Liebert 130 kVA User Manual

User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual – Hipulse
Installation & Maintenance of Hipulse 130kVA Single phase 110V, Single & 1 + N System
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Please accept our thanks for giving us the privilege to serve you by choosing a Liebert make ‘UPS’.
If this is your first Liebert UPS, we hope it is the beginning of a long relationship which delivers value to your organisation. If you already own and use a Liebert product, we are doubly honoured by your decision of continuing this relationship.
It is our constant endeavor to partner you for the growth and success of your business. This philosophy is reflected in our Mission statement “To deliver value through Air & Power Quality solutions to achieve customer delight”. Please do give us feedback to help us realize our Mission.
Emerson Network Power (India) Private Limited
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Rev. No. Revision details Date
IMPORTANT
This manual contains information concerning the installation, operation and maintenance of the Hipulse Uninterruptible Power System (UPS) for the single module and one plus one Systems.
All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or his agent) before being put into service. Failure to observe this condition will invalidate any implied warranty.
The Hipulse UPS has been designed for Commercial / Industrial use only. The Hipulse has not been designed for direct use in any life support application.
If you encounter any problem with the procedures contained in this manual you should seek immediate assistance from Emerson Network Power (India) Pvt. Ltd. Sales Office from whom the equipment was purchased. Alternatively contact the Emerson Network Power (India) Pvt. Ltd Customer Service & Support department at the address shown below:
EMERSON NETWORK POWER (INDIA) PRIVATE LIMITED Plot No. C-20, Road No. 19
Wagle Industrial Estate Thane – 400 604, INDIA
Phone : (00 91 22) 25807000
25828405
Fax : (00 91 22) 25800829 25828358
Emerson Network Power (India) Private Limited pursues a policy of continual product development and reserves the right to change the equipment without notice.
@ Copyright 1999 by Emerson Network Power
Unauthorized reproduction prohibited
All rights reserved
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
REGISTERED HEAD OFFICE
Emerson Network Power (India) Private Limited
PLOT NO. C-20, ROAD NO. 19
WAGLE INDUSTRIAL ESTATE
THANE – 400 604 MAHARASHTRA, INDIA
TELEPHONE: (00 91 22) 25807000/ 25828405 / 25802388
FAX: (00 91 22) 25800829 / 25828358
*** WEST ZONE ***
Mumbai
Address: B-414, 424, Bhaveshwar Arcade, (opp. Shreyas cinema), LBS Road, Ghatkopar, Mumbai Tel: 91-22-2500 2318, 2500 2294, 2500 2437
Fax: 91-22-2500 2415
400 086
Pune
Address: B/6, Shree Dwarka Co-op. Soc., Hare Krishna Mandir Path, Model Colony, Off. University Tel: 91-20-2567 0709, 2567 6975
Fax: 91-20-400 4020
Road, Pune 411 016
Baroda
Address: 39 / 2, Arunodaya Soc., Alkapuri, Baroda 390 005 Tel: 91-265-231 4296 / 2330 383 Fax: 91-265-2343937
Nagpur
Address: 203, Ganga Apts, 13, Giripeth, Nagpur 400 010 Tel: 91-712-540 423 Fax: 91-712-540 423
*** SOUTH ZONE ***
Bangalore
Address: No. 412, Jindal Center, 2nd Flr, 100 Fleet Road, Koramangalam, Opp. Sukhsagar Hotel, Tel: 91-80-51135670 / 5770 / 5870
Fax: 91-80-2558 8546
Chennai
Address: OMS Court, No. 1, Nathamuni Street, T., Nagar, Chennai 600 017 Tel: 91-44-2815 1063, 2815 2596, 712 4863, 713 4884, 713 4883 Fax: 91-44-2815 1442
Kochin
Address: "Nedumparambil", No. 1419/36, Kattakara Road, Kaloor, Kochin 682 017 Tel: 91-484-2341 985/86 Fax: 91-484-2341 986
Secunderabad
Address: 1-1-40/1, 2nd floor, Vasavi Towers, S. D. Road, Secunderabad - 500 003 Tel: 91-40-27806774 / 5/ 6 Fax: 91-40-2780 6777
Bangalore - 95
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
*** EAST ZONE ***
Kolkatta
Address: Jindal Towers, 21/1A/3, Darga Road, Kolkata - 700 017 Tel: 91-33-2289 0493 / 033 2289 0490 Fax: 91-33-2289 0492
Bhubaneshwar
Address: 69, Satya Nagar, Bhubaneshwar 751 007 Tel: 91-674-2520 778 Fax: 91-674-2520 778
Jamshedpur
Address: Kashi Kunji, Road No. 2, Ground Floor, Contractors Areas, Bistupur, Jamshedpur 831 001 Tel: 91-657-2227 678 Fax: 91-657-2227 678
*** NORTH ZONE ***
New Delhi
Address: 18/14, WEA, Pusa Lane, Karol Baug; New Delhi 110 005 Tel: 91-11-2582 4206 / 2582 4208 / 2582 4214 / 18 Fax: 91-11-2575 7601
Chandigarh
Address: SCO No. 272, Sector 32 -C & D, 1st Floor, Above Punjab and Sind Bank,Chandigarh. Tel: 0172-5077531 Fax: 0172-5016531
Lucknow
Address: 213, 2nd Floor, Saran Chambers-II, 5, Park Road, Lucknow - 226 001 (U.P) Tel: 91-522-2237174 Fax: 91-522-2239877
Guwahati
Address : C/o. Ashok Bhasin, South Sarania, Ashram Road, (Near GMC Tax Office), Ulubari, 781 007.
Tel: 91-361-2453270 Fax: 91-361-2453270
Guwahati -
(Updated: December 1, 2004)
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Safety Procedure
WARNING
In a domestic environment, this product may cause radio interface in which case the user may be required to take additional measures.
WARNING
HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTIONS IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
This equipment must be earthed in accordance with local electrical codes.
WARNING
THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED PROTECTION. A WARNING LABEL MUST BE FITTED TO ALL EXTERNAL PRIMARY POWER ISOLATIONS STATING.
INSULATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
GENERAL
As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these is minimised as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
BATTERIES
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of a large bank of battery cells. These precautions should be followed implicitly at all times.
Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first-aid and fire fighting facilities
TEST EQUIPMENT
When the battery is under charge, it is earth-referenced about its mid-point –e.g. if the battery s being charged at 460V the battery extremities will be at +230V and – 230V with respect to neutral (earth). When using mains-powered test equipment such as oscilloscopes in the UPS voltage area, always use a differential mode of operation to disconnect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) it is recommended that protection be worn to prevent eye damage, should an electric ware be struck by mishandling or severe electrical fault.
Some of the power components are very heavy. If their removal is necessary, ensure that sufficient manpower is available; otherwise use adequate mechanical handling equipment.
When working in the general area of the UPS where high voltages are present, a second person should be standing-by to assist and summon help in case of accident.
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
I N D E X
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1 General Introduction 1
1.1 Introduction 1
1.2 Design Concept 1
1.2.1 Hipulse Module Design 1
1.2.2 Bypass Supplies 2
1.2.3 System control Philosophy 3
1.2.4 ECOMODE (for single UPS) 4
1.2.5 UPS Power Switch Configuration 5
1.2.6 Battery circuit breaker 5
1.2.7 Battery temperature compensation 5
1.2.8 System Expansion 5
2 Installation Procedure 7
2.1 Introduction 7
2.2 Environmental Considerations 8
2.2.1 UPS location 8
2.2.2 Battery Location 8
2.3 Mechanical Considerations 9
2.3.1 System composition 9
2.3.2 Moving the cabinets 9
2.3.3 Clearances 9
2.3.4 Fixing Magnetic Components 9
2.3.5 Cable entry 9
2.4 Preliminary Checks 10
2.5 Installation Drawings 10
3 Installation (Electrical) 13
3.1 Power Cabling 13
3.1.1 System Configuration 13
3.1.2 Cable rating 14
3.1.3 General Notes 14
3.1.4 Cable connections 14
3.1.5 Safety earth 14
3.1.6 Protective Devices 15
3.1.7 Cabling procedure 16
3.2 Control cables 19
3.2.1 Battery Control 19
3.2.2 Auxiliary Terminal Block X3 and X4 at UPS 20
3.2.3 Emergency Stop 21
3.2.4 Back feed Protection 21
4 Operator Control and Display 23
4.1 Introduction 23
4.1.1 Operator Control Panel 24
4.1.2 The Menu Options 27
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5 Operating Instructions 31
5.1 Introduction 31
5.1.1 General Notes 31
5.1.2 Power switches 31
5.2 Procedure for UPS Startup: without interrupting 32 power to the load
5.3 Procedure for UPS Startup: without power initially 34 supplied to the load
5.4 Procedure for Switching the UPS into Maintenance 36 Bypass condition from Normal Operation
5.5 Procedure for Switching the UPS ON from a 38 Maintenance Power condition
5.6 Procedure for completely Powering down the UPS 38
5.7 Procedure for carrying out at Reset after a recognized 39 controlled transfer to Bypass or EPO action
5.8 Adding a single module to an existing system 40
5.9 Procedure to completely switch ON/ OFF the UPS 41 at the UPS Display control panel
5.10 Procedure to switch ON/ OFF the Inverter at UPS 43 Display control panel
5.11 Setting the Battery test 44
5.12 Language selection 45
5.13 Changing the current Date and Time 45
6 Battery Installation 47
6.1 Introduction 47
6.2 Safety 47
6.3 UPS Batteries 48
6.4 Installation Design Considerations 49
6.5 Battery Installation and Maintenance 49
6.5.1 Temperature Considerations 49
6.5.2 Battery Population 49
6.6 Battery Protection 50
6.7 Battery Cabinet and Racks 50
6.7.1 Introduction 50
6.7.2 Specification 50
6.7.3 Battery racks 50
6.8 Battery Installation 52
6.9 Battery Circuit Breaker Boxes 52
6.10 Battery Temperature Board 54
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
7 Display Panel Interpretation 55
7.1 LED Interpretation 55
7.2 Display Panel Messages 57
8 1 + N System 63
8.1 General 63
8.2 Installation Procedure 65
8.2.1 Preliminary Checks 65
8.2.2 Protective Devices 65
8.2.3 Power Cables 65
8.2.4 Control Cables 65
8.2.5 Battery Control 66
8.2.6 Emergency Stop 66
8.3 Operating Instructions 67
8.3.1 System Start-up and Shutdown procedures (separate batteries) 67
8.4 Display Panel Message Interpretation in ‘1+N’ System 70
9 Specification 71
9.1 Conformity and Standard 71
9.2 UPS Environmental 71
9.3 UPS Mechanical Characteristics 71
9.4 UPS Electrical Characteristics 72
9.5 UPS Electrical Characteristics (DC Intermediate circuit) 73
9.6 UPS Electrical Characteristics (Inverter Output) 74
9.7 UPS Electrical Characteristics (Bypass Input Mains) 75
10. ANNEXURE 77
10.1 Remote Alarm Monitor 79
10.1.1 Ram Connections 79
10.2 Input Transformer Cubicle 81
10.2.1 Introduction 81
10.2.2 Termination 81
10.2.3 Indication and Metering 81
10.2.4 Protection 81
10.3 Bypass Isolation Cubicle 82
10.3.1 Introduction 82
10.3.2 Termination 82
10.3.3 Indication and Metering 82
10.3.4 Protection 82
---- x ---- x ----- x ---- x ----
---- x ---- x ----- x ----
---- x ---- x -----
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
CHAPTER 1
General Description
1.1 Introduction
The Hipulse Uninterruptible Power Supply (UPS) System is connected between a critical load, such as a computer, and its three phase mains power supply. Being designed to furnish a well regulated 1 phase output power supply under all rated load and input supply conditions, the system offers the user the following advantages:
Increased power quality:
The UPS has its own internal voltage and frequency regulators which ensure that its output is maintained within close tolerances independent of voltage and frequency variations on the mains power lines.
Increased noise rejection:
By rectifying the input a.c. power to d.c. power, and then converting it back to a.c., any electrical noise present on the input mains supply line is effectively isolated from the UPS output, therefore the critical load sees only clean power.
Power blackout protection:
If the mains power fails, the UPS continues to power the critical load from its battery source, leaving the load immune from power disturbances.
1.2 Design Concept
1.2.1 Hipulse Module Design
This section describes an individual module's operating principles. The UPS basically operates as an a.c. - d.c. - a.c. converter (see figure 1 -1 ). This first conversion stage (from a.c. to d.c.) uses a 3 phase, fully-controlled SCR bridge rectifier to convert the incoming mains supply into a regulated d.c. busbar.
Mains Supply
(a.c.) (d.c.) (a.c.)
RECTIFIER
INVERTER
STATIC
SWITCH
(d.c.)
BATTERY
Fig 1-1 : Single Module block diagram
The d.c. busbar produced by the rectifier provides both battery charging power ­being equipped with a temperature compensated battery charging system, to prolong battery life - and power to the inverter section - which utilizes the latest IGBT switching pulse width modulation (PWM) design - and provides the second conversion phase, i.e. reconverting the d.c. busbar voltage back into an a.c. voltage waveform.
UPS Output Supply
1
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
During normal operation both the rectifier and inverter sections are active and provide regulated load power whilst simultaneously float charging the battery. In the event of a mains power failure, the rectifier becomes inoperative and the inverter is powered solely from the battery. Critical load power is maintained under these conditions until battery is fully discharged, where upon the UPS shuts down. The end of battery discharge is assumed when the battery voltage falls below a preset value (i.e. 330 / 340V d.c. for a 400 V a.c. system).
The period for which the load can be maintained following a mains power failure is known as the ‘System’s Autonomy Time’ and is dependent upon both the battery A/Hr capacity and the applied percentage load.
1.2.2 Bypass Supplies
The circuit block annotated ‘Static Switch’ in figure 1-2 contains an electronically controlled switching circuit which enables the critical load to be connected either to the inverter output or to a bypass power source via the ‘static bypass line’. During normal system operation the load is connected to the inverter and the ‘inverter -side’ of the Static Switch is closed; but in the event of a UPS overload, or inverter failure, it is automatically transferred to the static bypass supply line.
Maintenance Bypass Isolator
Maintenance Bypass Line
Bypass Supply
Bypass Isolator
Static Bypass Line
STATIC
SWITCH
Mains Supply
Input
Isolator
RECTIFIER
INVERTER
Battery Isolator
STATIC
SWITCH
Output
Isolator
UPS Output Supply
BATTERY
Fig 1-2 : UPS Power switches configuration
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the static switch activates connecting the load to the bypass supplies. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics which make the inverter frequency track that of the static bypass supply provided that the bypass remains within an acceptable frequency window. The synchronizing window is pre-selected to 2% of nominal frequency, giving an acceptable frequency window ±1 Hz.
A manually controlled, ‘Maintenance Bypass’ supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from the mains (bypass) supply while the UPS is shut down for routine maintenance.
Note: The load equipment is not protected from normal supply aberrations when operating on Bypass side or in the maintenance bypass mode
2
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1.2.3 System Control Philosophy
Normal Operation
During normal operation, i.e. when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker is also closed and the battery is therefore permanently float charged at the d.c. busbar voltage level.
(1+N Parallel UPS System) Note: As the unit outputs are connected in parallel, the System checks that the inverter control circuits are perfectly synchronised with one another and with the Bypass Mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronisation is in progress.
A module's static switch cannot close until these conditions are satisfied.
Mains Failure
If the power mains has a failure or is out of tolerance the rectifier will go off automatically, while the Inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not retuned within this time, the Inverter will go off automatically and an alarm message will appear on the UPS operator control panel display.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
Return of power mains
When the mains return within the required tolerance, the Rectifier will start up again automatically and gradually (power walk in), supplying power to the Inverter and recharging the battery at the same time. There will be no interruption of the critical load.
Off-Battery
If the battery system only is taken out of service for maintenance, it is disconnected from the rectifier/ charger and inverters by means of (an) external disconnect breaker(s). The UPS shall continue to function and meet all of the specified steady­state performance criteria, except for the power outage back-up time capability.
UPS Module fault
In the event of an Inverter fault, the Static Transfer Switch will automatically transfer the load onto the Bypass Mains with no interruption. In such an event, request qualified technical assistance.
(1+N Parallel UPS System)
In the event of a fault in a unit, the unit's Static Transfer Switch will automatically exclude the unit from the system. If the system is still capable of providing the required load, the remaining units will continue to supply the load with no interruption. When the units still present in the system are no longer capable of fulfilling power requirements, the load will automatically be transferred onto the MSS Bypass Mains. The load will be transferred with no interruption if the Inverters are synchronised with the network; if this is not the case, there will be an interruption lasting about 20 milliseconds.
3
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Overload
In the event of an overload at the Inverter output which lasts longer than the typical time/ current (refer to Chapter 9 - Specifications), the Inverter will shut down and the Static Transfer Switch will automatically transfer the load onto the MSS Bypass Mains with no interruption. If the overload falls within the typical time/ current that has been specified, the load will be returned to the inverters when the power drops to a level which can be supported by the number of active units in the system (parallel 1+N).
In the event of a short circuit in the output, the load will normally be transferred onto the MSS Bypass Mains, which will cause the Inverter to shut down; this switch is determined above all by the features of the protective devices in use in the system. In either case, an alarm message will appear on the UPS operator control panel display.
(1+N Parallel UPS System)
The control logic system constantly monitors load requirements and controls the power supplied by the UPS modules. In the event that an overload condition is sustained for greater than a preset time, the load will transfer to the mains bypass supply, when the number of active modules are unable to satisfy load requirements. The load returns to the inverter supply if the power is reduced it a value that can be sustained by the number of active modules in the system.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the 'Maintenance Bypass' line is included to enable a 'raw' mains supply to be made available to the load while facilitating a safe working environment for carrying out scheduled UPS system maintenance or troubleshooting. The circuit is manually selected by the Maintenance Bypass Isolator which can be padlocked in the OFF position.
WARNING
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
CAUTION
If an automatic circuit breaker device is not present in the input distribution panel, there remains a dangerously high voltage at the output busbars of the UPS module that is switched off
1.2.4 ECOMODE
In this operating mode the System prefers to put the load on the Bypass Mains, with the Inverter on stand-by. The load is switched over to the Inverter when the mains goes outside of standard frequency and voltage values (or the values as modified using the operator panel when starting up the system). The ECOMODE configuration requires a different setup in the default menu configuration, which may be prepared in the factory before shipment or during installation by personnel trained in the use of the System.
Note: In order to operate in ECOMODE, UPSs must be provided with compatible software versions:
The 'UPS Logic' card must be release 9.0 or later (the S/W release of the cards may be read on the front panel display, referring to Section 4.1.2 - Operating Instructions).
Operating Instructions in ECOMODE are the same as those described in Chapter 5, except that the load is normally on the Bypass mains, the Load LED is normally on Inverter (5), and corresponding alarm message will be replaced with Load on Mains (6).
4
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
WARNING
In ECOMODE the load is not protected against mains distortion.
1.2.5 UPS Power Switch Configuration
Figure 1-2 illustrates the Hipulse UPS module in what is known as the "Split Bypass" configuration. In the Split Bypass configuration, the static bypass line is connected by a separate power switch to a dedicated 'bypass' power source which also feeds the maintenance bypass line. Where a separate power source is not available the Bypass (Q2) and Rectifier input supply connections would be linked together.
With the exception of maintenance bypass isolator, all the isolators shown must be closed during normal UPS operation.
1.2.6 Battery circuit breaker
The battery should be connected to the d.c. busbar through a circuit breaker fitted inside the battery cabinet or located adjacent to batteries where a battery cabinet is not used. This circuit breaker is closed manually, but it contains an undervoltage release coil which enables it to be tripped from the UPS control electronics following certain detected faults. It also has a magnetic trip facility for overload protection.
1.2.7 Battery temperature compensation
Hipulse UPS System offers a battery temperature compensation circuit. As the temperature inside the battery cabinet area rises, the d.c. busbar voltage reduces in order to sustain the battery at its optimum charge voltage. This must be used in conjunction with the battery sensor board.
1.2.8 System Expansion
If necessary, a single -module system can be expanded to cater for an increased load requirement by adding additional modules - upto a maximum of six UPS modules can be connected in parallel. System expansion requires change in the SETUP of the display panel.
Note: System expansion should be carried out only by trained service personal. The individual modules connected to the system must be of the same power rating
5
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
CHAPTER 2
Installation Procedure
2.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with the details its own mechanical and electrical installation.
WARNING - Battery Hazards
Special care should be taken when working with the batteries
associated with this equipment. When connected together, the battery terminal voltage will exceed 400V DC, and is potential lethal.
Eye protection should be worn to prevent injury from accidental
electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it
must be replaced, stored in container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area
should be washed immediately with water.
NOTE
The UPS System can be connected to an IT (isolated neutral) power system
This section describes the UPS system’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide as to the general procedures and practices that should be observed by the installing engineer.
7
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.2 Environmental considerations
2.2.1 UPS location
The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Chapter 9 - Specifications).
All models in the ‘Hipulse’ UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located on the back of UPS. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS via the floor void. If necessary, a system of extractor fans should be installed to aid cooling air-flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.
Note 1: When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS.
Note 2: Power losses from the System which may be used in an air conditioning system are intended for operation using the Inverter, as in the ECOMODE configuration they would be undersized.
2.2.2 Battery location
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote figures for an operating temperature of 20oC. Operating above this temperature will reduce the battery life, operation below this temperature will reduce the battery capacity. On a normal installation the battery temperature is maintained between 15oC and 25oC. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Keep batteries away from main heat sources or main air inlets etc.
The batteries can be mounted in purpose-built battery cabinet, which is positioned adjacent to the UPS module. Pedestals are required for the battery cabinets when they are located on raised floors, in the same way as for the UPS cabinets. If the batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a battery circuit breaker must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible. A customized remote battery circuit breaker box, containing the circuit breaker and its necessary control board, is also available as a standard option.
8
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.3 Mechanical Considerations
2.3.1 System composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements - e.g. UPS cabinet, Battery cabinet. In general, all the cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form an aesthetically appealing equipment unit.
2.3.2 Moving the cabinets
WARNING
Ensure that any lifting equipment that used in moving the UPS cabinet has sufficient lifting capacity.
Ensure that the UPS weight is within the designated surface weight loading (Kg/sq.cm.) of any handling equipment. See the UPS specification for weight details.
The UPS cabinets can be moved by fork lift or crane. For operations with fork lift, it is necessary to remove both the front, rear (or side) grille panels located on the base of the cabinet. To enable the cabinet to be lifted by a crane, removable lifting bars, are fitted to the top of the cabinet.
In the eventuality that the equipment cannot be moved by fork lift or crane, then rollers should be used.
2.3.3 Clearances
As Hipulse has no ventilation grills at either the sides or the rear, no clearances are required. Back -access is not an essential requirement for maintenance; however, where space permits, a clearance of approximately 1000mm will ease access to magnetic component parts. This will also ensure proper exhaust from rear. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened.
2.3.4 Fixing magnetic components
After the equipment is in place, remove the transportation restraints that hold the output transformer in place.
2.3.5 Cable entry
Cables can enter for ‘Hipulse’ UPS and battery cabinet either from below or through either side. Side entry is made possible by removing blanking pieces fitted in the side panel to reveal the cable entry holes. This cable entry method allows the equipment to be positioned on a solid floor without the need for cable trenching and allows cables to pass from one module to the other when positioned side-by-side.
Note: When selecting the power cables for side entry to a module located on a solid floor, consideration must be given to the minimum permissible bending radius of the proposed cables to ensure that they can be fashioned to reach the UPS connection busbars.
9
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.4 Preliminary Checks
Before you install the UPS hardware you should carry out the following preliminary checks:
1. Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
2. Remove any packaging debris, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper immediately.
2.5 Installation Drawings
The following diagrams illustrate the key mechanical characteristics of the various UPS system cabinets
Fig 2-1: Overall General Arrangement for 130 kVA Single Phase 110V UPS with 6 Pulse rectifier Single Module and ‘1+N’
Fig 2-2: Cable entry and Foundation details for 130 kVA Single Phase 110V UPS with 6 Pulse rectifier Single Module and ‘1+N’.
10
Loading...
+ 72 hidden pages