LG LTNC242QLE0 INSTALLATION MANUAL

P/NO : MFL42291413
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
TYPE : Ceiling Cassette
www.lg.com
2 Ceiling Cassette Air Conditioner
Ceiling Cassette Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions ..............................3
Introduction..........................................6
Symbols used in this Manual ............6
Features ............................................6
Installation............................................7
Installation Tools................................7
Installation of Indoor,
Outdoor Unit ......................................8
Air purging .......................................23
Test running.....................................25
Installer Setting -PQRCUSA0..........27
Installation guide at the seaside......37
Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose
(Inner Dia.............32mm)
Horizontal meter
Screw driver
Electric drill
Hole core drill (ø70mm)
Flaring Tools set
Torque Wrenches
Hexagonal Wrench (4mm, 5mm)
Gas-leak detector
Owner’s Manual
Installation Manual
Thermometer
Installation
Requirements
Required Parts Required Tools
Installation Manual 3
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
n
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
n
LG Electronics is not responsible for Product`s malfunction or damage which caused by improper installation or misuse of operation guide.
n Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
n Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
Use a vacuum pump or Insert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
4 Ceiling Cassette Air Conditioner
Safety Precautions
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Operation
Do not touch(operate) the product with wet hands.
• There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.
Do not let electric parts of the product get wet.
• It may cause There is risk of fire, failure of the product, or electric shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Turn the main power off when cleaning or maintaining the product.
• There is risk of electric shock.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
• There is risk of electric shock or fire.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Installation Manual 5
Safety Precautions
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration.
Do not install the product where the noise or hot air from the outdoor unit could be offensive to the neighborhoods or damage property.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operation
Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
• This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
• It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
• There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
• There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
• It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
• Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
• Could adversley effect operation.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
• They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
6 Ceiling Cassette Air Conditioner
Introduction
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the air conditioner.
This symbol indicates special notes.
Introduction
Symbols used in this Manual
Features
NOTICE
Air Outlet Air Inlet
Remote
Controller
Anti-bacteria
Installation
Installation Manual 7
Installation
Installation Tools
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Name
Ohmmeter
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Horizontal meter
Flaring tool set
8 Ceiling Cassette Air Conditioner
Installation
Installation of Indoor, Outdoor Unit
Selection of the best location
1) Indoor unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance space.
2) Outdoor unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Unit:mm
Ceiling
Ceiling Board
Ceiling Board
300 or more
Above 2500
400 or less
1000
or more
500 or
more
500 or more
300 or less
Floor
More than 300mmm
h Please use an annexed sheet or the
corrugated cardboard on the bottom of packing as installation sheet.
h When using the bottom sheet, please use it
after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
More than
300mm
Fence or
Sunroof
More than
More than 300mm
300mmm
obstacles
More than 600mm
More than 700mm
Installation
Installation Manual 9
3) Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Model
*Additional
refrigerant
(g/m)
Pipe Size
mm(inch)
Length A(m) Elevation B(m)
Gas Liquid Standard Max. Standard Max.
LT-H182QLE0 12.70(1/2”) 6.35(1/4”) 7.5 30 5 20 30
LT-H242QLE0 15.88(5/8”) 6.35(1/4”) 7.5 30 5 20 35
LT-H302PLE0 15.88(5/8") 6.35(1/4") 7.5 50 5 30 25
LT-H362NLE0 15.88(5/8") 6.35(1/4") 7.5 50 5 30 45
LT-H482MLE0 19.05(3/4") 9.52(3/8") 7.5 50 5 30 45
LT-H602MLE0 19.05(3/4") 9.52(3/8") 7.5 50 5 30 50
LT-C182QLE0 12.70(1/2”) 6.35(1/4”) 7.5 30 5 20 30
LT-C242QLE0 15.88(5/8”) 6.35(1/4”) 7.5 30 5 20 35
LT-C302PLE0 15.88(5/8") 6.35(1/4") 7.5 50 5 30 30
LT-C362NLE0 15.88(5/8") 6.35(1/4") 7.5 50 5 30 30
LT-C482MLE0 19.05(3/4") 9.52(3/8") 7.5 50 5 30 55
LT-C602MLE0 19.05(3/4") 9.52(3/8") 7.5 50 5 30 55
10 Ceiling Cassette Air Conditioner
Installation
• Select and mark the position for fixing bolts and pip­ing hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the ceiling.
• The hole size for four anchor bolts is Ø 14.5mm & 40mm depth.
• When using cardboard on the bottom of packaging, use after separating installation paper from bottom of the product packaging using back of a knife as shown in the picture (TM/TN/TP)
CAUTION:
• This air-conditioner uses a drain pump.
• Horizontly install the unit using a level gauge.
• During the installation, care should be taken not to damage electric wires.
• Thoroughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduc­tion, spraying, dispersing of water drops, drain pump malfunction, etc. In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient
capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it
may not suck in oily steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
Ceiling opening dimensions and hanging bolt location
• The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.
• Please use included paper or cardboard on the bottom of packaging as installation paper
Ceiling board
Level gauge
Ceiling
Unit: mm
875(TM/TN/TP)
585~660(TQ)
787(TM/TN/TP)
517(TQ)
684(TM/TN/TP)
517(TQ)
671(TM/TN/TP)
523(TQ)
875(TM/TN/TP)
585~660(TQ)
840(TM/TN/TP)
570(TQ)
840(TM/TN/TP)
570(TQ)
Included Paper Cardboard on the bottom
of packaging
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
NOTICE
Installation Manual 11
Installation
The Indoor Unit Installation
• The following parts is option.
Hanging Bolt - W 3/8 or M10Nut - W 3/8 or M10Spring Washer - M10Plate Washer - M10
• Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
CAUTION:
Tighten the nut and
bolt to prevent unit falling.
Remote Controller Installation
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
• Select control position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power cables (audio equipment, television set, etc.)
• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Keep the length of the bolt
from the bracket to 40mm
Flat washer for M10 (Attached Insulator,
accessory)
Flat washer for M10
(accessory) Nut (W3/8 or M10)
Ceiling board
Air Conditioner body
Keep the length of 31~34mm between the air conditioner bottom surface and the ceiling surface
Paper model for installation
Ceiling
Set screw of paper model (4 pieces)
Open the ceiling board along the outer edge of the paper model
180mm
Ceiling board
Indoor
Wall
Slope gradient for drain Should be 1/50 ~ 1/100
Outdoor
12 Ceiling Cassette Air Conditioner
Installation
2
2
1
3
3
1. Please fix tightly using provided screw after placing remote controller setup board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
- Install the product so as not to make a gap with the wall side and to prevent shaking after the installation.
2. Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller cable guide groove.
Remove guide groove with long nose.
Reclamation to the surface of the wall
Upper part guide groove
Right part guide groove
WIRED REMOTE CONTROL INSTALLATION
<Wire guide grooves>
<4 Hole reclamation box> <2 Hole reclamation box>
Loading...
+ 26 hidden pages