This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance
is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or
gas fitter.
See Table of Contents for location of additional
Commonwealth of Massachusetts requirements.
WARNING: IF THE INFORMATION IN THIS MANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• If your gas supplier cannot be reached, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
US
A French manual is available upon request. Order Form Number
850,043CF.
Ce manuel d’installation est disponible en francais, simplement
en faire la demande. Numéro de la pièce 850,043CF.
OTL Report No. 116-F-47-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
MERIT
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS
P/N 850,043M REV. E 06/2008
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE
BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser
d'essence ni d'autre vapeurs ou liquides inflammables
dans le voisinage de cet appareil ou de tout autre
appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où
vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié
installeur, agence de service ou le fournisseur de gaz.
The assembled vented gas fireplace heater is
packaged with the folowing:
1 - The logs are packaged in a carton located
within the firebox.
2 - One bag of volcanic stones is located in the
bottom compartment.
3 - One envelope containing the litera-
ture package, which consists of the
homeowner's manual, installation instructions, log set supplement, warranty,
gas access plate, screws (4) and gasket.
The envelope is located in the bottom
compartment.
4 - One vent restrictor, to be used as detailed
on page 10.
5 - One hood and one control compartment
cover and one 45 degree starter elbow are
strapped to the top of the unit.
INTRODUCTION
These fireplaces are designed, tested and listed
for operation and installation with, and only with,
Secure Vent™ Direct Vent System Components,
Secure Flex™ Flexible Vent Components manu-
factured by Security Chimneys International and
Z-Flex™ Model GA Venting Systems, listed to
UL1777 and ULCS635 manufactured by Flexmaster Canada Limited. These approved vent
system components are labeled for identification. DO NOT use any other manufacturer's vent
components with these appliances.
Millivolt appliances are designed to operate
on natural or propane gas. A millivolt gas
control valve with piezo ignition system provides safe, efficient operation. There is no
optional blower with these units.
Both millivolt and electronic versions of these
appliances are listed by Omni-Test Laboratories for installation in bedrooms and mobile homes.
The Installation must conform to local codes
or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA
54
, or the
Natural Gas and Propane Installa-
tion Code, CSA B149.1
The appliance, when installed, must be electrically grounded in accordance with local
codes or, in the absence of local codes, with
the
National Electrical Code, ANSI/NFPA 70
or the
Canadian Electrical Code, CSA C22.1
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appliance should be inspected annually by a qualified
professional service technician. More frequent
inspections and cleanings may be required due
to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways
of the appliance be kept clean. S'assurer que le
brùleur et le compartiment des commandes sont
propres. Voir les instructions d'installation et
d'utilisation qui accompagnent l'appareil.
TYPICAL INSTALLATION
,
.
This manual is part of a set of three supporting this product. Refer to manuals 875,036M
for Care & Operations and 750,230M for Log
Placement Guide.
Please read and understand these
instructions before beginning your
installation.
2
Electronic appliances are designed to operate
on natural or propane gas. An electronic intermittent pilot ignition system provides safe, efficient operation. External electrical power is
recommended to operate these units. If the
system operates on line voltage with 3V adapters, two (2) "D" batteries can be used as a
backup in case of a power outage. The electronic appliance can be operated solely with two
(2) "D batteries.
These appliances comply with National Safety
Standards and are tested and listed by OmniTest Laboratories (Report No. 116-F-47-5) to
ANSI Z21.88 (in Canada, CSA-2.33), and CAN/
CGA-2.17-M91 in both USA and Canada, as
vented gas fireplace heaters.
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front openings of the appliance.
These appliances are designed to operate on
natural or propane gas only.
Millivolt And Electronic Models -
Millivolt and Electronic models come standard
with the manually-modulated gas valve; flame
appearance and heat output can be controlled at
the gas valve.
Input of millivolt and electronic models is
shown in the following table:
htiwsledoMcinortcelEdnAtlovilliM
evlaVsaGdetaludoM-yllaunaM
saGlarutaNsaGenaporP
DLPMV03
DLPMV53
.oNledoM
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
000,31
ot
000,01
000,91
ot
000,51
000,52
ot
005,81
000,62
ot
02000,
.oNledoM
DLPMV03
DLPMV53
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
005,11
ot
000,9
000,81
ot
000,41
005,12
ot
005,61
000,52
ot
000,91
All Models -
Maximum manifold pressure is 3.5 in. w.c.
(0.87 kPa) for natural gas and 10 in. w.c.
(2.49 kPa) for LP/Propane gas.
Note: Power venting of direct vent fireplaces
may result in the reduction of efficiencies by
as much as ten percent. Consider this in
making any venting and heating decisions in
any installation application.
Installations at Altitudes of 0 to 4500 ft.Units are tested and approved for elevations
of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.For elevations above 4500 feet (1372
meters), install the unit according to the
regulations of the local authorities having
jurisdiction and, in the USA, the latest edition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the
CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
The millivolt appliances are manually controlled
and feature a spark ignitor (piezo) that allows the
appliance's pilot gas to be lit without the use of
matches or batteries. This system provides
continued service in the event of a power outage.
.taN.porP
54#
)"280.0(
14#
)"690.0(
04#
)"890.0(
ezisecifirO
16#
)"930.0(
"840.0
45#
)"550.0(
35#
ledoM
.oN
03VDLPM"070.0
53VDLPM
04VDLPM
54VDLPM
Table 1
Do not use these appliances if any part has been
under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control
system and any gas control which have been
under water.
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
EUFA
un technicien qualifié pour inspecter l'appareil et
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home,
where not prohibited by local codes. This
appliance is only for use with the type of
gas indicated on the rating plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
Cet appareil peut être installé dans un
maison préfabriquée (É.-U. seulement)
ou mobile déjà installée à demeure si
les réglements locaux le permettent.
Cet appareil doit être utilisé uniquement
avec les types de gaz indiqués sur la
plaque signalétique. Ne pas l'utiliser
avec d'autres gaz sauf si un kit de conversion certifié est installé.
Test gage connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for the
manifold side). A 1/8" NPT test gage connection is provided at the inlet and outlet side of
the electronic gas control valve.
Minimum inlet gas pressure to these appliances is 5.0 inches water column (1.24 kPa)
for natural gas and 11 inches water column
(2.74 kPa) for propane for the purpose of input
adjustment.
noitavelE
teeF
)sretem(
Maximum inlet gas supply pressure to these
appliances is 10.5 inches water column (2.61
kPa) for natural gas and 13.0 inches water
column (3.23 kPa) for propane.
These appliances must be isolated from the
0054-0
)2731-0(
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2
)"5950.0(
psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures in excess of
1/2 psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These heater rated appliances are intended
for use as supplemental heaters only. Using
these appliances as a primary heat source
may void the manufacturers warranty.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or
nausea. If you have these signs, obtain fresh
air immediately. Turn off the gas supply to
the appliance and have it serviced by a
qualified professional, as it may not be operating correctly.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
WARNING: FAILURE TO COMPLY WITH
THE INSTALLATION AND OPERATING
INSTRUCTIONS PROVIDED IN THIS
DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING
APPLIANCE, VOIDING ITS WARRANTY.
ANY CHANGE TO THIS APPLIANCE AND/
OR ITS OPERATING CONTROLS IS DANGEROUS. IMPROPER INSTALLATION OR
USE OF THIS APPLIANCE CAN CAUSE
SERIOUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON MONOXIDE POISONING.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES. USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN
THE SAME ROOM AS THE APPLIANCE.
WARNING: DO NOT PLACE CLOTHING
OR OTHER FLAMMABLE MATERIALS
ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES À
COTE DE L'APPAREIL.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to the
exterior and access to the fuel supply are also
important. Consideration should be given to
traffic ways, furniture, draperies, etc., due to
elevated surface temperatures (
The location should also be free of electrical,
plumbing or other heating/air conditioning ducting. These direct vent appliances are uniquely
suited for installations requiring a utility shelf
positioned directly above the fireplace. Utility
shelves like these are commonly used for locating television sets and decorative plants.
Figure 2
).
Figure 3
KCAB
SEDIS
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
fomottoBmorF
gnilieCottinU
TNEV*)mm4.52(.ni1
TNORF)sretem9.0(.teeF3
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Above Fireplace With Top Venting
)mm4.52(.ni1
**)mm4.52(.ni1
*Note: 3 in. (76mm) above any horizontal/
inclined vent component for the MPLDV30
srecaps)mm0(.ni0
in all cases, and for the MPLDV35, MPLDV40
& MPLDV45, when the vent center line is
greater than 48" (1219 mm) above the fire-
srecaps)mm0(.ni0
place top wrapper surface. Increase this
clearance to 5" (127 mm) for the MPLDV35,
MPLDV40 & MPLDV45, when the vent center line is less than 48" (1219 mm) above the
)mm6261(.ni46
fireplace top wrapper surface.
**Note: See page 6, step 1 for clearance
requirements to the nailing flange located at
SECNARAELCECIVRES
each side of the unit and any screw heads
adjacent to it.
To provide for the lowest possible shelf surface
the venting attached to the top vent should be
routed in a way to minimize obstructions to the
use of the space above the appliance. Do not
insulate the space between the appliance and
the area above it. Refer to
Figure 3
. The
minimum height from the base of the appliance
to the underside of combustible materials used
to construct a utility shelf in this fashion is
shown in the table in
Figure 3
.
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.
APPLIANCE AND VENT CLEARANCES
Refer To Table 2 for approved clearances to
combustibles for the models covered in this
manual, with the following exception: When the
unit is installed with one side flush with a wall,
the wall on the other side of the unit must not
extend beyond the front edge of the unit. In
addition, when the unit is recessed, the side
walls surrounding the unit must not extend
beyond the front edge of the unit. See
Maintain a minimum 1" (25 mm) clearance
to combustible materials for all vertical
vent elements.
Clearances for horizontal vent elements are
1" (25 mm) at the sides and 1" (25 mm) on
the bottom. Clearances above horizontal
vent elements are 3" (76 mm) for all models
and all applications.
Exception: Clearance
is 5" (127 mm) for MPLDV35, MPLDV40 &
MPLDV45, when the center line of the horizontal run is less than 48" (1219 mm) above
the fireplace top wrapper surface.
Figure 2
Massachusetts And New York City, NY
Requirements
These appliances are approved for installation
in the following USA locations listed in the
following:
Massachusetts:
These fireplaces are approved for installation
in the US state of Massachusetts if the following additional requirements are met-
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a Thandle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector with
an alarm and battery back-up must be installed
on the floor level where the gas fireplace is
installed. The carbon monoxide detector must
.
comply with NFPA 720, be ANSI/UL 2034
listed and be ISA certified.
• A metal or plastic identification plate must be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade and be directly in line with the
horizontal termination. The sign must read, in
print size no less than one-half (1/2) inch in
size, GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS.
New York City, NY:
These fireplaces are approved for installation
in New York City in the US state of New York.
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building
components according to
Figure 4
.
Terminate multiple vent terminations according to the installation codes listed at the top of
this page.
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
Vertical
Wall
X
12
Roof Pitch is X/12
Figure 4
Horizontal Vent Termination Clearances
The horizontal vent termination must have a
minimum of 3" (76 mm) clearance to any overhead combustible projection of 2-1/2" (64 mm)
or less. See
ing 2-1/2" (64 mm), see
terminations may be located as close as 6"
(152mm) to any (non-combustible and combustible) exterior sidewall. This distance may
be decreased to 2" (51mm) for non-combustible exterior sidewalls only, if the SV4.5HT-2
termination is used. For additional vent location restrictions, refer to
Figure 5.
For projections exceed-
Figure 5
. All horizontal
Figure 8 on page 7
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows,
however, each installation is unique resulting in
variations to those described.
See the page numbers references in the following steps for detailed procedures.
Step 1. (page 6) Construct the appliance framing. Position the appliance within the framing
and secure with nailing brackets.
Step 2. (page 6) Route gas supply line to
appliance location.
Step 3. (page 10) Install the vent system
and exterior termination. Install additional
restrictor, if needed.
Step 4. (page 21) Field Wiring
a. Millivolt Appliances – The operating control
switch is factory installed.
b. Electronic Appliances – Connect 120 Vac
electrical power to the appliance receptacle.
Step 5. (page 22) Make connection to gas
supply.
Step 6. (page 23) Install the logs and glowing embers.
The appliance is shipped with all gas controls
and components installed and pre-wired. Remove the shipping carton, exposing the front
glass door. Remove the bottom panel by lifting
and pulling it towards the front.
Open the two latches (located under the firebox
floor) securing the glass door. Remove the
door by tilting it outward at the bottom and
lifting it up. Set the door aside protecting it from
inadvertent damage.
See Figure 39 on page 23.
Horizontal Vent Termination Clearances
Combustible Projection
2-1/2
inches or less in length
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
Figure 5 -
12"
(305 mm)
Termination Kit
Side Elevation View
3"
(76 mm)
Step 1. FRAMING
Frame these appliances as illustrated in
on page 8,
in a corner
See
unless the appliance is to be installed
.
Figure 10 on page 8
for corner framing
installations. All framing details must allow for a
minimum clearance to combustible framing members as shown in
Table 2 on page 4
If the appliance is to be elevated above floor level,
a solid continuous platform must be constructed.
Headers may be in direct contact with the appliance top spacers but must not be supported by
them or notched to fit around them. All construction above the appliance must be self supporting,
DO NOT use the appliance for structural support.
The fireplace should be secured to the side framing
members using the unit's nailing flanges - one top
and bottom on each side of the fireplace front. See
Figure 6.
Use 8d nails or their equivalent.
Figure 9
.
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside
of the left side framing as shown in
Gas lines must be routed, constructed and
made of materials that are in strict accordance
with local codes and regulations.
All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff
valve. (See step 6 on page 22).
Figure 7
All horizontal terminations
may be located as close as
6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to 2”
(51mm) for non-ncombustible exterior
sidewalls only, if the
SV4.5HT-2 termination
is used.
Side
Framing
Left Side Top Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members
and screw heads located in areas directly adjacent
to the nailing flanges, are EXEMPT from the 1”
clearance to combustible requirements for the
firebox outer wrapper. Combustible framing may be
in
direct contact with the nailing flanges and may
be located closer than 1” from screw heads and the
firebox wrapper in areas adjacent to the nailing
flanges. Frame the opening to the exact dimensions
specified in the framing details of this manual.
To The Framing
Termination Kit
Nailing Flanges Are
Provided At All Four
Corners At 5/8”, 1/2”
And Flush Settings
Note: The appliance 45° collar can be rotated about its axis to align for
corner installation. Remove interfering corner spacer. This spacer is
used for shipping only.
b
7 (178)
May Be
Removed
*D
*C
a
May Be
Removed
*E
NoteVenting requirements for corner installations - the horizontal vent length
“a” to “b,” must not exceed 28 inches (711 mm)
Corner Framing with Square Termination (SV4.5HT-2)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
8
Figure 10
Back wall of chase/enclosure
(including any finishing materials)
*These dimensions occur when one 45 degree elbow
is connected directly to the appliance collar.
A
*B
Inches
(millimeters)
FIREPLACE SPECIFICATIONS
F
G
6 5/8
(168)
TOP VIEW
4 3/4
(121)
LEFT SIDE VIEW
2 9/32
(58)
13 11/64
(335)
E
3 5/16 (100 mm)
10
(254 mm)
A
C
D
H
B
FRONT VIEW
17
(432)
RIGHT SIDE VIEW
1
(25.4)
Unit Dimensions
Figure 11
.oNledoMABCDEFGH
.ni2/1042/1738/5028/1424/1034/3918/794/172
03VDLPM
mm9201359435316867205152296
.ni2/1042/1738/5028/1924/1534/3428/3214/172
53VDLPM
mm9201359435047598926413296
.ni2/1542/1248/5528/1434/1044/3928/7414/123
04VDLPM
mm651108011567682201657873918
.ni2/1542/1248/5528/1934/1544/3438/3714/123
54VDLPM
mm651108011564999411388144918
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and B149.2 in Canada.
These fireplaces are designed, tested
and listed for operation and installation
with, and only with, Secure Vent™ Direct
Vent System Components, Secure Flex™
Flexible Vent Components manufactured
by Security Chimneys International and
Z-FLEX™ Model GA Venting Systems
listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
These approved vent system components
are labeled for identification. DO NOT
use any other manufacturer's vent components with these appliances.
These fireplaces must be vented directly
to the outside.
Determine the venting for the appliance. If the
vent run will include at least 8 feet of vertical
rise, then install the second restrictor in the
appliance collar before connecting any vent
(Refer to
tor inside the fixed restrictor.
Note: The second restrictor is included within
the firebox.
Figure 12
Exhaust Vent
). Place the second restric-
Fixed Restrictor
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosing wall (such as a chase). There is no requirement for inspection openings in the enclosing
wall at any of the joints in the vent pipe.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, determine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior
wall) vent applications. Refer to the section
relating to your installation. A list of approved
venting components is shown in the tables on
page 26.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 13, 17 and 23 through 25 on pages
12, 14 and 15
and their associated Vertical
Vent Tables illustrate the various vertical venting configurations that are possible for use
with these appliances. Secure Vent pipe applications are shown in these figures; SecureFlex pipe may also be used.
A Vertical Vent Table summarizes each system’s
minimum and maximum vertical and horizontal
length values that can be used to design and
install the vent components in a variety of
applications.
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edition) (In Canada,
the current CAN-1 B149 installation code) by
major building codes. Always consult your
local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer
to
Figure 4
on page 6 ).
Vertical (Straight) Installation
SV4.5CGV-1
Termination
40' Max.
(12.2 M)
6' Min.
(1.8 M)
SV4.5FA OR
SV4.5FB Flashing
AND SV4.5SC
STORM COLLAR
1" (25.4 mm)
Minimum
Clearance to
Combustibles
*SV4.5VF
Firestop/Spacer
SV4.5L6/12/24/36/48
Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
Figure 13
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to Vertical Vent Fig-ures and Tables on page 14 and 15 to select
the type of vertical installation desired. Vent
sections are available in net lengths of 4-1/2"
(114 mm), 10-1/2" (267 mm), 22-1/2" (572
mm), 34-1/2" (876 mm) and 46-1/2" (1181
mm). Refer to the Vent Section Length Charton page 11 for an aid in selecting length
combinations. Elbows are available in 90° and
45° configurations. Refer to
SV4.5E45 and SV4.5E90 elbow dimensional
specifications.
Figure 18
for the
10
Second Restrictor (For Vertical Vent Only)
Figure 12
Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267
mm), 22-1/2" (572 mm), 34-1/2" (876 mm)
and 461/2" (1181 mm) net section lengths
are available. Plan the vent lengths so that a
joint does not occur at the intersection of
ceiling or roof joists. Refer to the Vent
Section Length Chart.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.