LG MFL40910613, Air Conditioner Installation Manual

ENGLISH FRANÇAIS ESPAÑOL
LG Air Conditioner
INSTALLATION MANUAL
LG
website http://www.lgservice.com
IMPORTANT
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
2 Air Conditioner
IMPORTANT!
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-410A causes frostbite burns.
• R-410A is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid,
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Special warnings
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
Installation Manual 3
ENGLISH
Air Conditioner Installation Manual
CONTENTS
Safety Precautions ..............................................................................................4
Installation of Indoor, Outdoor unit ...................................................................7
The indoor unit installation ..............................................................................10
Remote controller installation..........................................................................13
Wiring connection .............................................................................................16
Flaring Work and Connection of Piping ..........................................................20
Installation to decorative panel........................................................................23
Indoor unit drain piping ....................................................................................25
Test running .......................................................................................................29
Leakage test and Evacuation ...........................................................................32
Installation guide at seaside ............................................................................33
4 Air Conditioner
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to proper ties only.
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Always perform grounding.
• Otherwise, it may cause electrical shock.
Dont use a power cord, a plug or a loose socket which is damaged.
• Otherwise, it may cause a fire or electrical shock.
For installation of the product, always contact the service center or a professional installation agency.
• Otherwise, it may cause a fire, electrical shock, explosion or injury.
Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
• If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Always install an air leakage breaker and a dedicated switching board.
• No installation may cause a fire and electrical shock.
Do not keep or use flammable gases or combustibles near the air conditioner.
• Otherwise, it may cause a fire or the failure of product.
Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
• It may cause injury or an accident.
Do not disassemble or repair the product randomly.
• It will cause a fire or electrical shock.
Safety Precautions
Installation Manual 5
ENGLISH
Do not install the product at a place that there is concern of falling down.
• Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
• Sharp edges may cause injury.
Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
• Otherwise, it may cause a fire or electrical shock.
Do not use the power cord near the heating tools.
• Otherwise, it may cause a fire and electrical shock.
Do not open the suction inlet of the indoor/outdoor unit during operation.
• Otherwise, it may electrical shock and failure.
Do not allow water to run into electrical parts.
• Otherwise, it may cause the failure of machine or electrical shock.
Hold the plug by the head when taking it out.
• It may cause electric shock and damage.
Never touch the metal parts of the unit when removing the filter.
• They are sharp and may cause injury.
Do not share the outlet with other appliances.
• It will cause an electric shock or a fire due to heat generation.
Do not use the damaged power cord.
• Otherwise, it may cause a fire or electrical shock.
Do not modify or extend the power cord randomly.
• Otherwise, it may cause a fire or electrical shock.
Take care so that the power cord may not be pulled during operation.
• Otherwise, it may cause a fire or electrical shock.
Unplug the unit if strange sounds, smell, or smoke comes from it.
• Otherwise, it may cause electrical shock or a fire.
Keep the flames away.
• Otherwise, it may cause a fire.
Do not step on the indoor/outdoor unit and do not put anything on it.
• It may cause an injury through dropping of the unit or falling down.
Do not place a heavy object on the power cord.
• Otherwise, it may cause a fire or electrical shock.
When the product is submerged into water, always contact the service center.
• Otherwise, it may cause a fire or electrical shock.
Take care so that children may not step on the outdoor unit.
• Otherwise, children may be seriously injured due to falling down.
Operation
6 Air Conditioner
Safety Precautions
Installation
Install the drain hose to ensure that drain can be securely done.
• Otherwise, it may cause water leakage.
Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
• Otherwise, it may cause dispute with the neighbors.
Always inspect gas leakage after the installation and repair of product.
• Otherwise, it may cause the failure of product.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water leakage.
Avoid excessive cooling and perform ventilation sometimes.
• Otherwise, it may do harm to your health.
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
• The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or ar t ar ticles.
• Otherwise, it may damage your properties.
Do not place obstacles around the flow inlet or outlet.
• Otherwise, it may cause the failure of appliance or an accident.
Operation
Installation of Indoor, Outdoor Unit
Installation Manual 7
ENGLISH
Installation of Indoor, Outdoor Unit
1. Indoor unit Cassette type
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance space.
Floor Standing type
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance space.
Selection of the best location
Ceiling
Ceiling Board
Ceiling Board
Floor
Unit:mm(inch)
Unit:mm(inch)
300(11-
13
/
16
)
or more
Above 2500(98-
7
/
16
)
4000(157-
1
/
2
) or less
1000(39-
3
/
8
)
or more
500(19-11/16)
or more
500(19-
11
/16)
or more
300(11-
13
/
16
) or less
400(16)
400(16)
50(2)
1000(39.4)
8 Air Conditioner
Installation of Indoor, Outdoor Unit
2. Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows around front, back and side of the unit.
3. Do not place animals and plants in the path of the warm air.
4.Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
more than 700
(27 9/16)
more than 300
(11 7/16)
more than 300
(11 7/16)
more than 600
(23 21/32)
more than 600
(23 21/32)
Unit:mm(inch)
Installation of Indoor, Outdoor Unit
Installation Manual 9
ENGLISH
3. Piping length and the elevation
24k Btu/h
15.88(5/8) 9.5(3/8)
7.5(25) 5(16) 35(0.38)
Gas Liquid Standard Max. Standard Max
.
Capacity
Pipe Size Length A Elevation B
*Additional
Unit : mm(inch) Unit : m(ft) Unit : m(ft)
refrigerant
Unit : g/m(oz/ft)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION:
Rated performance for refrigerant line length of:7.5m(25ft)
Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters(32.8 ft).
50(164)
cassette type
30(98)
Floor standing type
30(98)
cassette type
20(66)
Floor standing type
10 Air Conditioner
The indoor unit installation
The indoor unit installation
1. Cassette type
Level gauge
Ceiling
Ceiling board
TM/TN/TP Chassis
Unit:mm(inch)
875(34-7/16) (Ceiling opening)
787(30-15/16)
(Hanging bolt)
bolt)
684(26-15/16)(Hanging bolt)
671(26-7/16)
875(34-7/16) (Ceiling opening)
840(33-1/16)
Unit size
840(33-1/16)
Unit size
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
NOTICE
CAUTION :
This air-conditioner uses a drain pump.
Install the unit horizontally using a level gauge.
During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
The indoor unit installation
Installation Manual 11
ENGLISH
Set screw of
paper model (4 pieces) Paper model for installation
Ceiling board
150mm
(5-7/8 inch)
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm(1-1/2 inch)
Open the ceiling board along the outer edge of the paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
Nut
(W3/8 or M10) Spring washer
(M10)
Air Conditioner body
Keep the length of 15~18mm(5/8~3/4 inch) between the air conditioner bottom surface and the ceiling surface
• The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
CAUTION :Tighten the nut and bolt to prevent unit from falling off.
• Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
12 Air Conditioner
The indoor unit installation
2. Floor Standing type
Wall
Core Drill
Tilt
Cut if necessary
More than 15mm(0.6 inch)
Wall
Plastic tube (Bushing)
INSIDE OUTSIDE
200(7.9)
70 (2.8)
70 (2.8)
200(7.9)
Unit : mm (inch)
1.The mounting floor should be strong and solid enough to prevent it from vibration.
2. Drill the piping hole with 70mm diameter hole­core drill at either the right or the left of indoor unit. The hole should be sightly slant to the outdoor side.
3. Insert the plastic tube through the hole.
4. Cut the extruded outside part of the plastic tube, if necessary.
Remote controller installation
Installation Manual 13
ENGLISH
Operation unit
ZONE
1234
Humidify
JET
AUTO
AUTO SWING OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI MED LO
Heater Defrost Filter
Preheat Out door
Time
Timer
On Set no.Time
Off
0103 05 07 0911 13 1517 19 2123
O
p
e
r
a
t
io
n
u
n
it
Z
O
N
E
1
2
3
4
H
u
m
i
d
i
f
y
JE
T
A
U
T
O
A
U
T
O
S
W
IN
G
O
P
E
R
A
T
IO
N
FAN
S
PEED
P
r
o
g
r
a
m
s
e
t
S
U
B
F
U
N
C
T
I
O
N
S
E
T
T
E
M
P
R
o
o
m
T
e
m
p
HI MED L
O
H
e
a
t
e
r
D
e
f
r
o
s
t
F
i
l
t
e
r
P
r
e
h
e
a
t
O
u
t
d
o
o
r
Time
Timer
O
n S
e
t n
o
.
T
im
e O
ff
0
1
0
3
05
07
09
11
1
3
15
1
7
1
9
21
2
3
5feet
(1.5meters)
Direct
Sun ray contact area
no
no
no
yes
Operation unit
ZONE
1234
Humidify
JET
AUTO
AUTO SWING OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI MED LO
Heater Defrost Filter
Preheat Out door
Time
Timer
On Set no.Time
Off
0103 05 07 0911 13 1517 19 2123
• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED.display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1.
Wired remote controller installation
Remote controller installation
(Fig.1)
14 Air Conditioner
Remote controller installation
1. Connect the wired remote controller cable to the wired remote controller installation board as shown in the right picture.
2. After fixing the cable to the guide slot, attach the wired remote controller installation board at the desired location.
• Before fixing the wired remote controller cable
to the guide slot, remove any clogged part of the case in the direction to install before the installation.
3. After locating the wired remote
controller installation board at the desired location, screw the unit firmly. (When there is a buried box, install the wired remote controller board to fit the
buried box.)
• Use the screw provided.
4. After fixing the top part of the wired
remote controller to the installation board as shown in beside picture, press the bottom part to assemble the controller to it’s board.
When disassemble the wired remote controller from the installation board, use the driver as shown in the right picture and insert it into the hole with the arrow. And when you pull the driver in the front direction, the wired remote controller will be separated.
12V Red wire
SIG Yellow wire
GND Black wire
The wired remote controller cable is connected as factory default.
12V SIG GND
Red Yellow Black
Remote Controller Cable
Guide slot
Fixate the remote controller cable to the guide slot.
Use the screws for fixate the unit firmly on the wall.
Installation board
<Front side of
installation board>
<Rear side of
installation board>
Top
Bottom
Wall Side
Wall
Side
Wall
Side
Wall
Side
Wall
Side
Installation of Wired remote controller(Cassette type)
Installation Manual 15
ENGLISH
Remote controller installation
5. Use the connecting cable to connect the indoor unit and the wired remote controller.
6.When the distance between the wired remote controller and the indoor unit is 10m and above, use the extension cable.
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable:2547 1007 22# 2 core 3 shield 5 or above.
Check whether the connector is connected correctly.
Connecting cable
Indoor unit side
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
1. Remove the battery cover from the remote controller.
• Slide the cover according to the arrow direction.
2. Insert the two batter ies.
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
3. Re-attach the cover.
• Slide it back into position.
• Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and performance.
• Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.
Wireless remote controller installation
16 Air Conditioner
Wiring Connection
Power Input
Terminals on the outdoor unit
1(L1) 2(L2)
3
2(L2)1(L1)
Terminal Block Indoor
1(L1) 2(L2) 3 4 5
Connected to outdoor unit
TO AIR FRESH
KIT
OPTION
Wiring Connection
WARNING : Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazzard may also exist. Therefore, be sure all wiring is tightly connected.
RECOMMENDATION:
The power cord connected to the outdoor unit should be
comply with the following specifications: ETL recognized and CSA certified.
GN/YL
Line voltage (208/230V)
AWG12
GN/YL
AWG18
RECOMMENDATION:
When using the separate wires as the power cord, please secure the separate wires into the control box panel using tie wraps to hold all wires together in place.
The power connecting cable connected to the indoor and outdoor unit should be comply with the following specifications: ETL recognized and CSA certified.
Wiring Connection
Installation Manual 17
ENGLISH
To Outdoor Unit
A
3
2(L2)1(L1)
Procedure for Connecting the Cable to Indoor Unit, is as follows:
1. Open The Front Door Manually, as shown in Fig. 1.
2. Open the Control Box Cover (A) with Driver, ( ) as shown in Fig. 2.
3. Connect the Cables (LG doesn't supply) to the terminal Block of Indoor Unit, as shown in Fig. 3.
4. Install a power supply line or connecting cables as the Fig. 4 in order to prevent the connecting wires from being cut by sharp edge of the hole.
5. Secure the Control Box Cover (A) to its original position with the help of Driver( ).
6. Close the Front Door.
(Fig.1)
Detail Wiring for Indoor Unit
(Fig.3)
(Fig.2)
2. Floor Standing type
1. Cassette type
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover screw
Lock nut
Conduit mounting plate
Conduit
Connecting the Cable to Indoor Unit
18 Air Conditioner
Wiring Connection
Lock nut
(field supply)
Conduit (field supply)
Conduit panel
Power supply line or Connecting cable
Cap(Remove)
(Fig.4)
Installation Manual 19
ENGLISH
Electrical Wiring
Connecting the cable to Outdoor Unit
Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4.The terminal screws inside the control box may be loose due to vibration during transpor t. Check the screws for loose connection. (Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
1. Remove the Cover control from the unit by loosening a screw. Connect the wires to the terminals on the control board individually as following.
2. Secure the cable onto the control board with the holder (clamper).
3. Refix the cover control to the original position with the screw.
4. Use a recongnized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
CAUTION:
The circuit diagram is not subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the wiring diagram.
Air
Conditioner
Main power source
Circuit Breaker Use a 25A circuit breaker or time delay fuse.
Outdoor unit
Over 5mm (3/16 inch)
Holder for
power supply
cord
Connecting
cable
Control cover
Terminal block
Power supply
cable
20 Air Conditioner
Wiring Connection
Connection method of the connecting cable(Example)
(1) Remove two-caps on the conduit panel.
(for low voltage line) (2) Pull out connection cable through conduit. (3) After conduit to the panel, fix nut to the opposite
side of panel. (4) Pass the connection cabel through the hole. (5) Properly connect the cable on the terminal block. (6) Fix the connection cable with cord clamp
provided on the unit not to have strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight
WARNING: Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist.Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For strand wiring
(1) Cut the wire end with a wire cutter or wire-
cutting pliers, then strip the insulation to expose the strand wiring about 10 mm(3/8").
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace
and tighten the terminal screw using a screwdriver.
G
Terminal block
Lock nut
Power supply line (1Ø, 208/230V)
Conduit panel
Cap(Reuse)
Cord clamp
Conduit Hole Cap(Remove)
Taping (for sealing)
Connecting cable (1Ø, 208/230V)
Power supply cable
Connecting Cable
Strip 10 mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
Lock nut (field supply)
Conduit (field supply)
Conduit panel
Power supply line or Connecting cable
Flaring Work and Connection of Piping
Installation Manual 21
ENGLISH
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m(4.9ft) longer than the pipe length.
2) Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
3) Putting nut on
Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
4) Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
5) Check
Compare the flared work with figure.
If flare is noted to be defective, cut off the
flared section and do flaring work again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flaring Work and Connection of Piping
Flaring work
mm inch mm inch Ø6.35 1/4 1.1~1.3 0.04~0.05 Ø9.52 3/8 1.5~1.7 0.06~0.07 Ø12.7 1/2 1.6~1.8 0.06~0.07
Ø15.88 5/8 1.6~1.8 0.06~0.07 Ø19.05 3/4 1.9~2.1 0.07~0.08
Outside diameter A
22 Air Conditioner
1. Form the piping according to its routing.
Avoid bending and bending back the same piping point more than three times. (This will result in hardening the pipe.)
2. After deforming the piping, align centers of
the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches.
3. Connect pipe to the service valve or ball
valve which is located below the outdoor unit.
4. After completing the piping connection, be
sure to check if there is gas leakage in indoor and outdoor connection.
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service por ts of both the liquid and gas side valves.
CAUTION:
Use two wrenches and
tighten with regular torque.'
Outdoor
unit
Liquid side
Flare connection
Flare connection
Gas side
Indoor
unit
Union
Piping Connection
Vacuum dr ying
Outside diameter torque
mm inch kgf.m(lbf.ft)
Ø6.35 1/4
1.8~2.5 (13~18)
Ø9.52 3/8
3.4~4.2 (24~30)
Ø12.7 1/2
5.5~6.6 (40~48)
Ø15.88 5/8
6.3~8.2 (46~59)
Ø19.05 3/4
9.9~12.1 (72~88)
Flaring Work and Connection of Piping
Installation Manual 23
ENGLISH
Installation to Decorative Panel
Installation to Decorative Panel
The decorative panel has its installation direction. Before installing the decorative panel, always remove the paper template.
1. Remove the packing and take out air inlet grille from front panel.
2. Remove the Corner covers of the panel.
3. Fit the panel on the unit by inser ting hooks as shown in picture.
4. Insert two screws on diagonal corners of panel. Do not tighten the bolts completely. (The fixing screws are included in the indoor unit box.) Check the alignment of panel with the ceiling. Height can be adjusted using hanging bolts as shown in picture. Inser t the other two screws and tighten all screws completely.
Front grille
Coner cover
Hook clip
Hook
24 Air Conditioner
Installation to Decorative Panel
5. Fit the cor ner covers.
6. Open two screws of control panel cover.
7. Connect one display connector and two
vane control connectors of front panel to indoor unit PCB. The position marking on PCB is as: Display connector : CN-DISPLAY Vane control connector : CN-VANE 1,2
8. Close the cover for control box.
9. Install the air inlet grille and Filter on the
panel.
Screw
CN-VANE 1,2
CN-DISPLAY
Installation Manual 25
ENGLISH
Indoor Unit Drain Piping
Air conditioner unit
Ceiling
board
Decorative panel
Decorative panel
Fit the insulator (this part) and be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
CAUTION:
Install certainly the decorative panel.
Cool air leakage causes sweating.
Water drops fall.
Indoor Unit Drain Piping
1.The drain hose should point downward for
optimum drainage.
2. Incorrect Installation Examples:
How to use the finishing tape for the drainpipe
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Kinking
Water leakage
Water leakage
Ditch
Less than 50mm (1 31/32 inch) gap
Water leakage
[Floor Standing Type]
Connecting pipe
Glue
Drain pipe
Refrigerant pipe
Refrigerant pipe
(Indoor unit}
Connecting wire
Pipe
Pipe
Finishing tape
Insulating material
After applying the glue, insert the drainpipe completely.
Wind the insulating material to connect the insulating material of the indoor unit and the insulating material of the connecting pipe.
Wind the finishing tape around the connecting pipe, the drainpipe, and the wire.
26 Air Conditioner
Indoor Unit Drain Piping
CAUTION :The supplied flexible drain hose should not be curved, neither screwed.The curved or screwed hose may cause a leakage of water.
• Connect the main drain pipe to the exterior and
leave it provisionally until the test comes to an end.
• Feed water to the flexible drain hose and chec k
the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is complete.
• When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Drain test
Feed water
Drain Pump
Drain pan
Flexible drain hose (accessory)
Main drain pipe
Glue the joint
Drain port
Drain hose connection Use the clip (accessory)
1/50~1/100
Flexible drain hoseFlexible drain hose
[Cassette T ype]
• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
• Dur ing drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is 32mm(1 1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm(1 inch) and pipe fittings
Heat insulation material: Polyethylene foam with thickness more than 8mm(5/16 inch).
Maintenance drain port
Upward routing not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX : 800mm (32-1/2 inch)
Indoor Unit Drain Piping
Installation Manual 27
ENGLISH
1. Use the heat insulation material for the refrigerant piping which has an excellent heat­resistance [over 120°C(248°F)].
2. Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default.However, if it is operated for a long time in high humid atmosphere [dew point temperature: more than 23°C(73.4°F)], water drops are liable to fall.In this case, add heat insulation material according to the following procedure:
• Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm.
• Stick glass wool on all air conditioners that are located in ceiling atmosphere.
Heat insulation
Attention
1. Possible drain-head height is up to 700mm(27 9/16 inch). So, it must be installed below 800mm (32-1/2 inch).
2. Keep the drain hose downward up to 1/50~1/100 inclination. Prevent any upward flow or reverse flow in any part.
3. 5mm(3/16 inch) or thicker formed thermal insulator is provided for the drain pipe.
4. Upward routing is not allowed.
5. Be sure to check the drain pump for normal operation and abnormal noise when electrical wiring is complete.
1/50~1/100
MAX : 800mm (32-1/2 inch)
Elbow
Drain pump
Unit
Drain pipe (Local supply)
Thermal insulator
(Local supply)
Wall
Drain hose
Indoor unit
Thermal insulator (accessory)
Fastening band (accessory)
Refrigerant piping
28 Air Conditioner
Indoor Unit Drain Piping
Forming the piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
• If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground.Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1.Tape the piping, drain hose and connecting
cable from down to up.
2. Secure the tapped piping along the exterior
wall using saddle or equivalent.
Trap is required to prevent water from entering into electrical parts.
Seal a small opening around the pipings with gum type sealer.
Taping
Drain hose
Pipings
Connecting cable
Plastic Band
Power supply cord
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1.Tape the piping and connecting cable from
down to up.
2. Secure the taped piping along the exterior
wall. Form a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or
equivalent.
Settlement of outdoor unit
1. Anchor the outdoor unit with a bolt and
nut[ø10mm(0.39in)] tightly and horizontally on a concrete or rigid mount.
2.When installing on the wall, roof or rooftop,
anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
3.
If the vibration of the unit is transmitted to the hose, secure the unit with an anti-vibration rubber.
Seal a small opening around the pipings with gum type sealer.
Trap
Installation Manual 29
ENGLISH
Test running
1. PRECAUTIONS IN TEST RUNNING
• The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated.
CAUTION For test run, carry out the cooling operation firstly even during heating
season. If heating operation is carried out firstly, it leads to the trouble of compressor.Then attention must be paid. Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later automatically)
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured data, etc.
• Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure.
• As to the structure and appearance, check following items.
2. Connection of power supply
1. Connect the power supply cord to the independent power supply.
• Circuit breaker is required.
2. Operate the unit for fifteen minutes or more.
3. Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
Is the circulation of air adequate? Is the draining smooth? Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated? Is there any faulty wiring? Are not terminal screws loosened?
M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}
Test running
Thermometer
30 Air Conditioner
Test running
Function Code Set
1
2
Keep pressing button setting for 4 secs to enter installer setting mode until code displayed in timer segment.
1
Press button to start.
2
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode. For details related to this operation, refer to the product manual.
18˚C cooling, High Fan Speed, Airflow direction mode will be operated during 18 minutes with ignoring
room temperature.
After running 18 minutes under test run mode, system will automatically turn OFF.In case of duct type, the Airflow UP/DOWN function is not displayed.Dur ing test r un mode, receiving signal from wireless remote controller will release this operation.
If you press any kind of button, Test Run mode will be released.
Cassette type
Floor Standing type
Push the temperature low key and On/Off Key For over 3 sec simultaneously indoor side
FAN
SPEED
ON
OFF
MODE
Loading...
+ 73 hidden pages