Liebert AC Power Medium Exposure Transient Voltage Surge Suppressor, a surge protective
device designed with sine wave tracking to protect electronic equipment and microprocessor-based
systems from transients on distribution panels or any medium exposure locations.
100 kA 160 kA
ORDERING INFORMATION
Building A Model Number:
1: Nominal Voltage Req uirements 2: System Configuration 3: Surge Current Capacity
Nominal Voltage Requirements Model ID System Configuration Model ID
L-N L-L L-G
120........N/A........120 ............................120 Single (2 Wire + Gnd) N or L
120 .......208 .......120 .................... .......120 Split (3 Wire + Gnd) S
120........240........240 .................... .......120 Wye (4 Wire + Gnd) Y
N/A........208........208 .................... .......208 Delta H i-Leg (4 Wire + G nd) H
230........ 400........230.................... .......230 Delta (3 Wire + Gnd) D
N/A........ 240........240.................... .......240
277........480........277 .................... .......277
N/A........400........400 .................... .......400
N/A........480........480 .................... .......480
Surge Current Capacity Model ID Surge Current Capacity Model ID
160 kA/Phase............................................160 100 kA/Phase ..........................100 – 2
(L-N: 80 kA + L-G: 80 kA; N-G: 80 kA) (L-N: 100 kA; N-G: 100 kA)
PANEL I.D. MODEL NUMBER(S)
ame______________________
Model# _________________________
C Power Medium Exposure TVSS Technical Specification
Connection Type................................................Parallel
Operating Voltage Range .................................+/-15%
Fault Current Rating (AIC)................................65 kAIC
Dimensions......................... (160 kA units) ......8”x6”x4”
.............................................. (100 kA units)......6”x4”x3”
Operating Frequency Range............................47 – 63 Hz
Capacity ..............................................................Continuous
50 EMI/RFI Attenuatio n..................................40 dB
Response Time ..................................................<0.5 ns
Operating Humidity ...........................................0% to 95%
Operating Temperature.....................................-40º c to +50ºc
Dry Contact Rating............................................125vac, 8.0A, 1.0pf
Status Indication................................................LEDs, Dry Contacts
Certifications......................................................UL 1449, CUL, ISO 9001
Warranty..............................................................5 Years Parts
120 volt systems................................400 volts all modes
208 and 277 volt systems .................800 volts all modes
480 volt systems................................1,500 volts all modes
UL 1449 (second edition) Classification
LPM 1 2 3