The instructions below must be followed to prevent product malfunction, property damage, injury or death to the user or other people. Incorrect operation due to ignoring any instructions will cause harm or damage. The level of seriousness is classified by the symbols below.
TABLE OF SYMBOLS
This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
Note:
Do not touch any exposed outdoor unit wiring, terminals, or other electrical components with tools or exposed skin. Only
qualied technicians should install, use or remove this unit.
Improper installation or use may result in re, explosion, electric shock, physical injury and/or death.
Don’t use or store ammable gas or combustibles near an outdoor or indoor unit.
There is risk of re, explosion, and physical injury or death.
The information in this manual is intended for use by a
MultiSITE CRC 1 Controller
trained technician familiar with the U.S. National Electric
Code (NEC) who is equipped with the proper tools and test
instruments.
Failure to carefully read and follow all instructions in this manual may
result in equipment malfunction, property damage, personal injury and/
or death.
Risk of electric shock. Disconnect all power before
servicing.
Do not install the MultiSITE Controller unit if it will be
exposed to rain or other precipitation.
Do not install the unit in a location exposed to open ame
or extreme heat.
Do not touch the unit with wet hands.
There is risk of re, electric shock, physical injury and/or death.
Replace all control box and panel covers.
If cover panels are not installed securely, dust, water and animals may
enter the unit, causing re, electric shock, and physical injury or death.
Wear protective gloves when handling equipment.
Sharp edges may cause personal injury.
This symbol indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action that should not be performed.
Dispose of any packing materials safely.
• Packing materials, such as nails and other metal or wooden parts
may cause puncture wounds or other injuries.
• Tear apart and throw away plastic packaging bags so that children
may not play with them and risk suffocation and death.
Do not change the settings of the protection devices.
If the pressure switch, thermal switch, or other protection device is
shorted and forced to operate improperly, or parts other than those
specied by LG are used, there is risk of re, electric shock, explosion,
and physical injury or death.
If the air conditioner is installed in a small space, take measures to prevent the refrigerant concentration from exceeding safety limits in the event of a refrigerant leak.
Consult the latest edition of ASHRAE (American Society of Heating,
Refrigerating, and Air Conditioning Engineers) Standard 15. If the re-
frigerant leaks and safety limits are exceeded, it could result in personal
injuries or death from oxygen depletion.
4
Due to our policy of continuous product innovation, some specifications may change without notification.
MultiSITE Controller is for use with select LG commercial air
conditioning systems only.
Do not attempt to use MultiSITE Controller with any other
type of system. Refer to the compatible equipment list in this
manual.
There is risk of equipment damage or degraded performance
Do not cut, lengthen or shorten the cable between the
MultiSITE Controller unit and the indoor unit.
Do not install the MultiSITE Controller unit in a location
where the cable cannot be safely and easily connected between the two units.
Do not allow strain on this cable.
There is risk of equipment damage.
Clean up the site after all procedures are nished, and check
that no metal scraps, screws, or bits of wiring have been left
inside or surrounding the controller or indoor units.
Provide power to the outdoor unit compressor crankcase
heaters at least six (6) hours before operation begins.
Starting operation with a cold compressor sump(s) may result in severe
bearing damage to the compressor(s). Keep the power switch on during
the operational season.
Do not block the indoor unit inlet or outlet.
Unit may malfunction.
Securely attach the electrical cover to the indoor unit. Non-
secured covers can result in re due to dust or water in the
service panel.
Do not allow water, dirt, or animals to enter the unit.
There is risk of unit failure or degraded performance.
Do not spill water or other liquid on the inside of the
indoor unit, especially on electrical components.
Do not drop the MultiSITE Controller unit into water. If the
unit is immersed in water or other liquid, contact your local
authorized LG distributor for support.
There is risk of unit failure or degraded performance.
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
This manual describes how to use the LG MultiSITE Commercial
Remote Controllers (CRC) 1. There are two models of this controller:
• MultiSITE CRC1 (Model PREMTBVC0)
• MultiSITE CRC1+ (Model PREMTBVC1)
The two models are identical with the exception of two functions
included in the MultiSITE CRC1+ only:
• Motion sensor
• Humidity sensor
Compatible Equipment
MultiSITE CRC1 Controllers are compatible with LG Commercial
Air Conditioning indoor units (except PTAC units).
Do not attempt to use a MultiSITE CRC1 controller with any
other equipment.
INTRODUCTION
Typical MultiSITE CRC1 Controller
09-26-2017
Occ Auto Heat
Indoor °F
2:43 PM
Auto
78
74°
Humidity
66 %
68
User Interface Guide
Accessories
These accessories are available for MultiSITE CRC1 controllers:
• ZigBee® Pro wireless card Model ZVRCZPWC1
• Door and window switch Model ZVRCZDWS1
• Wall mounted occupancy sensor Model ZVRCZWOC1
• Ceiling mounted occupancy sensor Model ZVRCZCOC1
The ZigBee® Pro wireless card is required for communication
between the controller and the other accessories.
Safety
Safety of personnel is the primary concern during all procedures.
Read and understand the safety summary at the front of this manual.
Ensure the controller is installed in accordance with the appropriate
LG installation manual.
If troubleshooting is required, it must be performed by trained personnel
and in accordance with national wiring standards and all local or other
applicable codes. Improper troubleshooting and repair/replacement of
equipment can result in re, electric shock, physical injury, or death.
Note:
Improper troubleshooting and repair/replacement of equipment can
result in damaged equipment or degraded operation.
MultiSITE CRC1 Controller Accessories
ZigBee® Pro Wireless CardDoor/Window Switch
*ZigBee is a registered trademark of the ZigBee Alliance.
Due to our policy of continuous product innovation, some specifications may change without notification.
Selecting modes available on this screen places the IDU in that mode and then the user will be returned
to the home screen. Selecting the mode that is currently highlighted will maintain the current mode and
return the user to the home screen.
OPERATION MODE
Cool
Fan
Dry
Heat
Auto
Auto
Setback
User Interface Guide
Due to our policy of continuous product innovation, some specifications may change without notification.
Setpoints can be modied in three different ways when in Auto Mode: Cooling Setpoint change, Heating Setpoint change, or
Cooling/Heating Setpoint change.
09-26-2017
Occ Auto Heat
2:43 PM
Auto
Indoor °F
78
74°
Humidity
66 %
MultiSITE CRC 1 Controller
Auto Mode, Cooling Cycle, Cooling Setpoint (Dual Setpoint setting)
When in cooling cycle of Auto Mode, use the up and down arrows to raise or lower the cooling setpoint.
When the setpoint is modified it will increase or decrease the difference between the cooling and heating setpoint values. The minimum difference allowed between cooling and heating setpoints is determined
by the Deadband control value setting (found in the Setpoint Config screen). "Cooling Setpoint" shows as
indicated on the screen to the left.
Auto Mode, Cooling Cycle, Heating Setpoint (Dual Setpoint setting)
To change the heating setpoint when in Auto Mode, cooling cycle, tap the up or down arrows to place the
controller into set point configuration mode and then immediately tap the Mode button once to change to
heating set point mode. "Heating Setpoint" shows when this parameter is set. Immediately move back to the
set point up or down arrows to change the heating set point.
Auto Mode, Cooling Cycle, Cooling/Heating Setpoint (Dual Setpoint setting)
To change the cooling and heating setpoints simultaneously, a third option is available for adjusting setpoints. If in Auto Mode (either cooling or heating cycle), tap either the up or down set point buttons, then
immediately tap the Mode button until “Cool/Heat” shows, indicating that the controller is in the correct set
point mode. Immediately move back to the up or down set point buttons to change the set points as desired.
68
10
Due to our policy of continuous product innovation, some specifications may change without notification.
Setpoints can be modied in three different ways when in Auto Mode; Cooling Setpoint change, Heating Setpoint change or
Cooling/Heating Setpoint change.
09-26-2017
Occ Auto Cool
Cooling Setpoint °F
74°
Humidity
45 %
09-26-2017
Occ Auto Heat
Heating Setpoint °F
74°
Humidity
45 %
2:43 PM
75.0
2:43 PM
75.0
Cooling mode or cooling only
sequence of operation
In Cooling mode, the setpoint displayed in the bar is the current occupied cooling setpoint.
During occupied setpoint adjustment, the large digits are temporarily used to display the occupied cooling setpoint while it
is adjusted.
Normal temperature display resumes after the setpoint is
adjusted and the actual occupied cooling setpoint is displayed
in the setpoint bar.
Heating mode or heating only
sequence of operation
In Heating mode, the setpoint displayed in the bar is the current occupied heating setpoint.
During occupied setpoint adjustment, the large digits are temporarily used to display the occupied heating setpoint.
Normal temperature display resumes after the setpoint is
adjusted and the actual occupied heating setpoint is displayed
in the setpoint bar.
User Interface Guide
Automatic Heating / Cooling mode
In automatic mode, the setpoint displayed at the top of
the set point bar represents the actual occupied cooling
setpoint.
During occupied setpoints adjustment, the large digits are
temporarily used to display the occupied “Cooling Setpoint” or occupied “Heating Setpoint”. The actual setpoint
is dependent on the last effective demand (heating or
cooling).
Normal temperature display resumes after the setpoints
are adjusted and the actual occupied heating and cooling
setpoints are displayed in the setpoint bar.
Due to our policy of continuous product innovation, some specifications may change without notification.
Some of the buttons on the Home screen display conguration screens. Controller operating parameters can be set as necessary for your system. The gure below describes how to use the conguration
screens.
Screen Name
Controls
The left side of the
screen lists controls and
monitored parameters.
Back Button
Tapping this button
MultiSITE CRC 1 Controller
goes back one level in
the screen hierarchy.
Left/Right Arrows
The left and right
arrows move between
screens on the same
level as the currentlydisplayed screen.
Control Values
The right side of the
screen is a button you
can tap to change the
value of the control or
parameter displayed to
its left.
Read Only
Dark gray buttons are
read only. These values
can’t be changed by the
user.
Up/Down Arrows
The up and down
arrows are used to
change the value of
the active (highlighted)
control.
12
Due to our policy of continuous product innovation, some specifications may change without notification.
Press the Schedule button on the Home screen to display the Schedule Screen. There are different
schedule setting screens, one for each day of the week (7 days) titled accordingly. Each can have different
scheduled events where the room controller is set for set point, system mode, fan speed and occupancy
status. Five (5) separate events can be configured per day.
Tap the left-hand button to set
the time for scheduled event.
When the time for a new event
Tap the right-hand side button
to enter the next screen.
is configured, the default system mode of “Off” will appear
in the event overview portion of
the control on the right side.
Adjust the time in the left column by pressing on the
Up and Down arrows. To configure the System mode
for the time selected tap on the right column.
This typical schedule screen shows the parameters that can be adjusted for a specific time and day in a week.
User Interface Guide
Once the event has been fully
configured, press the left arrow to be returned to the daily
schedule overview screen.
Due to our policy of continuous product innovation, some specifications may change without notification.
Up to 5 separate events per day can
be configured. User can set cooling
and heating set points, system mode
(Off, Dry, Cool, Heat, Fan and Auto),
fan speed and Occupied/Unoccupied
status.
13
Page 14
CONFIGURATION SCREENS
06:00AM
05:00PM
Monday Schedule
H74 / 70:O
C71 / 69:U
Off
--:--
--:--
09:00PM
Copyto
Delete
Copy to day(s)
Monday
Tuesday
Wednesday
Friday
Sunday
Thursday
Saturday
Daily Schedule Screens – continued
To modify an existing
event, tap either the
left side control to
edit the time or tap
H 74 / 70:O
the right-hand side of
the control to re-enter
the event screen and
make your desired
changes.
If desired, use the
'Copy to' button to
copy the schedule
to another day of
the week. First
choose the time of
the event you want
to copy and then
choose ‘Copy to’.
MultiSITE CRC 1 Controller
Event Overview DisplayParameter Meaning
First LetterMode (O=off, C=cool, H=heat, F=fan, A=auto, D=dry)
Second Number(s)Set Point(s)
Third Letter Occupancy Status (U=unoccupied, O=Occupied)
Example: H: 74 / 70: O = Heating Mode, Upper setpoint of 74, Lower setpoint of 70, Occupied
Press the right arrow button to display these screens. To adjust vane angle, user selects vane(s) by tapping
vane icon at the top of the screen, adjusts vane angle by using up/down arrows and then selects Apply button.
Note:
Vane xed angle control for multi-vane systems occurs in pairs. Refer to the Vane Fixed Angle screen. If a 4-louver
device is identied, when the user chooses Vane 1 or Vane 3 control, the opposite vane (Vane 3 or Vane 1) will be
controlled at the same time. If Vane 2 or Vane 4 is selected, Vane 4 or Vane 2 will be controlled in lockstep with its
matching pair as well. The same control behavior holds for a 2-louver device.
Airflow Up / Down and
Airflow Left / Right con-
trols can both be “On” at
the same time. However,
when Airflow Circular
control is “On,” both of
the other two controls will
be set to “Off.”
These screens are more commonly used during installation, system configuration, or troubleshooting than
by an end user. There is no icon on the Home screen to access these configuration screens. You must press
and hold the area of the screen indicated on the diagram below to access the first screen.
If a configuration / installer password is activated to prevent unauthorized access to the configuration menu
parameters, a password entry prompt will appear to prevent access to the device configuration components.
09-26-2017
Occ Auto Heat
Indoor °F
74°
Humidity
66 %
2:43 PM
Auto
78
68
User Interface Guide
Touch and hold here
for 3 seconds to enter
conguration mode.
Due to our policy of continuous product innovation, some specifications may change without notification.
There are two main configuration screens as shown below. Press the left and right arrow buttons to move
between these two screens. Press a button on a screen to display the parameter selections for that item.
Configuration 1/2
Enter Display, Date & Time, Filter, Setpoints, Override,
Building Manager
Setback and Outdoor Unit configuration
Installer
BMS Config
Basic Diagnostic
Password Setup
Factory Default
Configuration 2/2
MultiSITE CRC 1 Controller
Wireless Ecosystem
Enter General, Temperature, Fan and Heat settings and
Accessories configuration
Enter BACnet settings
View Diagnostic parameters
Setup a password to restrict/allow access to the thermostat
Reverts all controller control settings back to default values.
Note: User will be given the option to conrm that they wish to
proceed. Once in the Factory Default screen, if user proceeds with
this step, all schedules and current controller settings, along with time
and date will be cleared. There is no way to recover settings once a
Factory Default has been performed.
Enter ZigBee wireless zone configuration settings.
18
Due to our policy of continuous product innovation, some specifications may change without notification.
When ZigBee wireless sensors are set up to communicate with the controller, the functioning of each
such sensor is described in a separate Zone screen, up to a maximum of 10 Zones. Press the left and
right arrow keys to move between Zone screens. Select the appropriate type of sensor using the up
and down arrow keys.
Configuration 2/2
Wireless Ecosystem
Enter ZigBee wireless Zone
configuration settings.
User Interface Guide
Up to 10 separate
wireless sensors
can be configured,
each with its own
Zone screen
Due to our policy of continuous product innovation, some specifications may change without notification.
There are two main configuration screens as shown below. Press the left and right arrow buttons to move
between these two screens. Press a button on a screen to display the parameter selections for that item.
Customize Home View
Hide On/Off, Mode, Schedule,
More, Set Temp, Space Temp,
Fan and Humidity options on
home screen.
Code Search
Use the Up and Down arrows
to choose an available
Function Code and select the
Code Search button to navigate to the screen where that
function code resides.
Codes can be found in
brackets next to a parameter
throughout all menus. This
function is used for quicker
Press the Display / Date & Time button on the Building Manager screen to show the Display menu screen.
Press the right arrow button on the Display menu screen to show the Date & Time screen.
Press the right arrow button on the Display screen to show the screen below. The Clock settings screen allows the device’s internal time settings to be changed, including current time, standard day, month, year and
weekday options, as well as the choice between a 12 hour AM / PM display or a 24 hour display. Using the
Up and Down arrows adjust the Time, Year, Month and Day parameters. The Weekday is automatically filled
by the system and it cannot be adjusted.
Select between a 12 or
24-hour format.
Customize Home View
Press the Customize Home View button on the Building Manager Screen to select the Hide Controls menu
MultiSITE CRC 1 Controller
screen. The Hide Controls menu is used to select which parameters are displayed on the home screen of
the thermostat. You can select which parameter to show or hide by tapping it and then using the Up and
Down arrows. By default, all parameters are shown on the main screen.
1/2 Hide Controls
On / OffShow
ModeShow
ScheduleShow
MoreShow
Set TempShow
Space TempShow
2/2 Hide Controls
Fan SpeedShow
HumidityShow
Select between the
Show and Hide options.
22
Due to our policy of continuous product innovation, some specifications may change without notification.
Press the Filter Functions button on the Building Manager screen to display the Filter Functions screen. The
Filter Functions menu displays the time and alarm parameters. These cannot be adjusted by the user.
Default value: Dual SP(1)
Default value can be changed by user
Dual Setpoint Mode
Setpoints Config. 2/2
Cooling SP Max
Cooling SP Min
Heating SP Max
Heating SP Min
Deadband
Single SP
(Single Setpoint Adjustment)
Setpoint Maximum is 86 °F
Setpoint Minimum is 60 °F
Dual SP
(Dual Setpoints Adjustment)
Maximum upper cooling temperature is 99 °F
Minimum lower cooling temperature is 52 °F
Maximum upper heating temperature is 90 °F
Minimum lower heating temperature is 40°F
Deadband range is 1 °F - 10 °F
99 °F
52 °F
90 °F
40 °F
4 °F
Minimum deadband value
between the heating and cooling
setpoints. Applied only when any
of the setpoints are modied.
Range is 1 °F - 10 °F
24
Due to our policy of continuous product innovation, some specifications may change without notification.
Press the Override Setup button on the Building Manager screen to display the Override Setup screen. The user can configure override settings including set points, system mode, fan speed and override duration.
Override Operation
Override mode can only be activated if the current system status is Unoccupied. If this condition is met, the controller will
enter Override mode as soon as the user taps the screen the first time (from dim state). If the user makes any changes to
the settings, those are accepted and the controller stays in Override mode. When the override timer expires, the controller
returns to the original settings (Mode, Fan Speed, Set Points) in effect prior to entering Override. If a scheduled event starts
during Override mode, the controller accepts the scheduled event and exits Override mode.
User Interface Guide
Setpoint (Single Setpoint)
Default value: 72°F
Setpoint cool (Dual Setpoint)
Default value: 78°F
Setpoint heat (Dual Setpoint)
Default value: 68°F
System mode
Default value: Auto
Fan Speed
Default value: Medium
Override
Default value = 30 minutes
Default Parameters are dependent on if the controller is in Single Setpoint Mode or Dual Setpoint Mode.
Press the Setback Setup button on the Building Manager screen to display the Setback Setup screen. Setback parameters
including set points, system mode, and fan speed are configured on this screen.
Setback Operation
If the controller is in Setback mode and the user changes the Mode, Fan Speed or Set Points, the controller exits Setback
mode and keeps settings as applied by the user until the next scheduled event occurs. Setback mode can also be exited if
the user presses the Setback mode button again from the Operation Mode screen while in Setback mode. The setback icon
on the Operation Mode screen will indicate if that mode is active or not.
Press the Outdoor Unit Control button on the Building Manager screen to display the Outdoor Unit Control screen. The Outdoor Unit Control lets you manage outdoor units through the controller interface.
Press the Installer button on the Configuration screen to display the Installer screen. The Installer menu lists
the controller’s setup parameters and the accessories menu.
Code Search
Use the Up and Down arrows
to choose an available Function
Code and select the Code Search
button to navigate to the screen
where that function code resides.
Codes can be found in brackets
next to a parameter throughout all
MultiSITE CRC 1 Controller
menus. This function is used for
quicker menu navigation.
28
Due to our policy of continuous product innovation, some specifications may change without notification.
There are four Installer / General Settings screens. Press General
Settings on the Installer screen to display the first General Settings
screen. Press the right arrow on the screen to display screens 2, 3,
and 4.
This value will be used to
decide if Auto mode appears
in the Operation Mode screen
and whether to show “Auto”
text at the top of the Home
screen during Auto operation
mode.
Using the Up and Down arrows select
between Heating, Cooling or Off
modes. The Test run will end after 18
minutes and then turn system off. Test
mode can be interrupted by changing
fan speed, set point, or turning off the
IDU from the home screen.
Using the Up and Down arrows select
a guard time of 0, 15, 30, 45 or 60
minutes.
Press the Temperature Settings button on the Installer screen to display the Temperature Settings screen. Press the right
arrow button to display the second page of the Temperature Settings screen.
Press the Fan Settings button on the Installer screen to display the Fan Settings screen. Press the right arrow
button to display the second page of the Fan Settings screen.
Press the Accessories button on the Installer screen to display the Accessories screen. Press the right arrow to display the
second page of the Accessories screen.
This option enables the related
control on the MORE screen that
turns the Vent kit on or off.
This option enables the related
control on the Filter Functions
screen that controls Raise/Lower
Grill functions.
This option enables the related control
on the MORE screen that turns the
Plasma Purifier on or off.
User Interface Guide
Global setting which applies to both
the onboard PIR sensor as well as any
installed ZigBee motion sensors.
Due to our policy of continuous product innovation, some specifications may change without notification.
Press the BMS Config button on the Configuration screen to display the BMS Config screen.
User Interface Guide
BACnet Settings
Press the BACnet* settings button on the BMS Config screen to display the BACnet Network screen. Press the right arrow to
display the BACnet Instance screen.
"254" value will set BACnet
network "Offline." To activate
Imperial or Metric units
Baud rate settings
"Online," choose a different
value
Indicates the controller
status on the network.
*BACnet is a registered trademark of ASHRAE
Due to our policy of continuous product innovation, some specifications may change without notification.
Terminal Equipment Controller
Networking address
Default value = 254
Range is: 0 to 254
Network units
Default value = SI
Baud rate
Default value = Auto
Communications Address
For BACnet MS/TP models, the valid range is from 0 to 253.
Default value of 254 disables BACnet communication for the
Controller.
Measurement Units
Imperial: Network units shown as “imperial” units.
SI: Network units shown as “international metric” units.
Baud Rate
Auto: Will automatically detect the BACnet MS/TP baud rate.
Other choices: (115200) (76800) (57600) (38400) (19200)
(9600)
Leave the value at auto unless instructed otherwise.
The default BACnet instance number is generated by the model number and COM address of the controller. For
example, the instance number of a MultiSITE CRC1 Series with a COM address of 57 is generated as “83057”.
The default instance number appears first. To change the instance number, use number pad and press Accept
and save.
Press Reset to automatic instance addressing to reset to automatic instance addressing.
MultiSITE CRC 1 Controller
Instance number of the controller.
38
Back to Setup page
Reset to automatic instance
addressing
Due to our policy of continuous product innovation, some specifications may change without notification.
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254
Node type
Coord; Router
ZigBee Pan ID
Personal Area Network Identication
Default value = 0
Range is: 1 to 1000
ZigBee channel
Channel selection
Default value = 10
Range is: 10 to 25
ZigBee status
(read only)
For wireless models, the use of the COM address is not mandatory. COM address is
an optional way to identify a device on the network and is recommended if used with an
MPM.
It is Mandatory for BACnet.
Set Node type to Coord if controller will be responsible for controlling Zigbee sensor
network.
This parameter (PAN ID) links specic Controllers to specic ZigBee coordinators. For
every Controller reporting to a coordinator, make sure to set the SAME channel value
both on the coordinator and the Controllers.
The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from
1 to 1000.
This parameter (Channel) is used to link specic Controllers to specic ZigBee
coordinators. For every Controller reporting to a coordinator, be sure you set the SAME
channel value both on the coordinator and the Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available channels is
from 11 to 25.
ZigBee status
The following read only messages show in this eld:
• (Not Det): ZigBee Pro module not detected
• (Pwr On): ZigBee Pro module detected but not congured
• (No NWK): ZigBee Pro congured but no network joined
• (Joined): ZigBee Pro network joined
• (Online): Communicating
*ZigBee is a registered trademark of the ZigBee Alliance.
Due to our policy of continuous product innovation, some specifications may change without notification.
Press the right arrow on the ZigBee Configuration screen to display the second page of the ZigBee Configuration
screen. The blue fields indicate the controller is paired with a sensor.
Press the right arrow on the Basic Diagnostic screen to display the next Basic Diagnostic screen.
Screens 5/6 Basic Diagnostic and 6/6 Basic Diagnostic display a historical
list of the 10 most recent
error codes generated by
the Indoor Unit. The most
recent error code appears
at the top of the list.
Error Code
Error Code
Error Code
Press the right arrow on the Basic Diagnostic screen to display the Basic Diagnostic screen.
MultiSITE CRC 1 Controller
Error Code
44
Due to our policy of continuous product innovation, some specifications may change without notification.
This parameter sets a protective access password to prevent
unauthorized access to the conguration menu parameters.
A default value of “0” will not prompt a password or lock the
access to the conguration menu. User must include any
leading “0” if anything less than a 4-digit code is selected
for a password. A default value of “0” will not prompt for a
password.
Range is: 0 to 9999.
User password
This parameter sets a protective access password to prevent
user unauthorized access to main screen adjustments. A
default value of “0” will not prompt for a password.
Range is: 0 to 9999.
Due to our policy of continuous product innovation, some specifications may change without notification.
Answering Yes to both parameters and tapping ‘push to accept’ erases all values and sets the controller
to factory default values.
Note:
Once in the Factory Default screen, if user proceeds with this step, all schedules and current controller settings, along with time and date will be cleared. There is no way to recover settings once a Factory Default has
been performed.
MultiSITE CRC 1 Controller
46
Due to our policy of continuous product innovation, some specifications may change without notification.
Relative humidity is displayed on the MultiSITE CRC1+ controller only. Apart from the visual indication of relative
humidity, this data is also available as a monitoring point via MSTP BACnet to be used by the user as desired.
45 %
Relative humidity
Time and Date
Time and date are displayed at the top of the home screen.
09-26-2017
Occ Auto Heat
Indoor °F
74°
Humidity
2:43 PM
75.0
User Interface Guide
09-26-2017
Occ Auto Heat
Indoor °F
74°
Humidity
45 %
Due to our policy of continuous product innovation, some specifications may change without notification.
Time and Date will display when
updated in display settings. Time
and Date must be reset if Controller
is set to factory default values.
47
Page 48
CONFIGURATION SCREENS
PIR (Motion Sensor)
The MultiSITE CRC1+ version of the controller comes with an onboard PIR style motion sensor. If the sensor is
enabled (installer configuration under Accessories), status from the PIR sensor will be used to control the operation of the IDU as follows:
If the IDU status is currently Occupied and the onboard PIR goes Unoccupied, the IDU will operate according to
the Setback values of the controller and will change its status to Unoccupied.
If the IDU status is currently Unoccupied and the onboard PIR goes Occupied, the IDU will operate according to
the settings in use during the last Occupied status and will change its status to Occupied.
If the IDU is currently in Setback or Override modes, information from the PIR sensor will be ignored.
MultiSITE CRC 1 Controller
48
Due to our policy of continuous product innovation, some specifications may change without notification.
Freight Damage and Unit Replacements Your LG Manufacturer Representative
Missing Parts Your LG Manufacturer Representative
Freight Damage and Unit Replacements Your LG Manufacturer Representative
Received Wrong Indoor Unit Model Your LG Manufacturer Representative
Installation, Startup, and Commissioning Technical Assistance 1-888-865-3026
For warranty information, visit www.lghvac.com.
Page 50
LG Electronics
Commercial Air Conditioning Division
4300 Northpoint Parkway
Alpharetta, Georgia 30022
www.lghvac.com
LG Customer Information Center, Commercial Products
1-888-865-3026 USA
Follow the prompts for commercial A/C products and parts.
UM_CRC1_Series_Controllers_05_17
Supercedes: UM_CRC1_Series_Controllers_3_17
Supercedes: UM_CRC1_Series_Controllers_10_16
Loading...