LG PT-HCC INSTALLATION INSTRUCTIONS

ELECTRIC HEATERS
INSTALLATION INSTRUCTIONS
Models: LKAEH052, LKAEH102, LKAEH152,
LKAEH09B, LKAEH18B, LKAEH36B, LKAEH36BL
• Please read this instruction sheet completely before installing the product.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
P/No.: 3828A30038B
Table 1 Accessory Heaters Electrical Data
Ton
3RT
4/5RT
6.25/7.5RT
8.5/10/12.5 RT
15/17.5RT
20/25RT
Heater
Model No.
LKAEH052 LKAEH102 LKAEH052 LKAEH102 LKAEH152 LKAEH09B LKAEH18B LKAEH09B LKAEH18B LKAEH18B LKAEH36B
LKAEH36BL
Heater
KW Rating
3.6/5.0
7.2/10.0
3.6/5.0
7.2/10.0
14.4/15.0
7.8/9.0
15.6/18.0
7.8/9.0
15.6/18.0
15.6/18.0
31.2/36.0
31.2/36.0
Control Stages
1 1 1 1 1 1 1 1 1 1 2
2
27.6/32.2
47.4/55
29.6/34.2
49.4/57.0
69.0/79.7
30.4/35.1
50.9/58.7
35.7/41.2
56.2/64.8
56.2/64.8
97.1/112.1
97.1/112.1
60/60 60/60 60/60 60/60 90/90 60/60 70/70 60/60 70/70 70/70
125/125
125/125
60/60 60/60 60/60 60/60 90/90 60/60 70/70 60/60 70/70 70/70
125/125
125/125
-
-
-
-
-
33.0/38.1
53.3/61.5
42.0/48.4
62.4/72.0
62.4/72.0
103.4/119.3
103.4/119.3
-
-
-
-
­60/60 70/70 60/60 80/80 80/80
125/125
125/125
-
-
-
-
­60/60 70/70 60/60 80/80 80/80
125/125
125/125
Heater
Rated Volts
208-240/60/1 208-240/60/1 208-240/60/1 208-240/60/1 208-240/60/1 208-240/60/3 208-240/60/3 208-240/60/3 208-240/60/3 208-240/60/3 208-240/60/3
208-240/60/3
Standard indoor fan motor
M.C.A M.C.AM.F.S M.F.SM.C.B M.C.B
Over size indoor motor
Note; Heater KW ratings are at 208/240V for 220V unit.
M.C.A; Minimum Circuit Ampere M.F.S; Maximum Fuse Size M.C.B; Maximum Circuit Breaker * HACR type Circuit Breaker per NEC.
Installation
1. Loosen the screw that secures heater compartment access panel. Lift up, pull towards you and slide it down to remove.
2. Remove four(4) screws from block off panel to expose heater cavity and heaterʼs back support bracket. Save screws for installing heater later.(See Figure 2.)
Heater Access Panel
Compressor Access Panel
Figure 1
Figure 2
: Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts.
WARNING
Support Bracket
Block off panel
Heater Cavity
Heater and Control Box Assembly
3. Insert heater into the opening hole of heater control box.
4. Align holes and secure screws to the control box as shown in Figure 3.
Single Bank Heater Installation
-
LKAEH052, LKAEH102, LKAEH152, LKAEH09B, LKAEH18B, LKAEH36BL
5. Place the heater control assembly in the heater cavity.
6. Secure the heater control assembly of heater cavity using four(4) screws. (See Figure 4.)
Important: Make sure the heater arm slides
into heaterʼs back support bracket.
Two Bank Heaters Installation
-
LKAEH36B
7. For two heaters installation, align holes and secure screws to the control box as shown in Figure 3.
8. Secure the heater control assembly on heater cavity using four(4) screws.(See Figure 5)
Important: Make sure the heaterʼs arm slides
into heaterʼs back support bracket.
Heater Control Box
Heater
Figure 3
Figure 4
Figure 5
9. Remove the nut, lock washer and flat washer from heater terminal posts marked L1, L2 and L3.
10. Connect wiring from control box panel to
the correct terminal post as shown on heaterʼs wiring diagram.
Note: The correct sequence for replacing the hardware on the heater terminal posts is: 1) wire connector 2) flat washer 3) locking washer
4) nut. “DO NOT OVER TIGHTEN NUT ON
TERMINALS” use a nut driver only to tighten connection.(See Figure 6.)
L3
L2
Figure 6
Control Wiring
11. Connect control wires(Brown) on terminal
block (and P.C.B) as shown on wiring diagram attached on compressor access panel.
Power Wiring
12. Then route wires down through the
opening in the top of control box. Connect wires to high voltage terminal block. Refer to wiring diagram supplied with heater.
13. Check to make certain the proper size
fuses are installed per the fuse table for the exact heater being used.
14. Ground unit at the grounding lug
provided. Make sure all field wiring complies with all applicable codes and water tightness.(Figure 7)
15. Remove compressor panel, then remove
unitʼs control box cover. Connect high voltage leads to bottom of compressor contactor or terminal block.(See unitʼs wiring diagram.) Replace control box cover and access panel onto unit. (Figure 7)
CAUTION: Use copper conductors only to prevent equipment damage. Unit terminals are not designed to accept any other wiring.
16. Replace control box cover using four(4) screws.
17. Replace heater access panel.
CAUTION: Do not over tighten the nuts on the heater terminals. if the nuts are over tightened the ceramic insulators will break and heaters must be replaced.
Maximum torque on nuts is 11 inch pounds.
To Unit Control Box.
Ground
Power Supply
Terminal Block
Figure 7
Loading...