Liberty Pumps IP User Manual

Intelligent Panel Series
Installation Instructions and Operation/Troubleshooting Manual
This control panel must be installed and serviced by a
the sump or tank to the control panel must be sealed with conduit sealant to prevent moisture or gases from entering the panel. NEMA 4X enclosures are for indoor or outdoor use, primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water and hose-directed water. Cable connectors must be
liquid-tight in NEMA 4X enclosures.
The Level Sensor is suitable for use in sewage applications.
Do NOT use in potable water.
Installation
Intelligent Panel Series control panels are designed to control pump(s). The controller records pump status, number of cycles, elapsed run time, alarm counts, and signal error counts.
Mounting the Control Panel
Note: The control panel should not be mounted in a location that may be subject to submersion.
Warranty void if panel is modifi ed.
Call factory with servicing questions:
1-800-543-2550
7000 Apple Tree Avenue
Bergen, New York 14416 USA
Phone: 1-800-543-2550
www.libertypumps.com
©SJE-Rhombus
Printed in USA
1031286D • Rev 06/12
7281000A
1. Determine mounting location for panel. If distance exceeds the length of either the sensor or fl oat cables or the pump power cables, splicing will be required. Note: For splicing Level Sensor cord, use only shielded cable. Splice conductors as well as shielding. Maximum total cable length is 100 feet. For outdoor or wet installation, we recommend the use of an SJE-Rhombus liquid-tight junction box with liquid-tight connectors to make required connections. You must use conduit sealant to prevent moisture
or gases from entering the panel.
2. Mount control panel with mounting devices furnished.
3. Determine conduit entrance locations on control panel. Check local
codes and schematic for the number of power circuits required.
(Level Sensor cable requires separate conduit from power and pump cables.)
Note: Be sure the proper power supply voltage, amperage, and phase
meet the requirements of the pump motor(s) being installed. If in doubt, see the pump identifi cation plate for voltage/phase requirements.
4. Drill proper size holes for type of connectors being used.
Note: If using conduit, be sure that it is of adequate size to pull the
pump cable(s) through.
5. Attach cable connectors and/or conduit connectors to control panel.
FOR INST ALLATION REQUIRING A SPLICE, FOLLOW STEPS 6-10;
FOR INST ALLATION WITHOUT A SPLICE, GO TO STEP 11.
6. Determine location for mounting junction box according to local code requirements. Do not mount the junction box inside the sump or basin.
®
Installation Instructions
7. Mount junction box to proper support.
8. Run conduit to junction box. Drill proper size holes for the type of conduit used.
9. Identify and label each wire before pulling through conduit into control panel and junction box. Make wire
splice connections at junction box.
10. Firmly tighten all ttings on junction box.
11. Set motor protective switches: a) set the dials to match motor full load amps. b) turn dial on motor protective switch to the ON position.
NOTE: Resetting the dial with power applied to the motor protective switch could start the motor.
12. If a junction box is not required, pull cables through conduit into control panel.
13. Connect pump wires per wiring diagram or schematic, and sensor or oat wires to the proper terminals as
shown on the schematic.
14. Connect pump, control, and alarm incoming power conductors to proper position on terminals. See schematic for terminal connections.
VERIFY CORRECT OPERATION OF CONTROL PANEL AFTER INSTALLATION IS COMPLETE.
Installation of Level Sensor and Floats
CAUTION: If control switch cables are not wired and mounted in the correct order, the pump system will not function properly. Sensor and fl oat cables need to run in separate conduit from pump and power lines.
WARNING: Turn off all power before installing pump wires in pump chamber. Failure to do so could result in serious or fatal electrical shock.
NOTE: The Level Sensor operates between 0 and 39.9 inches of water pressure. The Level Sensor reads 0 inches at the approximate point shown in Figure 2. As the liquid level rises, the IFS display shows depth of liquid from the zero point. The minimum set point for the stop or redundant off level is 3 inches (measured from 0) see Figure 2.
The maximum set point allowed is 39.9 inches (measured from 0). Operating temperature range is 32ºF (0ºC) to 120ºF (50ºC).
1. Determine the nominal operating levels for the con guration, as illustrated in Figure 3 or 4.
2. Position Level Sensor at appropriate location on pipe and secure sensor and vent as shown in Figure 2 using
hose clamps.
WARNING: Do not support the Level sensor by the cable. Position the sensor in the tank so that nothing is
pushing in the diaphragm.
3. Position vent so it is above the water level and stow excess vent tube as shown in Figure 2.
WARNING: Do NOT kink or place black tubing under hose clamp. Doing so will cause sensor to fail.
4. If optional high water or redundant off fl oats are used, position and secure as shown in Figures 1, 3 or 4. Redundant off fl oat should be located to activate at approximately the zero point for the Level Sensor per
Figure 3 or 4.
NOTE: Liberty Pumps, Inc. recommends using the optional high water alarm oat for added protection against
ooding.
5. Tighten all hose clamps using a screw driver. Over tightening may result in damage to the plastic parts.
NOTE: All hose clamp components are made of 18-8 stainless steel material. See your Liberty Pumps, Inc.
supplier for replacement parts.
6. Functionally test the system by fi lling the tank and witnessing proper operation.
7281000A
-2-
Loading...
+ 4 hidden pages