LG S092CG, S122CG, S122HG, S182CG, S182HG User Manual

...
Page 1
Room Air Conditioner
SVC MANUAL(Exploded View)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
N40
S092CG
U40
S092CG
S41
S092CP
S41
S122CG
N40
S122CG
U40
S122CG
S41
S122CP
S41
S122HG N40 S122HG U40
S122HG
S41
S182CG
N50
S182CG
U50
S182CG
S52
S182CP
S52
S182HG
N50
S182HG
U50
S182HG
S51
S242CG
N50
S242CG
U50
S242CG
S51
S242CP
S51
S242HG
N50
S242HG
U50
S242HG
S51
S092CG
N41
S092CG
U41
S122DC
S40
S122DC
S40
S242CG
N51
S242CG
U51
S122DP
S41
S122DP
S41
S182CG
N51
S182CG
U51
S122DH
S40
S122DH
S40
G122C
SR2
S182DP
S52
S182DP
S52
S182GP
S52
S182GP
S52
Page 2
- 2 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions....................................................................................................................................................10
Symbols Used in this Manual...................................................................................................................10
Indoor Unit................................................................................................................................................10
Outdoor Unit.............................................................................................................................................13
Product Specifications .................................................................................................................................16
Installation .....................................................................................................................................................18
Selection of the Best Location..................................................................................................................18
Piping Length and Elevation.....................................................................................................................18
How to Fix Installation Plate.....................................................................................................................19
Drill a Hole in the Wall..............................................................................................................................19
Drain hose junction...................................................................................................................................19
Flaring work and connection of piping .......................................................................................................20
Flaring work..............................................................................................................................................20
Connection of Piping Indoor.....................................................................................................................20
Connection of the Pipes-Outdoor.............................................................................................................24
Connecting the cable between indoor unit and outdoor unit ...................................................................25
Connect the Cable to the Indoor Unit.......................................................................................................25
Connect the Cable to the Outdoor Unit ....................................................................................................26
Checking the drainage and forming the pipings........................................................................................27
Checking the Drainage.............................................................................................................................27
Form the Piping........................................................................................................................................27
AIR PURGING ................................................................................................................................................28
Air purging................................................................................................................................................28
Air purging with vacuum pump.................................................................................................................28
Test Running .................................................................................................................................................30
Operation .......................................................................................................................................................31
Function of Controls .................................................................................................................................31
Display Function ......................................................................................................................................35
Self-diagnosis Function............................................................................................................................35
Remote Control Operations......................................................................................................................36
Disassembly ..................................................................................................................................................37
Indoor Unit................................................................................................................................................37
Schematic Diagram.......................................................................................................................................40
Electric Control Device.............................................................................................................................40
Wiring Diagram.........................................................................................................................................41
Components Location ..............................................................................................................................45
Troubleshooting Guide.................................................................................................................................47
Refrigeration Cycle Diagram ....................................................................................................................47
2-way, 3-way Valve .................................................................................................................................48
Cycle Parts...............................................................................................................................................54
Electronic Parts ........................................................................................................................................55
Exploded View...............................................................................................................................................62
Page 3
- 3 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
LG Model Name
2003
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
Page 4
- 4 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2004~
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z
L Chang_won R22 A Chang_won R410A C Chang_won R407C T China K Turkey R22 E Turkey R410A H Thailand
N India Z Brazil D Indonesia X Mexico V Vietnam S Out sourcing
Refrigerant
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F NBF F+(A/changeove)+A/clean+Low A G NBF F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K NBF F+(A/changeove)+A/clean L NBF F+(A/changeove)+A/clean+4way M NBF F+(A/changeove)+A/clean+PTC N NBF F+(A/changeove)+Autoclean+4way+PTC P NBF F+(A/changeove)+A/clean+4way+Low A+PTC Q (Nano)Plasma+ION+A/Clean S 4way+(Nano)Plasma F+
Negative ION+Healthy dehumidification
+A/Clean T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry contact W Wire remocon 8
Page 5
- 5 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
.Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
Page 6
- 6 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the
product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
Page 7
- 7 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
Page 8
- 8 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam­age.
Safety Precautions
Page 9
- 9 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Safety Precautions
Page 10
- 10 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Dimensions
Installation plate
D
H
W
W mm 840
H mm 270
D mm 153
Model
Dimension
9k, 12k Btu Series
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Page 11
- 11 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Installation plate
D
H
W
W mm 1090
H mm 300
D mm 178
Model
Dimension
18k, 24k Btu Series
Page 12
- 12 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Installation plate
D
H
W
W mm 900
H mm 285
D mm 156
Model
Dimension
12k (G122C
SR2)
Page 13
- 13 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
Outdoor Unit
MODEL
DIM unit
W mm 575 717
H mm 525 498
D mm 260 229
L1 mm 301 270
L2 mm 73 56
L3 mm 392 464
L4 mm 35 17
L5 mm 100 130
12k9k
Page 14
- 14 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
W
D
L1
L2
H
L3
L4
L5L6 L7 L8
L9
L10
Liquid side 2-way valve
Gas side 3-way valve
MODEL
18k Btu Cooling Only Model
DIM unit
W mm 801
H mm 555
D mm 262 L1 mm 339 L2 mm 37 L3 mm 543.6 L4 mm 11.4 L5 mm 591 L6 mm 105 L7 mm 105 L8 mm 72.5 L9 mm 86.4
L10 mm 77
Dimensions
Page 15
- 15 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
MODEL
DIM
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
W mm 840
H mm 577 D mm 276
L1 mm 337 L2 mm 64 L3 mm 611
L4 mm 16 L5 mm 156
18k, 24k Btu Heat Pump,
24k Btu Cooling Only Model
Page 16
- 16 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Product Specifications
Table-1
Product Specifications
Model Name
Item Unit
Cooling Capacity
Btu/h
Heating Capacity
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
Btu/hW
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant g
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
9,000 12,000
1.2 1.2
1Ø, 220V, 60Hz 1Ø, 220V, 60Hz
6.5 8.2
20 22
33 41
48 49
880 1,200
4.1 5.7
10.23 10.0
714
23 23
840x270x153 840x270x153
575x525x260 717x481x228
77
25 25
660(R22) 650(R22)
OO
XX
OO
24Hr ON/OFF 24Hr ON/OFF
OO
L.C.D wireless L.C.D wireless
1/4" (6.35) 1/4" (6.35)
3/8" (9.52) 1/2" (12.7)
OO
OO
1.0mm
2
x 3 1.0mm2 x 3
1.0mm
2
1.0mm
2
12,000
12,500
1.2
1Ø, 220V, 60Hz
8.2
22
41
49
1,150
1,150
5.4
5.4
10.4
10.9
14
23
840X270X153
717X481X228
7
25
850(R22)
O
X
O
24Hr ON/OFF
O
L.C.D wireless
1/4” (6.35)
1/2” (12.7)
O
O
1.0mm2 x 3
1.0mm
2
12,000
-
1.2
1Ø, 220~240V, 50Hz
8.8/9.5
22
40
49
1,250
-
5.6
-
9.6
-
9.5
23
900X285X156
717X481X228
7.2
25
660(R22)
O
X
O
7Hr OFF
O
L.C.D wireless
1/4” (6.35)
1/2” (12.7)
X
O
1.0mm2 x 3, 0.75mm2 x 2
1.0mm
2
S092CG S092CP
S122CG S122DC S122DP
S122HG S122DH
G122C SR2
Page 17
- 17 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Product Specifications
Table-2
Model Name
Item Unit
Cooling Capacity Btu/h
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input W
Running A
E.E.R. Btu/hW
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant g
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
18,000 24,000
1.8 2.9
1
Ø, 220V, 60Hz1Ø, 220V, 60Hz
13 15
42 42
42 45
56 56
1,950 2,350
8.9 11.0
9.23 10.21
20.6 19
45 86
1090 x 300 x 178 1090 x 300 x 178
801 x 555 x 262 840 x 577 x 276
13.5 13.5
60 60
1,240(R22) 1,350(R22)
OO
OO
OO
24Hr ON/OFF 24Hr ON/OFF
OO
L.C.D wireless L.C.D wireless
1/4"(6.35) 3/8"(9.52)
5/8"(15.88) 5/8"(15.88)
OO
OO
1.5
mm2 x 3 2.5
mm2x 3
1.5mm2 x 3
2.5mm2 x 3
18,500/19,800 24000/26,400
1.8 2.9
1\
1Ø,220V,60Hz1Ø
,220V,60Hz
13 15
42 42
42 45
56 56
1,960/1,810 2,600/2,550
9/8.5 12/11.5
9.44/10.94 9.23/10.35
20.6 19
45 86
1090
x
300x 178 1090x 300x 178
840x 577x 276 840x 577x 276
13.5 13.5
60 60
1,200(R22) 1,480(R22)
OO
OO
OO
24Hr ON/OFF 24Hr ON/OFF
OO
L.C.D wireless L.C.D wireless
1/4"(6.35) 3/8"(9.52)
5/8"(15.88) 5/8"(15.88)
OO
OO
1.5mm2x 3, 0.75mm2x 3 2.5mm2x 3, 0.75mm2x 3
1.5mm2x 3 2.5mm2x 3
S182CG S182CP S182DP S182GP
S242CG S242CP
S182HG S242HG
Page 18
- 18 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
Indoor unit
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of the unit.
• Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
• Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
• Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
• Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account and select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
• If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
• Consult local codes regarding rooftop mounting.
More than 10cm
More than
5cm
More than 2.3m
More than
5cm
• Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
5K~28K 10 5
30K~38K 30 12
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
5k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
Installation
Page 19
- 19 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
How to Fix Installation Plate
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
• Mount the installation plate horizontally by align­ing the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
ABCD
7K,9K,12K 75 65 105 65
18K, 24K 105 65 260 65
SR2(12K) 0 40 20 40
CHASSIS
(Grade)
Distance (mm)
Installation Plate
Type "A" screw
Chassis
Hook
Installation plat
SR2(12K)
SR2(12K)
e
Left rear piping Right rear piping
Ø70mm
Ø70mm
DB
A
C
Installation Plate
Type "A" screw
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
• Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
• Open the Front Grille.
• Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
• Connect Telephone Control Cord Wire to the phone jack
of telephone PCB of Control Box.
• Fix Telephone Control Cord Wire inside Control box so
as not to disconnect.
• Close the Front Grille.
Drill a Hole in the Wall
Drain hose junction
• Remove the rubber stopple in the desired drain direc­tion.
• Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Connecting
part
Adhesive
Drain
hose
Only the desired direction
Page 20
- 20 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
• Use the piping kit accessory or pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than the measured distance.
• Cut the cable 1.5m longer than the pipe length.
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared sec­tion and re-flare it.
• Preparing the indoor unit's piping and drain hose for instal-
lation through the wall.
• Remove the plastic tubing retainer(see illustration below)
and pull the tubing and drain hose away from chassis.
• Replace the plastic tubing holder in the original
position.(Optional)
• Carry out flaring work using flaring tool as shown below.
Burr removal
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
• Firmly hold copper pipe in a die in the dimension shown in the table above.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Drain hose
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Ø19.05 3/4 1.0~1.3
Outside diameter A
Connection of piping -- Indoor
When install, make sure that the remaining parts must be removed clearly so as not to damage the pip­ing and drain hose, especially power cord and connecting cable.
Flaring work and connection of piping
Page 21
- 21 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Route the indoor tubing and the drain hose in the direction of rear right.
Drain hose
Connecting
cable
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Plastic bands
Insulation material
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Indoor unit tubing Flare nut Pipes
Drain hose
Connecting pipe
Connecting cable
Tape
Drain hose
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
• Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe.
• Align the center of the pipes and sufficiently tighten the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the con­necting portion.
•Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
• Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5
Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
For right rear piping
Page 22
- 22 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
• Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
• Align the center of the pipes and sufficiently tighten the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the con­necting portion.
• Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
Indoor unit installation
• Hang the indoor unit from the hooks at the top of the instal­lation plate.
• Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Tape the drain hose and the connecting cable.
• Connecting cable
Drain pipe
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipes
Installation plate
Spacer
Indoor unit
8cm
Plastic bands
Insulation material
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
For left rear piping
mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5
Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Flaring work and connection of piping
Page 23
- 23 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Installation Information (For left piping)
• Good case For left piping. Follow the instruction below.
• Press on the upper side of clamp. (Ⓐ)
• Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Indoor unit installation
• Remove the spacer.
• Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Set the pipings and the drain hose to the back of the chassis with the tubing holder.
• Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Tubing holder
Drain hose
Connecting
cable
• Unfold the tubing to downward slowly. (Ⓑ)
• Bend the tubing to the left side of chassis.
Page 24
- 24 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
• Bad case
• Following bending type from right to left could cause problem of pipe damage.
Connection of the pipes-Outdoor
mm inch kg.m Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5
Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Flaring work and connection of piping
Page 25
- 25 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
Connect the cable to the Indoor unit.
• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.). The earth wire should be longer than the common wires. The above circuit diagram is subject to change without notice. When installing, refer to the circuit diagram on the control box inside Indoor Uint.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
(mm2)
• The above circuit diagram is subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
• If a power plug is not to be used, provide a circuit
breaker between power source and the unit as shown below.
Connecting the cable between indoor unit and outdoor unit
• When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
5k~9k 12k 14K~18k 24k~28k 30k, 32k 36k, 38k
1.0 1.0 1.5 2.5 2.5 5.5
Unit(A) Indoor Indoor Indoor Indoor Outdoor Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
5k~12k 14k~18k 24k~28k
1.0 1.5 2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F
NORMAL
CROSS
-SECTIONAL AREA
Grade
(mm2)
Page 26
- 26 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the con­trol board individually.
Secure the cable onto the control board with the cord clamp.
Refix the control cover to the original position with the screw.
Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Outdoor Unit
Cover control
Cord clamp
1(L) 2(N) 34 1(L) 2(N) 34
CASE 1 CASE 2
Connecting cable
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 24))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Connect the cable to the outdoor unit
5k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Connecting the cable between indoor unit and outdoor unit
Page 27
- 27 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To remove the front panel from the indoor unit.
• Set the air direction louvers up-and-down to the position(horizontally) by hand.
• Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
• If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
• Tape the piping, drain hose and connecting cable from down to up.
• Secure the tapped piping along the exterior wall using sad­dle or equivalent.
To check the drainage.
• Pour a glass of water on the evaporator.
• Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
• Tape the piping and connecting cable from down to up.
• Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
• Fix the piping onto the wall by saddle or equivalent.
Drain piping
• The drain hose should point downward for easy drain flow.
• Do not make drain piping.
Pull the right and the left side.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Page 28
- 28 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
• Pressure in the system rises.
• Operating current rises.
• Cooling(or heating) efficiency drops.
• Moisture in the refrigerant circuit may freeze and block cap­illary tubing.
• Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
• Do a leak test of all joints of the tubing(both indoor and out­door) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
• After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet­ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
AIR PURGING
Air purging
Air purging with vacuum pump
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Page 29
- 29 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Evacuation
• Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
• When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
• With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
• Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
• Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
• Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
• Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way valves.
(2) Remove the service-port cap from the 3-way valve.
(3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less than 10m (33 ft)
if tubing length is longer than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Page 30
- 30 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Test running
TEST RUNNING
1. Check that all tubing and wiring have been properly con-
nected.
2. Check that the gas and liquid side service valves are fully
open.
Settlement of outdoor unit
• Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
• In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration bushing.
NOTE: If the actual pressure is higher than shown, the system is
most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Power-Failure Compensation Function User Selection ON/OFF
1) Operation Sequence
Press the forced switch until BUZZER sounds 2 times
(beep~beep~).
Release the forced switch if BUZZER sounds. Check the function selection ON/OFF with the operation LED.
2) Checking function-selection ON/OFF
- Function-Selection ON: One time blinking of operation LED would repeat 4 times.
- Function-Selection OFF: Two times blinking of operation LED would repeat 4 times.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to
0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Power
button
Page 31
- 31 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Function of Controls
Operation
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Page 32
- 32 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
• When the intake air temp reaches +3°C above the setting temp, the compressor is turned off. When reaches
the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the defrost control time is 7 min or longer, defrost control is then carried out.
• While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con­trol is completed and heating mode operation is carried out.
• While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost control stops and heating mode operation is carried out regardless of the above condition.
• When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of the defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
Page 33
- 33 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.
Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.
Heat pump Model
Cooling Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
High High High High
Setting Temperature
22°C 22°C 23°C 24°C
Page 34
- 34 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem­perature and resets in 18±1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
If you want to stop the operation, re-press the button.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
Protection of the evaporator pipe from frosting
• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
Page 35
- 35 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Self-diagnosis Function
Operation
Display Function
1. Heating Model 2. Cooling Model
• Cooling, Soft Dry, Fan, Heating • Cooling, Soft Dry, Fan
• Hot-start, Deice
Operation Indicator
Deicer Indicator
Operation Indicator
Compressor on Indicator
OUT
DOOR
3sec 3sec 3sec
(once)
Error
Code
1
Error Display LED
(Indoor body operation LED)
Error contents
• Indoor room temperature thermistor open/short
• Indoor pipe temperature thermistor open/short.
• Indoor Thermistor assembly check
SVC check point
Page 36
- 36 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Remote Control Operations
Operation
The controls will look like the following.
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
5. JET COOL
Used to start or stop the speed cooling. (speed cooling operates super high fan speed in cooling mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. PLASMA(OPTIONAL)
Used to start or stop the plasma function.
14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL)
Used to set the desired horizontal airflow direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2ND F BUTTON
Used prior to using modes printed in blue at the bottom of buttons.
17. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
ON
OFF
CANCEL
AUTO CLEAN
SET
1
3
5
4
9
10
12
14 16
7
2
8
13
15
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
17
Operation Mode
Page 37
- 37 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
Disassembly
Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Earth Conductor
Page 38
- 38 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis carefully.
3. To remove the Discharge Grille.
• Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
• Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Screw
• When repair, do not damage the Caution label.
Page 39
- 39 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
• Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
• Remove 2 securing screw.
• Pull the motor cover out from the chassis carefully.
6. To remove the Cross-Flow Fan
• Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
• Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
• Remove the left end of the cross-flow fan from the self-aligning bearing.
Motor cover
Bearing
Cross-flow fan
Page 40
- 40 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Schematic Diagram
Electric Control Device
Heat Pump Model(LED TYPE)
Page 41
- 41 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Wiring Diagram
Schematic Diagram
Indoor Unit
Models: 9k, 12k, 18k, 24k Cooling only Model
MOTOR
OR
RD BK
BK BK BK BK
POWER
GN/YL
GN/YL
BR(BK/Plained)
BL(WH/Ribbed)
BK
YL
SH-CAPA
TERMINAL
BLOCK
CN-MOTOR
THERMISTOR
OPTION
PWB ASM.
STEP
MOTOR
CN-TH1
CN-U/D CN-OPTIONCN-L/R
CN-HVBCN-12V
CN-DISP1
DISPLAY
PWB ASM.
P/No : 3854A20427C
TRIAC
MAIN PWB ASM.
CN-N1
CN-N2
RY-COMP
TO OUTDOOR UNIT
43
1(L)
BR
BR
BL
GN/YL
2(N)
1(L) 2(N)
FUSE
250V T2A
STEP
MOTOR
H.V.
ASM.
S/W1
AIR CLEAN (PLASMA)
CN-DISP2
WIRING DIAGRAM
CONDUCTIVE ENCLOSURE MOTOR ONLY
Models: 12k, 18k, 24k Heat pump Model
Models: G122C
SR2
MOTOR
OR
RD
BK
BK BK BK BK
POWER
GN/YL
GN/YL
BR(BK/Plained)
BL(WH/Ribbed)
BK
YL
SH-CAPA
TERMINAL
BLOCK
RY-4WAY
RY-FAN
CN-MOTOR
THERMISTOR
OPTION
PWB ASM.
STEP
MOTOR
CN-TH1
CN-U/D CN-OPTIONCN-L/R
CN-HVBCN-12V
CN-DISP1
DISPLAY
PWB ASM.
P/No : 3854A20427B
TRIAC
MAIN PWB ASM.
CN-N1
CN-N2
CN-4WAY
RY-COMP
TO OUTDOOR UNIT
43
1(L)
BR
BR
BL
BK
RD
GN/YL
2(N)
3 4
1(L) 2(N)
3 4
FUSE
250V T2A
STEP
MOTOR
H.V.
ASM.
S/W1
AIR CLEAN (PLASMA)
CN-DISP2
WIRING DIAGRAM
CONDUCTIVE ENCLOSURE MOTOR ONLY
Page 42
- 42 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Outdoor Unit
Models: 9k, 12k Cooling only Model
Models: 12k Heat pump Model
Page 43
- 43 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Models: 24k Cooling only ModelModels: 18k Cooling only Model
Models: 18k, 24k Heat pump Model
Page 44
- 44 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Components Location
MAIN P.W.B ASSEMBLY
TOP VIEW
BOTTOM VIEW
Page 45
- 45 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
MAIN P.W.B ASSEMBLY
TOP VIEW
BOTTOM VIEW
Model : G122C
SR2
Page 46
- 46 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
DISPLAY ASSEMBLY
– 6871A20574B
- 6871A20575A (G122C
SR2)
Page 47
- 47 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
COMPRESSOR
ACCUMU LATOR
GAS SIDE
GAS SIDE
3-WAY VALVE
LIQUID SIDE
LIQUID SIDE
3-WAY VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
(Heating Model only)
COOLING HEATING
REVERSING VALVE (Heating Model Only)
(1) Cooling Only Models
Refrigeration Cycle Diagram
(2) Cooling & Heating Models
Page 48
- 48 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
Page 49
- 49 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valves stem nuts and the ser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
Do not use the existing charge set for R-22. It is necessary to use new charge set for R-410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pressure side gauge of charge set should be used higher pressure gauge of 50kg/cm2 range.
Page 50
- 50 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed. – Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig­erant until the gauge indicates 0.5 to 1 kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 51
- 51 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Use vacuum pump equipped with check value applied to be prevented from flowing backward.
Page 52
- 52 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
This unit is charged with R-410A. Pay attention not to charge R-22.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Lo
Charging cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way valve
3-Way valve
OPEN
Open
Check valve
(1)
Page 53
- 53 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc­tion pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem­perature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12
11
10
9
8
7
6
5
5 10152025303540
50˚C
40˚C
30˚C
20˚C
10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure (For R401A)
(According to Indoor & Outdoor Temperature)
Page 54
- 54 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
Operating Current
• All amount of refrigerant leaked out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle Defective compressor
• Excessive amount of refrigerant
• Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
NOTICE
NOTICE
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
Cycle Parts
Page 55
- 55 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting cable
• Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-NI, RY-COMP NO.3
• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PCB Assembly Check
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector
Main PCB Board Operation Check
Items
• SMPS Transformer
(Indoor unit)
- Input Voltage
- Output Voltage(C03D)
󱍵
• IC01D(7805) Output
(Indoor/Outdoor unit)
󱍵
• IC01A(KIA7036, Reset IC)
OSC01B(8MHz)
• Replace Trans
• Replace IC01D
• Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About DC12V
• DC +5V
• Voltage of IC No.1, (DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)
Page 56
- 56 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISP1 connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check Display PCB Assembly
- Voltage between CN DISP1 ③ - ⑧ : DC
+
5V
Check the connecting circuit between the remote controller
MICOM (No. 󱈆) - R16(1.5k) - IR LED - TR - R17(1Ω).
or
MICOM (No. ) - R1(1.5k) - IR LED - TR - R2(1).
Check point
• Check the connecting circuit between CN-DIS1⑦-
R11L(100) - C01A(100nF) - MICOM PIN
• Check Receiver Assembly
61
Page 57
- 57 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of RY-FAN.
• Check the indoor temperature sensor is disconnected or not(About 10k/ at 25°C).
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor Fan Motor.
• Check the "open" or "short" of conmecting wires between indoor and outdoor.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Assembly is normal.
• Check the circuit related to the relay.
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
59) and GND
Between IC01M(No. 15) Below DC 1V
About DC12V
and GND (app)
Page 58
- 58 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Turn ON Main Power
Check the related circuit of indoor Fan Motor.
• The pin NO 58 of Micom, and the part for driving TRIAC(the input and output signal of IC01M, PIN NO 1, 16)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
When indoor Fan does not operate.
The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.
About AC 180V over About AC 50V over
TRIAC is not damaged TRIAC Check
Page 59
- 59 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
• Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
• Confirm that there is DC
+
12V between pin(RED) of CN-U/D and
GND.
• Confirm that there is a soldering short at following terminals.
- Between , , and of MICOM
- Between ③, ④, ⑤and ⑥ of IC01M
- Between ⑭, ⑬,⑫ and ⑪ of IC01M
60 61 62 63
Page 60
- 60 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
When Heating does not operate
Operate “Heating Mode( )” by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
• Check the related circuit of RY-4WAY
• Check the indoor room temperature is disconnected or not (about 10K/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about 5K/at 25°C).
Turn ON Main Power
Check the DC voltage on the PWB ASSEMBLY
• The details of check are as followings
Check point
Between Micom
(NO.59) and GND
Between IC01M
(NO.15) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
Check point
Between Micom
(NO.51) and GND
Between IC02M
(NO.11) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.12) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
• Comp Relay.
• 4 way Relay
• Outdoor fan Relay
Page 61
- 61 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor Fan Motor, 4 way.
• Check the "open" or "short" of connecting wires between indoor and outdoor.
Page 62
- 62 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
Exploded View
135314
152302
342800
264110
263230A
359011
131410 733010
135316
135311
159830
147581
268711A
146811
W6640
346810
266090
135516
35211B
352115
352116
354210
249951
268711B
267110
Part for
Plasma Models
Part for
Plasma Models
Indoor Unit
Page 63
- 63 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
135314
152302
342800
359011
131410 733010
135316
135311
159830
147581
268711A
146811
346810
135516
35211B
352115
352116
354210
249951267110
Part for
Plasma Models
Indoor Unit : LS-H2425HB1/GB1/DB0, LS-C2425GB0, ASNH2465DM1, LS-C1825GM2
LS-C1224DM1 ,LS-C1825GB2/GB0/DB0/GB1
Page 64
- 64 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
135314
152302B152302A
342800
359011
131410 733010
135316
135311
159830
147581
268711A
146811
346810
135516
35211B
352115
352116
354210
249951267110
Part for
Plasma Models
Indoor Unit : LS-C0924GL1, LS-C1224GL1, LS-C1224DB0, LS-H1224DB0
Page 65
- 65 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
Indoor Unit :
G122C SR2
346810
146811
131410
359011
342800
147581
354210
268711A
135311
135316
267110
249951
733010
35211B
135516
352150
Page 66
- 66 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
559010
552202
552111
649950
430411
552203B
546810
435301
437211
561410
567502
554160
552203A
552116
447910
554031
137213A
435300
137213B
435511
550140
549610
Part for External Models
Part for
H/P Models
Outdoor Unit: 12k Btu/h Seriess
Page 67
- 67 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
554031
437212
435511
552202
567502
552116
552102A
552102B
554160
561410
552111
550140
552203B
552203A
430411
447910
649950
549610
437211
435301
559010
546810
Part for
H/P Models
Part for
External Models
Outdoor Unit: 9k Btu/h Heating Series
Page 68
- 68 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
554031
437212
435511
567502
552102
554160
552111
550140
552203B
552203A
430411
447910
649950
549610
437211
435301
559010
546810
Part for
External Models
Outdoor Unit: 9k Btu/h Cooling Series
Page 69
- 69 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
430411
554031
437212
435511
552202
552116
554160
550140
552203A
552203B
447910
437211
649950
552102A
552113
552112
559010
546810
561410
552102B
549610
Part for
H/P Models
435301
Outdoor Unit: 18k, 24k Btu/h Heating Series
Exploded View
Page 70
- 70 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
430411
554031
437212
435511
554160
550140
552203A
552203B
447910
437211
649950
552102
552113
552112
559010
546810
549610
435301
Outdoor Unit: 24k Btu/h Cooling Series
Page 71
- 71 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
430411
554031
437212
435511
554160
550140
552203A
552203B
447910
649950
552102
552113
552112
559010
546810
549610
437211
435512
435301
Outdoor Unit: LS-C1825GM2 Series
Page 72
- 72 -
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
137213B
435300
137213A
435511
430411
554031
552202
552116
554160
550140
552203A
552203B
447910
649950
552113
552112
559010
546810
561410
549610
Part for
H/P Models
437211
435512
435301
Outdoor Unit: AS-W2465DH0/1 Series
Page 73
P/NO :3828A20462F
JULY, 2008
Loading...