Liebert 1000 - 3000VA User Manual

Page 1
Liebert PowerSure PSI™
User Manual 1000 - 3000VA, 60 Hz, 120V
Power Protection for Business Critical Continuity
Page 2
Page 3
TABLE OF CONTENTS
1.0 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.0 I
3.0 M
3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 6
3.2 Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Automatic Voltage Regulator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Inverter—1000/1440 Models Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.7 DC-to-DC Converter—1920/2200/3000 Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.8 Bi-Directional Converter—1920/2200/3000 Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
AJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.0 WHATS INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Rack-Mount UPS Conversion and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.4 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.0 CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.1 ON/Alarm Silence/Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.2 OFF Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.3 Voltage Programming Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4 Load Level Indicators—4 green, 1 amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5 Battery Level Indicators—5 green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.6 AC Input Indicator—Green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.7 Buck/Boost Indicator—Green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.8 Battery Indicator—Green/Amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.9 Over Temp Indicator—Amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.10 Fault Indicator—Red . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.0 MODES OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.1 Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
i
Page 4
7.2 Buck/Boost Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.3 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.4 Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.1 DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2 Remote Shutdown Via the DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2.1 Any Mode Shutdown—Via Pins 5 & 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2.2 Battery Mode Shutdown—Via Pins 4 & 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.3 USB Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.4 Data Line Protection Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.5 UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.0 VOLTAGE PROGRAMMING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
10.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10.1 Cleaning the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.2 Maintaining Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.3 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.3.1 Internal Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
12.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
12.1 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ii
Page 5
FIGURES
Figure 1 Front view of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 2 1000 and 1440VA PSI—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 3 1920 and 2200VA PSI—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 3000VA PSI—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5 Line diagram of PowerSure PSI 1000VA & 1440VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Line diagram of PowerSure PSI 1920VA, 2200VA & 3000VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 7 Support base for tower configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 8 Rack mount handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 9 Fixed rails with inner members extended . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Rack mounting rails and slide assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11 REPO switch connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Load level indicators—4 green, 1 amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 13 Battery level indicators—5 green. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 14 Normal mode operation with 26-50% load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 15 Buck/Boost mode operation with 51-75% load and 21-40% battery capacity . . . . . . . . . . . . . . . . 17
Figure 16 Battery mode at 61 – 80% battery capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 17 Low Battery mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 18 Load Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 19 Battery replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TABL ES
Table 1 DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 2 Troubleshooting chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 3 UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 4 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 5 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
iii
Page 6
iv
Page 7

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and batteries. Please read this manual thoroughly before attempting to install or operate this UPS.
WARNING
!
SAFETY PRECAUTIONS
To prevent the risk of fire or electric shock, install the UPS in a temperature and humidity controlled room, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
Operate the UPS only from a properly grounded (earthed) 110-127 VAC, 50Hz or 60Hz AC supply.
To reduce the risk of electric shock, do not remove the cover, as it has no user-serviceable parts inside except the internal battery pack. Some components are live, even when AC power is disconnected. For service, contact a qualified technician.
CAUTION
!
Although your UPS has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, please observe the following rules:
• Turn Off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A dry cloth is recommended to remove dust from the surface of your UPS.
• Do not install or operate your UPS in or near water.
• Do not place UPS on an unstable cart, stand or table.
• Do not place UPS under direct sunlight or close to heat emitting sources.
• Never block or insert any objects into the ventilation holes or other openings of the UPS. Keep all vents free of dust accumulation that could restrict air flow.
• Do not place UPS power cord in any area where it may get damaged by heavy objects.
WARNING
!
If your UPS demonstrates any of the following conditions, turn Off and unplug your UPS from the outlet and contact your local dealer, Liebert representative or Liebert Worldwide Support Group:
• The power cord or plug is damaged.
• Liquid has been spilled on the UPS.
• The circuit protector trips frequently.
• The UPS does not operate in accordance with the user manual.
CONDITIONS OF USE: The input receptacle must be within 10 feet (3 meters) of the UPS.
Your UPS provides conditioned power to connected equipment. Maximum load must not exceed that shown on UPS rating label. If uncertain, consult your local dealer, Liebert representative or the Lie­bert Worldwide Support Group.
Placing magnetic storage media on top of the UPS may result in data corruption.
The equipment can be installed and operated by individuals without previous training.
CAUTION
!
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners, laserjet/inkjet printers, hair dryers, overhead projectors.
1
Page 8
CAUTION
!
BATTERY HANDLING PRECAUTIONS
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from the batteries.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic.
• When replacing the battery, use same number and type of battery as the suitable recom­mended type of battery listed in specification table in back of this manual.
• Handle, transport and recycle batteries in accordance with local regulations.
NOTE
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment uses, generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference with radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment Off and On, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the UPS and the receiver.
• Connect the UPS into an outlet on a circuit different from the one on which the receiver is connected.
2
Page 9

1.0 GLOSSARY OF SYMBOLS

.
Risk of electrical shock
Indicates caution followed by important instructions
Glossary of Symbols
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF
Voltage Programming Button
3
Page 10

2.0 INTRODUCTION

Congratulations on your choice of the Liebert PowerSure™ PSI Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission it may be subject to voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data loss, or even damage equipment. The PowerSure PSI protects equipment from these disturbances.
The PowerSure PSI comes in nominal power ratings of 1000, 1440, 1920, 2200 and 3000 VA. Refer to the Specifications section for details.
The PowerSure PSI is a 2U, line-interactive UPS that may be installed in a rack or used in a tower configuration. A line-interactive UPS continuously conditions and regulates its output voltage, whether utility power is present or not. It supplies connected equipment with clean, sinewave power to simulate the power generated by the utility. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the PowerSure PSI contains Status Indicators to display Load Level, Battery Level, Buck/Boost, Over Temperature and Battery. It also provides self-diagnostic tests, a combination ON/ Alarm Silence/Battery Test button, an OFF button and Voltage Programming button.
The PowerSure PSI has USB, DB-9 (RS232/contact closure) and Intellislot interface ports for commu­nications between the UPS and a LAN server or other computer systems. The DB-9 port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert’s MultiLink software. MultiLink software can also remotely control UPS operation. The USB port provides detailed operating information and alarm status to the host system when used in conjunction with the Liebert Human Interface Device (HID) and Microsoft Power Manager software.
Introduction

Figure 1 Front view of UPS

OFF Button
ON/Alarm Silence/ Battery Test Button
Vol tag e Programming Button
Fault Indicator
Load Level Indicators
Battery Level Indicators
UPS Status Indicators
UPS Display (bezel removed)
4
Page 11
Figure 2 1000 and 1440VA PSI—rear view
REPO
1 2 3 4
REPO
RS-232
INTELLISLOT
Intellislot Port
PHONE / FAX / MODEM / NETWORK
INPUT
Data Line Connectors
OUT
IN
PROTECTION
INPUT
BREAKER
PUSH TO RESET
Output Receptacles
LOAD 2 LOAD 1
Introduction
BATTERY CONNECTOR 1440VA/DC 48V/30A 1000VA/DC 48V/20A
+
-
USB Port
RS232 (DB-9) Port
Attached Power Cord, 10ft (3m)
Figure 3 1920 and 2200VA PSI—rear view
Intellislot
REPO
USB Port
1 2 3
REPO
4
RS-232
RS232 (DB-9) Port
Port
INTELLISLOT
Circuit Breaker
INPUT
BREAKER
PUSH TO RESET
INPUT
Attached Power Cord, 10ft (3m)
Circuit Breaker
Data Line Connectors
PHONE / FAX /
MODEM / NETWORK
PROTECTION
IN
OUT
Output Receptacles
LOAD 1
BREAKER
15A/120VAC
LOAD 2
BREAKER
Circuit Breaker (2200 VA only; not supplied on 1920VA unit
External Battery Cabinet Connector
Circuit Breaker (2200 VA only; not supplied on 1920VA unit
BATTERY CONNECTOR DC 72V / 30A
+
-
External Battery Cabinet Connector
Figure 4 3000VA PSI—rear view
Intellislot
REPO
USB Port
1 2 3
REPO
4
RS-232
RS232 (DB-9) Port
Port
INTELLISLOT
Circuit Breaker
INPUT
BREAKER
PUSH TO RESET
INPUT
Attached Power Cord, 10ft (3m)
Data Line Connectors
PHONE / FAX /
MODEM / NETWORK
PROTECTION
IN
OUT
5
Output Receptacles
LOAD 3
Circuit Breaker
LOAD 1
BREAKER
15A / 120 VAC
LOAD 2
BREAKER
Circuit Breaker
External Battery Cabinet Connector
BATTERY CONNECTOR DC 72V / 40A
+
-
Page 12

3.0 MAJOR COMPONENTS

Figure 5 Line diagram of PowerSure PSI 1000VA & 1440VA

Major Components
Input
G G
EMI/RFI
Filter
Relay
AVR
Transformer
InverterBatteryCharger
Output

Figure 6 Line diagram of PowerSure PSI 1920VA, 2200VA & 3000VA

Input
EMI/RFI
Filter
Relay
AVR
Transformer
Output
BatteryCharger
G G
DC-to-DC
Converter
Bi-Directional
Converter

3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters

These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize surges or interference present in the utility line and keep the sensitive equipment protected.

3.2 Relay

In Normal mode the Relay passes utility AC power to the connected load. When input utility voltage or frequency is outside acceptable limits, the Relay activates and transfers the UPS to battery.
6
Page 13

3.3 Automatic Voltage Regulator

The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This keeps the UPS output voltage within the connected equipment’s tolerance and accommodates wide utility voltage fluctuations without utilizing the batteries.

3.4 Battery Charger

In Normal mode, the Battery Charger converts utility AC power into regulated DC power to float charge the battery. It is continuously charging the battery whenever the UPS is plugged into a power outlet and utility power is within acceptable limits - even if the UPS is turned Off.

3.5 Battery

The PowerSure PSI utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional external battery cabinets are available to extend battery run times.
3.6 Inverter—1000/1440 Models Only
In battery mode operation, the inverter utilizes the DC output of the battery and inverts it into pre­cise, regulated, sinewave AC power.
Major Components
3.7 DC-to-DC Converter—1920/2200/3000 Models Only
The DC-to-DC Converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the Bi-Directional Converter. This allows the Bi-Directional Converter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
3.8 Bi-Directional Converter—1920/2200/3000 Models Only
In normal operation, the Bi-Directional Converter changes utility AC power into regulated DC power to “float charge” the battery system. This converter is continuously charging the battery whenever the UPS is plugged into a power outlet and utility power is within acceptable limits—even if the UPS is turned Off. When utility power fails, the Bi-Directional Converter draws energy from the battery through the DC-to-DC Converter and inverts it into a regulated sinewave supplying power to con­nected equipment.
7
Page 14

4.0 WHATS INCLUDED

The PowerSure PSI is shipped with the following items:
• PowerSure PSI user manual
• Warranty card
• MultiLink software CD
• MultiLink serial cable, 10 ft (3m)
• USB cable, 6 ft (1.8m)
• RJ-11 cord, 7 ft (2.1m)
• Rack mount handles
• Support base
• Fixed rails
• Mounting hardware (screws/washers)
•Front bezel
• Vertical display overlay
What’s Included
MultiLink
software CD
Support base
Ver tical display overlay
Fixed rails
MultiLink
serial cable
10 ft (3m)
Mounting hardware (screws & washers)
USB cable
6 ft (1.8m)
RJ-11 cord
7 ft (2.1m)
Front bezel
Rack mount
handles
8
Page 15

5.0 INSTALLATION

5.1 Preparation

1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see Table 4 - Battery cabinet specifications). Take proper precautions when lifting or moving it.
2. Decide where to place the PowerSure PSI. Install the UPS indoors in a controlled environment where it cannot be accidentally turned Off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces battery life.
3. The PowerSure PSI may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either Tower UPS Installation or Rack-Mount UPS Conversion and Installation.
Installation

5.2 Tower UPS Installation

When using the PowerSure PSI in a tower configuration, use the included support base (shown below, left) to stabilize the UPS. If two or more battery cabinets are added, the spacers—included with the battery cabinets—should be used to accommodate the additional cabinets.

Figure 7 Support base for tower configuration

Tower Stand - Fully Extended
Spacers Can be Added to Accommodate External Battery Cabinets
1. To orient the display for vertical viewing, remove the front plastic bezel by pulling forward evenly on both sides.
2. Peel the backing from the vertical display overlay and apply to the existing display.
3. Snap the front bezel back into place.
Connectors Snap into Slots on Base
9
Page 16

5.3 Rack-Mount UPS Conversion and Installation

NOTE
When rack mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.
1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see Figure 8).

Figure 8 Rack mount handles

Installation
Two (2) M4x6 Flat Head Screws
Two (2) M4x6
Flat Head Screws
2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend the inner members to their outermost position (see Figure 9).

Figure 9 Fixed rails with inner members extended

Adjustable Length Maximum 800 mm
Minimum 485 mm
Rack Mount Handles
Wing Nuts for
Adjustment
M4x6 Flat Screw
Adjustable Slide Assembly
CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.
3. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet. Make sure fixed rails are at the same mounting height on each of the four (4) rack mounting rails.
10
Page 17
4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the inside of the rack mounting rails.
5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front of the fixed rail assembly (see Figure 10).
6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed rail assembly.
8. Check alignment of fixed rails and tighten all screws to ensure locking action.

Figure 10 Rack mounting rails and slide assemblies

B
Installation
B
A
9. Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward and backward on the fixed rails. If not, recheck alignment.
CAUTION
!
Lifting equipment into rack may be a two-person job, depending on weight of equipment.
10. Use the extra M5 screws provided, secure front of the UPS to rack mounting rails to prevent the UPS from sliding out of position.
11. Plug the PowerSure PSI’s attached 10 ft. (3m) power cord into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with national and local electrical codes. Use a 15A-rated device for the 1000 or 1440 VA units, 20 amp for the 1920VA, 30 amp for the 2200VA or 3000 VA units. The wall receptacle must be grounded.
12. Turn On the UPS by pressing the ON button. Check that the AC Input Indicator is not flashing. If it is flashing, refer to 11.0 - Troubleshooting. Then turn On the connected equipment. The UPS is now providing conditioned power to your equipment.
A
A
A
B
A - Washer
B - M5x12 Flat Screw
B
Vertical overlay for tower UPS
Horizontal overlay for rack UPS
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.
11
Page 18
Installation
13. Connect Phone/Fax/DSL/Network/Modem devices to data line connectors.
RJ11/RJ45
connection
OUT
PHONE / FAX / MODEM / NETWORK
INPUT
IN
PROTECTION
BREAKER
PUSH TO RESET
INPUT
LOAD 2 LOAD 1
BATTERY CONNECTOR 1440VA/DC 48V/30A 1000VA/DC 48V/20A
+
-
1 2 3
REPO
4
RS-232
INTELLISLOT
14. Communication options (see 8.0 - Communications for details):
Option 1 - Serial Communications
Serial communications provides parametric data, for example, input voltage and battery voltage. a. Connect MultiLink serial cable included with the UPS to communications port. b. Install the MultiLink software. The software and installation instructions, as well as the user
manual, are on the CD included in the PowerSure PSI package.
Option 2 - Contact Closure Communications
Contact Closure communications provides on-battery and low-battery signals for orderly shut­down.
a. Refer to the MultiLink user manual for instructions on making your own contact closure
cable.
b. Install the MultiLink software. The software and installation instructions, as well as the user
manual, are on the CD included in the PowerSure PSI package.
Option 3 - USB Communications
a. Connect USB cable provided with the UPS to the PSI’s USB port and the USB port on your
computer. The PSI will work automatically with your built-in power management software on Windows XP and 2000 and Mac OS 10.2 or later (see 8.3 - USB Interface Port for details).
Option 4 – Intellislot
The UPS contains one communication slot, called “Intellislot™,” to allow the operator to field install optional communication cards. These optional cards allow the UPS to communicate via either OpenComms Web Card (OCWEBCARD), connected directly to the LAN; or Intellislot Relay Interface card (RELAYCARD-INT) communication card. Once the OCWEBCARD is installed, the Serial communication via the RS232 is disabled. The USB, Intellislot, and Contact Closure com­munications operate in parallel.
15. REPO Switch—The PowerSure PSI is equipped with a Remote Emergency Power Off (REPO) switch.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
12
Page 19

Figure 11 REPO switch connections

REPO Connection
Installation
REPO Switch
as shipped
REPO connections
for normally open
switch system
12341234
Key to REPO switch connections
1. 24 VDC,
2. Sense
3. Sense
4. Ground

5.4 External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The run time is limited to a maximum of four (4) hours.
CAUTION
!
The external battery cabinet(s) are heavy (see 12.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
REPO connections
for normally closed
switch system (fail-safe)
1234
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
2. The rack-mount handles are shipped with the external battery cabinet and may be installed at this time (see 5.3 - Rack-Mount UPS Conversion and Installation).
3. Fixed rails and securing hardware ship with the external battery cabinet. Fasten the fixed rails into position with the screws per the instructions included with the UPS. Repeat Steps 1 through 10 from 5.3 - Rack-Mount UPS Conversion and Installation.
4. Use the support bases included with the UPS for the tower option to prevent tip-over. One additional set of support base spacers ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS, as shown at right.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 5 - Battery run times.
BATTERY CONNECTOR 1440VA/DC 48V/30A 1000VA/DC 48V/20A
IN
PHONE / FAX / MODEM / NETWORK
INPUT
PROTECTION
OUT
INPUT
BREAKER
PUSH TO RESET
LOAD 2
1 2 3
REPO
4
RS-232
INTELLISLOT
BATTERY CONNECTOR 1440VA/DC 48V/30A 1000VA/DC 48V/20A
BATTERY CONNECTOR 1440VA/DC 48V/30A
LOAD 1
1000VA/DC 48V/20A
+
-
13
Page 20

6.0 CONTROLS AND INDICATORS

All indicators illuminated for illustrative purposes only.

6.1 ON/Alarm Silence/Battery Test Button

This button controls output power to connected load(s) and has three functions:
•On
• Alarm Silence
•Battery Test
Controls and Indicators
ON—When the UPS is Off, pressing the ON/Alarm Silence/Battery Test button for more than one (1) second will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on
battery (battery start).
Alarm Silence—When a UPS audible alarm is active, pressing and releasing the ON/Alarm Silence/ Battery Test button will silence the active audible alarm, whether utility power is present or not. Once the alarm silence function has been activated, all active audible alarms will remain silenced until a new alarm condition is detected.
NOTE
The LOW BATTERY, OVER TEMP and OVERLOAD warning audible alarms CANNOT be silenced.
Battery Test—To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for at least one second while operating from utility power with no alarm conditions present.
• If all five (5) Battery indicators are not illuminated, allow the UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if all five (5) Battery indicators are not illuminated, con­tact your local dealer, Liebert representative or Liebert Worldwide Support Group.

6.2 OFF Button

When the UPS is on (in either Normal or Battery mode), pressing the OFF button for more than one (1) second will shut down the UPS. An audible alarm sounds briefly.
14
Page 21

6.3 Voltage Programming Button

The PowerSure PSI contains a Voltage Programming button that allows the operator to select the nominal utility voltage. This setting changes the utility transfer points (low and high) of the UPS and the nominal output voltage when operating in Battery mode. The operator can select between 110, 120 and 127 VAC output. The factory-default setting is 120 VAC.
The Voltage Programming button is a push button type and is behind the plastic bezel on the front panel of the UPS. To access the button, the front bezel must be removed.
6.4 Load Level Indicators—4 green, 1 amber
The Load Level Indicators display the approximate electrical load placed upon the UPS.
The UPS Load Level Indicators are displayed in 25% increments as shown in Figure 12.
Figure 12 Load level indicators—4 green, 1 amber
Upon detection of an output overload condition, the amber overload (>100%) indicator flashes and an audible alarm activates. If the UPS shuts down due to an overload condition, the amber overload (>100%) indicator illuminates (see Troubleshooting section for details).
Controls and Indicators
6.5 Battery Level Indicators—5 green
The Battery Level Indicators display the approximate battery capacity.
The approximate battery capacity is displayed when the UPS is operating in Normal, Buck/Boost, or Battery mode.
The Battery Level Indicators are displayed in 20% increments as shown in Figure 13:
Figure 13 Battery level indicators—5 green
The PowerSure PSI is equipped with automatic and remote battery test features. The automatic test occurs every 14 days if utility has not been interrupted; this option may be configured by the user. Should the battery fail this test, the amber Battery Indicator will be illuminated and an alarm will sound (see Troubleshooting section for details).
The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery test.
6.6 AC Input Indicator—Green
The AC Input Indicator illuminates when utility power is available and within the input specifica­tions. This indicator flashes when the UPS detects a Site Wiring Fault (line-neutral reversal or neu­tral not grounded properly) (see Troubleshooting section for details).
6.7 Buck/Boost Indicator—Green
The Buck/Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a low utility voltage condition. This indicator flashes when the UPS is operating in Buck mode to com­pensate for a high utility voltage condition (see Troubleshooting section for details).
6.8 Battery Indicator—Green/Amber
The Battery Indicator illuminates green when the UPS is operating on battery and flashes green when a low battery condition occurs. The Battery Indicator illuminates amber when a bad battery is detected, indicating that the batteries need to be replaced (see Troubleshooting section for details).
15
Page 22
6.9 Over Temp Indicator—Amber
The Over Temp Indicator flashes when the UPS detects an over temperature condition. This indicator illuminates when the UPS shuts down due to an over temperature condition (see Troubleshooting section for details).
6.10 Fault Indicator—Red
The Fault Indicator illuminates when the UPS detects an internal problem (see Trouble­shooting section).
Controls and Indicators
16
Page 23

7.0 MODES OF OPERATION

7.1 Normal Mode

During Normal mode operation, the PowerSure PSI supplies conditioned, computer-grade power to the connected equipment: utility power passes through the TVSS circuitry and the EMI/RFI filters and then through the Inverter (1000VA & 1440VA) / Bi-Directional Converter (1920VA, 2200VA and 3000VA) to connected equipment.
When the UPS is in Normal mode, the AC Input Indicator illuminates green. The UPS display in Figure 14 shows the UPS operating in Normal mode with 26% - 50% load connected to the output.

Figure 14 Normal mode operation with 26-50% load

Utility power present ...
... and within operational limits
Modes of Operation
The PowerSure PSI continuously monitors the batteries to maintain them in a fully charged state. The battery charger operates whenever AC power is present, even if the UPS is switched Off. By default, the UPS is set to perform an automatic battery test after it has been operating continuously for two (2) weeks. The automatic battery test can be disabled via MultiLink.

7.2 Buck/Boost Mode

The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the PowerSure PSI detects an abnormality, it raises the undervolt­age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main­tains the output voltage to the connected critical equipment, without utilizing the batteries.
The Buck/Boost Indicator flashes green when the UPS is operating in Buck mode and illuminates green when the UPS is operating in Boost mode (see Troubleshooting section for details).

Figure 15 Buck/Boost mode operation with 51-75% load and 21-40% battery capacity

Indicator shows UPS in Boost Mode (solid green)
17
Page 24

7.3 Battery Mode

The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or complete utility failure. The battery system supplies power through the Inverter (1000VA & 1440VA) or through the DC-to-DC converter to the Bi-Directional Converter (1920, 2200VA and 3000VA) to generate power for the connected equipment.
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 16 shows the UPS in Battery mode with 61% - 80% battery capacity remaining.
Figure 16 Battery mode at 61 – 80% battery capacity
When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink. For more information, refer to Troubleshooting section.
Modes of Operation
Battery Indicator illuminated

Figure 17 Low Battery mode

For approximate battery run times, refer to Table 5 - Battery run times. These run times are approximates based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter­nal battery cabinets.
CAUTION
!
Turning Off the UPS while it is in battery mode will result in loss of output power.

7.4 Battery Recharge Operation

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.
Battery Indicator flashes green
18
Page 25

8.0 COMMUNICATIONS

r

8.1 DB-9 Connector

The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer system running MultiLink software. The DB-9 is capable of supplying serial communica­tion, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown soft­ware, is shipped with the UPS, along with a 10 ft. (3m) DB-9 cable required for running MultiLink.
When MultiLink is installed on the host computer, the UPS can signal “on battery” and “low battery” using opto-couplers. When the UPS is operating in Battery mode, it can receive a signal from the host computer system that will shut down the UPS (after gracefully shutting down the operating system on the host computer system) when the remaining battery run time is low. The timing of the signal depends on MultiLink’s configuration settings. This shutdown signal (5-12VDC) must have a dura­tion of at least 2 seconds for the UPS to be shut down. The UPS communicates via serial communica­tions using Liebert ESP II protocol.

Table 1 DB-9 pin assignment

DB-9 Pin Assignment Description
1 Low Battery (open collector) 2UPS TxD 3UPS RxD 4 Battery Mode Shutdown (5-12V) 5 Common 6 Any Mode Shutdown (short to pin 5) 7 Low Battery (open emitter) 8 Utility Fail (open emitter) 9 Utility Fail (open collector)
Communications
Pin Assignment Collector to Emitter*
6789
54321

8.2 Remote Shutdown Via the DB-9 Connector

The PowerSure PSI can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-9 connector.
8.2.1 Any Mode Shutdown—Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut Off regardless of what mode the UPS is oper­ating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Battery Test button.
8.2.2 Battery Mode Shutdown—Via Pins 4 & 5
While the UPS is operating on battery (with no battery test in progress), a 5-12VDC signal for 2 sec­onds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer inside the UPS begins a count­down. The timer cannot be stopped. If utility power returns during the 2-minute timer countdown, the shutdown timer continues until the end of 2 minutes and then the UPS turns Off. By default, autorestart is enabled so the UPS will restart after 10 seconds. If autorestart is disabled via Multi­Link software, the UPS remains Off until a manual restart.
330 Ohms
(+)
(-)
Open Collecto
Open Emitter
19
Page 26

8.3 USB Interface Port

The PowerSure PSI has a USB interface port for communication that will work with the built-in Microsoft Power Manger software on the user’s PC, if so equipped. It will provide UPS status and manages the automatic orderly shutdown of the computer. The UPS’s USB communications meet HID standard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.

8.4 Data Line Protection Connectors

Data line (in and out) connectors are on the rear of the UPS and provide transient voltage surge sup­pression (TVSS) for Phone/Fax/DSL/Internet/Modem devices.
Communications
Microsoft, Windows, and the Windows logo are trademarks, or registered trademarks of Microsoft Corporation in the United States and/or other countries.

8.5 UPS Intelligent Communications

The PowerSure PSI is equipped with an Intellislot® port to provide advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot OCWEBCARD is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the Intellislot OCWEBCARD and MultiLink License Kits, visit our Web site (www.liebert.com
Several option cards are available for use in the Intellislot port of the PowerSure PSI. The Intellislot OCWEBCARD provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor­dinate shutdown in the event of a power failure.
The RELAYCARD-INT provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.
NOTE
The USB, Intellislot and Contact Closure communications operate in parallel. Using the OCWEBCARD disables the Serial Communications of the DB-9.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.
) or contact your local dealer or Liebert representative.
20
Page 27

9.0 VOLTAGE PROGRAMMING PROCEDURE

Figure 18 Load Level Indicators

Vol tag e Programming Button
1. Remove the front bezel from the UPS.
2. UPS must be operating in Normal (AC) mode.
Voltage Programming Procedure
Load Level Indicators
NOTE
Utility power will be applied to the connected load.
3. The AC Input, Load, and Battery Level Indicators should be lit.
4. Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode. The UPS will beep and all of the indicators on the front panel display will flash on and off for about 5 seconds. The next cycle will display the current configuration, either 110, 120 or 127 VAC. One of the Load Level Indicators will be flashing. Initially, the 0%-25% Load Level Indicator will be flashing, indicating the default setting of 120V as shown in Figure 18.
5. Press the ON button to step through the voltage settings until the appropriate Load Level Indicator is flashing.
6. Press the Voltage Programming button. The UPS will return to Normal mode operation.
The Voltage Programming button allows the operator to select the utility transfer voltage at which the UPS will switch to battery power. This also changes the inverter voltages. The voltage settings are as follows:
Setting
120V (230V)
110V (220V) 78 - 138 VAC 110VAC
127V (240V) 90 - 150 VAC 127VAC
Input Voltage
Range
85 - 145 VAC
(default)
Output Voltage
(Battery Mode)
120VAC
21
Page 28

10.0 MAINTENANCE

The PowerSure PSI UPS requires very little maintenance. Follow these practices to prevent prob­lems.

10.1 Cleaning the UPS

The following will help ensure trouble-free operation for years:
• Vacuum dust from the ventilation intake occasionally.
• Wipe the cover periodically with a dry cloth.

10.2 Maintaining Batteries

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched Off.
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.

10.3 Battery Replacement

CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
Maintenance
• Remove rings, watches, and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Dispose of old batteries according to local codes.
NOTE
This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads. Caution should be exercised when replacing the batteries because the load is unprotected from disturbances and power outages during this procedure.
22
Page 29

10.3.1 Internal Battery Replacement Procedure

1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the five (5) screws on the front cover plate. Lay the cover plate aside for reassembly.
3. Loosen and remove four (4) screws on battery bracket.
4. Disconnect the two (2) slotted, red and black battery connectors.
5. Grasp the battery pack assembly by the pull tab and pull it out of the front of the UPS.
6. Unpack the new battery assembly, taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 7; otherwise STOP and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.
7. Slide in the new replacement battery pack.
8. Reattach the battery bracket with the four (4) screws.
9. Reconnect the two (2) slotted red and black battery connectors.
10. Reattach the front battery door with the five (5) screws.
11. Reattach the front plastic bezel cover to the UPS.
Figure 19 Battery replacement procedure
Maintenance
Battery Bracket
Front Plastic Bezel
Cover Plate
00 0102 03
Battery Connectors
Battery Pull Tab
23
Page 30

11.0 TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the PowerSure PSI experiences a problem. Use this information to determine whether external factors caused the problem. See Table 2 - Troubleshooting chart for suggested remedy.
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload warning and over-temperature warning conditions.
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

Figure 20 Status indicators

Troubleshooting
All indicators illuminated for illustrative purposes only.
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 5.0 - Installation. If the problem persists, refer to Table 2:
24
Page 31

Table 2 Troubleshooting chart

Problem Cause Solution
UPS will not start
UPS starts on battery, but will not switch to AC
UPS shuts down
AC Input is flashing
All Battery Level Indicators flashing
Battery Indicator illuminated amber; long beep every minute
Over Temp Indicator flashing
Fault Indicator lit but UPS is On
Troubleshooting
Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. For
Short circuit
Battery disconnected or is completely discharged
UPS not plugged in Plug in the power cord securely.
Circuit protector tripped Reset the circuit protector and restart the UPS.
Input voltage below threshold
AC overvoltage
Load exceeded UPS capacity (110%), All Load Level Indicators are illuminated; continuous beep
Over temperature shutdown, Over Temp Indicator lit; continuous beep
MultiLink shutdown
Internal UPS fault, Fault Indicator Lit; continuous beep
UPS shutdown due to a command from the communications port(s), Load Level 0-25% Indicator illuminated
Site Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding.
UPS is unable to perform manual or remote battery test; beep every half second for five seconds
UPS failed battery test Initiate battery test again.
Batteries weak Recharge batteries.
Batteries need to be replaced Replace batteries.
Over temperature warning; beep every half second
Fault warning; beep every half second
further help, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Check for proper connection of battery or batteries.
Wait until the voltage rises to an appropriate level or have the utility power checked by a qualified electrician.
Wait until voltage lowers to an appropriate level or have the utility power checked by a qualified electrician.
Check load level display and remove non­essential loads. Recalculate the load and reduce number of loads connected to UPS - the total wattage of your equipment must not exceed the capacity of the UPS.
Make sure that the UPS is operating in 32°F to 104°F (0°C to 40°C) and that it has adequate ventilation.
Consult the MultiLink user manual or contact your LAN administrator.
Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Have the utility checked by a qualified electrician.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
Make sure that the UPS is operating in 32°F to 104°F (0°C to 40°C) and that it has adequate ventilation.
Reset UPS.
NOTE
The 1920VA UPS will sound an Overload alarm under certain Low Line conditions when it is fully loaded and it exceeds the input current rating. Unless the load is reduced, the condition will trip the branch circuit breaker.
25
Page 32
Specifications

12.0 SPECIFICATIONS

Table 3 UPS specifications

Model Number
Power Rating, VA/W 1000VA/750W 1440VA/1080W 1920VA/1500W 2200VA/1650W 3000VA/2250W
Dimensions, W x D x H, in (mm)
Shipping
Weight, lbs (kg)
Shipping 80.7 (36.6) 85.8 (39.0) 95.9 (43.6) 95.9 (43.6) 100.5 (45.6)
Input AC Parameters
Surge Protection 570J
Voltage Range Without
Battery Operation
Frequency Range 45 - 65 Hz (±0.1 Hz)
Input Power Cord
(attached)
Output AC Parameters
Output Receptacles (8)NEMA 5-15 R (8) NEMA 5-15 R
Voltage (Normal mode) 110 / 120 / 127 VAC (configurable) ±10%
Voltage (Battery Mode)
Transfer Time 4-6 ms typical
Waveform Sinewave
Frequency (Normal Mode) 45 - 65 Hz (±0.1 Hz)
Frequency (Battery Mode) 50 or 60 Hz (±0.5 Hz); auto sensing
Overload Warning >100 - 110%
Overload Shutdown >200% - short circuit; after 15 cycles (normal mode)
Battery Parameters
Quantityx Voltage x Rating 4 x 12V x 7Ah 4 x 12V x 7Ah 6 x 12V x 7Ah 6 x 12V x 7Ah 6 x 12V x 9Ah
Backup Time See Table 5 - Battery run times
Full Load 11 5 6 5 6
Half Load 26 16 19 16 16
Recharge Time 4 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
Operating Temperature +32°F to + 104°F (0°C to + 40°C)
Storage Temperature +5°F to + 104°F (-15°C to + 40°C)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Audible Noise
PS1000RT2-120 PS1440RT2-120 PS1920RT2-120 PS2200RT2-120 PS3000RT2-120
3.43 x 22 x 17
Unit
(87 x 557 x 430)
11.8 x 27.8 x 23.5 (300 x 706 x 598)
Unit 61.7 (28) 68.2 (31.0) 77.0 (35.0) 77.0 (35.0) 81.6 (37.0)
10 ft. (3m),
NEMA 5-15 P
Type Valve-regulated, nonspillable, lead acid
<40 dBA, internal fan(s) Off <50 dBA, internal fan(s) On
3.43 x 22 x 17
(87 x 557 x 430)
11.8 x 27.8 x 23.5 (300 x 706 x 598)
10 ft. (3m),
NEMA 5-15 P
±5% before low battery warning; ±8% after low battery warning
3.43 x 24.1 x 17
(87 x 612 x 430)
13.1 x 34 x 23.5
(333 x 864 x 598)
78VAC - 150VAC, configurable
10 ft. (3m),
NEMA 5-20 P
(6) NEMA 5-15 R (2) NEMA 5-20 R
T-Slot, accepts 15APlug
110 / 120 / 127 VAC (configurable);
<40 dBA, internal fan(s) Off <60 dBA, internal fan(s) On
3.43 x 24.1 x 17
(87 x 612 x 430)
13.1 x 34 x 23.5
(333 x 864 x 598)
(6) NEMA 5-15 R (2) NEMA 5-20 R
T-Slot, accepts 15APlug
10 ft. (3m),
NEMA L5-30 P
3.43 x 24.1 x 17 (87 x 612 x 430)
13.1 x 34 x 23.5
(333 x 864 x 598)
10 ft. (3m),
NEMA L5-30 P
(4) NEMA 5-15 R (2) NEMA 5-20 R
T-Slot,accepts
15A Plug
(1) NEMA L5-30 R
26
Page 33
Table 3 UPS specifications (continued)
Model Number
Agency
Safety UL 1778, c-UL Listed
Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Emissions FCC Part 15, Class B FCC Part 15, Class A
Conducted Immunity EN61000-4-6
Harmonics EN61000-3-2
Flicker EN61000-3-3
Transportation ISTA Procedure 1A Certification
PS1000RT2-120 PS1440RT2-120 PS1920RT2-120 PS2200RT2-120 PS3000RT2-120
Surge
ESD EN61000-4-2, Level 3, Criteria B
ANSI C62.41, Category A, Level 3
(IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria B

Table 4 Battery cabinet specifications

Model Number
Used w/UPS Model
Dimensions, W x D x H, in (mm)
Unit 3.43 x 22 x 17 (87 x 557 x 430) 3.43 x 24.1 x 17 (87 x 612 x 430)
Shipping
Weight, lbs (kg)
Unit 66.1 (30) 101.4 (46)
Shipping 85.1 (38.6) 118.1 (53.6)
Battery Parameter
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating 2 strings of 4 x 12V x 7Ah 2 strings of 6 x 12V x 9Ah
Battery Manufacturers CSB, B&B Battery and EnerSys
Backup Time See Table 5 - Battery run times
Environmental
Operating Temperature +32°F to + 104°F (0°C to + 40°C)
Storage Temperature +5°F to + 104°F (-15°C to + 40°C)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class B
Transportation ISTA Procedure 1A Certification
PS2-48VBATT PS2-72VBATT
PS1000RT2-120 PS1440RT2-120
11.8 x 27.8 x 23.5 (300 x 706 x 598)
PS1920RT2-120 PS2200RT2-120 PS3000RT2-120
13.1 x 34 x 23.5
(333 x 864 x 598)
Specifications
27
Page 34

Table 5 Battery run times

Load% 1000VA 1440VA 1920VA 2200VA 3000VA
5% 174 138 181 171 177 10% 118 79 104 73 91 20%6545524747 30%4128312628
Internal Battery (minutes)
Internal Battery + 1 External Battery Cabinet (minutes)
Internal Battery + 2 External Battery Cabinets (minutes)
Internal Battery + 3 External Battery Cabinets (minutes)
Internal Battery + 4 External Battery Cabinets (minutes)
40%3724252322 50%2616191616 60%2414151314 70%1810111010 80%169108 9 90% 12 6 8 6 7
100% 11 5 6 5 6
5% 513 409 575 542 542 10% 305 265 294 266 257 20% 248 188 208 185 148 30% 177 125 143 135 141 40% 139 104 123 122 99 50% 119 72 105 99 67 60%9859827553 70%7545595545 80%6340534939 90%5335474434
100%4630434029
5% 1001 828 — 10% 565 461 590 493 444 20% 409 283 307 291 249 30% 283 219 243 222 168 40% 248 177 197 194 148 50% 209 133 163 150 129 60% 166 122 141 137 114 70% 136 98 128 122 92 80% 127 84 115 107 71 90% 110 64 102 92 56
100%9856897752
5% 1174 1001 — 10% 1001 655 590 — 20% 565 409 522 493 300 30% 409 283 298 283 240 40% 305 257 267 266 213 50% 274 209 237 222 168 60% 248 166 197 185 144 70% 209 136 166 156 129 80% 188 125 147 141 116 90% 145 110 138 131 101
100% 136 95 128 120 88
5% 1174 — 10% 1174 828 — 20% 828 565 639 590 444 30% 513 357 458 395 283 40% 461 292 322 300 266 50% 305 257 281 274 222 60% 283 230 252 240 179 70% 257 188 220 203 150 80% 239 156 192 173 139 90% 209 136 169 156 129
100% 188 125 150 144 118
NOTE
Approximate discharge times are in minutes and at 77°F (25°C) with resistive load.
Specifications
28
Page 35

12.1 Product Warranty Registration

To register for warranty protection, visit the Quick Links section of our Web site at:
www.liebert.com
Click on Product Warranty Registration and complete the form.
If you have any questions, please contact us at:
US: (800) 222-5877 Outside the US: (614) 841-6755 E-Mail:
upstech@liebert.com
Specifications
29
Page 36
The Company Behind the Products
Technical Support /Service
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems–close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control–from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23290 (03/06) Rev. 4
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 25722201
Fax: 852 28029250
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power Systems Connectivity DC Power Systems
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.
Embedded Power Power Protection Integrated Cabinet Solutions
Outside Plant Precision Cooling Site Monitoring and Services
EmersonNetworkPower.com
Loading...