LG S18AN, AS-W126RGH1, AS-W186TGH1 Schematic

Page 1
LG
Room
Air Conditioner
SERVICE MANUAL
LG
MODELS: AS-W096QGG1
AS-W126RGH1 AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Page 2
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions .....................................................................................................................................................9
Symbols Used in this Manual.....................................................................................................................9
Indoor Unit..................................................................................................................................................9
Outdoor Unit.............................................................................................................................................10
Product Specifications ................................................................................................................................12
Installation.....................................................................................................................................................14
Select the Best Location .........................................................................................................................14
Piping Length and Elevation.....................................................................................................................14
How to Fix Installation Plate.....................................................................................................................15
Drill a Hole in the Wall..............................................................................................................................15
Installation Instructions of Telephone Control(Optional)...........................................................................15
Flaring Work.............................................................................................................................................16
Connection of Piping Indoor.....................................................................................................................17
Connection of the Pipes-Outdoor.............................................................................................................20
Connect the Cable to the Indoor Unit.......................................................................................................21
Connect the Cable to the Outdoor Unit....................................................................................................22
Checking the Drainage.............................................................................................................................23
Form the Piping........................................................................................................................................23
Air Purging ...............................................................................................................................................24
Air Purging with Vacuum Pump................................................................................................................24
Test Running............................................................................................................................................26
Functions ......................................................................................................................................................27
Operation ......................................................................................................................................................30
Disassembly..................................................................................................................................................45
Indoor Unit................................................................................................................................................45
Schematic Diagram.......................................................................................................................................48
Electric Control device..............................................................................................................................48
Wiring Diagram.........................................................................................................................................51
Components Location ..............................................................................................................................53
Troubleshooting Guide.................................................................................................................................57
Refrigeration Cycle Diagram....................................................................................................................57
Pipe Length and the Elevation .................................................................................................................58
2-way, 3-way Valve...................................................................................................................................59
Cycle Parts...............................................................................................................................................66
Self-diagnosis Function............................................................................................................................67
Electronic Parts........................................................................................................................................69
Exploded View ..............................................................................................................................................80
Indoor Unit................................................................................................................................................80
Outdoor Unit.............................................................................................................................................81
Replacement Parts List ................................................................................................................................82
Indoor.......................................................................................................................................................82
Outdoor ....................................................................................................................................................83
Page 3
Service Manual 3
LG Model Name
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China U: China R410A
X: Mexico K: Turkey R22
V: Vietnam
E: Turkey R410A
S: Out Sourcing
H: Thailand 2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O
N: AC Inverter H/P
Q: DC Inverter C/O
W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP → SP Chassi
s
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model Development Serial No.
* ARTCOOL COLOR
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry Contact W Wired Remocon 8
R Mirror W White B Blue D Wood M Metal C Cherry
N Walnut A Gogh S Sisley Q Quran K Mecca
CHASSIS Look
D K L G M N D P
Division Panel Type(Deluxe) Fighting 'Look' (LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
S4/S5
S6 SQ SR ST
2003~
Page 4
4 Room Air Conditioner
12 -345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing
H: Thailand 2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump
X: C/O + E/Heater
Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h 6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase
5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase
6: 220-240V/50Hz E: 265V, 60Hz
7: 110V, 50/60Hz F: 200V, 50/60Hz
8: 380-415V/50Hz
9: 380-415V/60Hz 7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis 8 Look A~Z Look,
Color (Artcool Model) 9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
2003
Page 5
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire or electric
shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Installation
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion or injury.
Be cautious when unpacking and installing the product.
• Shape edges could cause injury. Be especially careful of the sharp edges.
Page 6
6 Room Air Conditioner
Safety Precautions
For installation, always con­tact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condi­tioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated break­er or fuse.
• There is risk of fire or electric shock.
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
• There is risk of fire or electric shock.
Use a dedicated outlet for this appliance.
• There is risk of fire or electric shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electric shock.
Page 7
Service Manual 7
Safety Precautions
Installation
Unplug the unit if strange sounds odors, or smoke comes from it.
• There is risk of fire, failure of the product, and/or electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product.
Be cautious that water could not enter the product.
• There is risk of fire, electrical shock or product damage.
Do not place a heater or other appliances near the power cable.
• There is risk of fire, failure of the product, and/or electric shock.
Do not allow water to run into electric part.
• There is risk of fire, failure of the product, and/or electric shock.
Do not store of use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Always check for gas(refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leak­age.
Thinner
Wax
90˚
Page 8
Safety Precautions
8 Room Air Conditioner
Operation
Use two or more people to lift and transport the air condi­tioner
Avoid personal injury.
Use a soft cloth to clean. Do not use harsh detergents, sol­vents, etc.
There is risk of fire, electric shock or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor unit)
There is risk of personal injury and failure of product.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
Page 9
Service Manual 9
Dimensions
Dimensions
Installation plate
D
H
W
W mm 824 900 1090
H mm 260 285 314 D mm 155 156 172
Model
Dimension
AS-W096QGG1 AS-W126RGH1
AS-W186TGH1 AS-W246TGH1
Indoor Unit
This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the
air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Page 10
10 Room Air Conditioner
Outdoor Unit
Dimensions
W
L2
L3
L1
D
H
L4
L5
Gas side (3-way valve)
Liquid side (2-way valve)
MODEL
DIM unit
W mm 770
H mm 540
D mm 245 L1 mm 285 L2 mm 65 L3 mm 518 L4 mm 10 L5 mm 100
AS-W096QGG1 AS-W126RGH1
Page 11
Service Manual 11
Dimensions
Outdoor Unit
W
L7 L6 L8 L9
D
L1
L2
L3
L10
L4L5
H
Gas side
Liquid side
AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
W mm 870
H mm 655
D mm 320 L1 mm 370 L2 mm 340 L3 mm 25 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54
L10 mm 74.5
MODEL
DIM
Page 12
12 Room Air Conditioner
Product Specifications
Table-1
Model Name
Item Unit
W
MIN kcal/h.(W)
Btu/h.
W
Cooling Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
W
MIN kcal/h.(W)
Btu/h.
W
Heating Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
IN:20°C,Out: -10°C(Heater ON)
Btu/h.
IN:20°C,Out: -10°C(Heater OFF)
Btu/h.
Power Input Cooling W
Heating W Heating(-10°C,Heater ON)
W
Heating(-10°C,Heater OFF)
W
Running Current Cooling A
Heating A Heating(-10°C,Heater ON)
A
Heating(-10°C,Heater OFF)
A
Starting Current Cooling A
Heating A
EER Cooling W/W
Btu/h.W COP Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal l/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge g Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in)
Indoor mm Dimension inch (W*H*D) Outdoor mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
AS-W096QGG1 AS-W126RGH1 AS-W186TGH1 AS-W246TGH1
Product Specifications
1,582 2,110 1,758 4,249 1,361 1,814 1,512 3,654 5,400 7,200 6,000 14,500 2,640 3,520 5,280 7,032 2,270 3,027 4,540 6,048 9,010 12,014 18,016 24,000 2,901 3,868 5,801 7,735 2,495 3,326 4,990 6,653 9,900 13,200 19,800 26,400 1,978 2,532 1,406 3,604 1,701 2,177 1,210 3,100 6,750 8,640 4,800 12,300 3,170 3,960 6,070 7,735 2,726 3,405 5,219 6,653
10,819 13,512 20,711 26,400
3,481 4,351 6,651 8,497 2,994 3,742 5,720 7,308
11,880 14,850 22,700 29,000
----
----
950 1,200 1,630 2,480
1,150 1,300 1,900 2,730
----
----
4.3 5.4 7.5 11.5
5.1 5.7 8.6 12.5
----
----
4.3 5.4 7.5 11.5
5.1 5.7 8.6 12.5
2.78 2.93 3.24 2.84
9.48 10.01 11.06 9.68
2.76 3.05 3.19 2.83
1,220-240,50 1,220-240,50 1,220-240,50 1,220-240,50
97 97 97 97
7.2(254) 8.70(307) 13.0(459) 16.0(565) 26(918) 26(918) 42(1483) 45(1589)
1.4(2.94) 1.5(3.2) 2.12(4.48) 2.90(6.13) 35 40 42 47 32 37 39 43 29 31 36 39 48 48 55 58
610 810 1180 1500 16:3*1.0 16:3*1.5 12:3*2.5 12:3*2.5 16:4*1.0 16:4*1.5 12:4*2.5 12:4*2.5
6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
7.5(295) 7.5(295) 7.5(295) 7.5(295)
21.5,16.0(0.85,0.63) 21.5,16.0(0.85,0.63) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 824*260*155 900*285*156 1090*314*172 1090*314*172
32.4*10.2*6.1 35.1*11.1*6.2 42.9*12.4*6.8 42.9*12.4*6.8 770*540*245 770*540*245 870*655*320 870*655*320
30.3*21.3*9.6 30.3*21.3*9.6 34.3*25.8*12.6 34.3*25.8*12.6
7.0(15.4) 9.5(20.9) 12(26.5) 12(26.5) 34(74.8) 38(83.8) 60(132.3) 65(143.3)
Page 13
Service Manual 13
Product Specifications
Table-2
Model Name
Item Unit
W
MIN kcal/h.(W)
Btu/h.
W
Cooling Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
W
MIN kcal/h.(W)
Btu/h.
W
Heating Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
IN:20°C,Out: -10°C(Heater ON)
Btu/h.
IN:20°C,Out: -10°C(Heater OFF)
Btu/h.
Power Input Cooling W
Heating W Heating(-10°C,Heater ON)
W
Heating(-10°C,Heater OFF)
W
Running Current Cooling A
Heating A Heating(-10°C,Heater ON)
A
Heating(-10°C,Heater OFF)
A
Starting Current Cooling A
Heating A
EER Cooling W/W
Btu/h.W COP Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal l/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge g Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in)
Indoor mm Dimension inch (W*H*D) Outdoor mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
AS-W246TLG1
4249 3654
14500
7032 6048
24000
7735 6653
26400
3604 3100
12300
7735 6653
26400
8497 7308
29000
-
­2320 2400
-
-
11.5
12.5
-
-
11.5
12.5
2.61
10.34
3.22
1,220-240,50
97
16.0(565) 42(1589)
2.9 45
­37 56
1500 12:3*2.5 12:4*2.5
9.52(3/8)
15.88(5/8)
7.5(295)
21.5,16(0.85,0.63) 1090*314*172
42.9*12.4*6.8 870*655*320
34.3*25.8*12.6 12(26.5)
60(132.3)
Page 14
14 Room Air Conditioner
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in
front of the unit.
Make sure that condensation drainage can be con­veniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnec­essary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than "A"
More than B
More than 2.3m
More than "B"
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
CAUTION: Install the indoor unit on the wall
where the height from the floors more than 2.3 meters.
CAUTION:
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
7K~28K 10 5
30K~38K 30 12
Pipe Size
Capacit
y
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Page 15
Service Manual 15
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the
hole which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Answering telephone / Normal telephone
(Not packed in the box)
Adaptor
(Not packed in
the box)
Telephone Control
Cord Wire
(Packed in the box)
Phone Conductor
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
Ø70mm
Left rear piping
Right rear piping
CE A
B
D
Installation plateInstallation plate
ABCD
SJ 90 20 80 20
SL, SK 45 40 80 20
SQ 75 12 80 12 SR 0 40 20 40 ST 105 0 210 0
CHASSIS
(Grade)
Distance (mm)
How to Fix Installation Plate Drill a Hole in the Wall
Installation Instructions of Telephone Control(Optional)
ABCDE SM 180 115 - 115 50 SN 180 115 195 115 -
CHASSIS
(Grade)
Distance (mm)
Page 16
16 Room Air Conditioner
Installation
Flaring Work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Carry out flaring work using flaring tool as shown below.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared
section and re-flare it.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3.8 0~0.5
Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3
Outside diameter A
Page 17
Service Manual 17
Installation
Connection of Piping Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction of rear right.
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insula­tion material* so that dripping from "sweating"(condensation) will not dam­age furniture or floors.
*Foamed polyethylene or equivalent is recom-
mended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are prop­erly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tight­en the flare nut by hand.
NOTICE
CAUTION:
When install, make sure that the remaining
parts must be removed clearly so as not to dam­age the piping and drain hose, especially power cord and connecting cable.
Tubing holder
Connecting cable
Loop
Gas side piping
Liquid side piping
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing Flare nut Pipes
Drain hose
Page 18
18 Room Air Conditioner
Installation
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
5. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip­ing housing section with vinyl tape.
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
For left rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3.8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Drain hose
Connecting
cable
Drain pipe
Connecting cable
Page 19
Service Manual 19
Installation
3. Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connec-
tion later.
4. Tape the drain hose and the connecting cable.
Connecting cable
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of the installation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
6. Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tight-
en the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
7. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip­ing housing section with vinyl tape.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3.8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
Page 20
20 Room Air Conditioner
Installation
Bundle the piping and drain hose together by wrapping them with cloth tape over the range with­in which they fit into the rear piping housing sec­tion.
8. Reroute the pipings and the drain hose across the back of the chassis.
9. Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
10. Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
1. Align the center of the pipings and sufficiently tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on the wrench.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Tubing holder
Drain hose
Connecting
cable
Connection of the Pipes-Outdoor
Page 21
Service Manual 21
Installation
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
CAUTION
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
7k, 9k 12k 18k
1.0 1.5 2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
7k, 9k 12k 18k
1.0 1.5 2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
(mm
2
)
CAUTION:
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the wiring diagram.
When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
Connect the Cable to the Indoor Unit.
CAUTION:
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Page 22
22 Room Air Conditioner
Installation
1. Remove the control cover from the unit by loos­ening the screw. Connect the wires to the terminals on the control board individually.
2. Secure the cable onto the control board with the cord clamp.
3. Refix the control cover to the original position with the screw.
4. Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
CAUTION: After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 20))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
7k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Connect the Cable to the Outdoor Unit
Page 23
Service Manual 23
Installation
Checking the Drainage Form the Piping
1. To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the
position(horizontally) by hand.
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille toward you and lift it off.
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out the drain exit.
3. Drain piping
The drain hose should point downward for easy
drain flow.
Do not make drain piping.
1. Form the piping by wrapping the connecting portion of the indoor unit with insulation materi­al and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose,
the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable
from down to up.
Secure the tapped piping along the exterior wall
using saddle or equivalent.
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down
to up.
Secure the taped piping along the exterior wall.
Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equiva-
lent.
Pull the right and the left side.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Page 24
24 Room Air Conditioner
Installation
CAUTION:
To avoid nitrogen entering the
refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and
block capillary tubing.
Water may lead to corrosion of parts in the refrig­eration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
1. Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylin­der valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo
Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
CAUTION:
Be sure to use a manifold valve
for air purging. If it is not available, use a stop
valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
Air Purging
Air Purging with Vacuum Pump
Page 25
Service Manual 25
Installation
3. Evacuation
Connect the charge hose end described in the pre­ceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tub­ing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacu­um pump.
4. Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter­clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way
valves. (2) Remove the service-port cap from the 3-way valve. (3) To open the 2-way valve turn the valve stem coun-
terclockwise approximately 90°, wait for about 2~3
sec, and close it. (4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connec-
tions by a soft brush to check for leakage of the
connecting points of the piping. (5) If bubbles come out, the pipes have leakage.
Soap water method
Required time for evacuation when 30 gal/h vacuum pump is
used
10 min. or more 15 min. or more
If tubing length is less than 10m
(33 ft)
if tubing length is longer than 10m
(33 ft)
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Indoor unit
Pressure gauge
Open
Outdoor unit
Manifold valve
Lo Hi
Close
Vacuum pump
Page 26
26 Room Air Conditioner
Installation
Test Running
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote control
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Remove the batteries from the remote control if the system is not going to be used for a long time.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is con­veyed to the hose, secure the unit with an anti­vibration bushing.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake tempera­ture and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pres­sure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
NOTICE
NOTICE
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Page 27
Service Manual 27
Functions
Room temperature sensor. (Thermistor)
Pipe temperature sensor. (Thermistor)
Maintain the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 sec at the starting.
Restarting is for approx. 2 minutes.
Super High, High, Med, Low
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Preheat Mode (for Heating Model)
--- Lights up in Plasma Air Clean Mode
Intermittent Operation of fan at low speed or off.
The fan is switched to low(Cooling), low(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting the Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops during defrosting.
The indoor fan stops until the evaporator pipe temperature will be reached at 34°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
Heater (Optional)
The function will be operated while in any operation mode with selecting the function.
The function is to be stopped while it is operating with selecting the function.
PLASMA
AUTO CLEAN(Optional)
Horizontal airflow Direction Control(Optional)
Energy-Saving control(Optional)
Auto Changeover
Functions
PLASMA
Page 28
28 Room Air Conditioner
Functions
If power is on, it will operate to chage capacitor on controller and power relay will operate after about 2~5sec.
If outdoor temp. is below 0°C, preheater is operating for 1~5min.
At the initial, It will be operated compressor after 1min. for preheating.
The active power filter is designed to correct power factor(cos θ) and to regulate DC link voltage.
It will be operated PFC circuit when the compressor freq. is over 30Hz and wattage is over 450 watt.
The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp.,
heat-sink temp., target freq., owing to CT.
It will be changed the drive freq. of comp. according to temp. of indoor and outdoor.
It will be changed the drive voltage of comp. according to operating frequency.
It is only operated in the heating operation mode except defrosting operation.
High speed
- Although fan motor speed is middle, it will change high speed in case of below AC193V, over 45°C of outdoor temp., and over fc, fh of comp. Freq.
Middle speed
- Nomal mode
Low speed
- Although fan motor speed is middle, it will change Low speed in case of over AC 270V, over 21°C (Heating Mode) of outdoor temp. below 24°C (Cooling Mode) of outdoor temp.
It controls optimum flow of refrigerant in system.
When the temp. of power module increases to 85°C, controller decreases Freq. of Comp.
Outdoor Unit
Power relay control
Stand by control at low temp.
Active power filter control(PSC)
Comp. Freq. control
Overheatng. Protection(Power module)
Freq. speed control(up/down speed)
V/F control
Total current control (over current protection)
DC peak current control
4 way valve control
Outdoor fan motor control
Discharge pipe temp. control
Low ambient
EEV Control
Page 29
Service Manual 29
Functions
Healthy Dehumidification Operation Mode.
( )
Remote Control
Operation ON/OFF
Reset
Operation Mode Selection
Temperature Setting
Timer Selection
Timer Setting
JET COOL
Timer Cancel
Sleep Operation
Airflow Direction Control
(Cooling
model only)
(Heating
model only)
TEMPERATURE
LOW HIGH
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Horizontal Airflow Direction Control Button(Optional)
Room, Temperature Display
Setting the Time or Timer
PLASMA(Optional)
ON OFF
SET
PLASMA
CANCEL
Heater
(Optional)
(Optional)
Auto Clean
Fan Speed Selection
(Low) (Med) (High) (CHAOS)
Power Save Cooling Button
AUTO CLEAN
: (High:39°C Low:11°C)
: OFF, ON, OFF ON
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
Cooling
Down to 18°C Up to 30°C
Heating
Down to 16°C Up to 30°C
Page 30
30 Room Air Conditioner
Operation
LED display of indoor unit
Operation
OEM Brand
LG Brand/OEM Brand
Operation Indicator
Sleep Timer Indicator
PLASMA Indicator
Timer Indicator
Preheat Indicator
Setting Temp.
On while in appliance operation, off while in appliance pause.
Blinking(3sec off/0.5sec on) according to Error Code as long as the system malfunctions.
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause.
On while in plasma mode, off when plasma mode cancel.
On while in timer mode(on/off), off when timer mode is completed or canceled.
Off except when hot start during heating mode operation or while in defrost control.
Cooling/heating/dehumidification mode : setting temperature from remote control
Fuzzy operation mode : fuzzy key data(5sec on) AI
Operation Indicator
Power Saving Indicator
Timer Indicator
Preheat Indicator
On while in appliance operation, off while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off/0.5 sec on)
On while in power saving cold mode, off when power saving cold cancel.
On while in timer mode(on/off) and sleep timer mode (on), off when timer mode is
completed or canceled.
Off except when hot start during heating mode operation or while in defrost control.
PLASMA
Operation
indicator
Shape of
display
Cooling
heating
dehumidifi-
cation
Setting
temp.
Standard Too hot Hot Cold Too cold
A.I operation mode
Comfortable
Jet
(Cool, Heat)
Energy save
in cooling
mode
Test
operation
Page 31
Service Manual 31
Operation
How to operate the power display (LG Brand/OEM Brand)
It must be displayed the power level that will be operating frequency of compressor.
It indicates power levels that compressor operating frequency is controlled to depend on indoor and outdoor
conditions.
It is displayed as below.
Heat mode operation
- Power level 1: below Step 2 of COMP. operating frequency
- Power level 2: below Step 4 of COMP. operating frequency
- Power level 3: Equal Step 5 of COMP. operating frequency
- Power level 4: below Step 7 of COMP. operating frequency
Power Level 1
Power Level 2
Power Level 3
Power Level 4
Power Level 1
Power Level 2
Power Level 3
Power Level 4
PLASMA
Page 32
32 Room Air Conditioner
Operation
If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in cooling cycle operation mode, compressor, outdoor fan are turned off.
When indoor pipe temp. is 7°C or higher after 2 min pause of compressor compressor, outdoor fan is turned on according to the condition of the room temperature.
Control condition : The system operates standard operation without this condition as follows. Setting temperature <25°C Indoor fan speed low speed Outdoor temperature < 30°C
Control method
In operation for 5~20 minutes in , , conditions, return to the previous COMP STEP after operation for 5~40 minutes at the COMP STEP 3.
Comp. free
Comp. Step 4 Comp. Step 2
Comp. off
0˚C
3˚C
6˚C
7˚C
Indoor pipe temp.
Protection of the evaporator pipe from frosting
Protection of the indoor fan from droplet formation (Enclosure sweat and condensed disposal test)
Page 33
Service Manual 33
Operation
Cooling mode operation
Operating frequency of compressor depend on the difference of the temperature. (= intake air Temp.- Compressor off Temp.
Compressor off temp.= setting temp. -0.5°C
on temp. = setting temp. +0.5°C
If compressor operates at some operating frequency, the operating frequency of compressor cannot be changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp.
-
0.5°C and setting temp.
-
1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp.
-
1.0°C.
Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences Comp. Operating frequency
over 3.0°C Step 7 over 2.5°C Step 6
2.0~2.49°C Step 5
1.5~1.99°C Step 4
1.0~1.49°C Step 3
0.5~0.99°C Step 2
0.0~0.49°C Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
AS-W096QGG1 35 40 47 57 62 65 69
AS-W126RGH1 35 40 53 60 70 75 80 AS-W186TGH1 20 32 58 64 72 80 90
AS-W246TGH1/TLG1 35 48 53 57 61 64 67
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5(Fc) Step 6 Step 7
Page 34
34 Room Air Conditioner
Operation
Healthy Dehumidification mode operation
When the dehumidification operation is set by the remote controller the intake air temperature is detected and the setting temp. is automatically set according to the intake air temperature.
When intake air temp reaches above the temp of setting +1.0°C, condition of compressor same as cooling mode operation.
When intake air temperature reaches bolow the temp of setting –1.0°C, compressor operate step1~step3 and indoor fan speed repeatly operate low or stop.
Intake air Temp.
32°C intake air temp.
26°C intake air temp. < 32°C
24°C intake air temp.< 26°C
18°C < intake air temp. < 24°C
intake air temp. ≤ 18°C
Setting Temp.
25°C 25°C
intake air temp. -1°C
intake air temp. -0.5°C
18°C
Page 35
Service Manual 35
Operation
Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 30°C
While in defrost control, between the indoor and outdoor fans are turned off.
Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 7 Step 6 Step 5 Step 4 Step 3 Step 2 Step 1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Heating mode operation
Model
AS-W096QGG1 35 43 53 64 74 77 80
AS-W126RGH1 35 43 53 64 76 78 80 AS-W186TGH1 25 38 47 65 82 87 92
AS-W246TGH1/TLG1 35 42 53 61 67 70 73
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5(Fc) Step 6 Step 7
Page 36
36 Room Air Conditioner
Operation
Fuzzy mode operation
When any of operation mode is not selected like the moment of the power on or when the unit turned off, the operation mode is selected.
When determining the operation mode, the compressor, outdoor fan are off and only the indoor fan is operat­ed for 15~20 seconds, then an operation mode is selected according to.
Basis of determining operating mode
Indoor temp.
over 24°C
21~24°C
below 21°C
Operating Mode
Cooling
Healthy Dehumidification
Heating
1. Fuzzy operation for cooling
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like cooling mode operation.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
When the Fuzzy key(=setting temp. key) is input after the initial setting temperature is selected, the Fuzzy key value and intake air temperature at that time are compared to select the setting temperature automatical­ly according to the fuzzy rule.
While in Fuzzy operation, the air flow speed of the indoor fan is automatically operated by Fuzzy logic.
at beginning
during opertion
Intake air temp.
over 26°C
18~26°C
below 18°C
18~30°C
below 18°C
over 30°C
Setting temp.
25°C
intake air temp. -0.5°C
18°C
Fuzzy rule 18°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
Page 37
Service Manual 37
Operation
2. Fuzzy operation for Heating
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like heating mode operation.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
When the Fuzzy key(=setting temp. key) is input after the initial setting temperature is selected, the Fuzzy key value and intake air temperature at that time are compared to select the setting temperature automatical­ly according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically operated by Fuzzy logic.
at beginning
during opertion
Intake Air temp.
over 20°C
below -20°C
16~30°C
below 16°C
over 30°C
Setting temp.
intake air temp. +0.5°C
20°C
Fuzzy rule 16°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
3. Fuzzy operation for dehumidification
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temperature at that time.
According to the setting temperature selected by Fuzzy rule, the operating frequency of compressor is deter­mined like dehumidefication mode operation.
at beginning
during operation
Intake Air temp.
over 26°C
18~26°C
below 18°C
18~30°C
below 18°C
over 30°C
Setting temp.
25°C
intake air temp. -0.5°C
18°C
Fuzzy rule 18°C Fuzzy rule 30°C Fuzzy rule
Fan speed
Fuzzy airflow
Page 38
38 Room Air Conditioner
Operation
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
While in cooling mode or Fuzzy operation, the Jet Heat key cannot be input. When it is input while in the Heating mode operation (dehumidification), the Jet Heat mode is operated.
In the Jet Heat mode, the indoor fan is operated super-high speed for 60 min. at Heating mode operation.
In the Jet Heat mode, the room temperature is controlled to the setting temperature, 30°C.
When the sleep timer mode input while the Jet Heat mode operation, the Jet Heat mode has the priority.
When the Jet Heat key is input, the upper/lower vane is reset to those of the initial Jet heating mode and
then operated in order that the air outflow could reach under flow.
1. Chaos swing mode
By the Chaos swing key input, the upper/lower vane automatically operates with the Chaos swing or it is fixed to the desired direction.
CLOSED
Chaos Swing On
Chaos Swing
The first path
Mode 9
Mode 8
Mode 7 Mode 6
Mode 5
Mode 4
Mode 3
Mode 2
Mode 1
OPEN
Jet cool mode operation
Jet heat mode operation
Swing mode
Page 39
Service Manual 39
Operation
1. Sleep timer operation for cooling cycle
While in cooling mode operation, 30 min. later since the start of the sleep timer, the setting temperature increase by 1°C. After another 30min. elapse, it increases by 1°C again.
2. Sleep timer operation for heating cycle
While in heating mode operation, 60 min. later since the start of the sleep timer, the setting temperature decrease by 1°C. After another 60min. elapse, it decreases by 1°C again.
Setting temp. (˚C)
1.0˚C up
1.0˚C up
Cooling ON temp. (Setting temp. +0.5˚C)
Cooling OFF temp. (Setting temp. -0.5˚C)
0.5 1 Sleep time (hr
)
When the sleep time is reached after [1,2,3,4,5,6,7hr] is input by the remote control during the operation, the operation of the appliance stops.
When the appliance is on pause, the sleep timer mode cannot be input.
Sleep timer operation
Setting temp. (°C)
Heating OFF temp. (Setting temp. +3.0°C)
Heating ON temp. (Setting temp)
1.0°C down
1.0°C down
1 2 Sleep time (hr
)
Page 40
40 Room Air Conditioner
Operation
Auto restarting operation
Forced operation
Trial Operation
When the power is restarted after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Operation mode that is kept on the memory
- State of operation ON/OFF
- Operation mode/setting temp./selected airflow speed
- Sleep timer mode/remaining time of sleep timer
- Chaos Swing
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
The operation condition is set according to the outdoor temp. and intake air temperature as follows.
The unit select before operating mode in 3 hours.
Press the Tact Switch for compulsory operation of the main body for 3 seconds in order to operate in the trial operation mode.
- Operation mode: Cold
- Indoor pan: Strong wind
- COMP frequency: Step 5
- COMP compulsorily operates for about 18 minutes irrespective of indoor temperature.
Indoor temp.
over 24°C
21~24°C
below 21°C
Setting temp.
22°C 23°C 24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Heating
Page 41
Service Manual 41
Operation
Power relay turns on 1 second later after the power is input to the outdoor unit.
Control sequence : power on PTC operating power relay on
CT1 control
If the operating current reaches I1, the operating frequency of the compressor decrease.
After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
CT2 control
If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the compressor restart again.
If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
DC Peak Current Error by a fault signal of IPM
If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6
.
DC Peak Current Error by the compressor lock
If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the Outdoor Fan Lock
If its 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is operating, the appliance turns off and display ERROR CODE 6.
Power relay control
Protection from total current control
Protection from DC Peak Current
I1
Cooling Heating Cooling Heating
Outdoor temp ≥ 38°C Outdoor temp < 38°C
I2
Model
1 AS-W096QGG1 5.5 6.5 6 7 9 3 AS-W126RGH1 6.5 7.5 7 8 10 4 AS-W186TGH1 10.5 11.5 11 12 14 5 AS-W246TGH1 13.5 14 14 14.5 15.5
Page 42
42 Room Air Conditioner
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below Fig.)
Temperature range by COMP SPEC varies by 10°C.
Operation
Portection from overheating of power module
Portection from overheating of compressor
1 AS-W096QGG1 85 95 2 AS-W126RGH1 85 95 3 AS-W186TGH1 85 95 4 AS-W246TGH1 85 95
No. MODEL T on T off
1 AS-W096QGG1 102 110 2 AS-W126RGH1 105 115 3 AS-W186TGH1 98 108 4 AS-W246TGH1 98 108
No. MODEL T on T off
T off °C
T = (T off - T on) T1 = T on + T T2 = T on + 2 * T
Heat Sink Temp.
T2 °C
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
D-Pipe T emp .
COMP Freq. Free Free
Fh min
T = (T off - T2)/2 T1 = T2 + 2 * T T3 = T2 + T
OFFFc-1 Fc-1Fc-2 Fc-2
Page 43
Service Manual 43
Operation
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
Defrosting control is available 50 minutes later since heating cycle started and the pipe temperature of out­door unit reaches below -6°C.
Setting Freq.
Operating Freq. of Comp.
4-Way
EEV Open step
Outdoor FAN
Indoor FAN
Pre-Heat LED
Deice STEP
Fh
min
Minimum Time 15s 6s 30s 10s 1 min
of Heating
Main Deice time
Fh
min
Fh
min
Step 5+
Step 6
ON
OFF
Setting Speed
ON
Hot
Start
OFF
Hot
Starting
ON
OFF
OFF
0123456
Setting
350(Option) Starting step
Setting Freq.
Setting Speed
Setting Speed
Hi Speed
Defrosting control
Page 44
44 Room Air Conditioner
Operation
Function used to perform the Self Cleaning to prevent the Unit from Fungus and Bad Odors.
Used after the Shut Down of Cooling Operation to Clean the Evaporator and keep it as fresh for the Next operation.
During Self Cleaning the Outdoor Unit is Switched off.
The function is easy to be operated as It is accessed through the Remote Controller.
Auto Cleaning
Auto Changeover
Low Ambient
Comp.
ON ON OFF
OFF Setting Step Low
Indoor Fan
ON
2) Cooling/only Model
Cool Start Cooling CYCLE
OFF
20 Sec
30 Min
Fan
ON
1) Heat/pump Model
Cool Start Cooling CYCLE
OFF
Comp.
ON ON ONOFF OFF
Indoor Fan OFF Setting Step Low Low Low
13 Min20 Sec
HeatingFan
60 Sec 120 Sec
Fan
The air conditioner changes the operation
mode automatically to keep indoor tempera­ture.
When room temperature vary over ±2°C with
respect to setting temperature, air condition­er keeps the room temperature in ±2°C with respect to setting temperature by auto change mode.
If outdoor temperature drops below certain temperature,liquid back is prevented by reducing fan speed.
It can prevent frosting of evaporator and keep cooling operation
No matter even if the outdoor temperature reaches -10°C.
You can Cool your room at your desired temperature all your around.
Freq.
- 0°C
°
Outdoor temp.
Outdoor pipe temp. 0°C outdoor fan On/Off control
°
Comp Freq.
Outdoor fan
On
On
Off
Off
Outdoor temp.:-10°C
-5
0
5
10
15
20
25
0 50 100 150 200
Time(Min.)
Temp.(°C)
Outdoor fan On/Off control
Cond . temp.
COOLING
Auto Change Mode.
Outdoor temp. Indoor temp.
Outdoor temp.
30°C
20°C
10°C
+
2°C
+
1°C
+
0.5°C
Set Temp.
-
0.5°C
-
1°C
-
2°C
HEATING
Page 45
Service Manual 45
Disassembly
Disassembly
Indoor Unit
Warning :
Disconnect the unit from power supply before making any checks. Be sure the power switch is set to OFF.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Display P.C.B Conductor
Step Motor Conductor
Earth Conductor
Motor Conductor
Sensor Conductor
Earth Conductor
Page 46
46 Room Air Conditioner
Disassembly
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Caution label
CAUTION:
When repair, do not damage
the Caution label.
Page 47
Service Manual 47
Disassembly
Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
6. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from
the self-aligning bearing.
Motor cover
Page 48
48 Room Air Conditioner
Schematic Diagram
Schematic Diagram
Electric Control Device
Indoor
Page 49
Service Manual 49
Schematic Diagram
Outdoor(AS-W096_Series, AS-W126_Series)
Page 50
50 Room Air Conditioner
Schematic Diagram
Outdoor(AS-W186_Series/AS-W246_Series)
Page 51
Service Manual 51
Schematic Diagram
Wiring Diagram
Indoor Unit AS-W096QGG1, AS-W126RGH1, AS-W186TGH1, AS-W246TGH1, AS-W246TLG1
POWER
TERMINAL ASSY
DISPLAY PWB ASSY
3854A20238W
CN­DISP1
CN­DISP2
RY-COMP
TO OUTDOOR UNIT
CN-T/BLOCK
INDOOR THERMISTOR
PIPE THERMISTOR
STEP
MOTOR
STEP
MOTOR
AC250V/T2A
CN-AC/DC
CN-AC/DC
CN-MOTOR
CN-THCN-U/DCN-L/R
CN-HVBCN-12VCN-CONT
H.V
ASM
S/W1
S/W2
AIR
CLEAN
(PLASMA)
SH-CAPA
43
MOTOR
AC PWB ASSY
DC PWB ASSY
SSR
GN (GN/YL)
OR
BK
BL(WH/Ribbed)
BL
RD
RD
BK
BK
BKBKBK BKBKBK
BK
GR
GN/YL
BR(BK/Plained)
BR
BR YL
1(L)
2(N)
34
BK
BK
WH
PTC HEATER
PTC CONROL PWB ASSY
CN-PTC
4
3
CN-PTC
Page 52
52 Room Air Conditioner
Schematic Diagram
Outdoor Unit AS-W096QGG1, AS-W126RGH1
AS-W186TGH1, AS-W246TGH1, AS-W246TLG1
3854A20310C
WCN-NOISE
20A/AC 250V
BR
3(BK)
WCN-NOISE
2(BK)
BL
BK
OR
YL
BK BK
RD BL YL
REVERSING VALVE
REACTOR
HEAT SINK TH.
OUTDOOR TH.
PIPE TH. COMP TH.
RD
GN/YL
CN­FAN1
WCN­CAP1
WCN­CAP2
RY-H
CN-COIL1 CN-COIL2
CN-U
+++
CN-V CN-W
CN-TH1 CN-D-PIPE
Motor
SPM2
COMP
TERMINAL BLOCK
TO INDOOR UNIT
Outdoor PWB ASSY
OUTDOOR WIRING DIAGRAM
CN-TH2
CN­4WAY
RY-4WAY
WCN-NOISE
4(BK)
WCN-NOISE
1(BK)
FUSE
1(L) 2(N)
3
Page 53
Service Manual 53
Schematic Diagram
Components Location
INDOOR MAIN P.W.B ASSEMBLY (DC PART)
TOP VIEW BOTTOM VIEW
INDOOR MAIN P.W.B ASSEMBLY (AC PART)
TOP VIEW BOTTOM VIEW
Page 54
54 Room Air Conditioner
Schematic Diagram
DISPLAY ASSEMBLY(AS-W096QGG1, AS-W126RGH1, AS-W186TGH1, AS-W246TGH1,
AS-W246TLG1)
TOP VIEW
BOTTOM VIEW
Page 55
Service Manual 55
Schematic Diagram
OUTDOOR MAIN P.W.B ASSEMBLY(AS-W096QGG1, AS-W126RGH1)
BOTTOM VIEW
TOP VIEW
Page 56
56 Room Air Conditioner
Schematic Diagram
OUTDOOR MAIN P.W.B ASSEMBLY(AS-W186TGH1, AS-W246TGH1)
TOP VIEW
BOTTOM VIEW
Page 57
Service Manual 57
Troubleshooting Guide
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
ACCUMU LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
EER
3-WAY VALVE
COOLING HEATING
REVERSING VALVE
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
ACCUMU LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
3-WAY VALVE
CHECK VALVE
COOLING HEATING
REVERSING VALVE
(1) Model Capillary Tube
Refrigeration Cycle Diagram
(2) Model Adopted Electrion Expansion Valve
Page 58
58 Room Air Conditioner
Troubleshooting Guide
CAUTION:* Capicity is based on standard length and maximum allowance length
is the basis of reliability.
* Oil trap should be installed per 5~7 meters.
Outdoor unit
Indoor unit
A
B
In case more than 5m
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Additional
Refrigerant
(g/m)
Max.
Length
A (m)
Max.
Elevation
B (m)
Standard
Length
(m)
Pipe Length and the Elevation
Oil trap
Indoor unit
A
Outdoor unit
B
Page 59
Service Manual 59
Troubleshooting Guide
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
Page 60
60 Room Air Conditioner
Troubleshooting Guide
Required tools :
hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints, and gas leak detector.
The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not be done correctly and there gas leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.
Procedure
(1) Recheck the piping connections. (2) Open the valve stem of the 2-way valve coun-
terclockwise approximately 90°, wait 10 sec­onds, and then set it to closed position.
– Be sure to use a hexagonal wrench to operate
the valve stem.
(3) Check for gas leakage.
Check the flare connections for gas leakage.
(4) Purge the air from the system.
– Set the 2-way valve to the open position and
remove the cap from the 3-way valves service port.
– Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
(5) Use torque wrench to tighten the service port
nut to a torque of 1.8kg.cm.
(6) Set the 3-way valve to the back seat. (7) Mount the valve stem nuts to the 2-way and 3-
way valves.
(8) Check for gas leakage.
– At this time, especially check for gas leakage
from the 2-way and 3-way valves stem nuts, and from the service port nut.
Service port nut: Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
CAUTION:
Do not leak the gas in the air during Air purging.
CAUTION:
If gas leakage are discovered in step (3) above, take the following mesures :
If the gas leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, dis­charge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
Liquid side
Outdoor unit
3-way valve
Gas side
Indoor unit
2-way valve
Open
Clsed
Air purging
Page 61
Service Manual 61
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valves stem nuts and the ser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
Page 62
62 Room Air Conditioner
Troubleshooting Guide
Re-air Purging
(Re-installation)
Procedure
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the Gas side valve.
Leave the valve on the gas cylinder closed.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare nut on the liquid side valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
(4) Check for gas leakage.
Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.
(6) Disconnect the charge set and the gas cylin-
der, and set the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION: Do not leak the gas in the air
during Air Purging.
Lo
Closed
OPEN
Closed
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
3-Way valve
3-Way valve
Page 63
Service Manual 63
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed. Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig­erant until the gauge indicates 0.5 to 1 kg/cm2G. if this is the case, it will not be neces­sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 64
64 Room Air Conditioner
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Page 65
Service Manual 65
Troubleshooting Guide
Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Indoor unit
Check valve
Charging cylinder
Lo
(1)
OPEN
Liquid side
Gas side
CLOSE
3-Way
Open
valve
Open
3-Way valve
Outdoor unit
Page 66
66 Room Air Conditioner
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
Operating Current
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakege
Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem­perature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
NOTICE
NOTICE
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
Cycle Parts
Page 67
Service Manual 67
Troubleshooting Guide
Self-diagnosis function
The cause of malfunction
Indoor TH. is short or open.
Temp. of Heat sink is over 95°C, or Heat sink TH. is shortor open.
Comunication error (serial comunication).
DC peak error.
Running current is over­loaded.
Outdoor fan lock error (BLDC fan model)
The LED01M will be blinking twice.
The LED01M will be blinking 4 times.
The LED01M will be blinking 5 times.
The LED01M will be blinking 6 times.
The LED01M will be blinking 7 times.
The LED01M will be blinking 9 times.
Keep operating state.
Restart compressor when heat sink Temp. is 85°C below.
The operation is off(enable to restart by remote controller).
Compressor will be turned off immediately. (not enable to restart by remote controller)
Compressor will be turned off immediately. (not enable to restart by remote controller)
The operation is off(enable to restart by remote controller).
Malfunction indicator The operating state
Error Code
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
The cause of malfunction
Error Code
1
Indoor TH. is short or open.
Outdoor TH. is short or open.
Temp. of Heat sink is over 95°C. /Heat sink TH. is short or open.
Comunication error (serial comunication).
DC peak error.
Running current is over­loaded. (CT2)
D-PIPE TH is short or open.
The operating LED will be blink­ing once.
The operating LED will be blink­ing twice.
The operating LED will be blink­ing 4 times.
The operating LED will be blink­ing 5 times.
The operating LED will be blink­ing 6 times.
The operating LED will be blink­ing 7 times.
The operating LED will be blink­ing 10 times.
Keep operating state.
Keep operating state.
Restart compressor when Heat sink Temp is 85°C below.
The operation is off(enable to restart by remote controller).
Compressor will be turned off immediately. (not enable to restart by remote controller)
Compressor will be turned off immediately. (not enable to restart by remote controller)
Compressor will be turned off immediately. (restart compressor when D-PIPE TH. is recovred)
Malfunction indicator The operating state
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error code ➅, ➆ cant be operated unless the power cord is removed.
2
4
5
6
7
2
4
5
6
7
9
D-PIPE TH is short or open. The LED01M will be blinking 10
times.
Compressor will be turned off immediately. (restart compressor when D-PIPE TH. is recovered)
10
10
Indoor fan lock error (BLDC fan model)
The operating LED will be blink­ing 8 times.
The operation is off(enable to restart by remote controller).
8
Outdoor fan lock error (BLDC fan model)
The operating LED will be blink­ing 9 times.
The operation is off(enable to restart by remote controller).
9
Page 68
68 Room Air Conditioner
Troubleshooting Guide
Precaution in Service or Check
Even after stopping the operation of product, it takes some time to discharge the remaining electricity of the electrolytic capacitor that was charged. Before starting a checking or repairing job, pull out the plug out of the outlet and make sure that the lamp on the control board outdoor unit is off.
The Diagnosis Procedure
Check the supplied voltage to product (AC 220V/230V ± 30V).
Check the connecting cable between Indoor and Outdoor.
Check the blinking number of operation indicator
(refer to the self-diagnosis function).
Check the self-diagnosis table
Check the condition of connectors
The condition of P.C.B pattern.
Check the condition of connectors.
The condition of P.C.B pattern.
The electronic components.
Indoor Outdoor
Page 69
Service Manual 69
Troubleshooting Guide
Electronic Parts
Refer to electronic contorol device drawing & schematic diagram.
The Product doesnt operate at all.
Turn off the main power and wait to 10 seconds
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
Primarily, the operating condi­tion of Micom is O.K.
Check CN-DISP1
CN-DISP2 of indoor DC PCB
Check the voltage of power(AC220V/AC240V, 50Hz).
The voltage of main power.
The voltage applied to the unit.
The connecting method of Indoor/Outdoor connecting cable (each color)
The P.C.B. Ass'y
(Fuse, Noise Filter, Power Module, Bridge Diode, etc.)
Trouble 1
NO
YES
The operation check of the Indoor P.C.B. Ass'y
Procedure
1) The input voltage of power mod­ule.
2) The output voltage of power mod­ule.
4) IC04D(7805)
5) IC01A(KIA7036)
Specification
1) AC230V ± 30V : Check the rated voltage
2) 12V ± 3V
4) DC5V
5) The voltage of micom pin 19 : DC4.5V
Remedy
1) Check the power outlet.
2) Replace P.C.B Ass'y
4) Replace P.C.B Ass'y
5) Replace P.C.B Ass'y
Page 70
70 Room Air Conditioner
Troubleshooting Guide
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 2 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force).)
Caused by the remote controller.
Caused by other parts except
the remote controller
When the mark ( ) is displayed in LCD
screen, replace battery.
Check the contact of CN-DISP 1, 2 connector
Check DISP P.C.B Ass'y
-Voltage between CN-DISP1 - : DC +5V
Check point
Check the connecting circuit between MICOM PIN and CN-DISP1 PIN
Check receiver ass'y
Product doesn't operate with the remote controller.
Trouble 2
Page 71
Service Manual 71
Troubleshooting Guide
Turn on the main power.
When in air circulation mode, compressor/outdoor fan is stopped.
Turn off main power.
Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor.
Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped.
Check the related circuit of R02H(12.1K), R01H(6.2K), R04H(1K), R03H(1K), C01H(102), C02H(102), Micom(pin No. , ).
Check the Indoor temperature sensor is disconnected or not (Resistance is about 10K at 25°C).
Check the Relay(RY-PWR) for driving Compressor.
Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC220V / 240V).
Check the related circuit of relay in Outdoor PCB Ass'y.
Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least.
The Compressor/Outdoor Fan are unable to drive.
Trouble 3
Check Point
Between Micom(No. 46) and GND
DC 5V DC 0V
DC 12VDC 1V
Between IC01M(No. 15) and GND
Comp. ON Comp. OFF
Page 72
72 Room Air Conditioner
Troubleshooting Guide
When indoor Fan does not operate.
Trouble 4
Check the SSR high speed operation by remote control.
(the Indoor Fan Motor is connected)
Turn off main power.
Check the connection of CN-MOTOR.
Check the Fan Motor.
Check the Fuse(AC250V, T2A).
Turn on the main power
Check the related circuit of indoor Fan Motor.
The pin No.45 of micom and the part for driving SSR.
Check the related pattern.
Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.
The voltage of Pin No 1(orange) and 3(black) of CN-MOTOR.
About AC 180V over About AC 50V over
SSR is not damaged Check SSR
Page 73
Service Manual 73
Troubleshooting Guide
Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the vertical louver with hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PCB) of CN-U/D Connector
Check the operating circuit of the vertical louver
Confirm that there is DC +12V between pin of CN-U/D and GND.
Confirm that there is a soldering short at following terminals.
- Between41,42,43and
44
of MICOM
- Between
4
,
5 , 6
and 7of IC01M
- Between
10, 11 , 12
and 13of IC01M
When the horizontal louver does not operate.
Trouble 5
If there are no problems after above checks.
Confirm the assembly condition that are catching and interfering parts in the link of the vertical louver
Page 74
74 Room Air Conditioner
Turn off main power
Check the wire connection of PTC Heater (Refer to Wiring Diagram)
Check the connecting condition of CN-PTC connector on the indor DC P.C.B Ass'y.
Check the soldering condition of CN-PTC connector on the indoor DC P.C.B Ass'y.
Check the Heater driving Circuit.
Check the pattern between MICOM Pin No.
48
IC02M Pin No.
7
IC02M Pin No.
10
CN-PTC
The heater does not operate at all.
Trouble 6
If there is no problem result of all above check.
Inner side disconnection of PTC Heater unit or restriced operating condition of PTC Heater (pipe temp. is over 45°C, defrosting operation, compressor off, indoor fan off).
Troubleshooting Guide
Page 75
Service Manual 75
Does the Operating LED of indoor unit blink when Operation's ON?
Is the Connection between indoor power relay Pin and terminal block No. 1 right?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 7
YES
Check the connecting state of connector
NO
NO
Is the connection of cable between indoor and outdoor unit right?
Indoor Outdoor
1(Brown) 1(Brown) 2(Blue) 2(Blue) 3(Green/YL) 3(Green/YL) 4(Red) 4(Red)
NO
YES
Is the voltage of Terminal Block , in outdoor Control Box about AC220V /
240V?
Check the Fuse of Outdoor PCB Ass'y.
NO
YES
Is the voltage of NF01J ➀, ➁ in outdoor PCB Ass'y about AC220V / 240V when
Operation's ON?
Check the PTC and RY-PWR.
NO
YES
Is the Bridge Diode(BD01S) right?
Check the Bring Diode.
NO
YES
Replace the PCB Ass'y.
NO
Troubleshooting Guide
Page 76
76 Room Air Conditioner
Does the LED01M of outdoor PCB Ass'y blink 6 times?
Check the state of connecting cable (3 line) between indoor and outdoor uint.
When compressor does not operate normally.
DC Peak Error(Error Code )
Trouble 8-1
NO
YES
Is the connecting state of connectors in out­door. PCB Ass'y right? (CN-UVW)
Electrical wiring diagram (Colors)
Check the connecting state of connectors
in PCB Ass'y
If CN-UWV is connected, the comprressor can be operated a opposite direction.
NO
YES
Is the power module in PCB Ass'y right?
Check the short P-N P-U, V, W, and N-U, V, W of IPM and then collector, emiter of IGBT
NO
YES
Is the voltage of T/Block , over than AC150V?
Check the supplied voltage.
NO
YES
Is the voltage of GND-IPM(32 pin) over than about DC280V?
Check the DC voltage between IPM 1pin GND
NO
YES
Is the refrigerant pressure right?
Replace the PCB Ass'y.
Main PCB Ass'y
Control Box Ass'y
Supply the refrigerant or Discharge refriger­ant.
NO
NO
Troubleshooting Guide
Page 77
Service Manual 77
When compressor does not oprate normally.
Communication error between Indoor and Outdoor (Error Code )
Trouble 8-2
Does the operating LED in display PCB Ass'y blink 5 times?
Check the state of connecting cable (3 line) bewteen indoor and outdoor unit .
Check Fuse, Noise Filter, PTC, etc.
NO
YES
Is the voltage of BR/BK, RD AC220/240V in Main PCB Ass'y.
Electrical wiring diagram(Colors)
Check the connecting state
of connectors in outdoor PCB Ass'y
Check the Fuse of outdoor PCB Ass'y.
NO
YES
Is the connection of CN-T/Block and in CN-AC/DC indoor P.C.B Ass'y is right?
Replace the PCB Ass'y.
Main PCB Ass'y (Indoor/Outdoor)
Control Box Ass'y.
Reconnect the connectors.
Check the PCB pattern(Resoldering).
NO
YES
Troubleshooting Guide
Page 78
78 Room Air Conditioner
When compressor does not oprate normally.
CT Error (Error Code )
Trouble 8-3
Does the operating LED in Display PCB Ass'y blink 7 times?
Check the state of connecting cable (3 line) bewteen Indoor and Outdoor Unit .
Check fuse, Noise Filter, PTC, etc.
NO
YES
Is the courrent transformer(CT) in Main PCB Ass'y right?
Check the PCB pattern(resoldering)
NO
YES
Is the indoor/outdoor fan locked?
Check the indoor/outdoor fan motor.
NO
YES
Is the discharge temperature of Indoor unit right(11°C~17°C) in the cooling mode?
Check the compressor.
NO
YES
Is the refrigerant pressure right?
Supply the refrigerant or Discharge the refrigerant.
NO
YES
Replace the PCB Ass'y.
Main PCB Ass'y(Outdoor)
Control Box Ass'y(Outdoor)
Troubleshooting Guide
Page 79
Service Manual 79
The problem of missing the connector (INDOOR MAIN PCB ASSY)
The problem of missing the connector (OUTDOOR MAIN PCB ASSY)
Connectors
CN-AC/DC
CN-FAN
CN-DISP1
CN-T/Block
CN-DISP2
CN-TH
CN-U/D
Condition
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN/SHORT
OPEN
Malfunctions all indoor & outdoor unit.
Malfunctions remocon, force, test operation mode.
Malfunctions remote contoller.
Don't operate the power display module.
Malfunctions outdoor unit.
Stop compressor and outdoor fan motor.
The operation LED blinks 5 times.
Communication error.
Don't operate the power display module.
The operation LED blinks twice.
Enable to receive remote singnal.
Malfunctions UP/DOWN step motor.
Don't operate louver.
Malfunctions indoor fan motor.
Problem (error mode)
Connectors
Condition
OPEN
OPEN
OPEN
Stop compressor.
Malfunctions 4-WAY valve.
Malfunctions fan
Problem (error mode)
CN-TH
CN-UVW
CN-4 WAY
CN-FAN
CN-D-PIPE
OPEN/SHORT
OPEN/SHORT
The operation LED blinks twice.
The LED01M blinks twice.
The LED01M blinks 10 times.
Continue Comp. operation.
(when the discharge pipe TH opens)
Stop Comp. operation (when the discharge pipe TH shorts)
Troubleshooting Guide
Page 80
80 Room Air Conditioner
Exploded View
Exploded View
346810
135516
352150
266090
267110
146811
131410
359011
342800
147581
268711-1
159830
135311
135312
249951
733010
152313
135314
152302
268714-1
268714-2
263230
264110
354210
W6640
W0CZZ
35211B
Indoor Unit
Page 81
554032
437212
435511
552202
552116
552201
554160
561410
552113
550140
552203-1
552203-2
430410
649950
552102-1
437211
435301
559010
546810
437210
447910
263230-1
435512
268711
Outdoor Unit
552102-2
Exploded View
Service Manual 81
Page 82
Replacement Parts List
Replacement Parts List
Indoor Unit
LOCATION
No.
131410 CHASSIS ASSMEBLY 3141A20006A 3141A20005A 3141A10002A 3141A10002A 3141A10002A R
135311 GRILLE ASSEMBLY, DISCHARGE(INDOOR) 3531A10232Z 3531A10192Y 3531A10231Z 3531A10231Z 3531A10116G R
135312 GRILLE ASSEMBLY, FRONT(INDOOR) 3531A24001D 3531A21018L 3531A21022G 3531A21022G 3531A20207C R
135314 GRILLE ASSEMBLY, INLET SUB - - - - 3531A20107Y R
135516 COVER ASSEMBLY, MOTOR 3551A20050P 3551A20050N 3551A20098B 3551A20098B 3551A20098B R
146811 MOTOR ASSEMBLY, STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH), A/C 5230A10005C 5230A20014A 5230A20001A 5230A20001D 5230A20001D R
152313 FILTER ASSEMBLY, DEODORIZER 5231A20032C 5231A20032C - 5231A20032M - R
159830 AIR CLEANER ASSEMBLY 5983A25005H 5983A10006X 5983A10006X 5983A10006X 5983A25002H R
159901-1 VANE HORIZONTAL 5990A10005A 5990A20007A 5990A20008A 5990A20008C 5990A20008A R
159901-2 VANE HORIZONTAL - - 5990A20009A 5990A20009A 5990A20009A R
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20267W 4995A20267X 4995A20267Y 4995A20267Z 4995A20522B R
263230 THERMISTER ASSEMBLY 6323A20004K 6323A20004K 6323A20004K 6323A20004K 6323A20004K R
264110 POWER CORD ASSEMBLY 6411A20046C 6411A20046D 6411A20046E 6411A20005P 6411A90032D R
DESCRIPTION
AS-W096QGG1 AS-W126RGH1 AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
PART No.
REMARKS
266090 H.V ASSEMBLY 6609A10003U 6609A10003U 6609A10003P 6609A10003P 6609A10003P R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20073U 6711A20091H 6711A20091H 6711A20091H 6711A20077D R
268712 PWB(PCB) ASSEMBLY, DISPLAY 6871A20254B 6871A20254B 6871A20254C 6871A20254C 6871A20254C R
268714-1 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20316B 6871A20316B 6871A20316F 6871A20316D 6871A20316D R
268714-2 PWB(PCB) ASSEMBLY, MAIN(DC) 6871A20317R 6871A20636B 6871A20636C 6871A20317Z 6871A20636E R
342800 BEARING 4280A20004A 4280A20004B 4280A20004B 4280A20004B 4280A20004B R
346810 MOTOR ASSEMBLY, INDOOR 4681A20062L 4681A20048R 4681A20003D 4681A20067C 4681A20067C R
35211B TUBE ASSEMBLY, TUBING 5211A21046H 5211A21046G 5211A30439E 5211AR7066T 5211AR7066T R
352150 HOSE ASSEMBLY, DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F R
354210 EVAPORATOR ASSEMBLY,FIRST 5421A10024B 5421A20086A 5421A20010D 5410A20010L 5421A20010L R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20007E 5901A20007D 5901A20008A 5901A20008A 5901A20008C R
733010 PLATE ASSEMBLY, INSTALL 3301A10003A 1H00843A 3301A10002A 3301A10002A 3301A10002A R
W0CZZ CAPACITOR, DRAWING 3H01487K 3H01487A 3H01487G 3H01487G 3H01487G R
W6640 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A20283P 6871A20283L 6871A20283Q 6871A20283M 6871A20283M R
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
82 Room Air Conditioner
Page 83
Outdoor Unit
Replacement Parts List
LOCATION
No.
261704 TRANSFORMER, POWER 6170A20004A 6170A20004A 6170A20004A 6170A20004A 6170A20004A R
263230-1 THERMISTOR ASSEMBLY 6323A20001C 6323A20001C 6323A20001B 6323A20001B 6323A20001B R
263230-2 THERMISTOR ASSEMBLY 6323A20003G 6323A20003G 6323A20003C 6323A20003C 6323A20003C R
430410 BASE ASSEMBLY, WELD(OUTDOOR) 3041A20066A 3041A20066A 3041A20022R 3041A30003H 3041A30003H R
435301 GRILLE, DISCHARGE 3530A20006G 3530A20006B 3530A20007B 3530A20007B 3530A20007B R
435511 COVER ASSMEBLY, CONTROL(OUTDOOR) 3551A23001B 3551A30058Z 3551A30071H 3551A30071H 3551A30071H R
437210 GRILLE, ASSEMBLY, FRONT(OUTDOOR) 3721A20027Q 3721A20027H 3721A20005H 3721A20005H 3721A20005H R
437212 PANEL ASSEMBLY, REAR(OUTDOOR) 3721A20026M 3721A20026B 3720AP0003D 3720AP0003D 3720AP0003D R
447910 BARRIER ASSEMBLY,OUTDOOR 4791A30002G 4791A30002G 2H02110G 2H02110G 2H02110G R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20068G 4681A20068G 4681A20028R 4681A20028K 4681A20028K R
550140 ISOLATOR, COMP 4H00982E 4H00982E 4H00637A 4H00637A 4H00637A R
552102 TUBE, CAPILLARY BEND
552116 TUBE ASSEMBLY, REVERSING 5211A10465A 5211A10466A 5211A21140A 5211A30668B 5211A30668B R
DESCRIPTION
AS-W096QGG1 AS-W126RGH1 AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
5210A31461A 5210A21447F 5210A31380D 5210A31380C 5210A31380C R
5210A21447F 5210A33068A 5210A31380E 5210A31380F 5210A31380F
PART No.
REMARKS
552201 VALVE,CHECK 3H01552F 3H01552F 5220A30004A 5220A30004A 5220A30004A R
552202 VALVE,REVERSING 5220AR3228F 5220AR3228F 5220AR3228E 5220AR3228E 5220AR3228E R
552111 TUBE ASSEMBLY, CAPILLARY 5211A30331Y 5211A21393A 5211A21382B 5211A21382A 5211A21382A R
552203-1 VALVE, SERVICE 5220A20001Q 5220A20006F 5220A20006A 5220A20013C 5220A20013C R
552203-2 VALVE, SERVICE 2H02479P 2H02479P 2H02479F 5220A20001R 5220A20001R R
554032 CONDENSER ASSEMBLY, BENT 5403A21004B 5403A20019V 5403A20022R 5403A20022R 5403A20022R R
554160 COMPRESSOR SET 5416A90028A 5416A90026A 5416A90024A 5416A90029B 5416A90029B R
559010 FAN ASSEMBLY, PROPELLER 5901A10033A 5901A10033A 1A00195B 1A00195B 1A00195B R
561410 COIL ASSEMBLY, REVERSING VALVE 6141AR3509J 6141AR3509J 6141A20010H 6141A20010H 6141A20010H R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A20203X 4995A20203Y 4995A20346B 4995A20346C 4995A20346C R
658740 REACTOR 3874A90003L 3874A90003L 3874A90003L 3874A90003L 3874A90003L R
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 83
Page 84
P/No.: 3828A20195S
February, 2007
Printed in Korea
Loading...