Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
User Manual – Hipulse
Installation & Maintenance of Hipulse 130kVA Single phase 110V, Single & 1 + N System
Page 2
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 3
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Dear Customer,
Please accept our thanks for giving us the privilege to serve you by choosing a
Liebert make ‘UPS’.
If this is your first Liebert UPS, we hope it is the beginning of a long relationship
which delivers value to your organisation. If you already own and use a Liebert
product, we are doubly honoured by your decision of continuing this relationship.
It is our constant endeavor to partner you for the growth and success of your
business. This philosophy is reflected in our Mission statement “To deliver value through Air & Power Quality solutions to achieve customer delight”. Please do give
us feedback to help us realize our Mission.
Emerson Network Power (India) Private Limited
Page 4
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 5
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Rev. No. Revision details Date
IMPORTANT
This manual contains information concerning the installation, operation and
maintenance of the Hipulse Uninterruptible Power System (UPS) for the single module
and one plus one Systems.
All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or his
agent) before being put into service. Failure to observe this condition will invalidate
any implied warranty.
The Hipulse UPS has been designed for Commercial / Industrial use only.
The Hipulse has not been designed for direct use in any life support application.
If you encounter any problem with the procedures contained in this manual you should
seek immediate assistance from Emerson Network Power (India) Pvt. Ltd. Sales Office
from whom the equipment was purchased. Alternatively contact the Emerson
Network Power (India) Pvt. Ltd Customer Service & Support department at the
address shown below:
Emerson Network Power (India) Private Limited pursues a policy of continual product
development and reserves the right to change the equipment without notice.
@ Copyright 1999 by Emerson Network Power
Unauthorized reproduction prohibited
All rights reserved
Page 6
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 7
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 11
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Safety Procedure
WARNING
In a domestic environment, this product may cause radio interface in which case the
user may be required to take additional measures.
WARNING
HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTIONS IS ESSENTIAL
BEFORE CONNECTING THE INPUT SUPPLY.
This equipment must be earthed in accordance with local electrical codes.
WARNING
THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED
PROTECTION. A WARNING LABEL MUST BE FITTED TO ALL EXTERNAL
PRIMARY POWER ISOLATIONS STATING.
INSULATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING
ON THIS CIRCUIT.
Page 12
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 13
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
GENERAL
As with other types of high power equipment, dangerous voltages are present within
the UPS and battery enclosure. The risk of contact with these is minimised as the live
component parts are housed behind a hinged, lockable door. Further internal safety
screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner,
following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and
should be carried out only by trained personnel.
BATTERIES
Battery manufacturers supply details of the necessary precautions to be observed
when working on, or in the vicinity of a large bank of battery cells. These
precautions should be followed implicitly at all times.
Particular attention should be paid to the recommendations concerning local
environmental conditions and the provision of protective clothing, first-aid and fire
fighting facilities
TEST EQUIPMENT
When the battery is under charge, it is earth-referenced about its mid-point –e.g. if
the battery s being charged at 460V the battery extremities will be at +230V and –
230V with respect to neutral (earth). When using mains-powered test equipment
such as oscilloscopes in the UPS voltage area, always use a differential mode of
operation to disconnect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) it is recommended that
protection be worn to prevent eye damage, should an electric ware be struck by
mishandling or severe electrical fault.
Some of the power components are very heavy. If their removal is necessary, ensure
that sufficient manpower is available; otherwise use adequate mechanical handling
equipment.
When working in the general area of the UPS where high voltages are present, a
second person should be standing-by to assist and summon help in case of accident.
Page 14
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 15
User Manual
I N D E X
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1 General Introduction 1
1.1 Introduction 1
1.2 Design Concept 1
1.2.1 Hipulse Module Design 1
1.2.2 Bypass Supplies 2
1.2.3 System control Philosophy 3
1.2.4 ECOMODE (for single UPS) 4
1.2.5 UPS Power Switch Configuration 5
1.2.6 Battery circuit breaker 5
1.2.7 Battery temperature compensation 5
1.2.8 System Expansion 5
2 Installation Procedure 7
2.1 Introduction 7
2.2 Environmental Considerations 8
2.2.1 UPS location 8
2.2.2 Battery Location 8
2.3 Mechanical Considerations 9
2.3.1 System composition 9
2.3.2 Moving the cabinets 9
2.3.3 Clearances 9
2.3.4 Fixing Magnetic Components 9
2.3.5 Cable entry 9
2.4 Preliminary Checks 10
2.5 Installation Drawings 10
3 Installation (Electrical) 13
3.1 Power Cabling 13
3.1.1 System Configuration 13
3.1.2 Cable rating 14
3.1.3 General Notes 14
3.1.4 Cable connections 14
3.1.5 Safety earth 14
3.1.6 Protective Devices 15
3.1.7 Cabling procedure 16
3.2 Control cables 19
3.2.1 Battery Control 19
3.2.2 Auxiliary Terminal Block X3 and X4 at UPS 20
3.2.3 Emergency Stop 21
3.2.4 Back feed Protection 21
4 Operator Control and Display 23
4.1 Introduction 23
4.1.1 Operator Control Panel 24
4.1.2 The Menu Options 27
Page 16
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 17
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5 Operating Instructions 31
5.1 Introduction 31
5.1.1 General Notes 31
5.1.2 Power switches 31
5.2 Procedure for UPS Startup: without interrupting 32
power to the load
5.3 Procedure for UPS Startup: without power initially 34
supplied to the load
5.4 Procedure for Switching the UPS into Maintenance 36
Bypass condition from Normal Operation
5.5 Procedure for Switching the UPS ON from a 38
Maintenance Power condition
5.6 Procedure for completely Powering down the UPS 38
5.7 Procedure for carrying out at Reset after a recognized 39
controlled transfer to Bypass or EPO action
5.8 Adding a single module to an existing system 40
5.9 Procedure to completely switch ON/ OFF the UPS 41
at the UPS Display control panel
5.10 Procedure to switch ON/ OFF the Inverter at UPS 43
Display control panel
5.11 Setting the Battery test 44
5.12 Language selection 45
5.13 Changing the current Date and Time 45
6 Battery Installation 47
6.1 Introduction 47
6.2 Safety 47
6.3 UPS Batteries 48
6.4 Installation Design Considerations 49
6.5 Battery Installation and Maintenance 49
6.5.1 Temperature Considerations 49
6.5.2 Battery Population 49
6.6 Battery Protection 50
6.7 Battery Cabinet and Racks 50
6.7.1 Introduction 50
6.7.2 Specification 50
6.7.3 Battery racks 50
6.8 Battery Installation 52
6.9 Battery Circuit Breaker Boxes 52
6.10 Battery Temperature Board 54
Page 18
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 19
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
7 Display Panel Interpretation 55
7.1 LED Interpretation 55
7.2 Display Panel Messages 57
8 1 + N System 63
8.1 General 63
8.2 Installation Procedure 65
8.2.1 Preliminary Checks 65
8.2.2 Protective Devices 65
8.2.3 Power Cables 65
8.2.4 Control Cables 65
8.2.5 Battery Control 66
8.2.6 Emergency Stop 66
8.3 Operating Instructions 67
8.3.1 System Start-up and Shutdown procedures (separate batteries) 67
8.4 Display Panel Message Interpretation in ‘1+N’ System 70
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Page 21
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 1
General Description
1.1 Introduction
The Hipulse Uninterruptible Power Supply (UPS) System is connected between a
critical load, such as a computer, and its three phase mains power supply. Being
designed to furnish a well regulated 1 phase output power supply under all rated load
and input supply conditions, the system offers the user the following advantages:
Increased power quality:
The UPS has its own internal voltage and frequency regulators which ensure that its
output is maintained within close tolerances independent of voltage and frequency
variations on the mains power lines.
Increased noise rejection:
By rectifying the input a.c. power to d.c. power, and then converting it back to a.c.,
any electrical noise present on the input mains supply line is effectively isolated from
the UPS output, therefore the critical load sees only clean power.
Power blackout protection:
If the mains power fails, the UPS continues to power the critical load from its battery
source, leaving the load immune from power disturbances.
1.2 Design Concept
1.2.1 Hipulse Module Design
This section describes an individual module's operating principles. The UPS basically
operates as an a.c. - d.c. - a.c. converter (see figure 1 -1 ). This first conversion stage
(from a.c. to d.c.) uses a 3 phase, fully-controlled SCR bridge rectifier to convert the
incoming mains supply into a regulated d.c. busbar.
Mains
Supply
(a.c.)(d.c.)(a.c.)
RECTIFIER
INVERTER
STATIC
SWITCH
(d.c.)
BATTERY
Fig 1-1 : Single Module block diagram
The d.c. busbar produced by the rectifier provides both battery charging power being equipped with a temperature compensated battery charging system, to prolong
battery life - and power to the inverter section - which utilizes the latest IGBT switching
pulse width modulation (PWM) design - and provides the second conversion phase,
i.e. reconverting the d.c. busbar voltage back into an a.c. voltage waveform.
UPS
Output
Supply
1
Page 22
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
During normal operation both the rectifier and inverter sections are active and provide
regulated load power whilst simultaneously float charging the battery. In the event of
a mains power failure, the rectifier becomes inoperative and the inverter is powered
solely from the battery. Critical load power is maintained under these conditions until
battery is fully discharged, where upon the UPS shuts down. The end of battery
discharge is assumed when the battery voltage falls below a preset value (i.e. 330 /
340V d.c. for a 400 V a.c. system).
The period for which the load can be maintained following a mains power failure is
known as the ‘System’s Autonomy Time’ and is dependent upon both the battery A/Hr
capacity and the applied percentage load.
1.2.2 Bypass Supplies
The circuit block annotated ‘Static Switch’ in figure 1-2 contains an electronically
controlled switching circuit which enables the critical load to be connected either to
the inverter output or to a bypass power source via the ‘static bypass line’. During
normal system operation the load is connected to the inverter and the ‘inverter -side’
of the Static Switch is closed; but in the event of a UPS overload, or inverter failure, it
is automatically transferred to the static bypass supply line.
Maintenance Bypass
Isolator
Maintenance Bypass Line
Bypass
Supply
Bypass Isolator
Static Bypass Line
STATIC
SWITCH
Mains
Supply
Input
Isolator
RECTIFIER
INVERTER
Battery
Isolator
STATIC
SWITCH
Output
Isolator
UPS
Output
Supply
BATTERY
Fig 1-2 : UPS Power switches configuration
To provide a clean (no-break) load transfer between the inverter output and static
bypass line, the static switch activates connecting the load to the bypass supplies. To
achieve this, the inverter output and bypass supply must be fully synchronized during
normal operating conditions. This is achieved through the inverter control electronics
which make the inverter frequency track that of the static bypass supply provided that
the bypass remains within an acceptable frequency window. The synchronizing
window is pre-selected to 2% of nominal frequency, giving an acceptable frequency
window ±1 Hz.
A manually controlled, ‘Maintenance Bypass’ supply is also incorporated into the UPS
design. Its purpose is to enable the critical load to be powered from the mains
(bypass) supply while the UPS is shut down for routine maintenance.
Note: The load equipment is not protected from normal supply aberrations when operating on Bypass
side or in the maintenance bypass mode
2
Page 23
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1.2.3 System Control Philosophy
Normal Operation
During normal operation, i.e. when the UPS input supply is present and within
specification, both the rectifier and inverter sections are active and the static switch is
turned on to connect the inverter output to the critical load busbars. The battery
circuit breaker is also closed and the battery is therefore permanently float charged at
the d.c. busbar voltage level.
(1+N Parallel UPS System)
Note: As the unit outputs are connected in parallel, the System checks that the inverter control circuits
are perfectly synchronised with one another and with the Bypass Mains in terms of both frequency and
phase and that they have the same output voltages. Current supplied to the load is automatically
divided among UPSs. A warning message appears while synchronisation is in progress.
A module's static switch cannot close until these conditions are satisfied.
Mains Failure
If the power mains has a failure or is out of tolerance the rectifier will go off
automatically, while the Inverter will continue to operate on power from the battery for
a period of time which depends on the load and the capacity of the battery. If the
mains supply has not retuned within this time, the Inverter will go off automatically and
an alarm message will appear on the UPS operator control panel display.
Critical load will not be interrupted in the event of a drop or return of the AC power
mains.
Return of power mains
When the mains return within the required tolerance, the Rectifier will start up again
automatically and gradually (power walk in), supplying power to the Inverter and
recharging the battery at the same time. There will be no interruption of the critical
load.
Off-Battery
If the battery system only is taken out of service for maintenance, it is disconnected
from the rectifier/ charger and inverters by means of (an) external disconnect
breaker(s). The UPS shall continue to function and meet all of the specified steadystate performance criteria, except for the power outage back-up time capability.
UPS Module fault
In the event of an Inverter fault, the Static Transfer Switch will automatically transfer
the load onto the Bypass Mains with no interruption. In such an event, request
qualified technical assistance.
(1+N Parallel UPS System)
In the event of a fault in a unit, the unit's Static Transfer Switch will automatically
exclude the unit from the system. If the system is still capable of providing the
required load, the remaining units will continue to supply the load with no interruption.
When the units still present in the system are no longer capable of fulfilling power
requirements, the load will automatically be transferred onto the MSS Bypass Mains.
The load will be transferred with no interruption if the Inverters are synchronised with
the network; if this is not the case, there will be an interruption lasting about 20
milliseconds.
3
Page 24
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Overload
In the event of an overload at the Inverter output which lasts longer than the typical
time/ current (refer to Chapter 9 - Specifications), the Inverter will shut down and the
Static Transfer Switch will automatically transfer the load onto the MSS Bypass Mains
with no interruption. If the overload falls within the typical time/ current that has been
specified, the load will be returned to the inverters when the power drops to a level
which can be supported by the number of active units in the system (parallel 1+N).
In the event of a short circuit in the output, the load will normally be transferred onto
the MSS Bypass Mains, which will cause the Inverter to shut down; this switch is
determined above all by the features of the protective devices in use in the system. In
either case, an alarm message will appear on the UPS operator control panel display.
(1+N Parallel UPS System)
The control logic system constantly monitors load requirements and controls the
power supplied by the UPS modules. In the event that an overload condition is
sustained for greater than a preset time, the load will transfer to the mains bypass
supply, when the number of active modules are unable to satisfy load requirements.
The load returns to the inverter supply if the power is reduced it a value that can be
sustained by the number of active modules in the system.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the 'Maintenance
Bypass' line is included to enable a 'raw' mains supply to be made available to the
load while facilitating a safe working environment for carrying out scheduled UPS
system maintenance or troubleshooting. The circuit is manually selected by the
Maintenance Bypass Isolator which can be padlocked in the OFF position.
WARNING
The internal maintenance bypass must not be used when the UPS
system is comprised of more than two UPS modules in parallel.
CAUTION
If an automatic circuit breaker device is not present in the input
distribution panel, there remains a dangerously high voltage at the
output busbars of the UPS module that is switched off
1.2.4 ECOMODE
In this operating mode the System prefers to put the load on the Bypass Mains, with
the Inverter on stand-by. The load is switched over to the Inverter when the mains
goes outside of standard frequency and voltage values (or the values as modified
using the operator panel when starting up the system). The ECOMODE configuration
requires a different setup in the default menu configuration, which may be prepared in
the factory before shipment or during installation by personnel trained in the use of the
System.
Note: In order to operate in ECOMODE, UPSs must be provided with compatible software versions:
The 'UPS Logic' card must be release 9.0or later (the S/W release of the cards may be
read on the front panel display, referring to Section 4.1.2 - Operating Instructions).
Operating Instructions in ECOMODE are the same as those described in Chapter 5,
except that the load is normally on the Bypass mains, the Load LED is normally on
Inverter (5), and corresponding alarm message will be replaced with Load on Mains
(6).
4
Page 25
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
WARNING
In ECOMODE the load is not protected against mains distortion.
1.2.5 UPS Power Switch Configuration
Figure 1-2 illustrates the Hipulse UPS module in what is known as the "Split Bypass"
configuration. In the Split Bypass configuration, the static bypass line is connected by
a separate power switch to a dedicated 'bypass' power source which also feeds the
maintenance bypass line. Where a separate power source is not available the Bypass
(Q2) and Rectifier input supply connections would be linked together.
With the exception of maintenance bypass isolator, all the isolators shown must be
closed during normal UPS operation.
1.2.6 Battery circuit breaker
The battery should be connected to the d.c. busbar through a circuit breaker fitted
inside the battery cabinet or located adjacent to batteries where a battery cabinet is
not used. This circuit breaker is closed manually, but it contains an undervoltage
release coil which enables it to be tripped from the UPS control electronics following
certain detected faults. It also has a magnetic trip facility for overload protection.
1.2.7 Battery temperature compensation
Hipulse UPS System offers a battery temperature compensation circuit. As the
temperature inside the battery cabinet area rises, the d.c. busbar voltage reduces in
order to sustain the battery at its optimum charge voltage. This must be used in
conjunction with the battery sensor board.
1.2.8 System Expansion
If necessary, a single -module system can be expanded to cater for an increased load
requirement by adding additional modules - upto a maximum of six UPS modules can
be connected in parallel. System expansion requires change in the SETUP of the
display panel.
Note: System expansion should be carried out only by trained service personal. The individual
modules connected to the system must be of the same power rating
5
Page 26
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6
Page 27
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 2
Installation Procedure
2.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the
arrival of the commissioning engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in
accordance with the information contained in this chapter and all
equipment not referred to this manual is shipped with the details its
own mechanical and electrical installation.
WARNING - Battery Hazards
• Special care should be taken when working with the batteries
associated with this equipment. When connected together, the
battery terminal voltage will exceed 400V DC, and is potential
lethal.
• Eye protection should be worn to prevent injury from accidental
electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
• If a battery leaks electrolyte, or is otherwise physically damaged, it
must be replaced, stored in container resistant to sulfuric acid and
disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin, the affected area
should be washed immediately with water.
NOTE
The UPS System can be connected to an IT (isolated neutral) power
system
This section describes the UPS system’s environmental requirements and mechanical
considerations that must be taken into account when planning the positioning and
cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step
installation instructions, but to act as a guide as to the general procedures and practices that should be
observed by the installing engineer.
7
Page 28
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.2 Environmental considerations
2.2.1 UPS location
The UPS module should be located in a cool, dry, clean-air environment with
adequate ventilation to keep the ambient temperature within the specified operating
range (see Chapter 9 - Specifications).
All models in the ‘Hipulse’ UPS range are cooled with the aid of internal fans. Cooling
air enters the module through ventilation grills located at various parts of the cabinet
and exhausted through grills located on the back of UPS. When the cabinet is located
on a raised floor, and bottom cable entry is used, additional cooling air also enters the
UPS via the floor void. If necessary, a system of extractor fans should be installed to
aid cooling air-flow, and a suitable air filtration system used where the UPS is to
operate in a dirty environment.
Note 1: When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which
dictates the designed maximum ambient temperature, not the UPS.
Note 2: Power losses from the System which may be used in an air conditioning system are intended
for operation using the Inverter, as in the ECOMODE configuration they would be undersized.
2.2.2 Battery location
Temperature is a major factor in determining the battery life and capacity. Battery
manufacturers quote figures for an operating temperature of 20oC. Operating above
this temperature will reduce the battery life, operation below this temperature will
reduce the battery capacity. On a normal installation the battery temperature is
maintained between 15oC and 25oC. Batteries should be mounted in an environment
where the temperature is consistent and even over the whole battery. Keep batteries
away from main heat sources or main air inlets etc.
The batteries can be mounted in purpose-built battery cabinet, which is positioned
adjacent to the UPS module. Pedestals are required for the battery cabinets when
they are located on raised floors, in the same way as for the UPS cabinets. If the
batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a
battery circuit breaker must be mounted as close as possible to the batteries
themselves, and connected using the most direct route possible. A customized
remote battery circuit breaker box, containing the circuit breaker and its necessary
control board, is also available as a standard option.
8
Page 29
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.3 Mechanical Considerations
2.3.1 System composition
A UPS system can comprise a number of equipment cabinets, depending on the
individual system design requirements - e.g. UPS cabinet, Battery cabinet. In general,
all the cabinets used in a particular installation are of the same height and designed to
be positioned side-by-side to form an aesthetically appealing equipment unit.
2.3.2 Moving the cabinets
WARNING
Ensure that any lifting equipment that used in moving the UPS
cabinet has sufficient lifting capacity.
Ensure that the UPS weight is within the designated surface weight loading
(Kg/sq.cm.) of any handling equipment. See the UPS specification for weight details.
The UPS cabinets can be moved by fork lift or crane. For operations with fork lift, it is
necessary to remove both the front, rear (or side) grille panels located on the base of
the cabinet. To enable the cabinet to be lifted by a crane, removable lifting bars, are
fitted to the top of the cabinet.
In the eventuality that the equipment cannot be moved by fork lift or crane, then rollers
should be used.
2.3.3 Clearances
As Hipulse has no ventilation grills at either the sides or the rear, no clearances are
required. Back -access is not an essential requirement for maintenance; however,
where space permits, a clearance of approximately 1000mm will ease access to
magnetic component parts. This will also ensure proper exhaust from rear.
Clearance around the front of the equipment should be sufficient to enable free
passage of personnel with the doors fully opened.
2.3.4 Fixing magnetic components
After the equipment is in place, remove the transportation restraints that hold the
output transformer in place.
2.3.5 Cable entry
Cables can enter for ‘Hipulse’ UPS and battery cabinet either from below or through
either side. Side entry is made possible by removing blanking pieces fitted in the side
panel to reveal the cable entry holes. This cable entry method allows the equipment
to be positioned on a solid floor without the need for cable trenching and allows
cables to pass from one module to the other when positioned side-by-side.
Note:When selecting the power cables for side entry to a module located on a solid floor,
consideration must be given to the minimum permissible bending radius of the proposed cables to
ensure that they can be fashioned to reach the UPS connection busbars.
9
Page 30
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
2.4 Preliminary Checks
Before you install the UPS hardware you should carry out the following preliminary
checks:
1. Verify that the UPS room satisfies the environmental conditions stipulated in the
equipment specification, paying particular attention to the ambient temperature and
air exchange system.
2. Remove any packaging debris, then visually examine the UPS and battery
equipment for transit damage, both internally and externally. Report any such
damage to the shipper immediately.
2.5 Installation Drawings
The following diagrams illustrate the key mechanical characteristics of the various
UPS system cabinets
Fig 2-1: Overall General Arrangement for 130 kVA Single Phase 110V UPS with 6 Pulse
rectifier Single Module and ‘1+N’
Fig 2-2: Cable entry and Foundation details for 130 kVA Single Phase 110V UPS with 6
Pulse rectifier Single Module and ‘1+N’.
10
Page 31
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1000
875
AIR FLOW
F R O N T
3
19031903
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
842
1400
LEFT SIDE VIEW FRONT VIEW
4
1903
5
1750
1
1600
REAR VIEW TOP VIEW
Note - All dimensions are in mm
1. Removable grill for lifting with fork-lift truck
2. Air inlet grill
3. Removable grill – if using side cable entry
4. Cooling fan assembly for Rectifier & Inverter
5. Cooling fan assembly for Transformers
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
.......................
2
1
Fig 2-1: Overall General Arrangement for 130kVA Single Phase UPS
11
Page 32
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1400
800
125
65
57090
40
57090
A. CABLE ENTRY DETAILS
42.5
90
1315
1220
37.5
85
755
660
800
1400
Dia 14.0 Holes
FOUNDATION DETAILS
Note: All dimensions are in mm
Fig 2-2 : Cable entry and Foundation details for 130 kVA Single Phase UPS
12
Page 33
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 3
Installation (Electrical)
The UPS requires both “Power” and “Control” cabling once it has been mechanically
installed. All Control cables, whether screened or not, should be run separate from
the Power cables in metal conduits or metal ducts which are electrically bonded to the
metalwork of the cabinets to which they are connected.
3.1 Power Cabling
WARNING
Before cabling-up the UPS, ensure that you are aware of the location
and operation of the external isolators that connect the UPS input/
bypass supply to the mains distribution panel.
Check that these supplies are electrically isolated, and post any
necessary warning signs to prevent their inadvertent operation.
For cable entry, refer to section 2.3.5
3.1.1 System Configuration
The power cables of the system must be size with respect to the following description:
Module input cables
The module input cables must be sized for the maximum input current, including the
maximum battery recharge current, given in the table 3-1, with respect to the module
rating and the input a.c. voltage.
Module Bypass and Output cables
The Bypass and Output cables must be sized for the nominal output current, given in
the table 3.1, with respect to the module rating and the output a.c. voltage.
Battery cables
Each UPS module has its own battery, which is connected using two cables, one
positive and one negative. The battery cables must be sized for the battery discharge
current at the end-of-discharge voltage, as given in the table 3-1, with respect to the
module rating.
13
Page 34
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
The following are guidelines only and superseded by local regulations and codes of
practice where applicable:
1. The neutral conductor should be sized same as the output/ bypass current.
2. The earth conductor should be sized for carrying fault current for atleast 3 to 5
seconds or as guided by local electrical rules.
3. Consideration should be given to the use of paralleled smaller cables for heavy
currents, as this can ease installation considerably.
4. When sizing battery cables, a maximum volt drop of 3V d.c. is permissible at the
current ratings given in Table 3-1.
3.1.4 Cable Connections
The rectifier input, bypass, output and battery power cables (all require lug type
terminations) and are connected to busbars situated below the power isolator
switches - as shown in figure 3.1 for 80kVA and fig 3.2 for 120 /160/ 200kVA.
A terminal block X3 is used for connecting the control cables to the battery circuit
breaker and a second terminal block X4 is used for the external emergency stop
facility, external OFF inverter, ext. Bypass, etc. these are female spade type
connections (Fast-on 6.3 x 0.8) and are described later in Section 3.2
3.1.5 Safety earth
The safety earth busbar is located between the Bypass and Output power supply
connections as shown in the figure 3.1. The safety earth cable must be connected to
the earth busbar and bonded to each cabinet in the system.
All cabinets and cable trunking should be earthed in accordance with local
regulations.
14
Page 35
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
WARNING
Failure to follow adequate earthing procedures can result in electric
shock hazard to personnel, or the risk of fire, should an earth fault
occur.
3.1.6 Protective devices
For safety reasons, it is necessary to install, external to the UPS, circuit breaking
protective devices in the input a.c. supply and towards the battery. Given that every
installation has its own characteristics, this chapter provides general useful
information engineers, with knowledge of operating practices, of regulatory standards,
and of the equipment to be installed.
Rectifier and bypass inputs:
Protection against excessive over currents and short circuits
These inputs must be protected, installing suitable protective devices at the
distribution panel of the incoming main supply, considering that the protection should
discriminate with overload capacity of the system (see Chapter 9: Specification Electrical Characteristics).
Split Bypass :
In the case of a split bypass being used, separate protective devices should be
installed in the incoming mains distribution panel.
The protective devices must be selected for the nominal input current, with respect to
the UPS rating and the input a.c. supply voltage as given in table 3-1.
Protection against earth faults (RCD devices):
In the event of a differential (RCD) device being installed upstream of the input supply,
one must take into account transient and steady state earth leakage currents that are
produced during start-up of the UPS.
The presence of an RFI suppression filter inside the UPS, determines a residual earth
current greater than 3.5mA and less than 1000mA.
Residual current circuit breakers (RCCB) must be sensitive to d.c. unidirectional pulse
(class A) in the network and insensitive to transient current pulses.
They are identified by the symbols respectively.
These isolators must have an average sensitivity, possible adjustable between 0.3 and
1A.
It is recommended that the selectivity with every differential switch be verified both
upstream of the input distribution board and downstream (towards the load).
15
Page 36
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Parallel 1+N:
Use of differential circuit breakers on UPS unit inputs in a configuration with separate
inputs and one battery for each unit requires installation of a common device only on
the System Bypass Mains.
Use of differential circuit breakers on UPS unit inputs sharing a common battery
requires installation of device common to all the input lines. If inputs are configured
for separate mains, a common device will also be required for all System bypass
mains.
UPS Battery:
The UPS Battery is protected by means of a control circuit that operates the tripping
mechanism of an automatic circuit breaking device (having a variable trip setting).
The tripping mechanism using an undervoltage release coil that operates on a present
minimum voltage level.
The circuit breaker is essential for maintenance of the battery and is normally located
near to the battery installation. The characteristics and operation of the automatic
circuit breaker are given in Chapter 6.
Output of the System:
In the eventuality that an external distribution panel is used for load distribution, the
selection of protective device must proved discrimination with those that are use at
the input to the UPS module.
3.1.7 Cabling procedure
Once the equipment has been finally positioned and secured, connect the power
cables as described in the following procedure.
Study the connection diagram in the figures below.
1. Verify that the UPS equipment is totally isolated from its external power source and
all the UPS power isolators are open. Check that these supplies are electrically
isolated, and post any necessary warning signs to prevent their inadvertent operation.
2. Open the door(s) to the UPS cabinet and remove the lower protective cover to gain
access to the connections bars.
3. Connect the safety earth and any necessary bonding earth cables to the copper
earth bus busbar located on the floor of the equipment below the power connections.
Note: The earthing and neutral bonding arrangement must be in accordance with local and national
codes practice
Input Connections:
4. Connect the a.c. input supply cables to the input busbars (U1-V1-W1 terminals)
and the bypass a.c. supply cables to the bypass busbars (U3 - N3 terminals) and
tighten the connections.
ENSURE CORRECT PHASE ROTATION
Output System Connections:
5. Connect the system output cables between the output busbars (U2 - N2 terminals)
and the critical load and tighten the connections.
16
Page 37
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
WARNING
If the load equipment will not be ready to accept power on the arrival
of the commissioning engineer then ensure that the system output
cables are safely isolated at their ends.
6. Connect the Battery cables between the UPS terminals (+/ -) and its associated
battery circuit breaker. Connect screened auxiliary cables from each battery circuit
breaker control board to the auxiliary terminal block (X3) of UPS of their metal frame of
the Battery breaker mounted in input transformer cubicle or Battery circuit breaker
box (if used).
As a safety precaution remove the battery fuse in the module until the arrival of
commissioning engineer.
OBSERVE THE BATTERY CABLE POLARITY
WARNING
Do not close the battery circuit breaker before the equipment has
been commissioned.
Input-module Parallel Connections:
7. 1+N Parallel UPS System: Inside the module there is an Parallel Connectors Board
mounted on the left hand side. Connect one end of the interconnecting ribbon cables
to interface connector (X1) of the first UPS module and the other end to connector (X2)
of the second module, and so to the next module until a closed loop is formed. (see
fig 8-2).
Auxiliary Connections:
8. Connect the auxiliary cables of any external interface/ signals to the respective
connections of the output auxiliary terminal block (X4).
9. Refit the lower protective cover.
17
Page 38
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Q3
Q1Q2Q4
X4
X3
Q1 - INPUT
SUPPLY
Q2 - BYPASS
ISOLATOR
BATTERY INPUT BYPASS OUTPUT
Q3 - MAINTENANCE
BYPASS
Q4 - OUTPUT
ISOLATOR
Q3
Q1
Q2Q4
U1 V1 W1+VE -VEU3N3U2N2
Fig 3-1 : Cable connections for 130 kVA 1Ph UPS
18
Page 39
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
3.2 Control cables
3.2.1 Battery Control
The battery circuit breaker is controlled by the Battery Circuit Breaker Controller Board
which is located within the Input Transformer Cubicle - or adjacent to the Battery
Circuit Breaker when the batteries are rack-mounted. This board controls the circuit
breaker’s undervolts release coil and also provides a path for the circuit breaker
auxiliary contacts to signal the circuit breaker status back to the UPS control logic. All
the connections between the controller board and the UPS module are made via the
Auxiliary Terminal Block which is located in the base of the UPS cabinet.
B A T T E R Y C I R C U I T
B R E A K E R C O N T R O L L E R
B O A R D
1 2 3 4 5
X1
LINKS
Fig 3-2 : Auxiliary Terminal Block detail
Connect the battery circuit breaker control and temperature compensation cables
between the UPS auxiliary terminal block and battery circuit breaker controller board
as shown in figure 3-3. These cable must be shielded, shield should be connected at
protective earth of Input transformer cubicle or battery breaker, not of UPS.
CAUTION
If battery temperature compensation is not used the system must be
de-activated by commissioning engineer.
1
2
Common
I batt.
3
Common
4
Batt. Sw.
5
Batt. trip
6
7
8
9
10
11
12
X3
1
Ext OFF Inv.
2
3
Ext Sw. Out
4
5
Ext EPO
6
7
Ext BYP
8
9
10
11
12
X4
Back feed
Int EPO
AUXILIARY
TERMINAL
BLOCK
LOCATED IN
UPS
CABINET
19
Page 40
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
3.2.2 Auxiliary Terminal Block X3 and X4 at UPS
X3 terminal reference Reference label Description
2 Common Temperature sensor common (0V)
3 T Batt. Temperature sensor signal
4 Common Common (0V)
5 Batt. Sw. Battery circuit breaker trip control
6 Bat Trp Battery circuit breaker trip control
Note: The auxiliary cables of the battery must be screened and double insulated.
The screen is connected to the earth of the battery cabinet or supporting rack.
Use multiple-core shielded cables with a section of 0.5 to 1mm2
Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)
X4 terminal reference Reference label Description
1-2 Ext. OFF Inv
3-4 Ext. Sw. Out
5-6 Ext. EPO
7-8 Ext. BYP
9-10 Back Feed
11-12 Int. EPO
Remotely provides control for switching off the inverter.
Normally open contact.
Indication to be provided at the UPS to note the opening of an external
module output isolator.
Normally closed contact.
If unused, leave the standard connectors in place.
Remotely provides control for switching off the UPS using a remote
emergency button.
Normally closed contact.
If unused, leave the standard connectors in place.
Indication to be provided at the UPS to note the opening of an external
maintenance bypass switch.
Normally closed contact.
If unused, leave the standard connectors in place.
Signal form the UPS to indicate a return flow of energy in the bypass mais.
Normally open contact.
Availability of a contact for switching off the UPS in the same way as the
internal emergency off button.
Normally closed contact.
Note: All auxiliary cables of terminal block X4 must be double insulated.
The cross-sectional area of the auxiliary cables is from 0.5 to 1 mm2
Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)
Maximum contact rating on auxiliary terminals: 50 Vdc @ 1 Amp.
20
Page 41
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
To Battery
+
Sensor
3
Temperature
2
(Optional)
1
X3
X4
X5
X6
X7
V<
X8
X9
+
BATTERY
CIRCUIT
BREAKER
1 2 3 4 5
X2
X10
X1
UPS CABINET
X3
1
2
3
4
5
6
7
8
9
10
+
11
12
Battery C.B.
Controller
Fig 3-3: Battery Connection
3.2.3 Emergency Stop
If an external Emergency Stop facility is required it is connected to terminals 5 & 6 of
the Auxiliary Terminal Block (X4) and connect the ‘normally closed’ remote stop switch
between these two terminals using shielded cable. If this facility is not used then
terminals 5 & 6 must be linked-out as shown in Figure 3-3.
Note:The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass
and trips the battery circuit breaker. It does not however internally disconnect the input mains supply.
If required, this additional action can be facilitated by feeding the UPS input via a circuit breaker
which can be tripped by a second contact of the Emergency Stop switch.
Note:Terminals 11 and 12 of the Auxiliary Terminal Block (X4) are connected to a normally closed
contact of the UPS Display Panel Emergency Stop button and go open circuit when the button is
pressed. This output can be used as part of a wider Emergency Stop system to initiate an external
action (such as tripping an external supply breaker)
3.2.4 Back Feed Protection
Using an auxiliary terminal (pins 9-10 of connector X4) the UPS provides a normally
open contact to be used for opening of an external circuit protection device, to protect
the operator against back feed of energy resulting from a short-circuit fault of the
Bypass line SCRs. This auxiliary contact can be used, for example, in series with an
external low voltage source, in order to supply the trip coil of an automatic circuit
breaking device, located upstream of the UPS Bypass mains input. In the vent of
energy being backfeed the auxiliary circuit will activate closing the normally open
contact and as a result opening of the external circuit-breaking device; the UPS is
disconnected from the Bypass mains supply. The electrical characteristics of the
auxiliary contact are 50V (a.c. or d.c.) @ 1 Amp.
21
Page 42
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
22
Page 43
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 4
Operator Control and Display Panel
4.1 Introduction
On the front of the UPS there is a display and control panel, from which it is possible to
easily verify the status of the UPS included all the measured parameters and alarms of
the UPS and Battery. The operator control panel is divided into three functional areas:
‘Mimic LED display’ and Inverter Control switch,
‘Operator Panel’ and ‘LCD display’,
‘Bargraph section’.
As can be seen the left section consists of LEDs which indicate the operational and
alarm status of the system by turning ON or OFF or by flashing ON/ OFF.
The middle section of the operator control and display panel consists of a LCD (Liquid
Crystal Display) and its associated switches.
The following functional area (right section) shows the various UPS load and Battery
charging conditions.
HIPULSE
INV
ESC
MENU
ENTER
Fig 4-1: UPS Operator Control / Display Panel
%
23
Page 44
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
4.1.1 Operator control panel
The control and display panel LEd indications are illustrated in figure 4-2 and
described in the following text:
6
1
2
3
INV
ESC
MENU
DISPLAY
%
ENTER
7891011121314151617181945
Fig 4-2: Single module operator control panel
Mimic indications
Six LED’s mounted on a single line diagram represents the various UPS power paths
and show the current UPS operation status:
1. Bypass supply healthy
This led illuminates when the bypass a.c. input power switch is closed and the input
supply is within of set value nominal voltage (default ±10%)
2. Input supply healthy and Rectifier is operative.
3. Battery voltage healthy (i.e. between ‘under - voltage cut-off’ and ‘over - voltage
trip’ levels).
4. Inverter output healthy.
5. Load on Inverter status
This led illuminates when the output power switch is closed and the load is connected
to the inverter.
6. Load on Bypass status.
This led illuminates when the output power switch is closed and the load is connected
to the bypass a.c. supply via the static switch.
Inverter control switch
7. Inverter ON (Only for UPS above 80kVA rating) - Manual inverter selection switch.
8. Inverter LED - inverter status indicator contained within the switch icon.
The Inverter LED (yellow) indicates when the Inverter is switched OFF.
24
Page 45
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Menu Control switches
Four push button switches ESCape[9], DOWN [10], UP [11], ENTER [12], are located
below the LCD display and are used to navigate a menu-driven UPS operating and
control system.
Note: In addition to entering the day-to-day operating functions, the menu system is also used to set-up
various UPS operating parameters during commissioning. A system of password protection is therefor
used to limit the control functions accessible to the operator, whilst allowing full access to
maintenance personnel. A full description of the available menus is provided in the appropriate User
and Commissioning manuals.
Note: From the Display panel menu it is possible to select one of the following languages: English,
French, Italian, Spanish, German, Dutch. The sequence is Default window > FUNCTION > ENTER
PASSWORD > PANEL SETUP > LANGUAGE
9. ESC Pressing the ESCAPE cancels the most recent actions;
i.e. when selecting options it returns the prvious window to the LCD.
when setting parameters, it exits the window without saving the new settings.
10. MENU ∨ The DOWN push button moves a cursor down the LCD over the options
offered on certain windows, and changes the highlighted parameter values in others.
11. MENU ∧ The UP push button moves a cursor up the LCD over the options offered
on certain windows, and move a rectangular cursor to the next digit on the right when
changing parameter values in others;
12 ENTER Pressing ENTER, when selecting options, displays the next window;
The next window is determined by the option which has been selected in the present
window. When selecting new parameters its saves the new parameters.
13 Warning indicator - The red LED with the Alarm Silence switch illuminates when a
WARNING alarm is displayed on the LCD message screen, and is normally
accompanied by an audible alarm.
14. Alarm Silence Switch - Pressing the Alarm Silence switch cancels the audible
alarm but leaves the warning message display until the inappropriate condition is
rectified.
Operator Panel and LCD Display
15. LCD Display
The LCD display is capable of showing four rows of 20 characters: the top row
displays the UPS warning and alarm messages and the lower row indicate the
selected metered parameters.
During normal operation the top line of the LCD panel shows the general UPS Status
(e.g. NORMAL OPERATION) and the bottom line will indicate the current time and date
- this is known as the ‘Default Screen’. Pressing the ESCape button [9] changes the
displayed information to indicate the Communication Port status (if connected) and
the version of the software fitted to the UPS control boards.
25
Page 46
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Pressing the ENTER button [12] from the Default Screen gives the operator access to
the ‘Measurements’ menu which facilitates access to the following measurements:
Output Parameters
- Output Voltage (L-N)
- Output Current (L-N current displayed in Amperes or as a % Load)
- Output Power (displayed in kW or kVA)
- Output Frequency (of inverter and bypass mains)
Input Parameters
- Input Voltage (L-N for Bypass input)
Battery Parameters
- Battery Voltage
- Battery Current
- Battery Charge (in %)
Temperature
- Temperature (°C) at critical points
Bargraph Selection
This following functional area shows the various UPS load and battery charging
conditions.
16. Load Battery
The amber led situated at the beginning of the % Autonomy bargraph illuminates
when the battery voltage has discharged to 1.8V /cell and indicates that the battery is
approaching its low voltage cut-off point and the UPS will shortly shutdown.
17. % Battery state Autonomy time bargraph
When the battery is being charged (normal) the six leds illuminate progressively to
indicate the state of battery charge as a percentage of a charge. When the battery is
discharging (battery on-load) the bargraph function changes to provide an indication
of the remaining battery autonomy time, each step indicate approximately 2 minutes.
With a fully charged battery all five LEDs are illuminated indicating greater than 10
minutes remaining, as the autonomy falls below this time the LEDs will extinguish in
steps starting from the right-hand end.
18. % Load bargraph
The six leds illuminate progressively to indicate the applied load as a percentage of
the rated maximum current increasing in 20% steps to 100% of full load when all five
are illuminated.
19. Overload
The amber LED situated at the end of the % Load bargraph illuminates if the applied
load exceeds 100% of modules rated output current. This indication will be
accompanied by an audible alarm a alarm message.
26
Page 47
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Emergency
Stop (EPO)
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
............................................
Fig 4 - 3: EPO on UPS module
20. Emergency Stop - housed beneath a safety cover to prevent inadvertent
operation.
When the emergency stop switch is pressed it disables the static switch block entirely
(so removing load power). It also disables the rectifier and inverter, and trips the
battery circuit breaker. Under normal circumstances it does not remove UPS input
power since this applied through a manually controlled external isolator; however, if
the UPS input supply is connected via a circuit breaker having an electrical trip facility,
another section of emergency power off can be used to drive the external circuit
breaker’s trip.
4.1.2 The Menu Options
A map of the routes to the options offered by the menu is provided in figure below.
Options include windows which show status information and windows which permit
data to be entered, or parameters for equipment control to be set. The menu map
shows that the route pass from the main menu through different intermediate
windows to reach the option targeted. The diagram shows each of the windows in the
format in which it appears on the LCD screen. The initializing, default & main menu
windows are described below.
27
Page 48
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
E
NORMAL OPERATION
NORMAL OPERATION
11:15.50 01.02.98
11:15.50 01.02.98
>MEASUREMENT <
>MEASUREMENT <
FUNCTION
FUNCTION
MAINTENANCE
MAINTENANCE
SETUP
SETUP
or. for
instanc
e
RECTIF. SWITCH OPEN
RECTIF. SWITCH OPEN
OUTPUT SWITCH OPEN
OUTPUT SWITCH OPEN
INV.: UNSYNCHRONIZED
INV.: UNSYNCHRONIZED
11:15.50 01.02.98
11:15.50 01.02.98
>OUTPUT <
>OUTPUT <
INPUT
INPUT
BATTERY
BATTERY
TEMPERATURE
TEMPERATURE
MODEM TYPE :
MODEM TYPE :
M-TECH.1932-ZDX
EE
>VOLTAGE <
>VOLTAGE <
CURRENT
CURRENT
POWER
POWER
FREQUENCY
FREQUENCY
M-TECH.1932-ZDX
MODEM STATUS :
MODEM STATUS :
NOT CONNECTED
NOT CONNECTED
OUTPUT : [Vrms]
OUTPUT : [Vrms]
VOLTAGE [Vrms]
VOLTAGE [Vrms]
L-N
L-N
XXX
XXX
CURRENT: [AMPS]
CURRENT: [AMPS]
L-N
L-N
XXXX
XXXX
LOAD : [%]
LOAD : [%]
L
L
XXX
XXX
REAL POWER : [KW]
REAL POWER : [KW]
B
B
XXX
XXX
SW VERSION
SW VERSION
PANEL V 02.0
PANEL V 02.0
UPS LOGIC V 01.0
UPS LOGIC V 01.0
FUNCTION
MAINTENANCE
SETUP
OUTPUT
OUTPUT
>INPUT <
>INPUT <
BATTERY
BATTERY
TEMPERATURE
TEMPERATURE
OUTPUT
OUTPUT
INPUT
INPUT
>BATTERY <
>BATTERY <
TEMPERATURE
TEMPERATURE
OUTPUT
OUTPUT
INPUT
INPUT
BATTERY
BATTERY
>TEMPERATURE <
>TEMPERATURE <
_WRITE SAVE _
_ WRITE SAVE _
_MOVE EXIT _
_ MOVE EXIT _
INPUT PASSWORD
INPUT PASSWORD
????????
????????
_WRITE SAVE _
_ WRITE SAVE _
_MOVE EXIT _
_ MOVE EXIT _
INPUT PASSWORD
INPUT PASSWORD
????????
????????
_WRITE SAVE _
_ WRITE SAVE _
_MOVE EXIT _
_ MOVE EXIT _
INPUT PASSWORD
INPUT PASSWORD
????????
????????
PRESS DOWN KEY
PRESS ENTER KEY
E
PRESS ESCAPE KEY
APP. POWER [KVA]
APP. POWER [KVA]
L
L
XXX
XXX
FREQUENCY : [Hz]
FREQUENCY : [Hz]
INVERTER XX.X
INVERTER XX.X
BYPASS XX.X
BYPASS XX.X
INPUT:
INPUT:
VOLTAGE [Vrms]
VOLTAGE [Vrms]
L-N
L-N
XXX
XXX
BATTERY:
BATTERY:
VOLTAGE XXX [V]
VOLTAGE XXX [V]
CURRENT XXXX [A]
CURRENT XXXX [A]
CHARGE XXX [%]
CHARGE XXX [%]
TEMPERATURE:
TEMPERATURE:
Tc xxx.x To xxx.x
Tc xxx.x To xxx.x
Ta xxx.x Tb xxx.x
Ta xxx.x Tb xxx.x
Fig 4 - 4: Map of screen display available to operator
28
Page 49
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
LCD Display Panel Messages
Initializing Window
After first connecting power to the UPS and closing
the bypass A.C. input power switch, the
EMERSON NETWORK POWER
EMERSON NETWORK POWER
3PH-1PH
3PH-1PH
UPS
UPS
INITIALIZATION message will appear on the LCD
screen. It persists for about five seconds while the
control firmware is loaded and the unit performs a
self-test. It is followed by a window showing
various messages with the time and date on the
bottom line.
RECTIF. SWITCH OPEN
RECTIF. SWITCH OPEN
BATTERY SWITCH OPEN
BATTERY SWITCH OPEN
OUTPUT SWITCH OPEN
OUTPUT SWITCH OPEN
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
When the power switches and battery circuit
breaker have been closed and the inverter has
stabilized the window will change to the default
window.
NORMAL OPERATION
NORMAL OPERATION
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
M0DEM TYPE
M0DEM TYPE
M-TECH.1932-ZDX
M-TECH.1932 -ZDX
MODEM STATUS
MODEM STATUS
NOT CONNECTED
NOT CONNECTED
Default Window
The message shown below, will be seen on the
default window whenever the UPS is operating
normally.
The top lines display the UPS operational status
and indicates alarm conditions when they occur;
and line four normally shows the time and date.
Info Window
From Default Window, pressing the ESC key,
information about the modem programmed in
memory and its connection are shown on display.
Pressing again the ESC key, software release are
shown, both on UPS board and on Panel board;
this feature is useful upgrading SW for next
versions and to know exactly features of present
release.
Pressing again ESC key it goes back to Default
Window.
Main Menu Window
The main menu is selected from the Default
Window by pressing the ENTER key:
The four windows accessed from the Main Menu
offer further options, which are described in the
relevant chapters of this manual.
>MEASUREMENT<
>MEASUREMENT<
FUNCTION
FUNCTION
MAINTENANCE
MAINTENANCE
SETUP
SETUP
The MEASUREMENT option gives access to
windows which show the present values of
parameters such as input & output voltages and
current, load, etc. These parameters are useful
when determining the state of UPS or the cause of
alarms, and are described in more detail below.
29
Page 50
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
The FUNCTION, MAINTENANCE and SETUP options all require a password which is
set by the commissioning engineer. This manual does not provide servicing
instructions and the options accessed from theses windows are therefore not shown
on the menu map in figure 4-4. Only trained service engineers should be authorized
with a password.
In any case FUNCTION, MAINTENANCE and SETUP options can be read but is not
possible to change them without password.
Option Selection Mode
If a window from which options can be selected is displayed, a pair of indicator arrows
appear at the extremities of the line.
The UP/ DOWN push buttons move these up and down the screen over the options.
When the arrows point at a chosen option, press ENTER to display the next window.
Press ESC to return the previous window to the screen.
Alarm / Warning Messages
The Alarm and Warning messages are shown on the three upper lines of the display.
The ALARM indicator (red) and audible warning accompany all Alarm messages.
There is a default selection for every message and corresponding mode of red
indicator (OFF, ON, FLASHING) and buzzer sound (OFF, ON INTERMITTENT, SINGLE
SOUND)
The default mode can be changed according to particular needs of the plant, a PC
and communication program are needed.
The Alarm and Warning messages are detailed in Chapter 7- Display Panel
Interpretations of this manual.
30
Page 51
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 5
Operating Instructions
5.1 Introduction
The UPS can be considered to be in one of three operating conditions:
Normal operation
All relevant power switches and circuit breakers closed, the load is powered by the
UPS.
Shutdown
All power switches and circuit breakers open - no load power.
On Static Bypass
The load power is supplied through the mains static bypass line. This may be
considered as an intermediate operating condition being utilized for the purpose of
load transfers between inverter and maintenance bypass or supply under abnormal
operating conditions.
ECOMODE
All the relevant power supply switches and the battery switch are off, and the load is
fed by the Bypass Mains through the UPS Static Transfer Switch, while the Inverter
remains on stand-by.
This chapter contains instructions which enable you to switch between the three
above conditions, to carry out a RESET after a fault transfer and how to switch OFF the
inverter.
5.1.1 General notes
Note1: All the user controls and indicators mentioned in these procedures are identified in chapter 1.
Some of diagrams are repeated here to assist in understanding the procedures.
Note2: The audible alarm may annunciate at various points in these procedures. It can be cancelled
at any time by pressing the ‘Alarm Reset’ push-button.
Note3: The Hipulse UPS System incorporates an optional automatic boost charge facility which can
be used in systems containing conventional flooded lead-acid batteries. If this type of battery
is used in your installation you may notice that the battery charger voltage may be greater
than its nominal (432V d.c. for 380V a.c., 446V d.c. for 400V a.c. and 459V d.c. for 415V a.c.
system) when the mains supply returns from a prolonged outage. This is the normal response
of the boost charge facility; the charger voltage should return to normal after a few hours.
5.1.2 Power Switches
The UPS can be separated by means of power switches, mounted inside the cabinet
and accessible after opening the front door, which has a key.
The location of the UPS power switches is shown in Figure 5-1. The UPS module
power switches are:
o Q1 - Input MCCB: connects the UPS with he mains supply.
o Q2 - Bypass Isolator: connects the UPS with the bypass supply.
o Q3 - Maintenance Bypass Isolator (Padlocked) permits supply of the load
directly by the bypass line for maintenance of the UPS module.
The internal maintenance bypass must not be used when the UPS system is comprised of more
than two UPS modules in parallel.
o Q4 - Output Isolator: connects the output of the UPS to the load.
Note: The battery interrupter is not expected inside of the UPS and should be installed in the proximity
of the respective battery bank.
31
Page 52
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.2 Procedure for UPS Start-up: without interrupting power
to the load
This procedure will describe
how to start the UPS and the
how to transfer the load from
the external maintenance
bypass to the UPS inverter. It is
assumed that the installation is
complete, the system has been
commissioned by authorized
personnel and the external
power isolators are closed.
Refer to Fig 5-1 for
corresponding isolators Q1 to
Q4, and Fig 5-2 Operator
Control Panel for various LEDs
and Display indications.
6
1
2
3
INV
7891011121314151617181945
ENSURE CORRECT PHASE ROTATION
EMERSON NETWORK POWER
EMERSON NETWORK POWER
3PH-1PH
3PH-1PH
UPS
UPS
Q1Q2Q4
Input
Supply
Bypass
Isolator
Fig 5 - 1: Location of Power Isolators
DISPLAY
ESC
MENU
ENTER
Fig 5 - 2: Operator Control Panel
1. Close Q3 Maintenance Bypass switch and
external switch (inside Maintenance Bypass) to
load.
2. Close the output power switch Q4 and the
Bypass power switch Q2.
Initializing Window:
After first connecting power to the UPS and closing
the isolator, this message will appear on the LCD
screen. It persists for about five seconds while the
control firmware is loaded by a screen showing
various messages with the time and date on the
bottom line.
The Module Mimic indicators Bypass supply
healthy (1) and after 20 seconds Load on Bypass
(6) will flash and red led (13) will illuminate.
Maint.
Bypass
%
Q3
Output
Isolator
32
Page 53
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
RECTIF. SWITCH OPEN
RECTIF. SWITCH OPEN
BATTERY C.B. OPEN
BATTERY C.B. OPEN
MANUAL BYPASS CLOSED
MANUAL BYPASS CLOSED
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The Display window will show the present status
of the UPS
3. Close the Rectifier input power switch Q1.
Note:
In ECOMODE the message 'LOAD ON BYPASS' will not
LOAD ON BYPASS
LOAD ON BYPASS
MANUAL BYPASS CLOSED
MANUAL BYPASS CLOSED
INV. OFF
INV. OFF
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
appear.
4. Wait for 20 seconds then close the battery circuit
breaker. This is located inside the battery cabinet
(if used) or is otherwise located adjacent to the
battery racks.
The Module Mimic indicator (3) Battery unavailable
should extinguish. Several LED’s on the Battery
state of charge bargraph will illuminate showing the
battery state of charge.
The rectifier will ‘walk-in’ and stabilize at float the
voltage.
5. Open the Maintenance Bypass power switch Q3
and fit lock.
The Module mimic indicator Load on bypass (6)
will flash amber.
LOAD ON BYPASS
LOAD ON BYPASS
INV.: OFF
INV.: OFF
The Display window will show the present status of
the UPS.
6. After 5 seconds the Module Mimic LED’s will
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
change so that the Load on inverter (5) will light
steady green and the Load on Bypass (6) will
extinguish.
Note: In ECOMODE the Load on Mains led (6) stays on
while the Load on inverter led (5) is off.
NORMAL OPERATION
NORMAL OPERATION
The message shown below, will be seen on the
Default screen whenever the UPS is operating
normally.
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The UPS is operating normally with its
Inverter supplying the load
NORMAL OPERATION
NORMAL OPERATION
(ECOMODE)
(ECOMODE)
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
ECOMODE: The following message will appear in
the default screen whenever the UPS is operating
on ECOMODE. The load is supplied by the Bypass
Mains.
The UPS is operating in ECOMODE with the Bypass
Mains supplying the load.
33
Page 54
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.3 Procedure for UPS Startup without power initially
supplied to the load
This procedure should be followed when turning on the UPS from fully powered down
condition i.e. where the load is not being initially supplied at all. It is assumed that the
installation is complete, the system has been commissioned by authorized personnel
and the external power isolators are closed. Refer to Fig 5-1 & 5-2 for corresponding
isolators Q1 to Q4, and Operator control Panel respectively.
1. Open the UPS doors to gain access to the main
power switches.
2. Close the Rectifier Power Switch (Q1).
The Module Mimic LED’s will indicate input supply
a.c. present (2 -steady green) and after
approximately 20 seconds the Inverter output
healthy (4- steady green) and Battery unavailable
(3) will light and also red led (13) will illuminate.
The Display screen will show the following:
Initializing Window:
EMERSON NETWORK POWER
EMERSON NETWORK POWER
3PH-1PH
3PH-1PH
UPS
UPS
BYPASS SWITCH OPEN
BYPASS SWITCH OPEN
BATTERY C.B. OPEN
BATTERY C.B. OPEN
OUTPUT SWITCH OPEN
OUTPUT SWITCH OPEN
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
After first connecting power to the UPS and closing
the Q1 isolator, this message will appear on the
LCD screen. It persists for about five seconds
while the control firmware is loaded. It is followed
by a screen showing various messages with the
time and date on the bottom line.
Note: If input power is present but the display remains
blank, then the Micro Controller is not working, please
contact your dealer for advice.
BATTERY C.B. OPEN
BATTERY C.B. OPEN
BYPASS SWITCH OPEN
BYPASS SWITCH OPEN
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
BATTERY C.B. OPEN
BATTERY C.B. OPEN
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
WARNING
The following action will apply power to load the
equipment - Ensure that it is safe do so
3. Close the UPS output power switch Q4.
The Module Mimic LED’s will change so that the
Load on Inverter (5 - steady green) and Battery
unavailable (3) will light and also red led (13) will
illuminate.
Note: In ECOMODE the Load on Inverter led (5) is off.
This display window will show:
4. Close the Bypass input power switch Q2.
Bypass input led (1-steady green) will light, after 20
seconds the inverter synchronises with the mains
bypass.
5. Before closing the battery circuit breaker check
the d.c. busbar voltage. From the above window
press the ENTER key:
The Main Menu Window will display:
34
Page 55
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
>MEASUREMENT <
>MEASUREMENT <
FUNCTION
FUNCTION
MAINTENANCE
MAINTENANCE
SETUP
SETUP
Select MEASUREMENT and press ENTER key.
OUTPUT
OUTPUT
INPUT
INPUT
>BATTERY <
>BATTERY <
TEMPERATURE
TEMPERATURE
Select BATTERY and d.c. busbar voltage will be
displayed:
BATTERY
BATTERY
VOLTAGE 446 [V]
VOLTAGE 446 [V]
CURRENT 001 [A]
CURRENT 001 [A]
CHARGE 000 [%]
CHARGE 000 [%]
If the voltage indicated is satisfactory (432V d.c. for
380V a.c. system, 446VV d.c. for 400V a.c. system
and 459V d.c. for a 415V a.c. system) press the
Escape key repeatedly until the display returns to
the original window.
6. Manually close the battery circuit breaker. This
is located inside the battery cabinet (if used) or is
otherwise located adjacent to the battery racks.
The Module Mimic indicator (3) Battery unavailable
should extinguish. Several LED’s on the Battery
state of charge bargraph (17) will illuminate
showing the battery state of charge
When the battery circuit breaker has been closed
and the inverter has stabilized the screen will
change to the default window.
Default window:
NORMAL OPERATION
NORMAL OPERATION
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The message shown below, will be seen on the
default screen whenever the UPS is operating
normally:
The top lines display the UPS operational status
and indicates alarm conditions when they occur;
and line four normally shows the time and date.
The UPS is operating normally with its
Inverter supplying the load.
ECOMODE:
NORMAL OPERATION
NORMAL OPERATION
(ECOMODE)
(ECOMODE)
The following message will appear in the default
screen whenever the UPS is operating in
ECOMODE. The load is supplied through Bypass
Mains.
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The UPS is operating in ECOMODE with the Bypass
Mains supplying the load.
35
Page 56
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.4 Procedure for Switching the UPS into a Maintenance
Bypass condition from normal operation
The first part of this procedure details how to select the Inverter OFF and power the
load from the bypass mains via the Static Switch. This procedure should be followed
to transfer the load from the UPS inverter output to the maintenance bypass system.
This may be required during UPS maintenance procedures.
NORMAL OPERATION:
Follow the procedure below to transfer the load from the output to the Maintenance
Bypass of UPS.
ECOMODE:
Follow the procedure below to transfer the load from the output Maintenance Bypass
of the UPS.
CAUTION
The following window alls the operator to select the UPS
inverter ON or OFF
Before making this operation, read messages on display to be sure
that bypass supply is regular and the inverter is synchronous with it,
not to risk a short interruption in powering the load.
IF YOUR ARE NOT SURE OF WHAT YOU ARE DOING
- THEN DO NOT DO IT
1. Press the INV switch on the left side of the
operator control panel.
WARNING! STOP
WARNING! STOP
INVERTER REQUESTED
INVERTER REQUESTED
ENTER TO CONTINUE ↵
ENTER TO CONTINUE ↵
ESC TO CANCEL
ESC TO CANCEL
2. Confirm this operation as instructed at the
display:
Press ENTER for 1 second to confirm INV OFF
Press ESC for 1 second.
3. If ENTER is pressed:
The Module Mimic indicator Load on Inverter (5)
will extinguish and the Load on Bypass indicator (6)
will flash amber, and also the red led (13) will flash
and normally will accompanied by an audible
alarm.
Pressing the Alarm Silence Switch cancels the
audible alarm but leaves the warning message
displayed until the appropriate condition is rectified.
4a) NORMAL OPERATION:
The UPS inverter will not shut down and the load
will transfer to the Bypass supply.
The Module Mimic indicator Load on Bypass (6)
will flash amber and the Load on Inverter (5)
indicator will extinguish.
Your load is now powered via the Static Bypass system.
4b) ECOMODE:
36
Page 57
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
At this point the UPS inverter stops but the load
continues to be supplied by the bypass mains.
The Load on Mains indicator light (6) on the unit's
synoptic panel flashes yellow, and the Load on
Inverter indicator light (5) goes off.
Your load is now powered via the Static Bypass system
5. Unfasten the lock, release the internal safety bar
and close the maintenance bypass power switch
Q3. Open the Rectifier input power switch Q1, the
Output power switch Q4, the bypass power switch
Q2 and the Battery circuit breaker. This is located
inside the battery cabinet (if used) or is otherwise
located adjacent to the battery racks. The unit will
power down but the load will continue to be
supplied by the manual bypass.
WARNING
Wait 5 minutes for the internal D.C. busbar capacitors
to discharge.
WARNING
The following points will be live within the UPS:
- Bypass a.c. input supply terminals.
- Maintenance Bypass power switch.
- Static Bypass power switch.
- UPS output terminals.
Input and Output terminals remain protected by a
metallic cover.
Your load is now powered from the maintenance bypass
system and the UPS is completely shut down.
37
Page 58
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.5 Procedure for Switching the UPS ON from a Maintenance
Power condition.
Follow the procedure for 'UPS startup: without interrupting power to the load' referring
to the paragraph 5.2, start from point number 2.
5.6 Procedure for completely powering down the UPS
This procedure should be followed to completely power down the UPS and LOAD. All
power switches, isolators and circuit breakers will be opened and there will be no load
power.
CAUTION
The following procedure will switch off all power to the load
equipment.
1. Open the Battery circuit breaker and the Rectifier
input power switch Q1.
The Module Mimic indicator Load on Inverter (5)
will extinguish and the Load on Bypass indicator (6)
will flash amber. The Battery not available indicator
(3) will light amber and the battery bargraph LED’s
will all extinguish.
LOAD ON BYPASS
LOAD ON BYPASS
BATTERY C.B. OPEN
BATTERY C.B. OPEN
RECTIF. SWITCH OPEN
RECTIF. SWITCH OPEN
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The display window will show messages reflecting
the actions taken (i.e. Load on Bypass; Battery
Breaker open; Rect. Switch open; etc).
Note: In ECOMODE the message 'LOAD ON BYPASS'
will not appear.
2. Open the Output power switch Q4 and the
bypass power switch Q2.
All operator LED indications and messages will
extinguish as the mains driven internal power
supplies decay.
3. To completely isolate the UPS from the a.c.
supplies, the main external power input isolator
(both isolators, where separate supplies are
provided for rectifier and bypass) should be
opened.
On the primary input distribution panel, which is often
located distant from the UPS area, a label should be
posted advising service personnel that the UPS circuit is
under maintenance.
38
Page 59
User Manual
SETUP
SETUP
↑
WRITE SAVE
↵↓
MOVE EXIT ESC
ENTER PASSWORD
00000000
↑
WRITE SAVE
↵ ↓
MOVE
EXIT ESC
ENTER PASSWORD
00000000
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
WARNING
Wait 5 minutes for the internal D.C. busbar capacitors
to discharge.
The UPS is now completely powered down.
IMPORTANT
The Maintenance Bypass Power switch may be
operated at any time when the UPS is powered down
to connect the load to the maintenance bypass supply
if required.
The load equipment is not protected from normal
supply aberrations when operating in the
maintenance bypass mode.
5.7 Procedure for carrying out a RESET after a recognized
controlled transfer to bypass or EPO action.
When the necessary action to correct the problem has been taken, this procedure
should be followed to restore the UPS back to its normal operating condition following,
a controlled transfer to bypass or when the Remote Emergency Power Off has been
activated.
A recognized controlled transfer to bypass is activated by the following problems:
Inverter Overtemperature, Cut-off Overload, Battery Over voltage, when configured for
manual return from bypass operation (only for system test).
EMERGENCY STOP
EMERGENCY STOP
LOAD ON BYPASS
LOAD ON BYPASS
INV: UNSYNCHRONISED
INV: UNSYNCHRONISED
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
MEASUREMENT
MEASUREMENT
>FUNCTION <
>FUNCTION <
MAINTENANCE
MAINTENANCE
Press the ENTER key.
Note: In ECOMODE the message 'LOAD ON BYPASS'
will not appear.
Select FUNCTION and press ENTER key.
When the PASSWORD has been completed press
ENTER key.
39
Page 60
User Manual
ON/OFF UPS CONTROLS
ON/
OFF UPS CONTROLS
RESET ALARM HISTORY
RESET EVENT HISTORY
>RESET ALARMS <
RESET ALARM HISTORY
RESET EVENT HISTORY
>RESET ALARMS <
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
BATTERY TEST
BATTERY TEST
GENERATOR
GENERATOR
PANEL SETUP
PANEL SETUP
>NEXT PAGE <
>NEXT PAGE <
PROTOCOLS
PROTOCOLS
RELOAD UPS DATA
RELOAD UPS DATA
>RESET BUFFERS <
>RESET BUFFERS <
RECTIFIER OFF
RECTIFIER OFF
Return the Display window to normal by repeatedly pressing the ESCAPE key back
through the various windows until the default screen is displayed.
These operations resets the logic circuitry to enable the rectifier, inverter and static
switch to operate normally.
Select NEXT PAGE and press ENTER key.
Press the ENTER key.
Select RESET ALARMS and press ENTER key.
Note: When the remote EPO switch has been activated it is necessary to manually close the battery
circuit breaker.
CAUTION
When the EPO system incorporates a trip facility of the external input
a.c. power supply circuit breaker, the RESET switch would have no
affect on it. First close the external input a.c. supply circuit breaker,
the UPS can be started in the normal manner, as the logic circuits will
automatically reset on return of the power supplies.
5.8 Adding a single module to an existing system
This procedure should be carried out only by trained service personal.
40
Page 61
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.9 Procedure to completely switch ON/ OFF the UPS at the
UPS Display Control Panel:
1. From the Default window, press the ENTER key:
MEASUREMENT
MEASUREMENT
>FUNCTION <
>FUNCTION <
MAINTENANCE
MAINTENANCE
SETUP
SETUP
↑WRITE SAVE ↵
↑ WRITE SAVE ↵
↓MOVE EXIT ESC
↓MOVE EXIT ESC
ENTER PASSWORD
ENTER PASSWORD
00000000
00000000
BATTERY TEST
BATTERY TEST
GENERATOR
GENERATOR
PANEL SETUP
PANEL SETUP
>NEXT PAGE <
>NEXT PAGE <
MODEM CONNECTION
MODEM CONNECTION
>ON/OFF UPS CONTROL <
>ON/OFF UPS CONTROL <
RELOAD UPS DATA
RELOAD UPS DATA
RESET BUFFERS
RESET BUFFERS
>INVERTER OFF <
>INVERTER OFF <
BYPASS ON
BYPASS ON
RECTIFIER ON
RECTIFIER ON
RECTIFIER MAN
RECTIFIER MAN
↑ROTATE START ↵
↑ROTATE START ↵
EXIT ESC
EXIT ESC
INVERTER ON
INVERTER ON
the Main Menu window will display:
2. Select FUNCTION and press ENTER key:
Before being allowed into the FUNCTION windows
you are requested to enter a password. This is
achieved by pressing the UP arrow key repeatedly
until the first digit displays the character required,
you then press the DOWN arrow key once to move
on to the second digit. This action is repeated for
all eight digits. When the PASSWORD has been
completed press the ENTER key.
CAUTION
This operation gives the operator access to modify
UPS's operating mode, it is advised that only trained
qualified personnel should attempt to do that.
3. You have now access to all function windows.
Press the DOWN arrow key until the cursors have
selected NEXT PAGE – press the enter key.
4. Press the DOWN arrow key until the cursors
have selected ON/OFF UPS CONTROL.
Press the enter key.
CAUTION
The following window allows the operator to select
the UPS inverter ON or OFF, select the rectifier ON or
OFF, select the rectifier to manual or float voltage and
a switch OFF the line (bypass) voltage to the load.
IF YOU ARE NOT SURE WHAT YOU ARE DOING,
THEN DO NOT DO IT.
NORMAL OPERATION:
5a. Ensure INVERTER is selected by the cursors
and press the ENTER key.
41
Page 62
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
The OFF selection will be highlighted, using the UP
arrow key, rotate between the selections offered (in
this case it will be ON or OFF) select ON. Press the
ENTER key to execute your order.
After approximately 20 seconds, the Module Mimic
will change so that the Load on Inverter (5) will light
steady green and the Load on Bypass (6) will
extinguish.
6a. Return the Display window to normal by
repeatedly pressing ESCAPE key back through the
various windows until the default screen is
displayed.
The UPS is operating normally with its
Inverter supplying the load.
ECOMODE:
>INVERTER OFF <
>INVERTER OFF <
BYPASS ON
BYPASS ON
RECTIFIER ON
RECTIFIER ON
RECTIFIER MAN
RECTIFIER MAN
↑ROTATE START ↵
↑ROTATE START ↵
EXIT ESC
EXIT ESC
INVERTER ON
INVERTER ON
5b. Ensure BYPASS is selected by the cursor and
press the ENTER key:
The OFF selection will be highlighted, using the UP
arrow key, rotate between the selection offered (in
this case it will be On or OFF) Select ON. Press the
ENTER key to execute your order.
The Module Mimic LED’s will change: Load on
Mains (6) will come on and Load on Inverter (5) will
go out.
6b. Return the Display window to normal by
repeatedly pressing ESCAPE key back through the
various windows until the default screen is
displayed.
The UPS is operating in ECOMODE with
Bypass Mains supplying the load.
42
Page 63
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.10 Procedure to switch ON/OFF the inverter at UPS display
control panel
CAUTION
This operation gives the operator access to modify UPS’’s operating
mode, it is advised that only trained qualified personnel should
attempt to do that.
NORMAL OPERATION
NORMAL OPERATION
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
NORMAL OPERATION
NORMAL OPERATION
(ECOMODE)
(ECOMODE)
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
WARNING! STOP
WARNING! STOP
INVERTER REQUESTED
INVERTER REQUESTED
ENTER TO CONTINUE ↵
ENTER TO CONTINUE ↵
ESC TO CANCEL
ESC TO CANCEL
INV OFF VIA DISPLAY
INV OFF VIA DISPLAY
LOAD ON BYPASS
LOAD ON BYPASS
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
NORMAL OPERATION
NORMAL OPERATION
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
NORMAL OPERATION
NORMAL OPERATION
(ECOMODE)
(ECOMODE)
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The display window will show the present status of
the UPS for normal operation.
The display window will show the following screen
for the UPS running in ECOMODE.
1. Press the INV switch on the left side of the
operator control panel.
2. Confirm this operation as instructed at the
display:
Press ENTER for 1 second to confirm INV OFF
Press ESCAPE for 1 second to exit.
3. If ENTER is pressed:
The Module Mimic indicator Load on Inverter (5)
will extinguish and the load on bypass indicator (6)
will flash amber, and also the red led (13) will light
and normally will be accompanied by audible
alarm. Pressing the Alarm Silence Switch cancels
the audible alarm. Pressing the Alarm Silence
Switch cancels the audible, but leaves the warning
message displayed until the appropriate condition
is rectified.
Note: In ECOMODE the message ‘LOAD ON BYPASS’
will not appear.
4. Press the INV switch on the operator control
panel to start up the INVERTER.
NORMAL OPERATION
After 20 second the Module Mimic LEDS will
change so that the local or the inverter (5) will light
steady green and the load on bypass (6) will
extinguish.
Return to the normal window.
ECOMODE:
The load on Mimic led (6) stays on while the load
on inverter led (5) will illuminate.
ECOMODE: The following message will appear in
the default screen whenever the UPS is operating
in ECOMODE. The load is supplied by the bypass
mains.
43
Page 64
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.11 Setting the Battery Test
A software-controlled battery facility can be initiated from the Operator control Panel
on an ‘immediate’ or ‘periodic’ basis. This test turns off the rectifier and runs the
inverter (and load) from the battery from the predetermined period. If the battery
voltage falls below an preset minimum level prior to the termination of the test period
a ‘BATTERY TEST FAILED’ alarm is annunciated and the rectifier is immediately turned
on to prevent the load from transferring to bypass – and recharge the battery. These
instructions given below initiates an immediate battery test.
For the following test to be ‘meaningful’ as part of the UPS commissioning procedure,
the batteries should be fully charges prior to the test being carried out. The UPS
rectifier section must be therefore allowed to be operated with the battery connected
for several hours to provide the battery with an adequate initial charge.
CAUTION
Do not continue with this procedure if the battery is not yet charged.
1. From the default window press the ENTER key: the Main Menu window will display.
2. Select FUNCTION and press ENTER key.
3. When the password has been completed press the ENTER key.
4. Select the BATTERY TEST and press ENTER key.
5. Verify that the parameters entered in the battery test set up menu are appropriate. If
not then enter the correct set up parameters (FUNCTION à BATTERY TEST à SET
UP)
6. Press ESC key to return to the battery test menu screen.
7. Using the ‘UP’ menu button, select ‘YES’ (Y), then press enter to initiate an immediate
battery test.
8. Step back to default screen, by continuously pressing the ESC button and verify that
the message: BATTERY UNDER TEST is displayed. The green LED battery bargraph
will indicate the remaining battery time.
Note: If the UPS is allowed to run in this condition the battery bargraph LED’s will progressively
turn off the indicating the remaining autonomy time.
9. The battery will be tested for the selected ‘DURATION’ time after which the UPS will
revert to normal operation.
Note: If the battery fails the test, the rectifier will immediately return to the float mode and the
‘BATTERY: TEST FAILED’ alarm will be displayed on the default screen.
44
Page 65
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
5.12 Language Selection :
If required, select the appropriate language using the following procedure.
MEASUREMENT
MEASUREMENT
>FUNCTION <
>FUNCTION <
MAINTENANCE
MAINTENANCE
SETUP
SETUP
↑WRITE SAVE ↵
↑WRITE SAVE ↵
↓MOVE EXIT ESC
↓MOVE EXIT ESC
ENTER PASSWORD
ENTER PASSWORD
00000000
00000000
BATTERY TEST
BATTERY TEST
GENERATOR
GENERATOR
>PANEL SETUP <
>PANEL SETUP <
NEXT PAGE
NEXT PAGE
>LANGUAGE ENG <
>LANGUAGE ENG <
TYPE 0000 MASTER
TYPE 0000 MASTER
GROUP 1 UPS 1
GROUP 1 UPS 1
PASSWORD 00000000
PASSWORD 00000000
From ‘Default’ window, press ENTER key.
Select the FUNCTION and press the enter key.
A password must be entered to gain a further
access to next menu. The initial default password
of ‘00000000’ need not be changed at this point of
time. Press the enter key.
Select PANEL SET UP and press enter key.
Select LANGUAGE and press the ENTER key.
Use the UP push button to rotate through the available options and select the required
default language. The options are: English, Italian, German, French , Dutch &
Spanish.
Press ENTER to accept and store the language selection, then step back to the
default window by repeatedly pressing ESC as required; the current alarms should
now be stored in the selected language.
Note: Ensure the data entered during the following procedures are r3cordded in the appropriate
commissioning documentation.
5.13 Changing the current Date and Time
1. From DEFAULT WINDOW, pressing ENTER key, select MAINTENANCE >>
ENTER>> PASSWORD>> ENTER>> select and enter the line showing the time and
date.
2. Position the cursor on the row on which the date-time is displayed, and press
ENTER.
3. Using the 'UP' and 'DOWN' menu buttons, enter the current time and date
information.
4. Press ENTER to save the settings, then press ESC twice to return to the DEFAULT
WINDOW.
45
Page 66
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
46
Page 67
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 6
Battery Installation
6.1 Introduction
The UPS battery consists of battery blocks connected in series to provide a nominal
d.c. input voltage for the UPS inverter. The required ‘Autonomy time’ (the time that
battery can maintain supply to the load in the event of a mains failure) is limited by the
ampere hour size of the individual battery blocks and in some cases it could mean
several strings are connected in parallel.
Usually, with UPS installations in the power range covered by the ‘Hipulse’ equipment,
the batteries are contained in a purpose built battery cabinet which sits alongside the
main UPS and the Battery Circuit Breaker Controller Board ( for all sizes).
The battery cabinet can be installed in one of the following forms:
Complete installation comprising the battery cabinet, batteries and the circuit breaker.
Battery cabinets and battery circuit breaker - with no batteries.
Battery cabinet only – with no batteries or circuit breaker.
It is possible to install batteries of various types and capacity in the cabinet to obtain
he required autonomy characteristics.
It must be possible to disconnect the battery from the UPS module when undertaking
maintenance or service procedures. This is facilitated by means of a suitably rated
circuit breaker which must be located as close as possible to the battery terminals,
and the power and control cables connected to the UPS using the most direct route
possible. The circuit breaker can be switched off manually ON or OFF, but should also
contain an under voltage release mechanism (to be energized by the UPS control
electronics) and a magnetic trip facility for overload protection which is used in
conjunction with battery circuit breaker controller module.
If multiple sets of batteries connected in parallel are used to increase battery
autonomy, the extension must be fitted with a sectioning device to permit work to be
performed on one set of batteries wile the others remain in service.
For external battery assembly, a customized Battery Circuit Breaker (the features of
which depend on the sizes of the UPS) including a Battery Circuit Controller Board
(the same for all sizes) can be provided. This box is designed to be either wall
mounted or assembled on a frame, and is connected between the UPS and the
battery. Refer to section 6.9 for more information.
A common battery circuit breaker is available for systems incorporating two parallel
UPS with a common battery. It comprises two switches, which may be used to
section one UPS while the other remains active. Refer to section 8.3 for more
information.
6.2 Safety
Special care should be taken while working on batteries associated with Hi-pulse UPS
system equipment. When all the cells are connected together, the battery terminal
voltage will exceed 400 V DC and is potentially lethal. A primary safety consideration
is to physically isolate the battery installation from all but appropriately qualified
maintenance personnel, which is best achieved by locating in a key locatable cabinet
or a purpose designed, dedicated battery room.
47
Page 68
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
The following general battery safety precautions and WARINGS should be observed all
the time.
CAUTION
• A battery can present risk of electric shock or burn from high short
circuit currents.
• When connected in a string the voltage could be 460 V d.c. this
voltage is potentially lethal always observe high voltage
precautions.
• Only qualified personnel should install or service batteries.
• Eye protection should be worked to prevent from accidental
electrical arcs.
• Only use tools with insulated handles.
• Wear rubber gloves and a rubber apron when handling batteries.
• If a battery leaks electrolyte, or is otherwise physically damaged, it
should be placed in a container resistant to sulphuric acid and
disposed of in accordance with legal regulations.
• If electrolyte comes into contact with the skin the affected area
should be washed with plenty of clean water immediately.
• Batteries must be always disposed of according to local
environmental laws.
6.3 UPS Batteries
It is common practice in UPS installations to use valve-regulated cells. The term
‘valve regulated’ is used currently in place of either ‘sealed’ or maintenance free both
of which have been used in the past.
Valve regulated cells are not ‘sealed’ and will vent, particularly on overcharge. The
amount of gas given off is less than for a flooded cell but when considering the design
of the battery installation allowances must be made for adequate ventilation and
heating of the cells. Boost charging must not be applied to valve regulated cells, as
this will cause them to overcharge and subsequently vent.
Similarly, valve regulated cells cannot be regarded as ‘maintenance free’ as they
must be kept clean and their connections checked periodically for tightness and lack
of corrosion. It is not possible to check the cells’ specific gravity directly but the
battery can be checked by the ‘CS PG battery service programme’, which can give an
indication of faulty cell degradation within the battery.
Batteries are fully charged before delivery, however, storage and transportation times
mean that, inevitably, some charge is lost by the time the battery is commissioned.
All the cells forming the battery should be brought to the same state of charge and
recharged within 6 months of the factory charge.
It is especially important that the battery is fully charged before attempting a witness
test of the autonomy time. This may require several days to complete; therefore, any
witness test concerning the batteries should take place only after the battery has
been on uninterrupted float charge for at least one week.
Cell performance typically improves after a few weeks in service or after two or three
discharge / recharge cycles.
48
Page 69
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6.4 Installation design considerations
Note:Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturers’ manuals. The battery safety information contained in this
section relates to the key considerations, which must be taken into account during the installation
design process and might affect the design outcome depending on localized conditions.
6.5 Battery installation and maintenance
6.5.1 Temperature considerations
Battery performance depends on the ambient battery temperature. Capacity and
autonomy are quoted for a new battery operating at 20o C. Battery capacity is
increased by 1% for every 1o C increase in temperature up to 25o C. If a battery is
used at a temperature above 25o C, its life is reduced; consequently, its capacity and
UPS autonomy time will reduce more rapidly over a period of time. Operating below
20o C will reduce the battery capacity by approximately 1% -1.5% per 1o C. For
example if a battery discharge test is attempted during the middle of winter when the
ambient temperature is 5o C the battery capacity will be only 77.5% of its design value
and will not satisfy its specified autonomy time.
Ambient temperature, ventilation, spacing, float voltage and ripple current all affect
the battery temperature. Uneven temperature distribution through the battery string
will cause the voltage distribution to be uneven which can also lead to problems- it is
therefore very important to maintain an even temperature across the whole battery
chain. ‘Valve regulated’ cells are very sensitive to temperature and should be
operated at a temperature between 15o C and 25o C. To help sustain this operating
temperature range the battery is normally float charged at 2.25V/cell. When batteries
are cabinet mounted adjacent to the UPS module, it is the battery which dictates the
designed maximum ambient temperature, not the UPS.– i.e. in the case of ‘valve
regulated’ cells the ambient regulated cells the ambient room temperature should be
kept between 15oC and 25oC, and not between 0oC and 40oC (which is the specified
main equipment operating temperature range) Temperature excursions are
permissible for short periods of time provided the ambient temperature does not
exceed 25oC.
6.5.2 Battery population
The nominal DC bus voltage, and therefore battery float voltage, is set according to
the module’s rated input/output voltage and usually set top 432Vdc (380Vac) 446 Vdc
(440Vac) or 459Vdc (415Vac). Given that the desired cell float voltage is 2.25V, this
means that a different number of cells are required in each case. (See Table 6-1).
Parameter 380V 400V 415V
Number of cells used (Standard) 192 198 204
End-of-discharge voltage 320 330 340
Float voltage 432 446 459
Table 6-1 – Battery population
49
Page 70
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6.6 Battery protection
The battery is connected to the UPS through a circuit breaker which is manually
closed and electronically tripped via the UPS control circuitry. If the cells are cabinet
mounted this circuit breaker is fitted within the cabinet, however, if they are rack
mounted (or located remote from the main UPS cabinet) then the battery circuit
breaker must be mounted as near as possible to the batteries themselves, and the
power and control cables connected to the UPS using the most direct route possible.
The UPS electronic circuitry will trip the circuit breaker if any of the following conditions
occur:-
1. If the d.c. busbar drops below 330Vd.c. (this would normally occur during a
mains failure when the battery autonomy time has been exceeded.
2. If there is a rectifier problem and the d.c. bus rises above (2.45 V/cell exceeded
on the battery).
3. If the emergency stop is operated.
To achieve the required autonomy time, it may be necessary to parallel the battery
strings. In which case, the battery circuit breaker should be placed downstream of all
parallel battery strings.
Note: All equipment servicing procedures should be carried out by trained personnel only.
6.7 Battery Racks
6.7.1 Introduction
These are custom build fabricated racks for keeping the batteries. These are similar
in construction to Battery cabinets except for the external covers. There are no
covers and batteries are allowed to cool naturally.
6.7.2 Fitting the Batteries
1. In general, a minimum space of 10 mm must be left on all vertical sides of the
battery block to permit free air movement around cells.
2. Clearance should be allowed between the top of the cells and the underside of the
shelf above (this is necessary for monitoring and servicing cells.
3. When installing the batteries, please always work from the bottom shelf upwards to
prevent raining the center of gravity.
6.7.3 Connecting the Battery
1. All the cabinets/ racks must be earthed and bonded together.
2. When the cabinet/ rack is installed on a raised floor, the battery power cables and
circuit breaker control cables can be routed to the UPS cabinet via the floor of the
cabinets. If the cabinets are located adjacent to each other located on a solid floor
these cables can be passed between the cabinets via the lifting apertures located
in the lower sides of the cabinets
3. In general, it is recommended that the inter-connecting cables are fitted to the
batteries within their particular level before fitting the inter-level connecting cables,
followed finally by the cables to the circuit breakers.
4. An insulating shroud should be fitted cables, followed finally by the cables to the
circuit-breaker.
5. When connecting the cables between the battery extremities to the circuit breaker
always connect the circuit breaker end of the cable first .
50
Page 71
User Manual
Figure 6
-
1: A typical arrangement of Batteri
es in a Battery Rack
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
The battery cabinet also indicates the power and auxiliary connection cables (3 meters in
length) between the cabinet and the UPS. Refer to section 3.3.1 to identify connections.
BATTERY SUPPLY
TO UPS CABINET
51
Page 72
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6.8 Battery Installation
Whatever the type of mounting system selected, following conditions should be noted:
Layout of the cells:
Whatever battery mounting system is used, the batteries should be laid out in such a
manner as to make simultaneous contact with two exposed live parts having a
potential greater than 150V impossible. Where this is not possible, insulated terminal
shields must be installed and insulated cable must be used for connection.
Service platform:
The service platform (or duckboard) must be slip-proof, insulated from the floor and
be at least one meter wide.
Connections:
All connections must be as short as possible.
Battery Protection Circuit Breaker:
A battery circuit breaker is generally installed in an enclosure of the wall close to the
battery installation. The connection of the circuit breaker box available for the Hipulse is described in the following paragraph.
6.9 Battery circuit breaker:
The Battery circuit breaker is fitted inside the Input Transformer cubical along with its
control board and is used to connect the battery to the UPS in installations where the
batteries are not contained in the standard battery cabinet.
Usually the breaker is fitted as close as possible to the batteries. Figure 6-3 shows
details of the power and control cable connections between the circuit breaker or
battery cabinet and the UPS itself. Two methods of connecting the three pole battery
circuit breaker are illustrated in figure 6-2. Method A shows the spare pole being used
to divide the battery bank in half, thereby reducing the battery total voltage to half
when the circuit breaker is open during servicing etc. Method B connects the spare
pole in series with the positive connection, thereby providing two sets of contacts in
the positive line as an added safety precaution.
When installing the battery
cabinet remove the battery fuse
In the UPS before making the
battery circuit breaker power
connections.
++++
96 Cells96 Cells
++++
96 Cells96 Cells
A - Half potential switching method
B - Double positive pole method
Figure 6-2: Battery C/B layout of switching poles
52
Page 73
User Manual
Figure 6
-
3: Battery Control and Power Connections
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
A
+
UPS CABINET
+
Sensor
Temperature
(Optional)
V<
BATTERY
CIRCUIT
BREAKER
3
2
1
X3
X4
X5
X6
X7
X8
X9
X2
X10
1 2 3 4 5
X1
X4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Battery C.B.
Controller
B
+
UPS CABINET
+
Sensor
Temperature
(Optional)
V<
BATTERY
CIRCUIT
BREAKER
3
2
1
X3
X4
X5
X6
X7
X8
X9
X2
X10
1 2 3 4 5
X1
X4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Battery C.B.
Controller
A – Half potential switching method
B – Double positive pole method
53
Page 74
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
6.10 Battery temperature Board
A battery / sensor card supplied separately from the battery circuit breaker is
connected with the UPS logic through the battery circuit breaker card.
With this feature fitted, the nominal float voltage supplied to the battery is adjusted so
as to be inversely proportional to the ambient battery cabinet /room temperature.
This prevents the battery being over charged at high ambient.
54
Page 75
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
CHAPTER 7
Display Panel Interpretation
7.1 LED Interpretation:
The LED item number refers to details shown in the figure 7.1 below.
1
2
3
LED N0. NORMAL
STATE
1. ON If this green led is OFF, it signifies a problem with the Bypass input a.c.
2. ON If this led is OFF, a problem exists in the Input power supply or in a part of the rectifier. An alarm message
3. OFF If this yellow led is ON it signifies that the battery is not available. This could be due to the battery circuit
4. ON If this green led is OFF, it signifies that the inverter is not producing its correct output voltage.
6
DISPLAY
%
INV
ESC
7891011121314151617181945
MENU
ENTER
Fig 7-1: Single module operator control panel
INTERPRETATION – ACTION
Check the following –
1. Bypass input power switch Q2 is closed.
2. Input Supply voltage is within 10% of nominal
3. Power supply fuses are OK – on the a.c. Power supply board will extinguish if either fuse is
ruptured.
If the above checks prove unsatisfactory then seek qualified assistance.
is visible at the display.
Check the following –
1. The rectifier input isolator (Q1) is closed.
2. The input voltage is within the limits of normal operation.
3. The phase sequence of the mains input is correct.
4. Verify that condition leading to an emergency stop has not happened, in which case a Reset
must be carried out.
If these checks do not give a positive result, request qualified assistance.
breaker being open or that the d.c. busbar voltage is below the figures stated in the item(2) specified
above.
The battery circuit breaker will open automatically if the d.c. voltage falls below these levels.
Check the following –
1. Check that the conditions for led(2) are satisfied.
2. DC busbar voltage – if not above 320V, then carry out checks as for led(2) – mains rectifier
failure above. If d.c. busbar voltage is above 320V but you are unable to close the battery
circuit breaker then seek qualified assistance.
3. Battery circuit breaker is closed.
If the above checks prove unsatisfactory, then seek qualified assistance.
Check the following –
55
Page 76
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
1. If [OVERTEMPERATURE] or [OVERLOAD] alarm messages are active then (after allowing the
UPS to cool / checking that the load current on the Bypass line is not excessive) use the
procedure to carry out the reset (see Chapter 5 – Operating Instructions).
2. Check that the conditions for led(2) are satisfied.
3. Check that the Inverter led(8)- yellow – is OFF, otherwise follow Inverter switch ON procedure.
4. Check that no conditions exist which will prevent switching the INV ON (e.g. PC command).
5. Verify that condition leading to an emergency stop has not happened, in which case a Reset
must be carried out.
5. ON If this green led is OFF, then it signifies that the load has been transferred to the Static bypass supply. If
this is an automatic change over it will be accompanied by a fault warning on the display panel. Take the
appropriate actions for the display indication (see Display alarm message table 7-2).
6. OFF This led is mutually exclusive to led(5). If this amber led is ON, the load has been transferred to the
Bypass mains supply. Verify the cause by following the alarm indications at the LCD display panel. If the
above checks prove unsatisfactory then seek qualified assistance.
13. OFF This red led will flash ON and OFF and indicates that the UPS has detected fault, it will be accompanied by
a message on the display panel, take the required actions for the display panel message (see Display
alarm message table 7-2). This will be accompanied by an audible warning. Pressing the Alarm silence
switch (14) stops the audible alarm, but leaves the warning message displayed until the appropriate
condition is rectified.
16. OFF If this yellow led is ON it signifies that the battery voltage is low and that the end of battery discharge is
near. This will be accompanied by audible warning.
17. N/A This is a bargraph indicating the battery charge state and would normally have four or five of the leds ON.
When the unit runs on battery, this bargraph changes to give an indication of the time remaining on the
battery.
18. N/A This is a bargraph indicating the % of the total load that is being applied to the system.
19. OFF If this yellow led is ON it signifies that the applied load has exceeded the maximum. It will be
accompanied by all five load bargraph leds being ON (item 18), the Alarm warning indication flashing RED
(item 13) and an OVERLOAD messages on the visual display. This will be accompanied by an audible
warning. Reduce the load immediately.
56
Page 77
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
7.2 Display Panel Messages
The message displayed on Hipulse can be categorized into types:-
(a) ALARM messages - these are messages which needed urgent attention and warn
of a UPS shutdown or imminent shutdown the load would normally transfer to the
bypass supply if it is available. All alarm messages are accompanied by an audible
warning.
(b) WARNING messages - these are the messages generated to warn or confirm to
the operator of action taken (i.e. if the rectifier a.c. input supply power switch was
opened the Warning message would read RECTIF. SWITCH OPEN).
The following table lists the various messages displayed on the operator panel
together with a description of their interpretation.
Sr. No. Display Message Alarm Interpretation
1. EMERGENCY STOP This alarm indicates that the UPS was shut down by means of the
local or remote (if fitted) Emergency Power Off push button (EPO)
which is normally due to operation action – investigate the cause
for pressing the button. If this button was not pressed then check
the continuity of the circuit to the Remote switch, Customer
connections, Auxiliary terminal block X4; pin 5 and 6; normally
closed.
2. INV. OFF The INV. OFF alarm is active whenever the inverter is not producing
its correct output voltage, either because it has been switched OFF
or due to an internal fault, it will normally be accompanied by one
or more of the other inverter fault conditions.
3. INV: OVERVOLTAGE
INV: UNDERVOLTAGE
OUTPUT: NO VOLTAGE
OUTPUT: WAVEFORM ERR
Most of the inverter fault messages are self explanatory, however
the WAVEFORM ERR informs the operator that the output voltage
peak has flattened caused by an internal inverter problem and
therefore the output will be out of limits.
4. INV. OVERTEMPER. Over temperature is sensed by a normally-closed thermostat (90°C
operating) fitted to each inverter heat sink. If an over temperature
condition arises, the audible alarm will accompany this message;
the inverter stops and load transfers to Bypass after 3 minutes.
5. OVERTEMP. SHUTDOWN This message informs the operator that the inverter has been
switched OFF and that the load has been transferred ot Bypass due
to an Inverter over temperature.
6.
OVERLOAD PRESENT
The inverter overload has an inverse load/ time characteristic – i.e.
it will accept 125% overload for 10 minutes and 150% overload for
60 seconds. If this characteristic is exceeded the load transfers to
the bypass supply, the inverter stops and the overload alarm
annunciates. The [OVERLOAD PRESENT] alarm will annunciate as
soon as the load exceeds 100% of the UPS rating, and the load will
transfer to Bypass some time later, depending on the degree of
57
Page 78
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
overload present.
7. OVERLOAD SHUTDOWN This message informs the operator that the load has been
transferred to bypass due to an inverter overload.
8. OUTPUT SWITCH OPEN This is a status alarm. The output switch must be selected
‘CLOSED’ at all times except when operating on the Maintenance
bypass supply.
9. BYPASS SWITCH OPEN This is a status alarm. The bypass input switch must be closed all
the times.
10. BATTERY C.B. OPEN This is a status indication only. Note that if the UPS is operating
with the Battery circuit breaker open, and the mains power fails,
then the UPS output will also fail together with load power, since
the inverter has no battery backup.
11. BATTERY: FUSE FAIL This problem should be rectified as soon as possible. If the mains
power fails then the UPS output will also fail together with load
power, since there is no battery backup.
12. BATTERY: TEST FAILED The system has carried out a test of the battery. If this alarm is not
accompanied by a [BATTERY C.B. OPEN] or [BATTERY: FUSE FAIL]
message then a full check of the Battery bank is required.
13.
DC BUS: UNDERVOLTAGE
When the inverter is operating on the battery this message is
displayed on the condition when battery voltage has fallen below a
preset value. If the input a.c. power cannot be restored, you should
shut down your loads.
58
Page 79
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
14. BATTERY: E.O.D. Battery discharge has continued beyond a preset value. The
inverter will shut down, the system will attempt a transfer to bypass.
If Bypass is not available, any load connected to the UPS will be
without power.
15. RECT. OFF The RECT. OFF alarm is active whenever the battery charger
(rectifier) is not producing its correct output voltage. This can be
caused by an operator selection to OFF, an Input supply failure, an
open rectifier a.c. input power switch or an internal fault which may
be accompanied by one of the fault conditions.
16. RECT. SWITCH OPEN
RECT. CURRENT LIMIT
BATTERY: FUSE FAIL
Most of the rectifier fault messages are self explanatory however,
the DC BUS: FAST OVERVOLTAGE message informs the operator
the d.c. busbar voltage is too high.
DC BUS: FAST OVERVOL
17. BYP. ABSENT
BYP. OVERVOLTAGE
BYP. UNDERVOLTAGE
INPUT FAILURE: input a.c. supply failed or out of specified
acceptable range. Do not switch OFF the inverter while this
indication is active or the load will lose its power.
BYP. FREQUENCY ERROR
18. BYP. SCR FAILURE One or more of the static switch SCR’s has developed a fault. The
bypass would not support the load in the event of a UPS failure,
immediate action is required. Seek qualified assistance.
19. BYP. PHASE ROT. ERROR This message informs the operator that the input power lines have
been cross-connected and the phases sequence is incorrect.
20. MANUAL BYPASS CLOSED This is a status warning that the load is being powered through the
maintenance bypass line and is unprotected from mains supply
aberrations.
21.
INV. UNSYNCHRONIZED
This warns that the inverter is not synchronized with the bypass
supply, which is normally due to a problem with the bypass supply
being outside an acceptable frequency window. Do not switch OFF
the inverter when this alarm is active or the load will experience a
200 millisecond power break.
59
Page 80
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
22. BATTERY ON LOAD This is a status warning that the battery is discharging. It normally
accompanies a [BYP: ABSENT] or [RECT: OFF] message.
23. AUTONOMY XXXX min The micro monitors the battery percentage capacity while on charge
and the battery time remaining while on discharge. It calculates the
time remaining as function of the discharge current against the
programmed ampere-hour capacity of the battery. It will update the
time remaining as the load is change.
24. BATTERY UNDER TEST This message informs the operator that the system is carrying out a
periodic battery test.
25. BOOST TIME EXPIRED This message is only applicable to systems which include the boost
charge option, boost time charge elapsed set value, battery should
be controlled by service personnel.
26. LOAD ON BYPASS This is a status warning that the load is being powered through the
static bypass line and is unprotected from mains supply
aberrations.
This action is either selected by the operator or a fault condition,
check for other fault messages.
27. RECT: OFF
RECT: OFF VIA DISPLAY
This is a status message confirming that the rectifier has been
selected off by the operator from either the front panel display or an
external PC or by a switch on UPS microprocessor PCB.
28. BYP: OFF
BYP: OFF VIA DISPLAY
This is a status message confirming that the bypass has been
inhibited by the operator from either an external PC or by a switch
on UPS microprocessor PCB.
29.
INV: OFF
INV: OFF VIA DISPLAY
This is a status message confirming that the inverter has been
selected off by the operator from either the front panel display or an
external PC or by a switch on UPS micro controller PCB.
60
Page 81
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
30. BYP: XFER COUNT BLOCK This message informs the operator that the load has been
transferred to the bypass more than eight times in one minute.
After eight transfers the load will remain on bypass. This message
could be initiated by a load causing the UPS to overload, it requires
investigation.
31. BATTERY: GROUND FALUT This message informs the operator that the battery is not longer
isolated from ground and there is danger of electrocution.
32. BACKFEED FAULT This message informs the operator that the failure of the bypass
static devices has resulted in voltage being fed back to the bypass
supply input.
In addition to the above message there are a number of software alarms (i.e. BAD
EEPROM, BACK-UP, BATTERY LOW etc.) that will require attention from a qualified
service engineer.
61
Page 82
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
62
Page 83
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
Chapter 8
1 + N System
8.1 General
The system can comprise of up to 6 UPS modules of the same power rating and
connected in parallel without the need for a centralized mains static bypass. Instead
the bypass static switches of each UPS share the load when the system transfers to
the main bypass supply.
From a ‘power’ viewpoint, each module is internally identical to the single module
configuration. A 1+N parallel system requires inverter and bypass supplies, intermodule control signals to manage current sharing, synchronizing and bypass
switching between the module. In the figure 8-1, this is shown as the ‘inter-module
control bus’, which is facilitated through the use of multi-way ribbon cables connected
between the units of the system.
When three or more modules are to be connected in parallel it is recommended that
inductance should be inserted in the static bypass line. This can be installed internal
to the UPS as an option.
For each module it is necessary to program the display panel with the correct rating
and to identify that the internal static switch is being used.
63
Page 84
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Maintenance Bypass
Isolator Q3
Maintenance Bypass Line
Bypass Isolator Q2
RECTIFIER
Input
Isolator Q1
BATTERY 1
Maintenance Bypass
Isolator Q3
Bypass Isolator Q2
RECTIFIER
Input
Isolator Q1
BATTERY 2
Static Bypass Line
DC Bus
INVERTER
UPS MODULE 134
Battery
C.B. 1
Maintenance Bypass Line
Static Bypass Line
DC Bus
INVERTER
UPS MODULE 234
Battery
C.B. 12
Inter Module
Control Bus
Inter Module
Control Bus
STATIC
SWITCH
STATIC
SWITCH
Output
Isolator Q4
X4X4
Ext.
Sw .
Out
Output
Isolator Q4
X4X4
Ext.
Sw .
Out
UPS 1
Output
Supply
UPS 2
Output
Supply
I N P U T
D I S T R I B U T I O N
UPS MODULE 6
Ext.
Sw .
Out
D I S T R I B U T I O N
P A N E L
Fig 8-1: '1+N' System block diagram with Separate Batteries
UPS 6
Output
Supply
D I S T R I B U T I O N
O F L O A D
64
Page 85
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
8.2 Installation procedure
8.2.1 Preliminary Checks
Be sure that a parallel kit is present and fitted in each of the modules, and that the
modules are of the same rating and with the same software and hardware release
(see section 4.1.2 – Info window)
WARNING
Fitting of the parallel kits and board setting required to convert from
Single Module to 1+N must be made by qualified and trained
personnel. This operation involves also setting of system with
separate batteries or common batteries.
8.2.2 Protective Devices
Refer to the instructions supplied in Chapter 3 – Electrical Installation - Section 3.1.6.
8.2.3 Power Cables
Input Bypass and Rectifier, outputs of module as described in Chapter 3.
8.2.4 Control Cables
Inter-module control
Modules are connected as shown in figure 8-3 using connected the other via Parallel
Connector Board with shielded 34-way cables.
These cables are connected between the ‘N’ modules to pass control signals which
govern module synchronization, load sharing, battery charge current sharing (in a
common battery installation), load transfer operation and other general control and
alarm functions. These signals are necessary to ensure correct system operation,
and built-in redundancy allows the system to function if ever one of the ‘N’ cables
becomes disconnected.
Cables entry is as identified in the mechanical drawings in Chapter 2.
UPS Module 1
To Parallel PCB
X3
Parallel
Connect.
Board
X1
X2
UPS Module 2
To Parallel PCB
X3
Parallel
Connect.
Board
X1
X2
UPS Module 3UPS Module 4UPS Module 5UPS Module 6
To Parallel PCB
X3
Parallel
Connect.
Board
X1
X2
To Parallel PCB
X3
Parallel
Connect.
Board
X1
X2
To Parallel PCB
Parallel
Connect.
Board
Fig 8-2: Connection of '1+N' system parallel single bus cables
65
To Parallel PCB
X3
X1
X2
X3
Parallel
Connect.
Board
X1
X2
Page 86
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
8.2.5 Battery Control
The system is designed to operate with separate battery configuration. Installation
procedure is same as for single module.
8.2.6 Emergency Stop
The external emergency stop facility is identical to that described for the single
modules installation – that an individual Emergency Stop button is provided for each
module.
Auxiliary
Terminal
Block
X4
5
6
X4
5
6
EPO Push Button
Auxiliary
Terminal
Block
Module 2
Fig 8-3: Connection of EPO Push Button
Module 1
66
Page 87
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
8.3 Operating Instruction
Starting and stopping the ‘1+N’ system is the same as a single module, however the
module’s response depends on whether it is configured on the menu of the Operator
Control Panel.
8.3.1 System Start-up and shutdown procedures (Separate Batteries)
WARNING
If differential circuit breakers are used on UPS unit inputs, use a
common device only on the system’s bypass mains. At the instant of
electrical connection, the current may not be split instantaneously and
this may cause the residual current circuit-breakers to trip separately.
These operations must be performed one at a time, progressing to the next step only
after having completed the previous step on both UPS modules.
8.3.1.1 System Start-up
This procedure should be followed when tuning on the UPS from a fully powered down
condition – i.e. where the load is not being initially supplied at all. It is assumed that
the installation is complete, the system has been commissioned by authorized
personnel and the external power isolators are closed.
1.Open the UPS door(s) to gain access to the main
power switches.
WARNING
The following action will apply power to the load
equipment, ensure it is safe to do.
2. Close the Bypass power switch Q2
The Module Mimic LED’s will indicate Bypass
supply healthy (1-steady green) and the Load on
bypass (6 – flashing amber).
The display screen will show the following:
EMERSON NETWORK POWER
EMERSON NETWORK POWER
3PH-1PH
3PH-1PH
UPS
UPS
RECTIF. SWITCH OPEN
RECTIF. SWITCH OPEN
BATTERY C.B. OPEN
BATTERY C.B. OPEN
MANUAL BYPASS CLOSED
MANUAL BYPASS CLOSED
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
Initializing Window:
After first connecting power to the UPS and closing
the Q2 isolator, this message will appear on the
LCD screen. It persists for about five seconds
while the control firmware is loaded. It is followed
by a screen showing various messages with the
time and date on the bottom line.
Note: If input power is present but the display remains
blank, then the Micro controller is not working, pleas
contact your dealer for advice.
67
Page 88
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
3. Close the Rectifier input power switch Q1 and
UPS output power switch Q4.
BATTERY C.B. OPEN
BATTERY C.B. OPEN
After approximately 20 seconds the Module Mimic
led’s will change so that the Load on inverter will
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
light (5-steady green) and the Load on bypass (6)
will extinguish. The display window will show:
4. Before closing the battery circuit breaker check
the d.c. bus-bar voltage. From the above window
press the ENTER key. The Main menu will display:
>MEASUREMENT<
>MEASUREMENT<
FUNCTION
FUNCTION
MAINTENANCE
MAINTENANCE
SETUP
SETUP
Select MEASUREMENT and press ENTER key
OUTPUT
OUTPUT
INPUT
INPUT
>BATTERY <
>BATTERY <
TEMPERATURE
TEMPERATURE
Select BATTERY and the d.c. busbar voltage will
be displayed.
BATTERY
BATTERY
VOLTAGE 446 [V]
VOLTAGE 446 [V]
CURRENT 001 [A]
CURRENT 001 [A]
CHARGE 000 [%]
CHARGE 000 [%]
If the voltage indicated is satisfactory (432V d.c. for
380V a.c. system, 446V d.c. for 400V a.c. system,
and 459V d.c. for a 415V a.c. system ) press the
escape key repeatedly until the display returns to
the original window.
5. Manually close the battery circuit breaker.
The Module Mimic inidicator (3) Battery unavailable
should extinguish. Several led’s on the Battery
state of charge bargraph (17) will illuminate
showing battery state of charge.
When the battery circuit breaker has been closed
and the inverter has stabilized the screen will
change to the default window.
Default window:
The message shown below, will be seen on the
NORMAL OPERATION
NORMAL OPERATION
default screen whenever the UPS is operating
normally.
hh.mm.ss dd.mm.yy
hh.mm.ss dd.mm.yy
The top lines display the UPS operational status
and indicates alarm conditions when they occur;
and the bottom line shows the time and day.
The UPS is operating normally with its inverter
supplying the load.
Follow the foregoing procedure for the other UPS.
For a system configured in the “1+N system”, the
‘N’ UPS modules will simultaneously change from
“load on bypass” to “load on inverter” provided that
a sufficient number of modules are running, and
on-line, to satisfy the power load requirements.
68
Page 89
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
8.3.1.2 Switching the system to maintenance bypass from normal operation
WARNING
The internal maintenance bypass must not be used when the UPS
system is comprised of more than two UPS modules in parallel.
Follow the procedure for the single UPS by referring to Chapter 5 – Operating
Instructions: Paragraph 5.4. For a system configured in the “1+N system”, the
changeover from “load on inverter ” to “load on bypass” will occur only when the
operation described in point 3 has been completed on both UPS modules.
8.3.1.3 Switching the system ON from a maintenance power down condition.
Follow the procedure for single UPS, referring to Chapter 5 – Operating Instructions:
Paragraph 5.2 .
8.3.1.4 Switching OFF and isolating one UPS while the other remains in service.
1. In sequence, open the UPS isolators Q4 (output), Q1 (rectifier input), Q2 (bypass
input).
2. Open the circuit-breaker inside the battery cabinet.
To completely isolate the UPS, open the a.c. power supply circuit-breaker (both circuit
breakers if separate supplies are provided for the rectifier and the bypass supply) and
thee output circuit breaker on the power distribution switchboard.
If individual UPS output isolation circuit-breaker (and its auxiliary contacts) are not
installed on the power distribution switchboard, remember that voltage supplied by
the others UPS which remains in service still will be present on the output terminals of
the shutdown UPS.
WARNING
If individual UPS output isolation circuit-breaker are not installed on
the power distribution switchboard, remember that voltage supplied
by the others UPS remains in service will still be present on the output
terminals of the shutdown UPS.
Warning : Wait 5 minutes for the internal d.c. busbar
capacitors to discharge.
69
Page 90
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
8.3.1.5 Switching ON a UPS that was previously switched OFF and isolated from the system.
1. Close the circuit-breakers relative to the shutdown UPS that were previously
opened on the power distribution switchboard.
2. Close the switches Q1 (rectifier input) and Q2 (bypass input) of the UPS.
3. Select the MEASUREMENT function from the display on the main menu, then press
ENTER and select BATTTERY. Press ENTER and check that the voltage level has
reached the rated value (432V or 446 or 459 in accordance with no. of battery blocks).
4. Close the battery circuit-breaker.
5. Close the UPS switch Q4 (output), wait about 20 seconds and check the message
NORMAL OPERATION appearing on the display operator panel.
8.3.1.6 Complete system shutdown
Follow the procedure described in Chapter 5 - Operating Instruction : paragraph 5.6
by working on several UPS modules.
8.3.1.7 Complete system reset
Follow the procedure described in Chapter 5 - Operating Instruction : paragraph 5.7
by working on several UPS modules.
8.4 Display Panel message interpretation in '1+N' System
The alarms are the same as for the single module, as given in the previous paragraph,
with the additional alarms:
CODE DISPLAY ALARM MESSAGE INTERPRETATION
44 INV: PARALLEL ERROR The parallel board has detected a wrong sharing of the load and
has blocked its inverter. Seek qualified assistance.
46 NR: INVERTERS NOT OK. The number of active inverters is below the preset capacity value.
70
Page 91
User Manual
Hipulse -Single Phase ‘1+N’ UPS System130 kVA -110V
Chapter 9
Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
9.1 Conformity and Standard
The UPS has been designed to conform the following standards: IEC, EN
9.2 UPS Environmental
The UPS shall be able to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Environmental Characteristics Units
Rated Power kVA 130
Operating Temperature ºC 0 to 45 ºC
Relative Humidity % = 90% at 31 ºC, Saliferrous, Humid
Altitude of operation m = 1000m above sea level
Storage/ transport temperature ºC -25 to 70 ºC
9.3 UPS Mechanical Characteristics
Mechanical
Characteristics
Height mm 1900
Width mm 1400
Depth mm 925
Ventilation - By internal intake fans
Cable entry - Bottom
Protection IP 41
Units
130 kVA
6 pulse
71
Page 92
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
9.4 UPS Electrical Characteristics
R E C T I F I E R I N P U T M A I N S
I/P Ratings
Rated power kVA 130
Rated Mains
Voltage j
Supply
Input voltage
tolerance k
Frequency
Input
frequency tol.
Rated input
power l
Rated input
current l
Maximum
input power
m
Maximum
input current
m
Duration of
progressive
power walk-in
n
j = 380V or 415V set changing taps on auxiliary supply transformer
k = With mains at –15% and suggested battery elements the UPS maintains the output rated voltage at rated load
but cannot guarantee float charge to battery; the battery does not discharge.
l = EN 50091-3 (1.4.39): UPS, rated load, input rated voltage 400V, no current to battery
m = EN 50091-3 (1.4.40): UPS, rated load or overload, input rated voltage 400V, battery on boost charge with
maximum allowed current.
n = Set with jumper on Rectifier control board.
Units
Vac 380 – 400 – 415 V
Three phase without neutral
% ±10
Hz 50 or 60
% ± 5
kVA 143
A 206.4
kVA 178
A 257
sec
130 kVA
6 pulse
2 to 10
72
Page 93
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
j = Factory set 400V – 380V or 415V voltages with software setting
k = Factory set at 50Hz ; 60Hz with software setting.
l = EN50091-3 (1.4.58) crest factor 3.
m = EN50091-3 (4.3.4).
n = EN50091-3 (4.3.7) also for 0-100% load transient, restore time 20ms to ±1%.
o = Factory set at 0.1Hz/ sec; upto 2 Hz/sec with software setting.
Vac
380 - 400 - 415
Three phase with neutral
50 to 60
KVA
KW 104
% 150% FOR 60 sec
-
Hz
/sec
130
125% for 10 min
110% for 1 hr
100% Pn
± 1.5
± 5
0.1
74
Page 95
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
Delay time to recognize bypass
voltage returned to window
Inverter output voltage window
Frequency lHz 50 or 60
Input frequency tolerance m
Maximum frequency slew rate
Current rating of neutral cable
Protection, bypass line To avoid series fuses, the bypass line should be protected using an
Overload % 150% for 60 sec
Note:
j = Factory set 400V – 380V or 415V set changing taps on auxiliary supply transformer and with software setting
k = Other values 0-15% with software setting.
l = Factory set at 50Hz ; 60Hz with software setting.
m = Other values 1-9% with software setting.
Vac
380 - 400 - 415
A 1182
sec 10
% ± 10
%
Hz
/sec
external device should be sized to discriminate with the load
± 2
0.1
1.5 x In
protection.
125% for 10 min
110% for 1 hr
75
Page 96
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
76
Page 97
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
77
Page 98
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
78
Page 99
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
10.1 Remote Alarm Monitor
The Remote Alarm Monitor (RAM) Board can be used in conjunction with the AS400
Alarms Interface Board to display the UPS alarm and status information at a remote
station to 100 meters from the UPS.
The RAM, which can be mounted either horizontally or vertically contains a mainsdriven power supply for alarm LED annunciation and displays the following warnings:
Panel
Inverter ON
Utility failure
Battery low
Bypass ON
Maintenance
Alarm
Colour
Green
Red
Red
Red
Red
Red
Normal
state
ON
OFF
OFF
OFF
OFF
OFF
Interpretation
Normal operating condition indicating that the load is being supplied by the inverter.
This is not an 'alarm’ indicator.
When lit, it indicates that the input bypass is out of tolerance or missing.
When lit, it indicates that the battery voltage is below minimum or that the battery
circuit breaker is open.
When lit, it indicates that the load is being fed from the bypass supply, possibly due
to a UPS failure.
When lit, it indicates that the UPS has been selected to operate on the maintenance
bypass and load is unprotected.
This is a ‘common alarm’ and is lit when any of the red leds described above are lit
Table A
An audible warning accompanies any of the above alarm conditions. This is, however,
subject to a short time delay when activated in conjunction with the 'Utility Failure' and
'Bypass ON' alarms, to prevent the warning being activated by transient conditions.
Pressing the 'reset' push-button cancels the audible warning but the alarm indications
remain until the conditions is rectified.
10.1.1 RAM Connections
Power Supply
The RAM contains a single-phase 220-240 V AC mains-driven power supply. Power is
applied through a standard three-pin mains connector located in the RAM back panel
(plug provided) -use 3-core 0.5 mm cable (minimum). The supply is rated at
approximately 4 Watts and fused at 1 A.
It is advised that the power supply is taken from the UPS output, otherwise in the
event of a mains failure the RAM may be inoperative.
Alarm connections
A 9 pin D-type connector with solder points is provided with the RAM. This connector
fits into the 9 pin socket on the back of the RAM and should be cabled to the Interface
Board # 10020112003 fitted to the UPS, using 9 core, 0.22 mm. (minimum) shielded
cable as shown. The maximum recommended distance is 100 meters.
Note: Operation of the RAM indicators, is achieved by feeding a voltage across the module Alarm
Board relay contacts. No other connections should be made across the relay contacts used.
79
Page 100
User Manual
RL
–
K1
RL
–
K2
RL
–
K3
RL
–
K4
RL
–
K5
Liebert
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V