LG S18AN, AS-W126RGH1, AS-W186TGH1 Schematic

LG
Room
Air Conditioner
SERVICE MANUAL
LG
MODELS: AS-W096QGG1
AS-W126RGH1 AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions .....................................................................................................................................................9
Symbols Used in this Manual.....................................................................................................................9
Indoor Unit..................................................................................................................................................9
Outdoor Unit.............................................................................................................................................10
Product Specifications ................................................................................................................................12
Installation.....................................................................................................................................................14
Select the Best Location .........................................................................................................................14
Piping Length and Elevation.....................................................................................................................14
How to Fix Installation Plate.....................................................................................................................15
Drill a Hole in the Wall..............................................................................................................................15
Installation Instructions of Telephone Control(Optional)...........................................................................15
Flaring Work.............................................................................................................................................16
Connection of Piping Indoor.....................................................................................................................17
Connection of the Pipes-Outdoor.............................................................................................................20
Connect the Cable to the Indoor Unit.......................................................................................................21
Connect the Cable to the Outdoor Unit....................................................................................................22
Checking the Drainage.............................................................................................................................23
Form the Piping........................................................................................................................................23
Air Purging ...............................................................................................................................................24
Air Purging with Vacuum Pump................................................................................................................24
Test Running............................................................................................................................................26
Functions ......................................................................................................................................................27
Operation ......................................................................................................................................................30
Disassembly..................................................................................................................................................45
Indoor Unit................................................................................................................................................45
Schematic Diagram.......................................................................................................................................48
Electric Control device..............................................................................................................................48
Wiring Diagram.........................................................................................................................................51
Components Location ..............................................................................................................................53
Troubleshooting Guide.................................................................................................................................57
Refrigeration Cycle Diagram....................................................................................................................57
Pipe Length and the Elevation .................................................................................................................58
2-way, 3-way Valve...................................................................................................................................59
Cycle Parts...............................................................................................................................................66
Self-diagnosis Function............................................................................................................................67
Electronic Parts........................................................................................................................................69
Exploded View ..............................................................................................................................................80
Indoor Unit................................................................................................................................................80
Outdoor Unit.............................................................................................................................................81
Replacement Parts List ................................................................................................................................82
Indoor.......................................................................................................................................................82
Outdoor ....................................................................................................................................................83
Service Manual 3
LG Model Name
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China U: China R410A
X: Mexico K: Turkey R22
V: Vietnam
E: Turkey R410A
S: Out Sourcing
H: Thailand 2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O
N: AC Inverter H/P
Q: DC Inverter C/O
W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP → SP Chassi
s
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model Development Serial No.
* ARTCOOL COLOR
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry Contact W Wired Remocon 8
R Mirror W White B Blue D Wood M Metal C Cherry
N Walnut A Gogh S Sisley Q Quran K Mecca
CHASSIS Look
D K L G M N D P
Division Panel Type(Deluxe) Fighting 'Look' (LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
S4/S5
S6 SQ SR ST
2003~
4 Room Air Conditioner
12 -345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing
H: Thailand 2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump
X: C/O + E/Heater
Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h 6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase
5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase
6: 220-240V/50Hz E: 265V, 60Hz
7: 110V, 50/60Hz F: 200V, 50/60Hz
8: 380-415V/50Hz
9: 380-415V/60Hz 7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis 8 Look A~Z Look,
Color (Artcool Model) 9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
2003
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire or electric
shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Installation
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion or injury.
Be cautious when unpacking and installing the product.
• Shape edges could cause injury. Be especially careful of the sharp edges.
6 Room Air Conditioner
Safety Precautions
For installation, always con­tact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condi­tioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated break­er or fuse.
• There is risk of fire or electric shock.
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
• There is risk of fire or electric shock.
Use a dedicated outlet for this appliance.
• There is risk of fire or electric shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electric shock.
Service Manual 7
Safety Precautions
Installation
Unplug the unit if strange sounds odors, or smoke comes from it.
• There is risk of fire, failure of the product, and/or electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product.
Be cautious that water could not enter the product.
• There is risk of fire, electrical shock or product damage.
Do not place a heater or other appliances near the power cable.
• There is risk of fire, failure of the product, and/or electric shock.
Do not allow water to run into electric part.
• There is risk of fire, failure of the product, and/or electric shock.
Do not store of use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Always check for gas(refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leak­age.
Thinner
Wax
90˚
Safety Precautions
8 Room Air Conditioner
Operation
Use two or more people to lift and transport the air condi­tioner
Avoid personal injury.
Use a soft cloth to clean. Do not use harsh detergents, sol­vents, etc.
There is risk of fire, electric shock or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor unit)
There is risk of personal injury and failure of product.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
Service Manual 9
Dimensions
Dimensions
Installation plate
D
H
W
W mm 824 900 1090
H mm 260 285 314 D mm 155 156 172
Model
Dimension
AS-W096QGG1 AS-W126RGH1
AS-W186TGH1 AS-W246TGH1
Indoor Unit
This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the
air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
10 Room Air Conditioner
Outdoor Unit
Dimensions
W
L2
L3
L1
D
H
L4
L5
Gas side (3-way valve)
Liquid side (2-way valve)
MODEL
DIM unit
W mm 770
H mm 540
D mm 245 L1 mm 285 L2 mm 65 L3 mm 518 L4 mm 10 L5 mm 100
AS-W096QGG1 AS-W126RGH1
Service Manual 11
Dimensions
Outdoor Unit
W
L7 L6 L8 L9
D
L1
L2
L3
L10
L4L5
H
Gas side
Liquid side
AS-W186TGH1 AS-W246TGH1 AS-W246TLG1
W mm 870
H mm 655
D mm 320 L1 mm 370 L2 mm 340 L3 mm 25 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54
L10 mm 74.5
MODEL
DIM
12 Room Air Conditioner
Product Specifications
Table-1
Model Name
Item Unit
W
MIN kcal/h.(W)
Btu/h.
W
Cooling Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
W
MIN kcal/h.(W)
Btu/h.
W
Heating Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
IN:20°C,Out: -10°C(Heater ON)
Btu/h.
IN:20°C,Out: -10°C(Heater OFF)
Btu/h.
Power Input Cooling W
Heating W Heating(-10°C,Heater ON)
W
Heating(-10°C,Heater OFF)
W
Running Current Cooling A
Heating A Heating(-10°C,Heater ON)
A
Heating(-10°C,Heater OFF)
A
Starting Current Cooling A
Heating A
EER Cooling W/W
Btu/h.W COP Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal l/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge g Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in)
Indoor mm Dimension inch (W*H*D) Outdoor mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
AS-W096QGG1 AS-W126RGH1 AS-W186TGH1 AS-W246TGH1
Product Specifications
1,582 2,110 1,758 4,249 1,361 1,814 1,512 3,654 5,400 7,200 6,000 14,500 2,640 3,520 5,280 7,032 2,270 3,027 4,540 6,048 9,010 12,014 18,016 24,000 2,901 3,868 5,801 7,735 2,495 3,326 4,990 6,653 9,900 13,200 19,800 26,400 1,978 2,532 1,406 3,604 1,701 2,177 1,210 3,100 6,750 8,640 4,800 12,300 3,170 3,960 6,070 7,735 2,726 3,405 5,219 6,653
10,819 13,512 20,711 26,400
3,481 4,351 6,651 8,497 2,994 3,742 5,720 7,308
11,880 14,850 22,700 29,000
----
----
950 1,200 1,630 2,480
1,150 1,300 1,900 2,730
----
----
4.3 5.4 7.5 11.5
5.1 5.7 8.6 12.5
----
----
4.3 5.4 7.5 11.5
5.1 5.7 8.6 12.5
2.78 2.93 3.24 2.84
9.48 10.01 11.06 9.68
2.76 3.05 3.19 2.83
1,220-240,50 1,220-240,50 1,220-240,50 1,220-240,50
97 97 97 97
7.2(254) 8.70(307) 13.0(459) 16.0(565) 26(918) 26(918) 42(1483) 45(1589)
1.4(2.94) 1.5(3.2) 2.12(4.48) 2.90(6.13) 35 40 42 47 32 37 39 43 29 31 36 39 48 48 55 58
610 810 1180 1500 16:3*1.0 16:3*1.5 12:3*2.5 12:3*2.5 16:4*1.0 16:4*1.5 12:4*2.5 12:4*2.5
6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
7.5(295) 7.5(295) 7.5(295) 7.5(295)
21.5,16.0(0.85,0.63) 21.5,16.0(0.85,0.63) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 824*260*155 900*285*156 1090*314*172 1090*314*172
32.4*10.2*6.1 35.1*11.1*6.2 42.9*12.4*6.8 42.9*12.4*6.8 770*540*245 770*540*245 870*655*320 870*655*320
30.3*21.3*9.6 30.3*21.3*9.6 34.3*25.8*12.6 34.3*25.8*12.6
7.0(15.4) 9.5(20.9) 12(26.5) 12(26.5) 34(74.8) 38(83.8) 60(132.3) 65(143.3)
Service Manual 13
Product Specifications
Table-2
Model Name
Item Unit
W
MIN kcal/h.(W)
Btu/h.
W
Cooling Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
W
MIN kcal/h.(W)
Btu/h.
W
Heating Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
IN:20°C,Out: -10°C(Heater ON)
Btu/h.
IN:20°C,Out: -10°C(Heater OFF)
Btu/h.
Power Input Cooling W
Heating W Heating(-10°C,Heater ON)
W
Heating(-10°C,Heater OFF)
W
Running Current Cooling A
Heating A Heating(-10°C,Heater ON)
A
Heating(-10°C,Heater OFF)
A
Starting Current Cooling A
Heating A
EER Cooling W/W
Btu/h.W COP Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal l/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge g Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in)
Indoor mm Dimension inch (W*H*D) Outdoor mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
AS-W246TLG1
4249 3654
14500
7032 6048
24000
7735 6653
26400
3604 3100
12300
7735 6653
26400
8497 7308
29000
-
­2320 2400
-
-
11.5
12.5
-
-
11.5
12.5
2.61
10.34
3.22
1,220-240,50
97
16.0(565) 42(1589)
2.9 45
­37 56
1500 12:3*2.5 12:4*2.5
9.52(3/8)
15.88(5/8)
7.5(295)
21.5,16(0.85,0.63) 1090*314*172
42.9*12.4*6.8 870*655*320
34.3*25.8*12.6 12(26.5)
60(132.3)
14 Room Air Conditioner
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in
front of the unit.
Make sure that condensation drainage can be con­veniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnec­essary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than "A"
More than B
More than 2.3m
More than "B"
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
CAUTION: Install the indoor unit on the wall
where the height from the floors more than 2.3 meters.
CAUTION:
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
7K~28K 10 5
30K~38K 30 12
Pipe Size
Capacit
y
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Service Manual 15
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the
hole which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Answering telephone / Normal telephone
(Not packed in the box)
Adaptor
(Not packed in
the box)
Telephone Control
Cord Wire
(Packed in the box)
Phone Conductor
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
Ø70mm
Left rear piping
Right rear piping
CE A
B
D
Installation plateInstallation plate
ABCD
SJ 90 20 80 20
SL, SK 45 40 80 20
SQ 75 12 80 12 SR 0 40 20 40 ST 105 0 210 0
CHASSIS
(Grade)
Distance (mm)
How to Fix Installation Plate Drill a Hole in the Wall
Installation Instructions of Telephone Control(Optional)
ABCDE SM 180 115 - 115 50 SN 180 115 195 115 -
CHASSIS
(Grade)
Distance (mm)
16 Room Air Conditioner
Installation
Flaring Work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Carry out flaring work using flaring tool as shown below.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared
section and re-flare it.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3.8 0~0.5
Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3
Outside diameter A
Service Manual 17
Installation
Connection of Piping Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction of rear right.
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insula­tion material* so that dripping from "sweating"(condensation) will not dam­age furniture or floors.
*Foamed polyethylene or equivalent is recom-
mended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are prop­erly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tight­en the flare nut by hand.
NOTICE
CAUTION:
When install, make sure that the remaining
parts must be removed clearly so as not to dam­age the piping and drain hose, especially power cord and connecting cable.
Tubing holder
Connecting cable
Loop
Gas side piping
Liquid side piping
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing Flare nut Pipes
Drain hose
18 Room Air Conditioner
Installation
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
5. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip­ing housing section with vinyl tape.
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
For left rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3.8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Drain hose
Connecting
cable
Drain pipe
Connecting cable
Service Manual 19
Installation
3. Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connec-
tion later.
4. Tape the drain hose and the connecting cable.
Connecting cable
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of the installation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
6. Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tight-
en the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
7. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip­ing housing section with vinyl tape.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3.8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
20 Room Air Conditioner
Installation
Bundle the piping and drain hose together by wrapping them with cloth tape over the range with­in which they fit into the rear piping housing sec­tion.
8. Reroute the pipings and the drain hose across the back of the chassis.
9. Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
10. Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
1. Align the center of the pipings and sufficiently tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on the wrench.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Tubing holder
Drain hose
Connecting
cable
Connection of the Pipes-Outdoor
Service Manual 21
Installation
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
CAUTION
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
7k, 9k 12k 18k
1.0 1.5 2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
7k, 9k 12k 18k
1.0 1.5 2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
(mm
2
)
CAUTION:
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the wiring diagram.
When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
Connect the Cable to the Indoor Unit.
CAUTION:
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
22 Room Air Conditioner
Installation
1. Remove the control cover from the unit by loos­ening the screw. Connect the wires to the terminals on the control board individually.
2. Secure the cable onto the control board with the cord clamp.
3. Refix the control cover to the original position with the screw.
4. Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
CAUTION: After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 20))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
7k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Connect the Cable to the Outdoor Unit
Service Manual 23
Installation
Checking the Drainage Form the Piping
1. To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the
position(horizontally) by hand.
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille toward you and lift it off.
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out the drain exit.
3. Drain piping
The drain hose should point downward for easy
drain flow.
Do not make drain piping.
1. Form the piping by wrapping the connecting portion of the indoor unit with insulation materi­al and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose,
the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable
from down to up.
Secure the tapped piping along the exterior wall
using saddle or equivalent.
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down
to up.
Secure the taped piping along the exterior wall.
Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equiva-
lent.
Pull the right and the left side.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
24 Room Air Conditioner
Installation
CAUTION:
To avoid nitrogen entering the
refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and
block capillary tubing.
Water may lead to corrosion of parts in the refrig­eration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
1. Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylin­der valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo
Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
CAUTION:
Be sure to use a manifold valve
for air purging. If it is not available, use a stop
valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
Air Purging
Air Purging with Vacuum Pump
Service Manual 25
Installation
3. Evacuation
Connect the charge hose end described in the pre­ceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tub­ing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacu­um pump.
4. Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter­clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way
valves. (2) Remove the service-port cap from the 3-way valve. (3) To open the 2-way valve turn the valve stem coun-
terclockwise approximately 90°, wait for about 2~3
sec, and close it. (4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connec-
tions by a soft brush to check for leakage of the
connecting points of the piping. (5) If bubbles come out, the pipes have leakage.
Soap water method
Required time for evacuation when 30 gal/h vacuum pump is
used
10 min. or more 15 min. or more
If tubing length is less than 10m
(33 ft)
if tubing length is longer than 10m
(33 ft)
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Indoor unit
Pressure gauge
Open
Outdoor unit
Manifold valve
Lo Hi
Close
Vacuum pump
26 Room Air Conditioner
Installation
Test Running
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote control
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Remove the batteries from the remote control if the system is not going to be used for a long time.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is con­veyed to the hose, secure the unit with an anti­vibration bushing.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake tempera­ture and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pres­sure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
NOTICE
NOTICE
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Loading...
+ 58 hidden pages