LG RVL469 User Manual

Page 1
Heating Controller
for use with a partner unit
527
2
Series B
RVL469
Use
Functions
Heating zone control
Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or without room temperature compensation
For exclusive use on the bus together with an RVL47... heatinmg controller as a partner unit
1 programmed plant type: three-position control of the mixing valve in a heat­ing zone
Analog or digital setting of the heating curve, analog room temperature read­justment, operating line principle for all other parameters
Operating voltage AC 230 V, CE conformity
Types of buildings:
– Multi-family houses – Single-family houses – Smaller non-residential buildings
Types of plants:
– Combined plants consisting of several heating zones and heat generation
Types of heating systems:
– Radiator, convector, underfloor and ceiling heating systems, radiating panels
Weather-dependent flow temperature control through control of the mixing valve in a heating zone in combined plants.
Operating modes
Frost protection is ensured in all operating modes. The controller can be switched to manual operation.
Siemens Building Technologies CE1N2527E / 04.03.1999 Landis & Staefa Division 1/8
Automatic mode
Automatic changeover from normal to reduced temperature, and vice versa, according to the seven-day program, automatic changeover to holiday mode, demand-dependent control of heating system (ECO function)
Setback mode
Continuous heating to the reduced temperature, with ECO function
Comfort mode
Continuous heating to the normal temperature, no ECO function
Standby
Page 2
Other functions
Optimization functions Protective functions Remote control Commissioning aids Communication functions
Ordering
Equipment combinations
Partner unit
Suitable sensors and room units
When ordering, please give type reference
RVL469
. Partner unit, sensors, actuator and
valve and, if required, room unit must be ordered as separate items.
Suitable partner units are:
RVL470 (data sheet CE1N2522E) RVL471 (data sheet CE1N2524E) RVL472 (data sheet CE1N2526E) RVL47 (data sheet CE1N2523E)
Flow and return temperature: all sensors with LG-Ni 1000 Ω at 0 °C, for example:
Clamp-on temperature sensor QAD22 Immersion temperature sensors QAE22... and QAP21.3
Room temperature:
Room unit QAW50 Room unit QAW70 Room temperature sensor QAA24
Outside temperature:
Outside sensor QAC22 (Ni sensing element) Outside sensor QAC32 (NTC sensing element)
Suitable actuators
Communication
Technical design
Working principle
Plant type
All electric and electrohydraulic actuators for three-position control made by Lan­dis & Staefa can be used. For the different types of actuators, refer to data sheets 4500…4599.
The controller is capable of communicating with:
All units with LPB capability made by Landis & Staefa SYNERGYR OZW30 central unit (from software version 3.0)
Connection to an RVL47... partner unit is mandatory. The partner unit is defined by as­signing an address. Each partner unit can be operated with only one RVL469.
The RVL469 ha one plant type preprogrammed: room heating with mixing zone, three­position control acting on mixing valve.
BUS (LPB)
B9
A6/B5
2527S01
E1
B7
A6 Room unit QAW50 or QAW70 E1 Load (space) B1 Flow sensor LPB Data bus B5 Room sensor M1 Heating circuit pump B7 Return sensor N1 Controller RVL469 B9 Outside sensor Y1 Mixing valve heating circuit
CE1N2527E / 04.03.1999 Siemens Building Technologies 2/8 Landis & Staefa Division
Page 3
Enduser settings
With weather-dependent control, the flow temperature is controlled in function of the pre­vailing outside temperature via the heating curve. Its basic setting is made with the little bar on the front of the unit or on an operating line. The room temperature can be read­justed with the knob. In addition, following can be entered by the enduser: – Room temperature setpoints for normal heating, reduced heating and frost protec-
tion/holidays
Seven-day switching program and a maximum of eight holiday periods per year Operating mode Time of day and date
Temperature acquisition
Space heating
Flow temperature: with one or two (averaging) sensors Outside temperature: with Ni or NTC sensor; the RVL469 identifies the type of sensor
used; with interlinked controllers, it is also possible to define the source of the outside temperature
– Room temperature: with a room temperature sensor or a room unit, or both (averaging)
The room temperature is included in the control. It can be acquired with a sensor or
simulated by a room model with an adjustable building time constant. When using a sensor, the effect on the control can be adjusted. It is also possible to limit the maximum room temperature.
The heating is switched on and off depending on demand (ECO function). It is swit-
ched off when the amount of heat stored by the building mass is sufficient to maintain the required room temperature. In that case, the controller takes into account the de­velopment of the room temperature and the building's heat storage capacity. It is pos­sible to set two heating limits, one for normal heating and one for reduced heating.
The control is optimized. Switching on, heating up and shutting down are controlled
such that, during occupancy times, the required room temperature is always main­tained. At the end of each occupancy period, the heating will be shut down (circulating pump) until the room temperature setpoint for the non-occupancy time is reached (quick set­back, can be disabled). During heating up, the room temperature setpoint can be boosted (boost heating). It is possible to set maximum limits for the heating up time and for early shutdown.
Three-position control
Minimum limitation of return temperature
Locking functions
Time switch
Remote control
Three-position control operates as weather-dependent or load-dependent flow tem­perature control. P-band and integral action time are adjustable. The flow temperature is controlled via the regulating unit (control or slipper valve). Minimum and maximum limitation of the flow temperature as well as maximum limitation of the rate of setpoint rise are adjustable.
Minimum limitation of the return temperature acts with both three-position control and load­dependent control of the boiler temperature and helps prevent flue gas condensation.
On the software side, all settings can be locked to prevent unauthorized readjustments.
– The RVL469 has one seven-day time switch for entering the daily occupancy times.
Each day can accommodate three occupancy times, whereby each weekday may have different occupancy times
– For entering a maximum of eight holiday periods, the RVL469 is equipped with a
yearly time switch featuring automatic summer- / wintertime changeover
Changeover of operating mode with the QAW50 room unit Overriding the major controller functions with the QAW70 room unit Selection of another (programmable) operating mode with an external contact Preselection of a fixed flow temperature setpoint with an external contact. Type of
setpoint (fixed or minimum) and flow temperature can be selected
Siemens Building Technologies CE1N2527E / 04.03.1999 Landis & Staefa Division 3/8
Page 4
Communication
To provide this function, connection of the RVL469 to ist partner unit via the data bus is mandatory. Each RVL469 requires one partner unit. Communication with other units also takes place via the data bus and facilitates:
Signalling of heat demand to the heat source Exchange of locking and enforced signals Exchange of measured values such as outside temperature, return temperature, flow
temperature and of clock signals
Communication with other devices Reception of heat demand signals from the SYNERGYR OZW30 central unit (from
software version 3.0)
– Exchange of error messages
Fault messages and flow temperature alarm
Other functions
Fault message in the event of sensor faults Fault message in the event of data bus faults Flow temperature alarm; adjustable is a period of time during which the flow temp-
perature may stay outside the set limits; a fault message is given when the time has elapsed
Display of parameters, actual values, operational statuses and fault messages Simulation of outside temperature Relay test; all relays can be controlled manually Sensor test; all measured values of the sensors can be displayed Testing the contacts connected to terminals H1M and H2M Outside temperature-dependent frost protection for the plant; a minimum flow tem-
perature is maintained, its setpoint and the response threshold can be adjusted
Pump overrun time to prevent buildup of heat Periodic pump run (pump kick) to prevent seizing of the pump in the summer Controller hours run meter
For more detailed information about technical features, functions and communication with LPB, please refer to the following pieces of documentation:
Basic Info RVL470: CE1P2522E Data sheet “Basic System Data LPB: CE1N2030E Data sheet “LPB: CE1N2032E
Mechanical design
Analog operating elements
Digital operating elements
The RVL469 is comprised of controller insert, which accommodates the electronics, the power section, the output relays and - on the front - all operating elements, and the base, which carries the connection terminals. The operating elements are located be­hind a lockable transparent cover. The operating instructions can be inserted in the transparent cover.
The controller insert is secured to the base with two screws, one of which can be sealed. The cover can also be sealed. The RVL469 can be fitted in three different ways:
Wall mounting (on a wall, in the control panel, etc.) Rail mounting (on a standard DIN mounting rail) Flush panel mounting (control panel door, etc.)
Buttons for selecting the required operating mode Info button Direct adjustment of the heating curve with the the little bar on the front of the unit
(only if analog setting is selected)
Knob for manual readjustment of the room temperature Three buttons for manual operation and manual positioning commands
The entry or readjustment of all setting parameters, activation of optional functions and reading of actual values and statuses is made according to the operating line principle. An operating line with an associated number is assigned to each parameter, each actual value and each function that can be selected. One pair of buttons is used to select an operating line and one pair to readjust the dis­play.
CE1N2527E / 04.03.1999 Siemens Building Technologies 4/8 Landis & Staefa Division
Page 5
1 Operating mode buttons (selected button is lit) 2 Buttons for operating the display
= selection of operating line
Prog
= readjustment of displayed value
--
+
3 Operating instructions 4 Button for «Close valve» in manual operation 5 Button for «Open valve» in manual operation 6 Button for manual operation 7LEDs for:
Manual operation Valve opens Valve closes
Pump runs 8 Sealing facility in the cover 9 Info button for display of actual values 10 Display (LCD) 11 Setting slider for flow temperature setpoint at an outside temperature of –5 °C 12 Setting slider for flow temperature setpoint at an outside temperature of 15 °C 13 Knob for room temperature readjustments 14 Fixing screw with sealing facility
2522Z04
Notes
Engineering
Commissioning
Siemens Building Technologies CE1N2527E / 04.03.1999 Landis & Staefa Division 5/8
The wires of the measuring circuits carry extra low voltage, those to the actuator and the pump carry AC 24230 V. The local electrical regulations must be complied with. Sensor cables should not be run parallel to mains carrying cables for loads such as ac­tuator, pump, etc.
The data bus address must be entered. The partner unit must be available on the data bus. Each controller is supplied complete with installation and commissioning instructions.
Page 6
Technical data
–conformity to
EMC directive
Immunity Emissions
Low voltage directive
Safety
89/336/EWG EN 50082-2 EN 50081-1 73/23/EWG
EN 60730-1 Rated operating voltage AC 230 V Frequency 50 Hz Power consumption 8 VA Degree of protection (cover closed) IP42 EN 60529 Safety class II EN 60730 Output relays
Rated voltage Rated current Contact current at AC 24...90 V Contact current at AC 90...250 V Rated current of ignition transformer Switch-on current of ignition transformer
AC 230 V
2 (2) A
0.1...2 A, cos ϕ >0.6
0.02...2 A, cos ϕ >0.6
max. 1 A during max. 30 s
max. 10 A during max. 10 ms Perm. ambient temperature
Transport and storage Operation
-25...+65 °C
0...50 °C Perm. cable lengths to the sensors and external contacts
Copper cable 0.6 mm dia. Copper cable 1.0 mm Copper cable 1.5 mm
Perm. cable lengths to the room unit
Copper cable 0.25 mm Copper cable from 0.5 mm
2 2
2
2
20 m 80 m 120 m
25 m
50 m Bus loading characteristic E (LPB) 6 Backup of time switch 12 h min. Weight (net) 1.1 kg
Connection diagrams
Basic connections on the low voltage side
LPB
D1
D2
L
N
AC 230 V
B9
B7
Basic connections on the mains voltage side
AC 230 V
H2
S2
B5
2527A01
2527A02
A6 Room unit QAW50 or QAW70 M1 Heating circuit pump B1 Flow sensor N1 Controller RVL469 B5 Room sensor S1 Remote control operating mode B7 Return sensor S2 Remote control flow temperature setpoint B9 Outside sensor Y1 Actuator heating circuit LPB Data bus
CE1N2527E / 04.03.1999 Siemens Building Technologies 6/8 Landis & Staefa Division
Page 7
Dimensions
139
951,5 (42,5)
144
15
19
26 26 26 26
144
144
4,5
14
39
35
106
50
39
36 29
36
72 106 108
-0/+1
138
max. 3
138
18
-0/+1
Dimensions in mm
Siemens Building Technologies CE1N2527E / 04.03.1999 Landis & Staefa Division 7/8
Page 8
1999 Siemens Building Technologies Ltd.
CE1N2527E / 04.03.1999 Siemens Building Technologies 8/8 Landis & Staefa Division
Loading...