)G(mm)L(mm)S(mm)
Unit base
Fixing screw
Screw anchor (not supplied)
Cement base
Rubber supports + 1000 liters tank
Unit Configuration
C R H --- SR H
204---206-- -004 --- 006
C R H --- SR H
207---007-- -008 --- 011
C R H --- SR H
014---016
017---020-- -023 --- 025 --- 028 --- 030 --- 032
017---020-- -023 --- 025 --- 028 --- 030 --- 032
Each kit is complete with stainless steel fixing screws and plain washers for unit assembly.
C R H --- SR H
C R H --- SR H
1000 liters tank Loose supplied 485620 270327 4
With or without
tank
Without tank 485625
With tank 485626
Support kit code
485620 4
485621
485622 8
28
Single support
code
270327
270326
Kit support
pieces
6
8
10
151
f
r
B
Ext. 352
1739
ic panel and
Elect
M
279
30
M
30
30
151
C
M
30
352 Ext.
E
30
1739
M
Fron t view
30
110
1501
Flanged (Opt.)
M
MMM
Lateral view
M
M
Air flow
Over air discharge
852 Ext.
148 279
Right air discharge
(move the “A” with “B” panel/s)
(Standard supply)
A
148 852 Ext. 279
Left air discharge
(move the “A” with “C” panel/s)
Duct Flanged (Opt.),
not possible with coil metal filter s
Coil metal filters (Opt.), not possible
with ducted flange
Removable panel
E
B
C
Top vie w
F
M
(rear front
control unit
691
removable panel)
352 Ext.
A
158
279
148 852 Ext. 279
148 852 Ext.
”D”
Fig. 9 --- Overall dimensions CRH/SRH 004 --- 016
M
M
2242
M
M
M
236±5
±
699
5
Y
X
1522 720
M
M
M
236±5
±
699
5
Y
X
present on mod. 007 - 207
875 852 Ext.
Z
W
430,5 170 600,5
”A” + 40 (Heat recovery, Opt.)
Fan and hole panel not
”A”+40
Supply cable inlet
(Prepunch ø 67 + ø 30)
132
140 80 2022
Rear view
(Std. unit)
= =
Rear view
= =
(with heat recovery)
Fan and hole panel not
148852 Ext.279
”A”
E
30 (Opt.)
1201
6001642
875852 Ext.279
present on
mod. 007 - 207
M
148852 Ext.279
M
M
M
852 Ext.
875 279
Fan and hole panel not
present on mod. 007 - 207
M
Flanged (Opt.)
E
769
110 30 1441 30
(Opt.)
Flanged
94230
F
Flanged (Opt.)
194230
30
Flanged (Opt.)
rom “D”)
294230
(
Lateral view
29
Chilledwate
r
Inlet
W
Z
Outlet
”Gasmale
”Gasmale
2
/
1
2
CRH/SRH
014 --- 016
2
/
1
2
SRH
”Gasmale
4
/
1
”Gasmale
4
/
1
008---011 ---014 ---016
Inlet
Outlet
”Gasmale
”Gasmale
2
/
1
2
Outlet
2
/
1
2
CRH
”Gasmale 1
”Gasmale Not available
”Gasmale 1
4
Inlet
2
/
/
1
1
”Gasmale Not available
4
2
/
/
1
1
008---011 ---014 ---016
2” Gas male (mod. 007 --- 207)
1
” Gas male (mod. 008 --- 011) /
2
” Gas male (mod. 008 --- 011)
2
2
/
2” Gas male (mod. 007 --- 207)
1
2
--- 00 8 --- 0 1 1
(*)
CRH/SRH
007 --- 207
SRH
Inlet
(*)
--- 00 6 --- 2 0 6
(*)
CRH/SRH
004 --- 204
--- 1 1 (007 - -- 207) --- 2 (008 --- 011) 3
Outlet
Inlet
2” Gas male (mod. 007 --- 207)
1
2” Gas male
2” Gas male
X
” Gas male (mod. 008 --- 011)
2
/ 2
Outlet
” Gas male (mod. 008 --- 011)
2
2” Gas male (mod. 007 --- 207)
1
/ 2
004---006 ---007 ---204--- 206 ---207
Inlet
2” Gas male
CRH
1” Gas male 1” Gas male 1
2” Gas male Not available 2
1” Gas male 1” Gas male 1
2” Gas male Not available 2
Outlet
2” Gas male
Y
004---006 ---007 ---204--- 206 ---207
W
Z
“A” mm 2006 3006 4006
Fans number
connection
Chilled water
Models
Tota l
Partial
heat recovery inlet
heat recovery inlet
Tota l
Partial
heat recovery outlet
heat recovery outlet
tank + pump/s
Tab. 10 --- Chilled water connection CRH/SRH 004 --- 016
j = Standard, with tank, with
J =With pump/s (withouttank) j J j J j J
(*) ON 204 --- 206 --- 207 MODELS, TANK VERSION WITH / WITHOUT PUMP IS NOT AVAILABLE
Tab. 11 --- Heat recovery water connection (optional) CRH/SRH 004 --- 016
30
155
Z
X
W
X
Y
765 1220
255
Y
255 765 300 765
27
Flanged (Opt.)
1382 Ext.
27
832 Ext.
168 459
832 Ext.
168 459
(Std. unit)
M
1185 115
Left lateral view
M
1185 115
Left lateral view
(with heat recovery)
Part. L
2940 Ext.
Plane for
around the opening
canalization fixing all
3940 Ext.
4940 Ext.
Flanged (Opt.)
”D”
679
Flanged (Opt.)
1382 Ext.
459168168459
M
MM
M
M M
832 Ext.
168 459
M
M
M
M
832 Ext.
E E
E
F
168 459
M
M
Top vie w
M M M
832 Ext. 832 Ext. 832 Ext.
E
Fron t view
168459
M M
M
MM
832 Ext. 832 Ext.
M
832 Ext. 832 Ext.
”A”60
832 Ext.
M
179
Rear view
(from “D”)
405
Part. L
Flanged (Opt.)
Flanged (Opt.)
2940 Ext.405
Flanged (Opt.)
3940 Ext.
4940 Ext.
Fig. 10 --- Overall dimensions CRH/SRH 017 --- 032
168832 Ext.459
459 832 Ext. 168 168 459
M
M
M
M
459 832 Ext. 168 168 459
M M M MM
M
M
405
405
Heat recovery
Z
X
W
Y
std. pipe projection Heat recovery and
Part. G
210 80 90
352 88
B
M
30
A
30
850 352 98
Electric panel and control unit
(behind front removable panel)
M
30
C
352 88
1800
179
Flanged (Opt.)
1382 Ext.
30 (Opt.)
E
Part. H
102
pipe
1 ø30)
o
Unit connecting
”N”
2240
1800
1300
Part. H
M
view
Right lateral
2ø67-N
o
Supply cable inlet
(Prepunchs N
Rightairdischarge(movethe“A”with“B”panel/s)
Over air discharge (Standard supply)
Left air discharge (move the “A” with “C” panel/s)
Duct Flanged (Opt.), not possible with coil metal filters
Air flow
A
B
Coil metal filters (Opt.), not possible with ducted flange
E
F
C
PAR T. G
UNIT CONNECTING SYSTEM
Removable panel
M
Victaulic
coupling
X
“N” View
Y
Unit overall frame (”A”)
60
Y
X
31
Inlet
Chi
l
led
water
W
Z
Outlet
CRH/SRH
028 --- 030 --- 032
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
SRH
Not available
Not available
017 --- 020 --- 023 --- 025 --- 028 --- 030 --- 032
Inlet
CRH/SRH
023 --- 025
Outlet
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
CRH
2” Gas male 2” Gas male
Inlet
CRH/SRH
017 --- 020
--- 3 4 5
“A” mm 3750 4750 5750
Models
Fans number
Outlet
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
X
Y
connection
Chilled water
Models
017 --- 020 --- 023 --- 025 --- 028 --- 030 --- 032
W
Partial
heat recovery inlet
2” Gas male 2” Gas male
(like Part. “G”)
DN 80 --- 3” --- 88.9 mm
(like Part. “G”)
DN 80 --- 3” --- 88.9 mm
Z
Tota l
heat recovery inlet
Tota l
Partial
heat recovery outlet
heat recovery outlet
Tab. 12 --- Chilled water connection CRH/SRH 017 --- 032
Tab. 13 --- Heat recovery water connection (optional) CRH/SRH 017 --- 032
32
832 Ext.
168 459
832 Ext.
168 459
679
Flanged (Opt.)
1382 Ext.
M
M
MMMM
M
179
Rear view
(from “D”)
832 Ext.
M M
459168168459
4054940 Ext.405
168 459
M
M
M
M
M
M
832 Ext.
E
Part. L
168 459
E
M
M
Top vie w
Fron t view
832 Ext. 832 Ext.
M
M
M
832 Ext. 832 Ext.
”A”
M
M M M MM
832 Ext. 832 Ext. 832 Ext.
168459
832 Ext.
E
Flanged (Opt.)
F
Flanged (Opt.)
2940 Ext.405
M M M
E
3940 Ext.405
Flanged (Opt.)
M M
M
459 832 Ext. 168 168 459
M
459 832 Ext. 168 168 459
168832 Ext.459
M
M
1000
M
M
60
X
Y
Part. G
1800 352 88
Flanged (Opt.)
BC
M
30
30 (Opt.)
1382 Ext.
E
179
Inlet/Outlet pipes
1382 Ext.
Part. H
Flanged (Opt.)
27
projection
X
920
Y
255 1065
27
A
30
850 352 98
Electric panel and control unit
(behind front removable panel)
M
30
M
1300
1800 352 88
2240
Part. L
view
Right lateral
”N”
Plane for
around the opening
2940 Ext.
3940 Ext.
canalization fixing all
4940 Ext.
Flanged (Opt.)
pipe
M
1185 115
Left lateral view
210 80 90
”D”
102
Unit connecting
Part. H
Fig. 11 --- Overall Dimensions (with tank) CRH/SRH 017 --- 032
Victaulic
PAR T. G
coupling
UNIT CONNECTING SYSTEM
“N” View
X
Y
Unit overall frame (”A”)
1ø30)
o
60
(Prepunchs
2ø67-N
o
Y
X
Supply cable inlet
N
Over air discharge
(standard supply)
Right air discharge
(move the “A” with “B” panel/s)
Left air discharge
(move the “A” with “C” panel/s)
Duct Flanged (Opt.),
not possible with coil metal filters
Coil metal filters (Opt.),
Air flow
A
B
C
not possible with ducted flange
Removable panel
E
F
M
33
Inlet
Chilledwate
r
Outlet
CRH/SRH
028 --- 030 --- 032
CRH/SRH
023 --- 025
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
Inlet
Outlet
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
Inlet
CRH/SRH
017 --- 020
--- 3 4 5
Outlet
DN 80 --- 3” --- 88.9 mm
DN 80 --- 3” --- 88.9 mm
X
Y
“A” mm 4750 5750 6750
Models
Fans number
connection
Chilled water
Tab. 14 --- Chilled water connection (with tank) CRH/SRH 017 --- 032
34
Fig. 12 --- Refrigerant circuit (std.) with partial recovery (opt.)
CRH/SRH 004 ---006--- 007
7
9
8
19
HEAT RECOVERY WATER OUTLET
1” GAS MALE (OPT.)
11
12
19
FG
13
19
10
22
21
5
2
14
1
MC
4
HEAT RECOVERY WATER INLET
1” GAS MALE (OPT.)
6 3
19
15
18
T
16
19
17
T
20
8
CHILLED W ATER INLET
2” GAS MALE
CHILLED WATER OUTLET
2” GAS MALE
Refrigerant components
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Partial recovery heat exchanger (Opt.)
22
Antifreeze heater (Std. with heat recovery)
35
Fig. 13 --- Refrigerant circuit (std.) with partial recovery (opt.)
CRH/SRH 204 ---206---207---008 ---011---014---016
7
8
HEAT RECOVERY WATER OUTLET
Ø G --- G A S M A L E ( O P T. )
19 19
19
11
10
22
12
19
FG
2
14
21
HEAT RECOVERY
5
1
6
MC
WATER INLET
3
ØG --- GAS MALE (OPT .)
19
18
9
T
7
CHILLED W ATER
INLET
Ø H --- G A S M A L E
8
19
10
22
21
6
3
19
1
MC
11
12
25
19
14
FG
13
4
15
16
19
17
20
T
19
CHILLED WATER OUTLET
CRH/SRH
204 206 207 008 011 014 016
ØG 1” 1” 1” 11/4” 11/4” 11/4” 11/4”
ØH 2” 2” 2” 21/2” 21/2” 21/2” 21/2”
Refrigerant components
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Partial recovery heat exchanger (Opt.)
22
Antifreeze heater (Std. with heat recovery)
15
Ø H --- G A S M A L E
4
13
36
Fig. 14 --- Refrigerant circuit with total recovery (opt.)
CRH 004---006---007
ONLY FOR: CRH 007
ONLY FOR: CRH 004--- 006 --- 007
25
25
8 8
7
9
19
11
12
19
14
FG
13
19
2 5 36
25
HEAT RECOVERY WATER OUTLET
2” GAS MALE
10
22
23
MC
1
4
21
24
HEAT RECOVERY
WATER INLET 2” GAS MALE
19
16
15
19
18
T
17
T
20
CHILLED W ATER INLET
2” GAS MALE
CHILLED WATER OUTLET
2” GAS MALE
Refrigerant components
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Total recovery heat exchanger
22
Three way valve
23
Nonreturnvalve
24
Antifreeze heater
25
Liquid receiver
37
Fig. 15 --- Refrigerant circuit with total recovery (opt.)
CRH 204---206---207 ---008---011---014 ---016
ONLY FOR: CRH 207--- 008 --- 011 ---014 --- 016
25 25
8 8
HEAT RECOVERY
WATER OUTLET
7 7
19
11
12
19
FG FG
14
25 25
19
10
2 5 5 23 66 3
Ø G --- G A S M A L E
22 22
23 23
MC
21 21
HEAT RECOVERY
WATER INLET
Ø G --- G A S M A L E
19
9
2424
CHILLED W ATER
INLET
Ø H --- G A S M A L E
T
18
19
MC
ONLY FOR: CRH 207--- 008 --- 011 ---014 --- 016
19
10
19
11
12
19
14
13
1
4
16
1919
17
T
20
CHILLED WATER OUTLET
CRH
204 206 207 008 011 014 016
ØG 2” 2” 2” 21/2” 21/2” 21/2” 21/2”
ØH 2” 2” 2” 21/2” 21/2” 21/2” 21/2”
Refrigerant components
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Total recovery heat exchanger
22
Three way valve
23
Nonreturnvalve
24
Antifreeze heater
25
Liquid receiver
1515
Ø H --- G A S M A L E
1
4
13
38
Fig. 16 --- Refrigerant circuit (std.) with partial recovery (opt.)
CRH/SRH 017 ---020---023---025 ---028---030---032
9
8
HEAT RECOVERY WATER OUTLET
2” GAS MALE (OPT.)
19
10
19
21 21
5
HEAT RECOVERY WATER INLET
19
14 14
2
2
MC
13 13
MC
2” GAS MALE (OPT.)
3
6
18
19 19
T
T
20
77
2222
CHILLED W ATER INLET
VICTAULIC COUP LING
DN 80 --- 3” --- 88.9 mm
3
16
1919
17
1515
CHILLED WATER OUTLET
VICTAULIC COUP LING
DN 80 --- 3” --- 88.9 mm
6
MC
MC
44
11
44
11
19
10
5
2
2
1919
1111
19
1212
19
FGFG
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Partial recovery heat exchanger (Opt.)
22
Antifreeze heater (Std. with heat recovery)
39
Fig. 17 --- Refrigerant circuit with total recovery (opt.)
CRH 017---020---023 ---025---028---030 ---032
NOT PRESENT FOR: CRH 017--- 020
24 24
HEAT RECOVERY
WATER INLET
VICTAULIC COU PLING (OP T.)
13
11 11
19
19
FG FG
19
10
13
VICTAULIC COUP LING (OPT.)
2 2 2 2
5 5
1
MC
4
MC
1
4
23 23
HEAT RECOVERY
WATER OUTLET
DN 80 --- 3” --- 88.9 mm
6
3
15 15
DN 80 --- 3” --- 88.9 mm
21
22
CHILLED W ATER INLET
VICTAULIC COUP LING DN 80 --- 3” --- 88.9 mm
T
18
19 19
16
17
19 19
T
20
CHILLED WATER OUTLET
VICTAULIC COUP LING DN 80 --- 3” --- 88.9 mm
9
8
1
3
MC
6
4
MC
1
4
13
13
NOT PRESENT FOR: CRH 017--- 020
77
2424
19
10
1212
1919
19
19
1414
1313
Item Description Item Description
1
Compressor
2
High pressure switch (HP)
3
Low pressure switch (LP)
4
Crankcase heater
5
High pressure manometer (Opt.)
6
Low pressure manometer (Opt.)
7
Safety valve
8
Condenser
9
Fan(s)
10
Pressure transducer
11
Shut--- off valve
12
Filter dryer
13
Shut--- off solenoid valve
14
Sight glass
15
Thermostatic expansion valve
16
Evaporator
17
Antifreeze heater (Opt.)
18
Control temperature sensor
19
Charge connection
20
Antifreeze sensor
21
Total recovery heat exchanger
22
Three way valve
23
Nonreturnvalve
24
Antifreeze heater
25
Liquid receiver
40
F i g . 1 8 --- H y d r a u l i c c i r c u i t --- C R H 0 0 4 --- 0 0 6 --- 0 0 7 --- 2 0 4 --- 2 0 6 --- 2 0 7
LIEBERT--- HIROSS UNIT
18
ONL Y WITH P UMP VER SION
4
5
3
1
11
2
T
12
T
6
ONLY FOR 004 ---006 --- 007 MODELS
5
15
ONL Y WITH TANK VERSION
4
7
13
10
14a
NOT AVAILABLE IN
204--- 206 --- 207 MODELS
8
CHILLED W ATER INLET
9
14b
F
F
2” GAS MALE
16
1
11
T T
12
2
ONLY FOR 204 ---206 --- 207 MODELS
Hydraulic components
Item Description Item Description
1
Evaporator
2
Evaporator antifreeze heater (Opt.)
3
Rubber flexible pipe (only with pumps and/or tank))
4
Manual air valve
5
Gate valve
6
Pump
7
Safety valve
8
Expansion tank
9
Service ball valve
10
Drain valve
11 12
13 14a 14b
15
16
17
18
Control temperature sensor Antifreeze temperature sensor Tank antifreeze heater (Opt.) Flow switch (unit without tank, Opt. without pumps) Flow switch (unit with tank, Opt. without pumps) Rubber flexible pipe (only with pumps, without tank) Filter (Opt.) Nonreturnvalve Expansion tank + Safety valve (Opt. without tank)
CHILLED WATER OUTLET
2” GAS MALE
41
F i g . 1 9 --- H y d r a u l i c c i r c u i t --- C R H 0 0 8 --- 0 1 1 --- 0 1 4 --- 0 1 6
LIEBERT--- HIROSS UNIT
ONL Y WITH TANK VERSION
18
ONL Y WITH P UMP VER SION
4
17
17
3
6
6
5
5
7
4
8
CHILLED W ATER INLET
9
14b
13
F
21/2”GASMALE
16
1
11
T T
2
15
12
Hydraulic components
Item Description Item Description
10
F
14a
CHILLED WATER OUTLET
21/2”GASMALE
1
Evaporator
2
Evaporator antifreeze heater (Opt.)
3
Rubber flexible pipe (only with pumps and/or tank))
4
Manual air valve
5
Gate valve
6
Pump
7
Safety valve
8
Expansion tank
9
Service ball valve
10
Drain valve
42
11 12 13
14a
14b
15 16 17 18
Control temperature sensor Antifreeze temperature sensor Tank antifreeze heater (Opt.) Flow switch (unit without tank, Opt. without pumps) Flow switch (unit with tank, Opt. without pumps) Rubber flexible pipe (only with pumps, without tank) Filter (Opt.) Non ---return valve Expansion tank + Safety valve (Opt. without tank)
F i g . 2 0 --- H y d r a u l i c c i r c u i t --- S R H 0 0 4 --- 0 0 6 --- 0 0 7 --- 2 0 4 --- 2 0 6 --- 2 0 7
LIEBERT--- HIROSS UNIT
21
4
22 T
23
10
23
1
2
T T
4
ONL Y WITH P UMP VER SION
1822
4
T
20
10
11 12
23
23
2323
3
15
19
ONLY FOR 004 ---006 --- 007 MODELS
6
5
5
24
ONL Y WITH TANK VERSION
4
7
10
14a
NOT AVAILABLE IN
8
13
204--- 206 --- 207 MODELS
CHILLED W ATER INLET
9
14b F
F
CHILLED WATER OUTLET
2” GAS MALE
16
2” GAS MALE
1
11
T T
12
2
ONLY FOR 204 ---206 --- 207 MODELS
Hydraulic components
Item Description Item Description
1
Evaporator
2
Evaporator antifreeze heater (Opt.)
3
Rubber flexible pipe (only with pumps and/or tank))
4
Manual air valve
5
Gate valve
6
Pump
7
Safety valve
8
Expansion tank
9
Service ball valve
10
Drain valve
11
Control temperature sensor
12
Antifreeze temperature sensor
13
Tank antifreeze heater (Opt.)
14a 14b
15
16
17
18
19
20
21
22
23
24
Flow switch (unit without tank, Opt. without pumps) Flow switch (unit with tank, Opt. without pumps) Rubber flexible pipe (only with pumps, without tank) Filter (Opt.) Nonreturnvalve Air temperature sensor 3 --- w a y v a l v e Freecooling control temperature sensor Fan(s) Freecooling coil Rubber flexible pipe Expansion tank + Safety valve (Opt. without tank)
43
F i g . 2 1 --- H y d r a u l i c c i r c u i t --- S R H 0 0 8 --- 0 1 1 --- 0 1 4 --- 0 1 6
LIEBERT--- HIROSS UNIT
21
44
18
22
22
23
10
23
1
T T
2
T
10
23
23
3
11
15
12
20
ONL Y WITH P UMP VER SION
4
T
19
17
17
6
5
5
6
24
ONL Y WITH TANK VERSION
4
7
10
14a
8
9
14b
13
F
F
CHILLED W ATER INLET
21/2”GASMALE
16
CHILLED WATER OUTLET
21/2”GASMALE
Hydraulic components
Item Description Item Description
1
Evaporator
2
Evaporator antifreeze heater (Opt.)
3
Rubber flexible pipe (only with pumps and/or tank))
4
Manual air valve
5
Gate valve
6
Pump
7
Safety valve
8
Expansion tank
9
Service ball valve
10
Drain valve
11
Control temperature sensor
12
Antifreeze temperature sensor
13
Tank antifreeze heater (Opt.)
14a
14b
15 16 17 18 19 20 21 22 23 24
Flow switch (unit without tank, Opt. without pumps) Flow switch (unit with tank, Opt. without pumps) Rubber flexible pipe (only with pumps, without tank) Filter (Opt.) Non ---return valve Air temperature sensor 3 --- w a y v a l v e Freecooling control temperature sensor Fans Freecooling coil Rubber flexible pipe Expansion tank + Safety valve (Opt. without tank)
44
VICTAULIC
CONNECTION
DN 80--- 3” --- 88.9mm
W A T E R TA N K I N L E T ---
13
OPTION:
4
WITH UNIT
9
WATER TANK NOT ASSEMBLY
DN 80 --- 3” --- 88.9 mm
W A T E R TA N K O U T L E T ---
VICTAULIC CONNECTION
10
DN 80 --- 3” --- 88.9 mm
CHILLED W ATER INLET
VICTAULIC CONNECTION
3
DN 80 --- 3” --- 88.9 mm
VICTAULIC CONNECTION
CHILLED WATER OUTLET
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (Opt. without pumps)
Service valve with cap
Differential trasducer (only with electronic pump)
UNIT FRAME (WITH ASSEMBLED TANK)
5
4
9
8
UNIT FRAME (WITHOUT TANK) TANK FRAME
13
F
14
4
6
PUMP VERSION
ONLY WITH SINGLE
5 5
M1
10
ASSEMBLY WITH UNIT
ONLY WITH WATER TANK VERSION
16
p
15
1
15
11
12
T
T
2
LIEBERT--- HIROSS BASE UNIT
11
1213141516
45
7
PUMP VERSION
ONL Y WITH TW IN
F i g . 2 2 --- H y d r a u l i c c i r c u i t --- C R H 0 1 7 --- 0 2 0 --- 0 2 3 --- 0 2 5 --- 0 2 8 --- 0 3 0 --- 0 3 2
M1
5
M2
Evaporator
Evaporator antifreeze heater (Opt.)
Filter (Opt.)
Manual air valve
Butterfly valve
Single pump
Twin pump
Expansion tank + Safety valve (Opt.)
Manometer
Discharge valve
123456789
Item Description Item Descr ip ti on
10
Hydraulic components
VICTAULIC
CONNECTION
W A T E R TA N K I N L E T ---
DN 80--- 3” --- 88.9mm
13
4
OPTION:
WITH UNIT
9
WATER TANK NOT ASSEMBLY
DN 80 --- 3” --- 88.9 mm
W A T E R TA N K O U T L E T ---
VICTAULIC CONNECTION
10
DN 80 --- 3” --- 88.9 mm
CHILLED W ATER INLET
3
VICTAULIC CONNECTION
4
13
10
DN 80 --- 3” --- 88.9 mm
VICTAULIC CONNECTION
CHILLED WATER OUTLET
Control temperature sensor
Antifreeze temperature sensor
Tank antifreeze heater (Opt.)
Flow switch (Opt. without pumps)
Service valve with cap
Freecooling coil
Air temperature sensor
3wayvalve
Control freecooling thermostat sensor
Fans
Differential trasducer (only with electronic pump)
11
121314151617181920
21
9
F
14
8
6
M1
5 5
PUMP VERSION
UNIT FRAME (WITH ASSEMBLED TANK)
UNIT FRAME (WITHOUT TANK) TANK F R AME
PUMP VERSION
ONL Y WITH TW IN
5
7
M1
M2
ONLY WITH SINGLE
T
19
16
4
20
+
21 p
15
18
15
10
15
11
12
T
T
ASSEMBLY WITH UNIT
46
ONLY WITH WATER TANK VERSION
LIEBERT--- HIROSS BASE UNIT
2
5
T
17
F i g . 2 3 --- H y d r a u l i c c i r c u i t --- S R H 0 1 7 --- 0 2 0 --- 0 2 3 --- 0 2 5 --- 0 2 8 --- 0 3 0 --- 0 3 2
1
Evaporator
Evaporator antifreeze heater (Opt.)
Filter (Opt.)
Manual air valve
Butterfly valve
Single pump
Twin pump
Expansion tank + Safety valve (Opt.)
Manometer
Discharge valve
123456789
Item Description Item Description
10
Hydraulic components
Il Fabbricante dichiara c he questo prodotto è conforme alle direttive Europee: The Manufacturer hereby declares that this product conforms to the European Union directives: Der Hersteller erklärt hiermit, dass dieses Produkt den Anforderungen der Europäischen Richtlinien gerecht wird: Le Fabricant déclare que ce produit est conforme aux directives Européennes: El Fabricante declara que este producto es conforme a las directivas Europeas: O Fabricante declara que este produto está em conformidade com as directivas Europeias: Tillverkare försäkrar härmed att denna produkt överensstämmer med Europeiska Uniones direktiv: De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is: Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU-direktiivien vaatimukset: Produsent erklærer herved at dette produktet er i samsvar med EU-direktiver: Fabrikant erklærer herved, at dette produkt opfylder kravene i EU direktiverne:
Since the Liebert HIROSS Company has a policy of continuous
Ο ΚατασÀευαστÞj δηλþνει üτι το παÃüνπÃοΪüνεßναι ÀατασÀευασmÝνο αýmφωνα mετιj οδηγßεj τηj Ε.Ε.:
product improvement, it reserves the right to change design and specifications without previous notice.
98/37/CE; 89/336/CEE; 73/23/CEE; 97/23/CE
Printed in Italy by Liebert HIROSS S.p A.
Issued by T.D.Service
Zona Industriale Tognana
Via Leonardo da Vinci, 16/18
35028 Piove di Sacco (PD)
ITALY
Tel. +39 049 9719111
Telefax +39 049 5841257
Internet :
www.liebert-hiross.com
Since the Liebert HIROSS Company has a policy of continuous product improvement, it reserves the right to change design and specifications without previous notice.
Liebert HIROSS
is a division of
EMERSON
Printed in Italy by Liebert HIROSS S.p A.
Issued by T.D.Service
Loading...