Liebert 1800, 2100C, 2300C, CLINAC 18R, 2100D User Manual

...
Process Fluid Chiller Designed for
Keeping Business in Business
Varian CLINAC 18R, 1800, 2100C/D & 2300C/D
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional remote monitoring systems keep you informed of chiller operation.
• UL/CSA listing on standard models.
• ISO 9001 certified company.
CLINAC 18R, 1800, 2100C/D, 2300C/D Specifications
Fluid Specified Water
Heat Dissipation—BTUH (kW) 85,350 (30)
Fluid Temperature Range—°F (°C) 50-75 (10-25)
Fluid Flow Rate—GPM (l/m) 4 (15.2) @ 60°F (15.6°C)
Fluid Pressure Drop—PSI (kPa) 6 (41.4)
Performance is based on 95°F condenser ambient.
Note:
Process Fluid Chiller Specifications
Model Number PS096A PS096A PS096A
Fluid Circulated Water Ethylene Glycol Propylene Glycol
Net Cooling Capacity—BTUH (kW) 86,000 (25.2) 86,000 (25.2) 86,000 (25.2)
Leaving Fluid Temperature—°F (°C) 51 (10.6) 55 (12.8) 58 (14.4)
Fluid Flow Rate—GPM (l/m) 4.3 (16.2) 4.3 (16.2) 4.3 (16.2)
CLINAC Pressure Drop—PSI (kPa) 6 (41.4) 6 (41.4) 6 (41.4)
Chiller Pressure Drop—PSI (kPa) 4.1 (28.2) 5.5 (37.8) 6.3 (43.2)
Pump Total Head—PSI (kPa) 62.3 (428.6) 62.3 (428.6) 62.3 (428.6)
Head Available for Piping Circuit—PSI (kPa) 52.2 (360) 50.8 (350) 50 (345)
Pump HP (kW) 3 (2.2) 3 (2.2) 3 (2.2)
Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/ D 1
D
B
A
C
Model
No.
A-Width in. (mm)
B-Height
in. (mm)
C-Depth in. (mm)
D
lbs. (kg)
Voltage (60 Hz)
Weight
PS096A* 77 (1956) 69.25 (1759) 38.5 (978) 5.5 (140) 750 (340) 460, 3-phase; 208/230, 3-phase
PS120A* 77 (1956) 69.25 (1759) 38.5 (978) 5.5 (140) 750 (340) 460, 3-phase; 208/230, 3-phase
*Includes additional height due to storage tank.
Standard Features
• Indoor/outdoor cabinet
• Scroll compressor
• Refrigerant dehydrator
• Expansion valve
• Refrigerant receiver
• Stainless steel fluid reservoir expansion tank
• Pressure relief valve
• Hot gas bypass valve capacity control
• Stainless steel pump
Optional Features
• Refrigerant gauges and reservoir heater
Optional Accessories
• Emergency water bypass
• Enviro-source emergency bypass
• Water level control and alarm system
•Fluid pressure gauge
•Check valve
• Dial thermometer
• Relief valve
• Circuit setter
• Ball valve
• High temperature thermostat
• Low flow switch
• Liebert RCM8 monitor
Required Options
• 100 gallon stainless steel storage tank built into chiller frame.
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Phone: 800.877.9222 Fax: 614.841.6022
Liebert Web Site—http:www.liebert.com
SL-16563 (07/00)
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco Italy Phone: 39.049.9719.111 Fax: 39.049.5841257
Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/ D 2
23/F Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong Phone: 852.2.572.2201 Fax: 852.2.572.1182
©2000 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or regisered trademarks of their respective owners.
Loading...