DEFINING COMMON ERROR CODES
Standard Wall-Mounted High-Efciency Single Zone Systems
LS091HSV System (LSN091HSV Indoor Units / LSU091HSV Outdoor Units)
LS121HSV System (LSN121HSV Indoor Units / LSU121HSV Outdoor Units)
LSN091HSV and LSN121HSV Indoor Units
Location of LEDs
Error
Code
1 Indoor unit return air thermistor has disconnected or has shorted out. 1X —
2 Indoor unit inlet pipe thermistor has disconnected or has shorted out. 2X —
5 Communication failure from indoor unit to outdoor unit. 5X —
6 Indoor unit outlet pipe thermistor has disconnected or has shorted out. 6X —
9 Indoor unit EEPROM error. 9X —
10 Indoor unit fan has locked up (fan motor operation failure). — 1X
12 Indoor unit middle pipe thermistor has disconnected or has shorted out. 2X 1X
21 DC peak error / IPM fault; compressor DC voltage was too high. 2X 1X
22 Current transformer2 (CT2) error; AC input current is too high. 2X 2X
23 DC link voltage is too low. 2X 3X
25 Voltage to the system is too low or too high. 2X 5X
26 Inverter compressor has seized up or is not providing rotation. 2X 6X
Prospective short circuit (PSC) fault error; current to inverter compressor between
27
28 Inverter compressor DC voltage is too high. 2X 8X
29 Inverter compressor amperage is too high. 2X 9X
31 Current to the current transformer (CT) thermistor is too low. 3X 1X
32 Inverter compressor discharge pipe temperature is too high. 3X 2X
40 Current transformer (CT) thermistor has disconnected or has shorted out. 4X —
41 Inverter compressor discharge pipe thermistor has disconnected or has shorted out. 4X 1X
44 Outdoor unit inlet air thermistor has disconnected or has shorted out. 4X 4X
45 Outdoor unit condenser coil middle thermistor has disconnected or has shorted out. 4X 5X
46 Outdoor unit suction line thermistor has disconnected or has shorted out. 4X 6X
48 Outdoor unit coil outlet (liquid line) thermistor has disconnected or has shorted out. 4X 8X
53 Communication failure from outdoor unit to indoor unit. 5X 3X
60 Outdoor unit PCB EEPROM check sum error. 6X —
61 Outdoor unit condenser coil temperature is too high. 6X 1X
62 Outdoor unit inverter compressor PCB heat sink temperature is too high. 6X 2X
63 Condenser coil pipe thermistor temperature is too low. 6X 3X
65 Heat sink thermistor has disconnected or has shorted out. 6X 5X
67 Outdoor BLDC fan motor lock error. 6X 7X
AC and DC converter circuit is too high.
Description
No. of Times Indoor Unit LEDs Blink
LED1
(Heating LED)
2X 7X
(Cooling LED)
LED2
Defining Commom Error Codes
Refer to Service Manuals posted on www.lg-dfs.com to troubleshoot error codes.
1
DEFINING COMMON ERROR CODES
Standard Wall-Mounted High-Efciency Single Zone Systems
LS091HSV System (LSN091HSV Indoor Units / LSU091HSV Outdoor Units)
LS121HSV System (LSN121HSV Indoor Units / LSU121HSV Outdoor Units)
LSU091HSV and LSU121HSV Outdoor Units
Location of PCB LEDs: To access outdoor unit PCB LEDs, remove top cover,
and then remove lid to PCB box.
Error
Code
21 DC peak error / IPM fault; compressor DC voltage was too high.
22 Current transformer2 (CT2) error; AC input current is too high. 2X 2X
23 DC link voltage is too low. 2X 3X
25 Voltage to the system is too low or too high. 2X 5X
26 Inverter compressor has seized up or is not providing rotation. 2X 6X
27
28 Inverter compressor DC voltage is too high. 2X 8X
29 Inverter compressor amperage is too high. 2X 9X
Dening Common Error Codes
31 Current to the current transformer (CT) thermistor is too low. 3X 1X
32 Inverter compressor discharge pipe temperature is too high. 3X 2X
40 Current transformer (CT) thermistor has disconnected or has shorted out. 4X —
41 Inverter compressor discharge pipe thermistor has disconnected or has shorted out. 4X 1X
44 Outdoor unit inlet air thermistor has disconnected or has shorted out. 4X 4X
45 Outdoor unit condenser coil middle thermistor has disconnected or has shorted out. 4X 5X
46 Outdoor unit suction line thermistor has disconnected or has shorted out. 4X 6X
48 Outdoor unit coil outlet (liquid line) thermistor has disconnected or has shorted out. 4X 8X
53 Communication failure from outdoor unit to indoor unit. 5X 3X
60 Outdoor unit PCB EEPROM check sum error. 6X —
61 Outdoor unit condenser coil temperature is too high. 6X 1X
62 Outdoor unit inverter compressor PCB heat sink temperature is too high. 6X 2X
63 Condenser coil pipe thermistor temperature is too low. 6X 3X
65 Heat sink thermistor has disconnected or has shorted out. 6X 5X
67 Outdoor BLDC fan motor lock error. 6X 7X
Prospective short circuit (PSC) fault error; current to inverter compressor
between AC and DC converter circuit is too high.
Description
No. of Times Outdoor Unit PCB LEDs Blink
LED1 (Green) LED2 (Red)
2X 1X
2X 7X
LED1
LED2
Refer to Service Manuals posted on www.lg-dfs.com to troubleshoot error codes.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
For continual product development, LG reserves the right to change specifications without notice.
2
LG Electronics U.S.A. – Commercial Air Conditioning
DFS-TP-AH-001-US 012H10