LG PQRNC0 User Manual

Page 1
P/No.: 3828A20561U Printed in Korea
After reading this manual, keep it in a place easily accessible to the user for future reference.
Page 2
ENGLISH
LG
Junction Simple Wired Remote controller
LG
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
Owner's & Installation Manual
Visit us at : http://www.lgservice.com
Models: PQRNC0
ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
Page 3
2 Junction Simple Wired Remote controller
Junction Simple Wired Remote controller Owner’s & Installation Manual
TABLE OF CONTENTS
Safety Precautions....................................................................2
Part Description ........................................................................6
Junction Simple Wired remote controller....................................7
Junction Control System Structure.........................................9
Installation Method .................................................................10
Necessary functions before using .......................................12
Trial Operation..........................................................................12
Setting the Central-Control Address ........................................13
ESP Function ...........................................................................14
Main Function of Remote Controller.....................................15
On/Off Operation ......................................................................15
Cooling Operation ....................................................................16
Heating Operation ....................................................................17
Fan Speed Selection ................................................................18
Neutral / Gap setting function...................................................19
Power Failure compensation ....................................................20
Error code display function.......................................................20
Page 4
Safety Precautions
Installation Manual 3
ENGLISH
Entrust installation of the product to the service center because improper installation may cause fire, an electric shock, explosion, and physical injury.
Use the original parts in order to prevent fire, an electric shock, explosion, and product breakdown.
Keep combustible and/or inflammable materials away from the product in order to prevent fire or product breakdown.
Do not disassemble, repair, or modify the product at your discretion in order to prevent fire or an electric shock.
Do not install the product in wet and humid areas in order to prevent product breakdown.
Do not expose the product to the sun in order to prevent product breakdown.
Installation
Service Center
Original Parts
Safety Precautions
• The installation requires expert skills, and it should be installed by the service center or other shops specialized in the installation and recognized by our company.
• For all the problems arising after installation by someone who has no relevant qualifications, LG will not provide free service.
• The following safety cautions are provided to prevent unexpected dangers or losses.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
WARNING
CAUTION
Page 5
Safety Precautions
4 Junction Simple Wired Remote controller
Do not modify or lengthen the power cable at your discretion. It may cause fire or an electric shock.
Do not place a heating device near the product. It may cause fire.
Do not drop water on to the product. It may cause an electric shock or product breakdown.
Do not place something heavy on the power cable. It may cause fire or an electric shock.
Do not place a heavy thing on the product. It may cause product breakdown.
If the product was submerged under water, ask the service center for instruction. It may cause fire or an electric shock unless you do that.
In-use
In-use
Service Center
Make sure children or senor citizens use the product under proper observation in order to prevent safety accident.
Do not subject the product to shock. It will cause product breakdown.
Do not pick the product with a sharp tool. It may cause product breakdown with the damage to its parts.
Do not clean the product with strong cleanser such as solvent. Use soft clothes in order to prevent fire or product deformation.
Do not touch the product with a wet hand. Do not pull the lead cable. It may cause product breakdown or an electric shock.
CAUTION
Page 6
Installation Manual 5
ENGLISH
WARNING
Don't touch with the hands while the power is on
There is risk of fire or electric shock.
Use standard parts(connector).
Do not disassemble or repair the product. There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized
Service Center.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Installation
When the product is soaked (flooded or submerged), contact an Authorized Service
Center.
• There is risk of fire or electric shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Operation
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not install, remove, or re-install the unit by
yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
For installation, always contact the dealer or an
Authorized Service Center.
• There is risk of fire, electric
shock, explosion, or injury.
Page 7
6 Junction Simple Wired Remote controller
Part Description
PQRNC0
Cooling Heating Auto Dry Fan
Defrost Preheat Out door
Slo Lo
Med
Hi
Po
Room Temp
Total on
Central Run
FAN
SPEED
Yellow
White
3. LCD Screen
1. Connection cable for Dry contact Module (Linked Other equipment)
2. Connection cable for Air-conditioner
Wired Remote Controller
Part Description
1. Remote control part
Page 8
Installation Manual 7
ENGLISH
Part Description
Junction Simple Wired remote controller
PQRNC0
FAN
SPEED
Cooling Heating Auto Dry Fan
Defrost Preheat Out door
Slo Lo
Med
Hi
Po
Room Temp
Total on
Central Run
4. Fan Speed Button
3. Temperature Control Button
1. Operation Display Panel
2. On/Off Function
Each function will be shown on the display panel for three second or so when the power is applide at first.
When changing the group control switch, the power must be reconnected to reflect the changes.
On/Off operation can be operated by central controller only on cooling mode. But we do not recommend this method.
Group control switch
1. For individual control use
2. For group control use
Ceiling height selection switch
1. Low ceiling
2. Standard ceiling
3. High ceiling
Indoor temperature sensor selection switch
1. Use the temperature sensor on the remote controller
2. Use the temperature sensor on the product.
3. Use the sensor with the lower temperature between the remote controller and indoor unit.
Page 9
8 Junction Simple Wired Remote controller
Part Description
2. Dry contact module part
Accessor
y
CN-POWER : AC 220V Connector CN-CC : Remote controller Connector CN_DRY (L) : DRY CONTROLLER Connector CN_DRY ( SIG ) : DRY CONTROLLER Connector CN_DRY (ERROR CHECK) : ERROR Check Display Connector CN_DRY( OPER STATE): Operation Display
Connector
1
DRY CONTACT UNIT
LG
[Top case]
[Bottom case]
2
3 4 5 6
White Connector (10m, For Indoor)
Remote controller
(For installation, 4EA)
Yellow Connector (10m, For Dry Contact)
(For installation, 4EA)
Dry contact - 4EA
(For assembly the case)
Dry contact
User/Installation
Manual
Installation Paper
Page 10
Installation Manual 9
ENGLISH
Junction Control System Structure
Junction Control System Structure
< Simple Wired remote control System >
< Junction Wired remote control System >
Remote Controller
DRY CONTACT UNIT
AC power
(AC 220V~
234V)
A
Radiator
LG
Operation signal
(AC power)
Dry Contact Module
Actuator
Page 11
10 Junction Simple Wired Remote controller
Installation Method
CN-REMO
LO2K
J15
LO1K
LO1D
C07D
C01K
J14
CN-DISP
CN-M CN-ZONEC
IC01A
The position of the fixing screws
< Extension Cable for Indoor unit >
< Extension Cable for Dry contact module >
Main
indoor unit
Red Yellow Brown
Main frame
Dry Contact Unit
Indoor Unit PCB
Side of
remote Controller
Side of
Indoor Unit
BlueWhite
Side of
remote Controller
Side of Dry
Contact Module
White(9pin)Yellow
DRY CONTACT UNIT
LG
White : Extension Cable for Indoor unit
Yellow : Extension Cable for Dry contact module
AC 220V
Radiator Or Other equipment
1
Put the installation paper on the place and determine the position and height of the fixing screws of the wired remote controller.
Refer to the printed side of the installation paper.
2
Plug the Air-conditioner connecting cable into the indoor unit.
Use Extension cable for connecting Remote controller to Indoor Connect cable for Air-conditioner
3
Plug the Dry contact Module connecting cable into the Dry contact Modul
Installation Method
Page 12
Installation Manual 11
ENGLISH
Installation Method
4
Remove the installation paper before installing the remote controller so that it can fit at the right place.
*
Do not embed the remote controller into the wall.
(It
may cause the breakdown of the temperature sensor.)
*
If you want to install a number of remote controller at the same place in a vertical line, install them at regular intervals of 2cm. (It may cause the breakdown of the temperature sensor.)
5
Install Dry contact Module
Connect CN-CC with Remote controller by the cable(already linked previous step)
*
Do not install the cable with a distance of 50 m or longer. (This can cause communication error.)
*
When installing the cable, check whether the connector between the remote controller and the product is installed properly. The connector will not be connected when installed in opposite sides.
Connect CN-Dry No.1 & No.4 with Actuator by the Power cable
Note : Supply the power after connecting wired remote controller. When you need to change wired remote controller, switch off the main power and change it. If the wired remote controller is changed before switching off the main power, the option function of the indoor unit can't be used. (option function like "slo" fan speed selection)
Note : The power of actuator is supplied by output of power of Dry contact
Side of
remote Controller
Fixing the
remote controller
5cm
RY2
RY1
L
N
INPUT AC 220V
N
Output AC 220V
L
CN_Dry
Page 13
12 Junction Simple Wired Remote controller
Necessary functions before using
Necessary functions before using
1
If you want to set the trial operation mode, press the Fan Speed button and None button same time for 10 seconds.
2
Then the product will begin the trial operation and the display will be like as shown on left side picture.
3
If you want to cancel the trial operation mode, just press the On/Off button.
4
The trail operation will be shut down automatically after 18 minutes and system will go to the standby mode.
Trial Operation
The trial operation is to check the installation status of the product. The temperature will not be controlled during trial operation. Instead the product will operate in several modes such as cooling, strong wind, comp-on Auto Swing.
* This function might not be available for Multi Product like Multi V system.
PQRCFCS0
Defrost Preheat
Out door
Room Temp
Total on
Central Run
FAN
SPEED
Page 14
Installation Manual 13
ENGLISH
Necessary functions before using
Out doorDefrost Preheat
PQRCFCS0
FAN
SPEED
Group No.
Indoor Unit No.
FAN
SPEED
Central Run
1
If you want to set the address on the display panel, press both temperature control buttons
(/)
same time for 10 seconds.
2
Press the temperature-increasing button to change the group number. Press the temperature-decreasing button to change the indoor unit number. e.g. As shown on the left side panel, it displays 23. Group No. : 2 Indoor Unit No. : 3
3
Set the address by pressing both temperature control buttons again
(/)
at the same time
for 2 seconds.
If you connect the indoor unit to the central controller, You should set the indoor unit address so that the central controller could recognize it.
The Central-control address is composed of the group number and the indoor-unit number.
Setting the Central-Control Address
Please set the address while using the central controller.
You don't need to set address if you don't use central controller.
Note : The remote controller displays 'HL' if central controller has locked the remote controller.
On/Off operation can be operated by central controller only on cooling mode. But we do not recommend this method.
Page 15
14 Junction Simple Wired Remote controller
Necessary functions before using
Out door
Room Temp
Total on
Central Run
Defrost Preheat
PQRCFCS0
Lo
Med
200
100
Setting the Low wind to 210 Setting the Medium wind to 175
FAN
SPEED
1
Press the room temperature button and temperature incrreasing button same time for 10 seconds
2
Set the volume of each fan speed(Low, Medium, Hi) by using the temperature control button. Press the fan speed button to select the fan speed. The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP function, it will be canceled. (The picture on the left side is the example of setting the Hi wind to ESP 10.)
4
Press the Fan Speed button and the temperature increasing button () at the same time for 2 seconds. Then the ESP setting will be activated after the temperature display flashes three times.
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is recommended that you should not use this function while using the remote controller.
EX)
* The E.S.P value is set at the proper value at the factory. So it is highly recommended that you should do not
change the E.S.P value at your discretion.
Note : You can set the ESP only indoor is running.
ESP Function
Page 16
Owner’s Manual 15
ENGLISH
Main Function of Remote Controller
On/Off Operation
Main Function of Remote Controller
1
On/off operation will operate if you press the On/Off button.
2
There is no function to choose the mode.
3
setting Temperature will be displayed as Temp code(-3, -2, -1, 0, 1, 2, 3) on the LCD
4
Press the temperature button and set the expected temperature (18~30°C)
* Refer below table
Note : when you reset the controller Both Cooling & Heating will be off. Because the code value will be '0'.
-3 18
°C
-2 20°C
-1 22°C 024°C 126°C 228°C 330°C
Temp Code Temp.
PQRCFCS0
Defrost Preheat
FAN
SPEED
A click of the button will increase the expected temperature by 2°C.
A click of the button will decrease the expected temperature by 2°C.
Page 17
16 Junction Simple Wired Remote controller
Main Function of Remote Controller
Defrost Preheat
PQRCFCS0
FAN
SPEED
1
Cooling operation could begin if you press the On/Off button.
2
When you press the temperature button and set the temperature code from -1 to -3, the cooling operation will be started according to the set Temp.
3
If you want to change operation to Heating during the cooling operation, press the Temp button and increase the Temp code from ‘1’ to ‘3’.
4
If you press the On/Off button or set the temp code by 0 during operation, the cooling and heating operation will be stopped.
You can change the fan speed during cooling operation when you turn on the controller after turn off, the controller maintain the previous mode.
Cooling Operation
Note : This controller is not permitted to control by Wireless remote controller.
But On/Off Operation and Changing Fan speed by wireless remote controller is possible only on cooling mode. (it is impossible during heating mode)
Please do not use this function by wireless remote controller.
On/Off operation also can be operated by central controller only on cooling mode. But we do not recommend
this method.
Page 18
Owner’s Manual 17
ENGLISH
Operation Table
How to use the Mode Selection Button
Room Temp
Total on
Central Run
Defrost Preheat
PQRCFCS0
FAN
SPEED
1
Heating operation could begin if you press the On/Off button.
2
When you press the temperature button and set the temperature code from ‘1’ to ‘3’, the Heating operation will be started according to the set Temp.
3
If you want to change operation to Cooling during the Heating operation, press the Temp button and decrease the Temp code from -1 to -3’.
4
If you press the On/Off button or set the temp code by 0 during operation, the heating and cooling operation will be stopped.
You can not change the fan speed during Heating
operation.
Please refer to the below Operation table for more
detail.
Heating Operation
3 Heating Mode 2 Heating Mode 1 Heating Mode
0
Both Heating/Cooling OFF
(Maintain normal Temp.)
-1 Cooling Mode
-2 Cooling Mode
-3 Cooling Mode
Display (Temp. code) Contents
Page 19
18 Junction Simple Wired Remote controller
How to use the Mode Selection Button
1
Select the proper fan speed which you want by pressing the fan speed button on the remote controller.
If you press the fan speed button, the fan speed will change in the order of Low Medium Hi.
The initial fan speed is "Hi"
If the product is not compatible with the fan speed
control, it will not function as per your selection.
You can easily control the fan speed.
Fan Speed Selection
Fan speed "Slo" can be select optionally depend on indoor product.
PQRCFCS0
Defrost Preheat
FAN
SPEED
Room Temp
Total on
Central Run
Fan Speed Selection in Cooling Operation
Lo
Med
Hi
Page 20
Owner’s Manual 19
ENGLISH
Defrost
PQRCFCS0
FAN
SPEED
FAN
SPEED
FAN
SPEED
FAN
SPEED
FAN
SPEED
FAN
SPEED
Press 10 Sec. (into the mode)
Adjust the value of Neutral
Press 2 Sec.
Adjust the value of Gap
Press 2 Sec. Save and Exit mode
1
Press the Room Temperature button(▲) and None button at the same time for 10 seconds.
2
Set the value of Neutral (code ‘0’) by using the temperature control button(▲/▼). The value of Neutral (code ‘0’) could be adjusted from 22°C to 26°C
3
Press the Room Temperature button(▲) and None button at the same time for 2 seconds.
4
Set the value of Temperature Gap per code by using the temperature control button(▲/▼). Gap Could be adjusted 1 or 2.
5
If you press the Room Temperature button
() and None button at the same time for 2 seconds, you should out the Neutral setting mode and controller will run as your setting.
Neutral / Gap setting function
How to use the Mode Selection Button
-3 -2 -1 0 1 2 3
26 23 24 25 26 27 28 29
25 22 23 24 25 26 27 28
24 21 22 23 24 25 26 27
23 20 21 22 23 24 25 26
22 19 20 21 22 23 24 25
Neutral
Temp.Code
value
Temp.Code value
Neutral
setting value
In case "Gap = 1"
-3 -2 -1 0 1 2 3
26 20 22 24 26 28 30 30
25 19 21 23 25 27 29 30
24 18 20 22 24 26 28 30
23 18 19 21 23 25 27 29
22 18 18 20 22 24 26 28
Neutral
Temp.Code
value
Temp.Code value
Neutral
setting value
In case "Gap = 2"
Default setting value
After completing the Neutral / Gap setting,
the Temp code will be "0"
Page 21
20 Junction Simple Wired Remote controller
How to use the Mode Selection Button
Power Failure compensation
1. When the power has been shut off due to power failure or other reasons, it is automatically operated as previous operation condition with the power failure compensation function.
2. In case of power failure condition, the remote controller display is off but the settings are restored to normal after the power recovery.
3. After power failure, the Neutral/Gap will come back default value. (Neutral = 24, Gap = 2)
Note : When the power Failure has occurred on [0~3] Temperature code, Power failure compensation function
is not operated. At that time Indoor, Remote controller and Radiator maintain off condition.
Error code display function
When the error is occurred on indoor unit, the error code will be displayed on remote controller
- CH and error code No. keep display by turns
Page 22
Owner’s Manual 21
ENGLISH
Memo
Loading...