LG Chem RESU7H StorEdge, RESU10H StorEdge Installation Manual

1
StorEdge™ Inverter Wiring Guide & On Site Checklist for Europe, APAC, South Africa
This document is a battery wiring guide and contains an on-site checklist with steps for post-installation verification of a StorEdge system for the following batteries:
LG Chem RESU7H/RESU10H
For more details, please refer to the StorEdge Installation Guide supplied with the StorEdge Inverter. For additional assistance contact SolarEdge Support (see page 8).
WARNING!
For LG Chem RESU7H/RESU10H batteries:
Before wiring the system, make sure that the battery is powered off, using both of the following switches: * Auxiliary power supply switch * Circuit breaker switch
Figure 1: LG Chem Auxiliary Power Switch and Circuit Breaker Switches
StorEdge Inverter Wiring and On Site Checklist
2
Wiring Types and Connectors
To connect the battery to the StorEdge Inverter, use the following wiring types and connectors:
Recommended Cable Type (min-max cross section)
SolarEdge Connector
LG Chem RESU7H/RESU10H Battery
Connector
DC: 6 mm2 (2.5-6 mm2), 600V insulated
BAT DC +
DC +
BAT DC -
DC -
Ground
Control and monitoring: 5-wire shielded twisted pair cable, 0.2 mm2 (0.2-1.5 mm2), 600V insulated.
CAT5 600V insulated can also be used.
En (enable)
ENABLE_H
V+
Not connected
B- (RS485)
RS485_L
A+ (RS485)
RS485_H
G (RS485) or Thermal (depending on inverter type)
EN_G
Wiring Diagrams – Connecting Batteries to the StorEdge Inverter
The diagrams on the following pages illustrate the connection of batteries to the StorEdge system. The following table will help you find the appropriate wiring diagram for your system configuration. Pay attention to whether the battery DIP switch setup on the communication unit main board has 2 or 3 switches.
Battery Type
Connected to
Wiring Diagram
DIP Switches
LG Chem RESU7H/RESU10H
StorEdge Inverter with 2 DIP Switches
See Figure 2 on page 3
StorEdge Inverter with 3 DIP Switches
See Figure 3 on page 3
StorEdge Inverter Wiring and On Site Checklist
3
Connecting the LG Chem RESU7H/RESU10H to a StorEdge Inverter with Two DIP Switches and SolarEdge Meter
0.2 mm² 300VG <> G
StorEdge Inverter SolarEdge Modbus Meter
B- <> B- and A+ <> A+ on the same twisted pair
RS485_H <> A+ and RS485_L <> B- on the same twisted pair
ENABLE_H <> En
EN_GND <> Thermal
0.2 mm² 600V
LG Chem Battery
2 DIP
Switches
RS485-terminated
B A G
Figure 2: Connecting the LG Chem RESU7H/RESU10H to a StorEdge Inverter with Two DIP Switches and SolarEdge Meter
Connecting the LG Chem RESU7H/RESU10 H to a StorEdge Inverter with Three DIP Switches and SolarEdge Meter
0.2 mm² 300VG <> G
StorEdge Inverter SolarEdge Modbus Meter
B- <> B- and A+ <> A+ on the same twisted pairRS485_H <> A+ and RS485_L <> B- on the same twisted pair
ENABLE_H <> En
EN_GND <> G
0.2 mm² 600V
LG Chem Battery
3 DIP
Switches
RS485-terminated
B A G
Figure 3: Connecting the LG Chem RESU7H/RESU10H to a StorEdge Inverter with Three DIP Switches and SolarEdge Meter