The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in Important Safety Instructions
and 4.4 - Battery Maintenance.
WARNING
!
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT prior to moving battery cabinets (after initial installation).
CONTACTING LIEBERTFOR SUPPORT
To contact Liebert Global Services for information or repair service in the United States, call
1-800-LIEBERT (1-800-543-2378). Liebert Global Services offers a complete range of start-up
services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Global
Services, if available in your area. For areas not covered by Liebert Global Services, the authorized
distributor is responsible for providing qualified, factory-authorized service.
For LGS to assist you promptly, please have the following information available:
Part numbers: _________________________________________________________________
Serial numbers:________________________________________________________________
kVA Rating: ___________________________________________________________________
Date purchased: _______________________________________________________________
Date installed:_________________________________________________________________
Location:______________________________________________________________________
Input voltage/frequency:________________________________________________________
Output voltage/frequency: ______________________________________________________
Battery reserve time:___________________________________________________________
This manual contains important instructions that should be followed during installation and maintenance of your Series 610 UPS and batteries.
WARNING
!
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. Refer to separate installation manual for equipment handling information and
installation procedures.
Follow all battery safety precautions in 4.0 - Maintenance when installing, charging or
servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can
be explosive and sulfuric acid can cause severe burns.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in electrical fire fighting.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages. With
input power off and the battery disconnected, high voltage at filter capacitors and power
circuits should be discharged within 30 seconds. However, if a power circuit failure has
occurred, you should assume that high voltage may still exist after shutdown. Check with a
voltmeter before making contact.
AC voltage will remain on the system bypass, the UPS output terminals and the static bypass
switch, unless associated external circuit breakers are opened.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the UPS system is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the UPS chassis frame by using rubber
mats.
Some components within the cabinets are not connected to chassis ground. Any contact
between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the
test instrument exterior does not make contact either physically or electrically with earth
ground.
1
1.0INTRODUCTION
1.1System Description
The role of the parallel-redundant multi-module UPS system is to supply uninterruptible, clean
power to the critical load. The UPS maintains a full-voltage, low-distortion output, even if the utility
source power sags, becomes distorted or fails.
If there is an outage of the source power, the UPS maintains power to the load until an alternate
source of power is activated or until the original power source is restored. If input AC power is not
restored, the UPS maintains the load (with a storage battery plant) long enough that the critical
equipment can be shut down in an orderly manner or an alternate power source (e.g., Genset) can be
brought on line. The Series 610 UPS module displays the rate of battery discharge and calculates the
amount of battery time remaining based on the actual connected load. The time that the battery will
maintain the load depends on the capacity of the battery backup plant and the size of the load.
The system control logic automatically manages critical bus operation. System logic is resident in digital control logic for precise control and improved reliability.
If the critical load current exceeds the rated load of the Series 610 UPS system, the control logic determines the magnitude of the overload and reacts appropriately. Overloads are usually the result of
inrush current requirements. The UPS system supports loads that are 150% of the rated load for up
to 30 seconds and 125% of the rated load for up to 10 minutes. If the system is operating in the nonredundant mode (e.g., a UPS module is off line), the overload limits are automatically adjusted.
Introduction
Figure 1Multi-Module UPS, 100-500kVA
100-500kVA
If the load surpasses the overload capacity of the UPS, the load is automatically transferred to bypass
without interruption. When the load returns to within the UPS rating, it is either automatically or
manually returned (retransferred) to the UPS. How and when the load is returned to the UPS
depends on several factors: how long the overload lasted, how many overload conditions occurred
before transfer, whether there is an imminent failure of any part of the UPS, etc. Refer to 3.5 - Auto-matic Operations.
2
Introduction
In the unlikely event of a fault within the UPS, the SCC control logic, which continuously monitors all
critical circuits within the UPS system, transfers the load to bypass without interruption and simultaneously activates local and remote alarms. If a fault is detected in an individual UPS module, that
module is automatically disconnected from the critical bus and shut down. A Module Off Line status
message will appear at the SCC display. The module can be manually returned to service when the
fault has been corrected.
If the multi-module UPS system is operating in the redundant mode (at least one extra module is
available for the connected critical load), the load will remain on the UPS system if one individual
module is disconnected from the critical bus (off line). If the UPS system is operating in the nonredundant mode, the load will be automatically transferred to bypass if a module goes off line.
The Series 610 UPS display system provides precise monitoring of the UPS, fast alarm response and
quick troubleshooting. For easy manual operations, menu-driven software provides access to several
step-by-step help screens. All operator functions are performed using menu-prompted displays and a
minimum number of operator controls. The System Control Cabinet includes external communication
capability with both automatic transmit and receive features for early warning and diagnosis of
abnormal conditions.
System software allows the operator or Liebert Global Services to enter application specific information. Overload, overvoltage, battery discharge and shutdown limits can be set by the operator. In
effect, UPS operations are tailored for each site.
The UPS system protects critical equipment from source power disturbances and outages, load faults
and UPS malfunctions. This triple protection virtually eliminates computer and computing equipment downtime as a result of utility source power problems.
Figure 2Multi-Module UPS, 500-750kVA
3
Figure 3System Control Cabinets
Introduction
Types of System Control Cabinets (SCCs)
• SCCT—A stand-alone cabinet containing system control logic for up to six UPS modules, a static
bypass switch, manually operated disconnects for the static bypass switch and two motor-operated system circuit breakers.
• SCCI—System control logic and static bypass switch are integrated into a switchboard cabinet
manufactured by others, which also includes the system circuit breakers.
• SCCC—An integrated configuration like the SCCI, but with a static switch rated for continuous
duty.
1.2Reliability
Reliability is the most important design goal for Uninterruptible Power Systems. Liebert Series 610
UPS systems have demonstrated reliability by achieving a field-proven critical bus MTBF in excess of
2 million hours. In addition, our Quality Assurance program is certified to the requirements of
ISO 9001 standards.
Liebert Large UPS systems are ETL listed to the requirements of UL 1778. All equipment and components are manufactured to applicable UL, NEC, NEMA, ANSI, IEEE and CSA standards and guidelines.
Designed for Success
The keys to reliability in the design of the UPS system are using conservatively rated components,
minimizing transfers to bypass, making operator controls understandable and providing easy access
for maintenance and repair. Liebert UPS systems lead the industry in all these areas.
For example, the Series 610 can handle substantial overloads through the solid state static bypass
switch without transferring to the bypass source. By minimizing transfers to bypass, the Series 610
minimizes operation of motor-operated circuit breakers and enhances system reliability.
As another example, the system control logic has been packaged into digital control logic to eliminate
the failure-prone discrete logic boards used in other brands of UPS products. Furthermore, the logic is
isolated from heat-generating components to ensure optimal operating temperatures.
4
Other Factors to Consider
Reliability depends on more than just UPS module design. Improper installation can cause any system to fail. To prevent this, customer engineers from Liebert Global Services thoroughly inspect the
installation of all our systems to ensure they are installed properly and operating within performance
specifications.
Once a UPS is properly installed, you—the on-site equipment operator—are the most important factor in preventing critical bus failures or unplanned transfers to bypass. To make your task easier, the
Series 610 UPS provides easy-to-follow, prompted instructions on the industry’s largest operator display screen.
If you ever need help, call Liebert Global Services (24 hours a day at 1-800-LIEBERT). Your attention
to proper installation, operation and periodic maintenance will ensure that your mission-critical operations receive the best possible protection from electrical disturbances and outages.
1.3Safety Precautions
Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the UPS. Also refer to the battery manufacturer’s manual, available on the manufacturer’s
Web site, before working on or near the battery.
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary.
The area around the UPS system and battery should be kept free from puddles of water, excess moisture or debris.
Introduction
Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system or the battery. Observe precautions in the separate Installation Manual
before handling or installing the UPS system. Observe precautions in 4.0 - Maintenance before as
well as during performance of all maintenance procedures on the UPS system or battery. Observe all
battery safety precautions in 4.0 - Maintenance before working on or near the battery.
This equipment contains circuitry that is energized with high voltage. Only test equipment
designated for troubleshooting should be used. This is particularly true for oscilloscopes. Always
check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when
the power is turned Off, dangerously high voltage may exist at the capacitor banks. Observe all battery precautions when near the battery for any reason.
ONLY qualified service personnel should perform maintenance on the UPS system. When
performing maintenance with any part of the equipment under power, service personnel and test
equipment should be standing on rubber mats. The service personnel should wear insulating shoes for
isolation from direct contact with the floor (earth ground).
Unless all power is removed from the equipment, one person should never work alone. A second person should be standing by to assist and summon help in case an accident should occur. This is particularly true when work is performed on the battery.
1.4Modes of Operation
Refer to 2.0 - Theory of Operation and 3.0 - Operation for more details.
1.4.1Normal—Load on UPS
The utility AC source provides power to the rectifier/charger in each UPS module. Each rectifier/
charger converts the utility AC power to DC and supplies DC power to the UPS module inverter while
simultaneously float charging the battery plant. Each UPS module inverter converts DC to AC and
furnishes AC power to the critical bus. The System Control Cabinet (SCC) is the tie point for the paralleled modules and monitors and controls the critical bus performance.
1.4.2Input Power Failure
If the utility source power fails or is outside the acceptable range, the battery plant becomes the primary supplier of DC power to the inverter.
5
1.4.3Recharge
After the utility source power is restored or an alternate power source becomes available, each rectifier/charger slowly walks-in to once again power the inverters and recharge the battery plant.
1.4.4Overload
Overloads in critical systems may be caused by inrush currents during connected equipment start-up
or by faults in the critical load or distribution network. The Liebert Series 610 UPS system can maintain full output voltage regulation while sustaining the following overloads:
• Up to 150% for 30 seconds
• Up to 125% for 10 minutes
• Up to 104% for an indefinite period of time
For momentary faults above 155% of rated SCC current, the static switch turns on for 40 milliseconds
to supply power from the bypass source. Up to 1000% of the rated current can be supplied for less
than one cycle, while up to 500% of rated load can be sustained for the full 40 milliseconds of pulsedparallel operation.
The critical load remains on the UPS modules for the above conditions. If the UPS system overload
capacity is exceeded, an automatic transfer to bypass is initiated, which closes the system bypass circuit breaker (SBB) and opens the UPS output circuit breaker.
CAUTION
!
Whenever an overload occurs, it is imperative to determine the cause of the overload.
1.4.5Redundant
If the multi-module UPS system includes one more module than the number required to supply the
critical load, the UPS system can operate in the redundant mode. This means that the load will
remain on the UPS system if one of the modules is disconnected because of an overload, an internal
fault or for maintenance. If the additional module is not included in the system design or if the additional module is disconnected from the critical bus, the UPS system operates in the non-redundant
mode.
1.4.6Bypass—Internal
The SCC control logic initiates an automatic transfer to the bypass source if the overload-current-versus-time curve is exceeded or if specified UPS system faults occur. You can also manually transfer the
load to the bypass (without interruption) if you must take the UPS module out of service for maintenance.
The SCC internal bypass will allow most key components and operating modes to be checked without
disturbing the critical bus. However, certain key power-carrying components, such as the output and
bypass circuit breakers, will require isolation through an external maintenance bypass cabinet or
complete system shutdown to maintain 100% critical load operation.
1.4.7Maintenance Bypass
The installation of a Maintenance Bypass Cabinet, Panelboard or Switchboard is recommended to
allow you to totally isolate the UPS from all power sources. Use of the Maintenance Bypass is
described in 3.0 - Operation.
1.4.8Off-Battery
The battery plant can be disconnected from the rectifier/charger by using an external Module Battery
Disconnect (MBD) circuit breaker. The UPS module continues to function normally, though it does
not have power outage back-up capability until the battery plant is reconnected.
Introduction
1.5Operator Controls
The Liebert Series 610 UPS System Control Cabinet (SCC) and each individual module are equipped
with a microprocessor-based Operator Display Screen and Control Panel designed for convenient and
reliable operation.
The front panel location of the monitoring and control system enables the user to quickly identify the
current status of the UPS and to perform most of the manual operations. The operator display screen
(a backlit liquid crystal display or LCD) is driven by an easy-to-follow menu-prompted software program that controls and monitors the UPS system.
6
Figure 4SCC controls and display screen with example of the Monitor/Mimic screen
The operator controls and Monitor/Mimic screen for the System Control Cabinet (SCC) are shown in
Figure 4. The controls and display screen for each UPS module are shown in Figure 5. Each cabinet
(SCC or module) has the displays and controls required to monitor and perform its functions.
Figure 4 shows a three-module system designed for redundant operation. A multi-module UPS system may include up to six (6) modules for each SCC.
Detailed instructions on how to interpret the displays and use the controls are in 3.0 - Operation.
Figure 5Module controls and display screen with example of the Monitor/Mimic screen
A number of options are available from Liebert for your UPS system. (Some options are not available
for all ratings.) Described below are the most frequently provided options. Note that the battery items
( 1- 3) are required to complete the UPS system. The remaining options provide improved system performance or convenience. Other options are available. Contact your Liebert sales representative for
more information.
1. Battery
The batteries provide power in the event of a power outage. The Liebert UPS can use a variety of
battery types, provided the battery plant is designed for the UPS DC voltage range and the load
requirements of your application.
8
Introduction
2. Battery Racks or Cabinets
The battery racks are specifically designed for stationary service batteries. They are painted with
electrolyte-resistant paint for corrosion resistance. Battery cabinets are available for 150 through
600kVA modules.
3. Module Battery Disconnect
The UPS system utilizes a separate Module Battery Disconnect for remotely located batteries. A
sensing circuit in the UPS module, set at the battery low voltage limit, trips the Module Battery
Disconnect to safeguard the battery from excessive discharge. The Module Battery Disconnect has
an undervoltage release mechanism designed to ensure that during any shutdown or failure mode
all battery potential is removed from the UPS system.
4. Input Current Distortion Filter
This filter reduces rectifier input current reflected harmonic distortion to less than 7% reflected
THD and less than 4% reflected THD for modules with the optional 12-pulse rectifier. The filter is
factory installed within the UPS. This filter also improves the input power factor to better than
0.92 lagging.
5. 12-Pulse Rectifier
All 500-750kVA models may be ordered with the optional 12-pulse rectifier section; this feature is
standard in 1000kVA models. This provides input isolation and reduces input current reflected
THD to less than 9% or less than 4% with optional input filter.
6. Isolation Transformers
An optional rectifier input isolation transformer is available in a matching transformer cabinet;
this feature is standard in 1000kVA models. A bypass isolation transformer is also available.
7. Three Breaker Maintenance Bypass
This switchboard provides make-before-break maintenance bypass. It includes: UPS Bypass
8. Two Breaker Maintenance Bypass
This switchboard provides make-before-break maintenance bypass. It includes: Maintenance
Bypass Breaker (MBB) and Maintenance Isolation Breaker (MIB).
9. Load Bus Synchronization (LBS)
The Load Bus Sync (LBS) option keeps two independent UPS systems (and therefore their critical
load buses) in sync, even when the modules are operating on batteries or asynchronous AC
sources. This means that critical loads connected to both load buses through a Static Bus Transfer
Switch can be switched seamlessly between the two.
10. SiteScan Central Monitoring System
Liebert manufactures a central monitoring system that automatically displays key UPS measure-
ments and alarms, as well as data from a variety of sensors. This monitoring system activates
alarms so corrective action can be taken. Events and data can be printed in hard copy. Data can
be logged for analysis.
11. Remote Monitor Panel
The UPS system may also be provided with an optional Remote Monitor Panel. This Panel pro-
vides eight LED indicators and may be placed at a convenient location near the critical load. A
functional description of the Remote Monitor Panel is provided in 3.0 - Operation of this manual.
12. Customer Alarm Interface
This optional interface board allows the input and display of 8 alarms from customer-supplied
contacts, each with a customer-selected name of up to 16 characters. The following attributes can
be user programmed for each alarm: latching, summary, freeze history, sound horn, auto-dial and
time delay (0 to 999.9 seconds).
13. Temperature-Compensated Charging
When battery temperature climbs above a preset limit (typically 77 degrees F), this optional cir-
cuit proportionally reduces float charging voltage to prevent overcharging the battery.
14. Battery Load Testing
When activated, this option forces the battery string to assume the load for a short period of time.
The UPS then compares the test results to data collected during the UPS commissioning to see if
the battery system appears to meet specifications.
9
2.0THEORYOF OPERATION
2.1General Component Descriptions
The UPS system includes all of the equipment necessary to continuously provide computer-grade AC
power to a critical load, even when there is an interruption of the utility power. It consists of a System
Control Cabinet (SCC), UPS modules and a back-up battery plant. Refer to Figure 6 and Figure 7.
Except where otherwise noted, the configuration is presumed to be parallel-redundant (with at least
one more UPS module than required to support the rated load).
2.1.1System Control Cabinet
The System Control Cabinet (SCC) includes system controls, static bypass switch, load transfer control, protective devices and other accessories. The system controls simultaneously monitor two or
more parallel UPS modules sharing a critical load for increased capacity and/or redundancy. The two
(2) motor-operated system circuit breakers (system bypass breaker—SBB and UPS output breaker)
may be contained within the SCC, depending on the configuration designed for your installation.
System Controls: The system control logic automatically manages critical bus operation and monitors performance of the UPS modules. Microprocessor technology and dedicated firmware provide
advanced logic control and a comprehensive display of information. The system control logic synchronizes the output of the UPS system to the bypass source. The SCC includes ports for communicating
with external devices. Liebert Multi-Module Units do not require an SCC for load sharing. Automatic,
parallel module load sharing is a function built into the modules themselves; however interconnection
through the SCC enables the modules to share data for more precise control. Modules do not require
master clocks or controls in order to load share or free-run at 60.0 Hz.
Theory of Operation
Static Bypass Switch: The static (solid-state) bypass switch immediately transfers the load from
the inverter to the bypass AC power source in the event of a severe overload on the system or a failure
within the UPS. This transfer takes place without any interruption of the power supplied to the load.
In all SCCT control cabinets 1600A or larger and in all SCCI and SCCC control cabinets, the system
includes redundant circuits to detect and isolate shorted SCRs in the static switch.
Fuses are installed in series with the static bypass circuit (with the exception of the continuous duty
static switch installed in the SCCC control cabinet) to ensure reliable overload protection in the
unlikely event of a catastrophic output condition (e.g., a dropped wrench) electrically close to the output of your UPS system. The static switch SCRs themselves are rated to easily handle the fuse-blowing current.
Bypass Circuit: The bypass circuit consists of electrically operated circuit breakers and associated
synchronizing and control circuitry to transfer the load to/from the bypass source.
10
Figure 6UPS module block diagram
MULTI-MODULE UPS SYSTEM
CONTROL POWER
Theory of Operation
Control
Wiring
To SCC
Controls
Utility
Input
Power
2.1.2UPS Module
The UPS module consists of module controls, a rectifier/charger, an inverter, protective devices and
other accessories.
Module Controls: The module control logic monitors performance of the UPS module. The UPS
module status is displayed locally and is also sent to the System Control Cabinet.
Rectifier/Charger: The rectifier/charger converts utility power from AC to DC to charge the battery
and provide the DC input to the inverter. Its design limits reflected harmonic current distortion to
source power and provides low-ripple DC power for charging batteries. Multiple rectifier/chargers can
share a common battery plant, if that configuration is preferred for your application.
Inverter: The inverter converts DC power into the precise AC power required to supply a sensitive
critical load. The inverter converts DC power into a pulse-width-modulated (PWM)/six-step waveform
that is easily filtered into a clean sine wave output. The PWM/stepwave also minimizes the harmonic
voltage distortion caused by typical switching power supplies and other non-linear load components
used in computers and related electronics.
Input
CB
Rectifier/
Charger
Inverter
MBD
Output
Output
CB
Battery
CB - Circuit Breaker
MBD - Module Battery Disconnect
SCC - System Control Cabinet
Power
To SCC
2.1.3Battery Plant
The battery is used as the alternate source of power to supply DC power to the inverter if the AC supply voltage is outside the acceptable range. The battery supplies power to the inverter until the utility
power is restored or until an alternate power source is available. If AC source power is not restored or
an alternate power source is not available, the battery can be sized to provide power long enough for
an orderly shutdown of the load.
11
2.2Detailed Component Descriptions
2.2.1Controls
Hardware
The Series 610 UPS Operator Interface Display System is designed to provide all of the information
that is required for the operation of each UPS cabinet (the System Control Cabinet and each module).
The following is a list of the hardware features:
1. The control logic performs automatic operations with minimal operator interface. The limited
number of manual controls are easy-to-use.
2. Each Series 610 UPS cabinet is equipped with an easy-to-read 640 x 200 pixel backlit liquid
crystal display (LCD) screen. It presents information in a way that is easy to understand at an
eye-level front panel location.
3. The display is controlled by a dedicated microprocessor with a flash-updatable program, nonvolatile static RAM and a battery-backed system clock.
4. The Series 610 System Control Cabinet (SCC) has communication ports (terminal board
connections) for:
a. Transmission of present status information to remote terminals via a resident auto-dial
communications program and an optional internal or external modem. This port also
responds to inquiries of the UPS system status and history from the remote terminal.
b. Reporting UPS system status and history information in response to inquiries from a local
terminal (no modem required).
c.Reporting to a local monitor the information requested from the local terminal.
d. Reporting information to a Liebert SiteScan central monitoring system.
e.Relaying selected alarm messages to a Liebert Remote Monitor Panel and to a separate
terminal board for customer use.
f.Relaying performance and status information to your network monitoring system via SNMP
interface (optional).
Theory of Operation
Software
The operator interface display system software enables the operator to monitor the UPS system status, to control the power flow through the UPS, to monitor all of the meter readings, to execute the
start-up, shutdown and load transfer procedures, to access the event history files and to make adjustments to the programmable parameters. The following is a list of the software features:
1. The menu-driven software prompts the operator for input.
2. Step-by-step instructions assist the operator during the start-up, shutdown and load transfer
procedures. This helps to eliminate operator errors.
3. Graphics-based mimic diagrams illustrate circuit breaker status and the power flow through the
UPS system.
4. The Present Status screen reports information about the system’s present status. The History
Status screen chronicles the events leading up to and immediately after a fault. The Event
History screen lists all of the alarm messages that have been logged over a period of time.
5. The Battery Cycle Monitor records information on up to 132 battery discharge events.
Information includes date, time, length of discharge, highest current demand, lowest battery
voltage and cumulative battery amp hours discharged.
Refer to 3.0 - Operation for a description of the controls and indicators located on the Operator Control Panel.
12
2.2.2Rectifier/Charger
The UPS module rectifier/charger consists of an input circuit breaker, AC current limiting circuit,
battery equalize charge circuit, DC filter, battery charge current limiting circuit and bridge rectifiers.
Optional items are an isolation transformer and a 12-pulse rectifier (these are standard on 1000kVA
units).
Operation
The rectifier/charger converts the AC input power to DC power. This conversion is accomplished by
3-phase bridge rectifiers using SCRs. All phases are individually fused. Input current reflected THD is
less than 7% at full load with optional input filter or 30% without. For modules 500kVA and larger, the
optional 12-pulse rectifier reduces reflected THD to less than 4% with optional filter or 9% without.
The filtered output of the rectifier/charger provides regulated DC power to drive the inverter and
charge the battery.
Input Circuit Breaker
The input circuit breaker (CB1) is sized to allow enough current to recharge the battery and supply a
full rated load at the same time. The circuit breaker contains a thermal magnetic trip mechanism and
an undervoltage release that interrupts power, preventing damage to the system, if there is an internal AC overcurrent condition or a short circuit. The circuit breaker also opens during certain alarmed
faults. This circuit breaker must be closed manually.
Isolation Transformer
The optional input isolation transformer—standard with 1000kVA models and with the 12-pulse rectifier option—has a dry type core and copper windings with Class H insulation. The transformer on
modules with standard 6-pulse rectifier has wye primary and delta secondary windings. For models
with the optional 12-pulse rectifier, the transformer has a delta primary, with delta and wye secondary windings. The isolation transformer provides the initial step of critical bus isolation. This reduces
the AC shock hazard at the battery and at other DC components and prevents a DC fault from disrupting upstream AC circuitry.
The transformer has a nominal tap and one tap 6% below the rated nominal input voltage (normally
used for 460 VAC input).
Theory of Operation
Input Current Limit
AC input current-sensing transformers (CTs) are used to measure current levels. Control circuitry
connected to the CTs restricts the AC current to less than 125% of the full input current rating by
reducing the battery charging voltage. This current limit is adjustable from 100 to 125% and is factory-set at 115%.
An optional second level of input current limit is initiated by an external contact closure (field supplied for use with back-up generator) and is adjustable from 85 to 100% (factory-set at 100%). This
second level of input current limit may be used to set the maximum amount of input current permitted under all operating conditions of connected load and battery recharge.
During a start-up procedure, the current slowly ramps up (walks-in) from 20% of the rated input current to 100% over 15 to 20 seconds. The maximum rate of change of the AC input current is 15% per
second. The input current walk-in reduces the start-up surge effects on all other equipment connected
to the same source and prolongs the service life of internal components.
Input Current Inrush
The maximum sub-cycle of inrush current due to the optional input isolation transformer is typically
less than five times the rated input current for the first 1/2 cycle with the optional input filter. Without this transformer, inrush current is typically less than three times nominal.
Input Power Factor
The rated input power factor is not less than 0.85 lagging at the nominal input voltage and the full
rated UPS load. The optional input filter will improve the power factor to better than 0.92 lagging at
full load. Refer to your submittal package or installation drawings in the installation manual for your
specific model.
13
2.2.3Battery Charging Circuit
The UPS module charging circuit is capable of recharging the battery plant to 95% of full capacity
within 10 times the discharge time. Recharging the last 5% takes longer because of characteristics
inherent in the battery. DC ripple voltage is limited to less than 0.5% RMS to preserve battery life
during long-term float charging while the UPS system is operating on utility source power.
Multiple UPS module rectifier/chargers can share a common battery plant, if that configuration is
preferred for your application.
Operation After Discharge
When commercial power is interrupted, the battery continues to supply DC power to the inverter
without interruption to the critical load. If the AC source power is restored before the battery has
fully discharged, the rectifier automatically restarts and resumes carrying the inverter and battery
recharge load requirements.
Operation After End-of-Discharge
The battery time screen displayed on the control panel enables you to estimate when battery shutdown will occur. If the battery plant discharges to the shutdown point during an outage, the UPS
automatically disconnects the load, the AC input and the battery. After AC input power is restored,
the rectifier can be manually restarted by the user.
Battery Disconnect
The external module battery disconnect (MBD) circuit breaker is used to isolate the UPS module from
the battery during maintenance and to automatically disconnect the battery from the inverter at the
end of battery discharge. The MBD circuit breaker can be opened or tripped automatically, from the
control panel or manually. It must be closed manually.
Theory of Operation
Battery Charge Current Limiting
The battery recharge current, after a battery discharge, is limited to between 1 and 25% (adjustable)
of the full load discharge current. An additional (optional) charge-limiting circuit can be activated by
external dry contact closure (field supplied) for use when operating on a back-up generator. These two
levels of control regulate the amount of current that flows from the power source to the battery while
the battery is recharging.
The battery charge current limit is factory-set at 10% for normal operation and at 1% for alternate
power source recharge operation.
Battery Equalize Charge Circuit
The battery equalize charge feature can be manually initiated or it can be programmed to operate
automatically. Either can be selected from the battery equalize screen displayed on the control panel.
The battery equalizing charge circuit increases the rectifier/charger output voltage to charge the battery any time there is a power outage of 30 seconds or longer. The equalizing voltage is slightly higher
than the float voltage. Equalize charging is primarily used in flooded battery systems to boost individual cells that are at a low state of charge, per the battery manufacturer's specification and recommendations.
NOTE
Do not use equalize charging with valve-regulated lead-acid batteries.
Consult the battery manufacturer’s manual, available on the manufacturer’s Web site, for
specific information about equalize charging.
14
2.2.4Inverter
The inverter is a solid state device that converts the DC output of the rectifier/charger or the battery
to AC power.
Operation
The inverter converts DC power—from either the battery or the rectifier/charger—into three pulsewidth-modulated/six-step waveforms. These waveforms are filtered into low-distortion sine wave
power. The inverter is controlled by digitally controlled logic. This logic controls the precise synchronization, amplitude and frequency of the output voltage.
In addition to the inverter efficiently supplying a regulated AC output from a DC source, the output
isolation transformer acts as a second stage of isolation between the critical load bus and the commercial source power. The inverter is configured to handle most critical load inrush surges. It maintains
output voltage Total Harmonic Distortion (THD) within specifications even when handling non-linear
computer loads. Refer to Non-Linear Load Characteristics.
Output Regulation and Overload Performance
The inverter is capable of sustaining full output voltage (±2% of the nominal voltage) for up to 150%
overload at the output for as long as 30 seconds without reducing the output voltage. It can also handle at least 125% of the rated current for up to 10 minutes and 104% of the rated current continuously. The System Control Cabinet (SCC) will transfer the critical load to the bypass source if the
overload exceeds the system capacity or the capacity of the modules on-line. The multi-module overload capacity (in terms of percent of rated full load current of modules on-line) is 140% for 20 seconds,
108% for 10 minutes and 104% continuously.
Theory of Operation
Note that in normal operation the SCC will transfer the load to bypass before a UPS module exceeds
its overload capacity. If an individual module overload condition is sustained (beyond inverter capacity) the UPS module is automatically taken off-line (disconnected from the critical bus) and is shut
down. If the UPS system is operating in the redundant mode, the load may remain on the UPS system. Refer to 3.5 - Automatic Operations.
Non-Linear Load Characteristics
Computers and computer equipment with switching power supplies generate non-linear currents rich
in fifth and seventh harmonics.
The inverter pulse-width-modulated/six-step waveform, coupled with the output filter, provides a natural path for reducing the fifth and seventh harmonic currents produced by the load. The inverter/filter limits the output voltage THD to less than 5% with up to 100% typical electronic data processing
(EDP) loads. EDP equipment characteristically includes both non-linear and linear load components.
Unbalanced Load Characteristics
Unbalanced loads are actively regulated. The phase-to-phase voltage balance is maintained to within
2%, even with a 50% load imbalance.
The three-phase, root mean square (RMS—approximately 70% of the peak) average voltage is also
regulated through a separate control circuit (phase-to-phase sensing).
15
2.2.5Static Bypass
A static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7. The
static bypass consists of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase and
solid-state switching devices working in conjunction with the motor-operated System Bypass Breaker
(SBB). An automatic transfer control circuit senses the status of the operator controls, UPS logic signals and alarm messages and critical bus operating conditions. If the UPS modules can no longer supply the critical load, the static bypass switch (in conjunction with the SBB and UPS Output Breaker)
automatically transfers the critical load to the bypass source without interruption.
Figure 7System Control Cabinet block diagram
Bypass Line
Gate
Driver
Static
Bypass
Switch
Static Switch
Disconnects
Static Bypass Breaker
Theory of Operation
Sync &
Transfer
UPS
System
Modules
Control
Power
Supply
System
Monitor
Alarms
Voltage
Adjust
Transfer
Control
UPS Output
To Critical
Load
Fuse Protection
The static bypass switch path uses two back-to-back SCRs per phase. Each phase is individually protected by a fuse sized to clear only in the event of a catastrophic fault (with the exception of the continuous duty static switch used in the SCCC control cabinet). This is a more reliable method than
depending on external protection devices. The fuses are in the circuit to protect the critical bus distribution equipment against catastrophic faults. The static switch SCRs are oversized to easily handle
any current surges that may blow the fuses.
Shorted SCR Monitoring
In all SCCI and SCCC control cabinets, and all SCCT control cabinets 1600A and larger, the static
bypass system has redundant shorted SCR sensing circuits and disconnects. This will prevent UPS
output power backfeed to the distribution system even if two component failures exist simultaneously. If a shorted SCR is detected, the static bypass switch is isolated and annunciated at the SCC
control panel, and the critical load remains on UPS output power.
In all SCCT control cabinets smaller than 1600A, the static bypass system is equipped with redundant disconnect circuits that prevent backfeed of lethal voltage to a de-energized bypass input in the
event of a shorted static switch SCR. If the bypass input power is interrupted, the static switch disconnect devices will open, preventing backfeed of inverter voltage to the bypass input terminals.
16
Theory of Operation
Static Switch Isolation
The motor-operated system bypass circuit breaker (SBB), wired in parallel with the static switch,
automatically closes in approximately 200 milliseconds after the load is transferred to the bypass
power source, removing the static switch from the power flow.
Also, if required for maintenance, the static switch can be isolated from the bypass line by opening (to
the OFF position) the Static Switch Disconnects. For maintenance, this should only be done with the
UPS system critical load on bypass power.
Pulsed Parallel Operation
When an overload condition such as magnetic inrush current or a branch load circuit fault exceeds the
overload capacity of the connected modules, the static bypass switch pulses on for 40 milliseconds.
This allows up to 1000% of the rated full load current from the bypass line to clear the overload without closing the bypass circuit breaker. The bypass source is briefly in parallel with the UPS system,
permitting the bypass source to carry the initial overload current. If the overload clears before 40 milliseconds, a load transfer to bypass is not made. If the overload condition continues, the automatic
transfer is made (maintaining the load voltage within the specified limits).
This pulsed static switch operation reduces nuisance operation of motor-operated circuit breakers for
such short-term conditions and serves, under some circumstances, as a backup in the event that an
external bypass feeder breaker trips open during this pulse-paralleling period.
Load Transfers
Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in
a make-before-break sequence. This is accomplished through the overlapping operation of the UPS
output and the system bypass power switching devices.
Manual load transfers and retransfers are initiated by the operator from the System Control Cabinet
(SCC).
In a manual operation or an automatic retransfer, the two motorized circuit breakers—UPS output
and system bypass—are both closed simultaneously for a short period of time (overlap).
Automatic transfers are initiated by the SCC system control logic when an overload is beyond the
specified capabilities of the UPS system or when a fault occurs within a non-redundant UPS module.
An automatic retransfer is initiated if this function is enabled and if system conditions for a retransfer are present.
In an automatic transfer, the circuit breakers do not overlap, but, during the short time gap, bypass
power is supplied to the critical load through the solid state static switch. In an SCCC control cabinet
with a continuous duty static switch, if for some reason the Static Bypass Breaker (SBB) fails to close,
the static switch will carry the load continuously.
17
Theory of Operation
Transfer and Retransfer Conditions
1. Automatic Transfers to Bypass
Critical bus conditions that will initiate an automatic transfer of the critical load from the UPS
system to the bypass source are:
a. System Overload: overcurrent condition in excess of the overload rating of the System Control
Cabinet (SCC).
b. Output Overload: overcurrent condition in excess of the current-versus-time overload capacity
of UPS modules ON LINE.
c.Overvoltage/Undervoltage (OV/UV): critical bus voltage is outside the allowable tolerance.
d. Non-redundant UPS Module Inoperative: an essential UPS module is taken OFF LINE for
one of the reasons below.
1. Battery discharged to the shutdown voltage.
2. Inverter overload capacity exceeded.
3. Inverter or rectifier fault condition (power, logic or overtemperature) present or
imminent.
4. Failure of UPS module logic or logic power.
e.SCC Logic:
1. Emergency Module Off (EMO) circuit activated.
2. Failure of UPS system logic or logic power.
2. Manual Transfers
Manual transfers may be initiated at any time provided no transfer inhibition conditions are
present.
3. Transfer Inhibited
A manual transfer to the bypass source will be inhibited if any of the following conditions exist:
a. UPS system to bypass voltage difference (∆V) exceeds a predetermined percentage (normally
5%).
b. Static switch disconnects open.
c.OK to Transfer signal from the control logic is not present.
NOTE
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass
is initiated. If the Static Switch Unable alarm message is present for any reason (including a
±20° phase lock synchronization error), the automatic transfer will be interrupted for
40-120 milliseconds. Because of the reliability of the UPS components, an interrupted load
transfer is a very unlikely occurrence.
4. Automatic Retransfers to UPS
Critical bus conditions that must be present to initiate an automatic retransfer (Auto-Rexfer) of
the critical load from the bypass source to the UPS system are:
a. The number of Auto-Rexfer Attempts selected must be greater than zero (0). If zero (0) is
selected, no automatic retransfer will occur.
b. Critical load was initially transferred to the bypass source due to a system overload only.
c.Overload has since dropped below 100% of the rated SCC current.
d. Enough UPS modules are ON LINE to supply the critical load.
e.OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes
of the overload transfer. (A manually initiated retransfer from bypass is required for
overloads lasting 5 minutes or more.)
f.Cyclic-type system overloads, which occur up to five (select range is 0 to 5) times in
60 minutes, are automatically returned to the UPS system for each event including the Nth
overload. A manually initiated retransfer from bypass is required for the N+1 overload.
5. Manual Retransfers
Manual retransfers may be initiated at any time provided no retransfer inhibition conditions are
present.
18
6. Retransfer Inhibited
A retransfer from the bypass source to the UPS system shall be inhibited if any of the following
conditions exist:
a. Manual (and Automatic) Retransfer Inhibitions:
1. UPS system-to-bypass voltage difference (∆V) exceeds a predetermined percentage
(normally 5%).
2. System circuit breaker (UPS output or SBB) is inoperative.
3. OK to Transfer signal from the control logic is not present.
4. Not enough UPS modules are ON LINE to supply the connected critical load.
b. Automatic Retransfer Inhibitions (in addition to those above):
1. The load transfer to bypass was not caused by a system overload.
2. Excessive cyclical overloads within a one-hour period.
3. Retransfer conditions are not satisfied within 5 minutes of the initial transfer.
2.2.6Redundant Mode
The typical multi-module UPS system is configured with a back-up (redundant) UPS module, connected in parallel to share the critical load with the other module(s). This parallel redundant system
includes one more module than is required to supply the full critical load.
A parallel redundant system will always be in the Redundant Mode if all modules are ON LINE. In
addition, if the critical load is reduced so that not all ON LINE modules are required, the UPS system
can also operate in the Redundant Mode with one or more modules OFF LINE. The critical load will
remain on the UPS system—even if one or more of the modules is taken OFF LINE for maintenance
or because of an internal fault—as long as the remaining ON LINE modules can carry the full connected system load.
Theory of Operation
The system control logic monitors the connected critical load and the number of UPS modules ON
LINE. If the UPS system is operating in the Redundant Mode, the REDUNDANT status message will
be displayed at the System Control Cabinet (SCC). If the UPS system is operating in the Non-Redundant Mode (redundant module is OFF LINE or was not included in the system configuration), the
NON-REDUNDANT status message is displayed at the SCC. In the Non-Redundant Mode, the critical load will be transferred to bypass if any UPS module goes OFF LINE and the remaining ON LINE
module(s) cannot carry the connected load without being overloaded.
The system control logic, located in the SCC, automatically adjusts the allowable overload limits
based on the connected load and the number of modules ON LINE.
19
3.0OPERATION
3.1Display Screen and Operator Controls
Each Liebert Series 610 UPS cabinet is equipped with a microprocessor-based Operator Control Panel
and Display Screen and System Control Panel designed for convenient and reliable operation. The
System Control Cabinet (SCC) performs different functions than the UPS modules. Each cabinet has
the controls and displays required to operate and monitor its functions. The locations of operator controls are shown in Figure 8 through Figure 11.
The front location of the control panel enables the user to quickly identify the current status of the
UPS system and to perform most of the manual operations. The operator display screen is driven by
an easy-to-follow menu-prompted software program.
Features
The Series 610 interface display system enables the operator to easily perform the following:
• Obtain a quick indication of operational status:
• Is the critical bus OK?
• Is the UPS system OK?
• Which UPS modules are available?
• Is the battery available?
• Is the bypass line available?
• Monitor the power flow through the UPS system and monitor all meter readings:
• Is the critical load being supplied power from the UPS system or bypass?
• Are input, battery and output voltage, frequency and current readings at nominal levels?
• How much battery time is still available during an outage?
• Is the battery recharging after discharge?
• Execute operational procedures:
• Perform critical bus transfer/retransfer between the UPS system and the bypass line.
• Start up and shut down the UPS system and each module.
• Shut down the system and all modules instantly in the event of an emergency.
• Access status reports and history files:
• Obtain a complete listing of the present status of the UPS system and all modules (input, output and battery voltage, frequency and current readings and any alarms that may be
present).
• Review a complete history report of all events leading up to and immediately after a fault condition.
• Examine an archive listing of all alarm conditions that have occurred over a period of time.
• Make adjustments to programmable parameters (access limited by Security Access function):
• Set the date and the time functions.
• Change the auto-dial phone number and the modem options.
• Select the number of auto-retransfer attempts.
• Make adjustment to the UPS output voltage before performing a manual load transfer.
Operation
20
Figure 8Typical operator controls
5
2
100kVA500kVA
5
4
Operation
1000kVA
1
Table 1Typical operator controls
ItemDescriptionFunction
1Input Circuit Breaker (CB1)
Module Output Circuit
2
Breaker (CB2)
3Operator Control PanelRefer to Figure 10 for controls available on this panel.
Control Disconnect
4
(behind inner door)
Interlock Button
5
(on rear of Control Panel)
This manually operated circuit breaker provides power to the UPS module rectifier. In
625-750kVA modules and some 500kVA modules, this breaker is located in the
transformer cabinet.
This manually operated circuit breaker connects the UPS module inverter output to the
UPS System Control Cabinet.
These two fuses provide power to the controls. They are normally closed (ON). Turn
Control Power OFF (by opening the two fuse holders) only for maintenance procedures.
Press this button to make authorized changes to any parameter protected by the
Security Access function. This includes time, date, auto-dial phone numbers, etc.
3
5
2
21
Figure 9Operator controls, typical SCCT System Control Cabinet
Operation
Table 2Typical SCCT System Control Cabinet operator controls
ItemDescriptionFunction
UPS Output Circuit
1
Breaker
System Bypass Circuit
2
Breaker
3Operator Control PanelRefer to Figure 10 for controls available on this panel.
Interlock Button
4
(on rear of Control Panel)
Close Bypass Switch
5
(behind door)
Bypass Reset Switch
6
(behind door)
Static Switch Disconnects
7
(behind door)
Reset Switches (SW1) for
8
Static Switch Disconnects
(behind door)
Control Power Disconnect
9
(behind door)
This motorized circuit breaker connects the critical load to the UPS system
output.
This motorized circuit breaker connects the critical load to the bypass line.
Refer to Figure 11.
Refer to Figure 11.
Refer to Figure 11.
These manually operated switches disconnect the static switch from the
bypass line and from the critical load. They are normally ON (closed). Turn
them OFF (open) only to isolate (disconnect) the static switch for
maintenance procedures. For SCCT less than 1600A, the static switch
disconnects are contactors that open automatically upon loss of bypass input
power and close automatically when bypass power is restored. Control power
fuse disconnects are used to manually open the contactors for maintenance.
Press these two switches before closing Static Switch Disconnects when
recovering from a shutdown that includes loss of Control Power. Green LED
on means Control Power is available. Red LED on means Reset Switch
needs to be pushed. Only SCCI and SCCC control cabinets and SCCT
1600A and larger.
Normally ON. Fuseblocks that are labeled F7 through F10. Turn OFF Control
Power only when required for maintenance procedures.
22
Figure 10 Series 610 UPS and SCC operator control panels
Numbers are used
as keys to data in
Table 3, below.
Table 3Series 610 UPS and SCC operator control panels
Item Description (Location)Function
Display Screen
1
(SCC and modules)
Up
2
(SCC and modules)
Down
3
(SCC and modules)
Select
4
(SCC and modules)
Alarm Reset
5
(SCC and modules)
Voltage Adjust
6
(SCC only)
UPS
7
(SCC only)
Bypass
8
(SCC only)
Control Enable
9
(SCC and modules)
Horn Off
10
(SCC only)
Alarm Horn and
11
Red LED (SCC only)
Emergency Module
12
Off (SCC only)
Battery Trip
13
(modules only)
Output Trip
14
(modules only)
This screen displays all vital UPS information in one convenient location. All of the
UPS monitoring functions and conditions are indicated here.
This touch-sensitive pad (button) is used to move the cursor up through various
selections present on the display screen. Note that all pads on this control panel
have touch-sensitive switches behind them.
Similar to the Up pad, this pad is used to move the cursor down through the
various selections present on the display screen.
After choosing the desired item (with highlighted cursor) from the display screen
with the Up and Down pads, pushing this pad tells the microprocessor to go to the
highlighted selection.
This pad is used to clear all of the alarm conditions that are no longer present.
However, all active alarms remain in memory and on the applicable screens until
they are corrected.
This push-to-turn knob permits adjustment of the UPS output voltage to meet load
requirements or to match the bypass voltage before transferring the load to or from
bypass.
This pad activates the circuits that connect the UPS to the critical load (a
retransfer). When this pad is pushed (along with Control Enable), the UPS output
circuit breaker closes and the bypass circuit breaker opens.
This pad activates the circuits that connect the bypass line to the critical load (a
transfer). When this button is pushed (along with Control Enable), the bypass
circuit breaker closes and the UPS output circuit breaker opens.
This pad must be pressed simultaneously with the UPS, Bypass, Battery Trip or
Output Trip pads to activate them.
This pad is used to silence the alarm horn after it is activated. When this switch is
pressed, the alarm horn is silenced but the active and latched alarm messages
remain on the screen. The alarm messages still displayed stop flashing to indicate
they have been acknowledged.
This electronic horn sounds to alert nearby personnel whenever a new alarm
occurs. A red LED (light emitting diode) is located in the middle of the alarm horn.
During an emergency, pressing this guarded switch will transfer the load to bypass
and then shut down the UPS modules. The load will remain on bypass power.
(Refer to 3.4.5 - Shutdown Procedures.)
This pad can be used (along with Control Enable) to trip the module battery
disconnect (MBD) circuit breaker open (disconnecting the battery from the UPS
module).
This pad can be used (along with Control Enable) to trip the module output circuit
breaker open (disconnecting the module from the UPS system).
Operation
23
Figure 11 Switches behind SCC control panel door
Numbers are used
as keys to data in
Table 4, below.
Operation
Table 4Series 610 UPS and SCC operator control panels
ItemDescription (Location)Function
Interlock Button
1
(on rear of Control Panel)
Bypass Reset Switch
2
(SW1, on Transfer
Relay Board)
Close Bypass Switch
3
(SW1, on System
Interface Board)
Press this button to make authorized changes to any site parameter protected
by the Security Access function. These include the time, date, auto-dial phone
number and other site parameters.
Press this button to reset the transfer relays during start-up, after an
Emergency Power Off shutdown. You must press this button before the Close
Bypass Switch (Item 3).
Press this button to close the Bypass circuit breaker during a start-up
procedure, if it remains open after a shutdown procedure (refer to 3.4.1 - SCC Start-Up Procedure). Note that the Static Switch Disconnects must be OFF to
reset the Bypass circuit breaker. See also Bypass Reset Switch (Item 2).
24
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.