JB Plugger Junction Box Installation Instructions
This junction box provides a convenient location to connect all wiring required for a typical pumping station installation. The
junction box employs a receptacle to accept a 120 VAC or 230 VAC piggy-back plug and a pump plug.
The JB Plugger also features an easy-to-use terminal strip which can be used for connecting an alarm system in the junction
box.
The JB Plugger package ensures a liquid-tight seal and strain relief for the cable entering the junction box from the pumping
station.
JB PLUGGER JUNCTION BOX
NEMA 4X enclosure rated for outdoor use.
Hinged cover for convenience.
Receptacle for pump & pump switch (120V or 230V).
Custom engineered liquid-tight cord seal.
Strain relief for pump and float cords provided by cord seal.
Terminal strip for use with alarm system.
Separate alarm and pump control circuitry provided by terminal strip.
Dual safety certification for the United States and Canada.
Three-year limited warranty.
PREVENTATIVE MAINTENANCE
• Periodically inspect the product. Check that the cable has not become worn or that the housing has not been damaged so as to impair the protection of the
product. Replace the product immediately if any damage is found or suspected.
• Periodically check to see that the floats are free to move and operate the pump and alarm.
• Use only SJE-Rhombus
®
replacement parts.
SJE-RHOMBUS® THREE-YEAR LIMITED WARRANTY
SJE-RHOMBUS® warrants to the original consumer that this product
shall be free of manufacturing defects for three years after the date of
consumer purchase. During that time period and subject to the conditions set forth below, SJE-RHOMBUS® will repair or replace, for the
original consumer, any component which proves to be defective due to
defective materials or workmanship of SJE-RHOMBUS®.
THIS EXPRESS WARRANTY DOES NOT APPLY TO THE MOTOR
START KIT COMPONENT. SJE-RHOMBUS® MAKES NO WARRANTIES OF ANY TYPE WITH RESPECT TO THE MOT OR ST ART KIT.
ELECTRICAL WIRING AND SERVICING OF THIS PRODUCT MUST
BE PERFORMED BY A LICENSED ELECTRICIAN.
THIS WARRANTY DOES NOT APPL Y : (A) to damage due to lightning or
conditions beyond the control of SJE-RHOMBUS®; (B) to defects or
malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with printed instructions provided; (C) to
failures resulting from abuse, misuse, accident, or negligence; (D) to
units which are not installed in accordance with applicable local codes,
ordinances, or accepted trade practices, and (E) to units repaired and/
or modified without prior authorization from SJE-RHOMBUS®.
Some states do not allow limitations on how long an implied warranty
lasts, so the above limitation may not apply to you. Some states do
not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
TO OBTAIN WARRANTY SERVICE: The consumer shall assume all
responsibility and expense for removal, reinstallation, and freight. Any
item to be repaired or replaced under this warranty must be returned
to SJE-RHOMBUS®, or such place as designated by SJE-RHOMBUS®.
ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS
ARE LIMITED TO THE DURA TION OF THIS WRITTEN WARRANTY.
SJE-RHOMBUS® SHALL NOT, IN ANY MANNER, BE LIABLE FOR
ANY INCIDENT AL OR CONSEQUENTIAL DAMAGES AS A RESULT
OF A BREACH OF THIS WRITTEN WARRANTY OR ANY IMPLIED
WARRANTY.
INSTALL INSTRUCTIONS
111
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this
product. A qualified service person must install and
service this product according to applicable electrical
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids.
Do not install in hazardous locations as defined by
National Electrical Code, ANSI/NFPA 70.
and plumbing codes.
Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged
or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric Code,
ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.
For detailed specifications on this product, or for the complete line of SJE-Rhombus
panel, alarm, and switch products, visit our web-site at www.sjerhombus.com.
INSTALLING THE JB PLUGGER JUNCTION BOX
1. Determine where the junction box will
be mounted on the riser. Mount the
junction box so the base of the enclosure will be at grade once backfilled as shown in Figure A.
NOTE: Bottom mounting to the 3/4”
terminal adapter may be preferred
in some instances as shown in
Figure B.
2. Access the riser by providing a 2 3/8”
access hole through the riser.
3. Place the 6” threaded conduit into the
terminal adapter that is already
installed in the junction box. Slip one
PVC washer over the conduit and
slide the conduit through the riser
wall as shown in Figure C.
4. After installation through the riser, slip
the 1/2” gasket and the second PVC
washer over the conduit. Determine if
the threads provided will be adequate
to tighten the assembly to the riser. If
threading is not adequate, remove the
assembly and shorten the conduit
until threading is adequate as shown
in Figure C. NOTE: The 1/2” gasket
should compress approximately
1/4” when lock nut is tightened.
5. Repeat steps 3 and 4 until desired
length is achieved. With PVC solvent,
weld the conduit into the terminal
adapter.
6. Mount the 3/4” terminal adapter to the
bottom of the junction box with the Oring and lock nut provided. A 1 1/16”
hole should be provided for the
adapter.
7. Mount the assembly through the riser
as described in steps 3 and 4. Using
the 2” lock nut, compress the gasket
and riser to secure the junction box.
8. Remove the backplate assembly from
the enclosure. Bring the wiring for the
pump power and alarm junction through
the 3/4” terminal adapter. Connect the
conductors for the pump to the terminal
block; connect N (neutral) to position 1,
and L1 (line) to position 2. Connect L2
to position 1 for 230 VAC installations.
NOTE: Overload protection, branch
circuit protection and main
disconnect provided by others.
Connect the conductors for the alarm
circuit to positions 3 and 4 as shown in
Figures C and D. Place the backplate
assembly back into the enclosure.
NOTE: If an alarm system is not
used, plug the third open position
in the cord seal with the PVC plug
provided.
9. Pass the piggy-back plug, pump plug
and alarm float cables through the 2”
conduit.
10. With the three position cord seal, route
the three cables through the seal,
leaving approximately 8” of cable to
work with. Insert the cord seal into the
panel terminal adapter and tighten the
hex nut until adequate strain relief is
achieved.
11. Gather all ground wires, including
grounding conductor on the cord seal,
and washer. Route and secure to
ground terminal as shown in Figures C
and D.
®
12. Connect the conductors from the
alarm float switch to positions 3 and 4.
Coil remaining cable into the junction
box as shown in Figures C and D.
13. Seal the 3/4” terminal adapter with a
conduit sealing compound.
14. Plug the piggy-back plug and pump
plug into the receptacle as shown in
Figure D.
15. Secure the junction box cover using
the two preinstalled screws.
16. Turn on power.
17. Check the installation by manually
tipping the floats on the pump and then
the alarm float.
18. Test the unit periodically to insure
proper operation.
Figure C
torque to
45 in-lbs
ground
pump
power
pump
float
switch
receptacle
terminal
adapter
riser wall
lock nut
1 2 3 4
N L1
cord
seal
torque to
7 in-lbs
to alarm
panel
alarm
float
PVC washer
gasket
PVC
washer
Figure D
pump plug
Figure A
riser
gasket
PVC washer
pump &
switch
cables
lock
nut
1-888-DIAL-SJE (1-888-342-5753)
INSTALL INSTRUCTIONS
112
PVC washer
terminal
adapter
22650 County Highway 6
JB Plugger
grade
level
3/4” terminal
adapter
conduit for electrical
(not included)
Figure B
JB
3”
3/4” adapter location
Phone: 218-847-1317 Fax: 218-847-4617
2 1/16”
conduit for
grade
level
electrical
(not included)
LB conduit box
(not included)
spacer for lip
on riser lid
(not included)
P.O. Box 1708 Detroit Lakes, Minnesota 56502 USA
Plugger
riser
pump &
switch cables
cable
coiling
detail
to alarm
panel
alarm float
switch
piggyback
plug
E-mail: sje@sjerhombus.com
©SJE-Rhombus Printed in USA 10/07