LG LS120HE, LS180HE, LS090CE, LS120CE, LS240CE User Manual

...
ENGLISH
LG Room Air Conditioner
INSTALLATION MANUAL
LG
http://www.lgservice.com
• Please read this instruction manual completely before installing the product.
• When the power cord is damaged, replacement should be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
FRANÇAIS ESPAÑOL
2 Room Air Conditioner
Room Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions .........................3
Introduction .....................................9
Symbols Ued in This Manual ......9
Features .......................................9
Installation .....................................10
Installation Parts ........................10
Installation Tools ........................10
Installation Map..........................11
Confirm The Refrigerant ...........12
Select The Best Location .........13
Piping Length And Elevation.....14
How To Mount Installation Plate
..15
Drill a Hole In The Wall..............15
Flaring Work...............................16
Connecting The Piping..............17
Connection Of The Drain Hose
...22
Connection Of Piping -Outdoor
...22
Connection Of The Cable .........23
Checking The Drainage ............25
Forming The Piping ...................26
Air Purging .................................27
Air Purging With Vacuum Pump
..27
Charging.....................................29
Tes t R unn ing .................................30
Installation plateFour type "A" screwsConnecting cable
Pipes: Suction line
Evaporator line (Refer to page 13)
Insulation materialsAdditional drain pipe
(
Outer Diameter
.........
15.5mm(0.61in))
Two type "B" screws
Installation
Requirements
Required Parts Required Tools
Level gaugeScrewdriverElectric drillHole core drill(ø70mm(2.76in))
Flaring tool setSpecified torque wrenches
4.2kg.m, 6.6kg.m (different depending on model No.) (Refer to page 17)
Spanner .....................Half union
AglassofwaterScrew driver
Hexagonal
wrench(4mm(0.16in))
Gas Leak DetectorVacuum pumpManifold Gauge
Owner's manualThermometerRemote Control Holder
Installation Manual 3
ENGLISH
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• There is risk of fire or electric shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion or injury.
4 Room Air Conditioner
Safety Precautions
Operation
Be cautious when unpacking and installing the product.
• Shape edges could cause injury. Be especially careful of the sharp edges.
For installation, always contact thedealeroranAuthorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Install the indoor unit on the wall where the height from the floors more then 8ft(2.4m)
• There are sharp moving parts that could cause personal injury.
Do not handle the pipe by yourself(customer)
• High-Pressure refrigent may cause personal injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electric shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electric shock.
Do not allow water to run into electric part.
• There is risk of fire, failure of the product, and/or electric shock.
8ft(2.4m)
Installation Manual 5
ENGLISH
Safety Precautions
Do not place a heater or other appliances near the power cable.
There is risk of fire, failure of the product, and/or electric shock.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Do not store of use flammable gas or combustibles near the air conditioner.
• There is risk of fire or product failure.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
• Some ventilation by opeing window is necessary for the fresh air.
When flammable gas leaks, turn off the gas and open a window for ventilation before turning the product on. Do not use the telephone or turn switches on or off.
• There is risk of explosion or fire.
Unplug the unit if strange sounds odors or smoke comes from it.
There is risk of fireproduct failure and/or electric shock.
Stop operation and close any window in storm or hurricane. before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of electrical shock.
Thinner
Wax
6 Room Air Conditioner
Safety Precautions
Installation
Always check for gas(refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause product failure.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
There could result in personal injury and product damage.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electrical shock.
Unplug the appliance before performing cleaning or maintenance.
Thereisriskofelectricshock.
When the product is not be used for a long time disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
90˚
Safety Precautions
Installation Manual 7
ENGLISH
Operation
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the air conditioner
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion in the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Do not direct airflow at room occupants.
This could damage your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor unit)
There is risk of personal injury and failure of product.
8 Room Air Conditioner
Safety Precautions
Disuse
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not drink the water drained from the unit.
It is not sanitary and could cause serious health issues.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
The chemicals in batteries could cause burns or other
health hazards.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
Be careful and avoid personal injury.
Replace all the batteries in the remote.
There is risk of fire or explosion.
Installation Manual 9
ENGLISH
Introduction
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Introduction
Symbols Used In This Manual
Features
Air Intake Vents
Air Outlet Vents
Connecting Wires
Piping
Drain Hose
Base Plate
Air Outlet Vents
Air Intake Vents
Piping
Connecting Wires
Drain Hose
Signal Receptor
Base Plate
Front Panel
Air Inlet
Air Filter
10 Room Air Conditioner
Installation
Type "A" screw and plastic anchor
Type "B" screw
Remote Control Holder
Installation plate
Figure FigureName
Screw driver
Electric Drill
Measuring Tape, Knife
Hole Core Drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Gas Leak Detector
Thermometer,
Level
Flaring Tool Set
Name
Installation Parts
Installation Tools
Installation
Read carefully, and then follow step by step.
Installation Manual 11
ENGLISH
Installation
Installation Map
Installation parts you should purchase.
Vertical Air deflector
Air Discarge
Forced Operation Button
Operation Indication Lamps/
Signal Receptor
Vinyl tape(Wide)
Apply after carrying out a drainage test.
To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Saddle
Gas side piping Liquid side piping Additional drain pipe
Drain Hose
Base Plate
Air Inlet Vents
Connecting cable
Installation Plate Sleeve Bushing-Sleeve
Putty(Gum Type Sealer)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
NOTICE
NOTE: refrigerant line wall thickness must be at least 0.8 mm (0.031 inch)
Air Outlet Vents
Installation
1. Check the quality label on the indoor and outdoor unit.
2. Make certain that the refrigerant is R-410A.
THIS PRODUCT CONTAINS R-410A REFRIGERANT
1) Different compressor oil
- R-410A(Polyol ester) / R-22(Mineral).
- Do not mix the existing mineral oil.
- Do not apply used pipe, tools and gauges covered with the existing mineral oil.
2) Absorption of moisture
-Compressor’s oil has the high absorption rate of moisture.
3) Composition
- R-410A(R32:R125=50:50wt%). NOTE: Never mix with other refrigerants
4) High pressure.
- 1.6 times higher than R-22.
- High Pressure refrigerant may cause personal injury.
Do not handle the pipe by yourself (customer) High-pressure refrigerant may cause personal injury.
- manifold gauge ,charging and any piping tools must be dedicated to R-410A systems.
NOTICE
Confirm The Refrigerant
12 Room Air Conditioner
Boiling Pt.(
°C) Vapor pressure(25°C)(kg f/cnf) Vapor density(25°C)(kg/m2)
R-410A -51.4 15.9 64 R-22 -40.8 9.6 44.4
Example : Split type 12,000 Btu/h
120
100
100
80
93
89
84
76
60
40
20
0 R-410A R-22
100%
70% 50% 30%
0%
100%70%50%30%0%
Installation Manual 13
ENGLISH
Installation
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the space around the back and sides is more than 10cm(3.9in). The front of the unit should have more than 70cm(27.6in) of space.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
If the outdoor unit is installed on roof structures or walls, this may result in excessive noise and vibration, and may be also classed as non serviceable installation.
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure that the space around the left and right of the unit is more than 30cm(11.8in). Theunitshouldbeinstalledashighonthe wall as possible, allowing a minimum of 12cm(4.7in) from ceiling.
6.Useastudfindertolocatestudstoprevent unnecessary damage to the wall.
Select The Best Location
Install the indoor unit on the wall where the height from the floors more than 2.3meters(7.6ft). A minimum pipe run of 7.5meters(24.6ft) is required to minimize vibration and excessive noise.
More than
12cm(4.7in)
More than
30cm(11.8in)
More than
30cm(11.8in)
More than 8ft(2.4m)
More than
10cm(3.9in)
More than
10cm(3.9in)
More than 60cm(23.6in)
More than
60cm(23.6in)
More than
70cm(27.6in)
14 Room Air Conditioner
Installation
Piping Length And Elevation
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7meters (16.4~23.0ft).
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length
A m(ft)
Additional Refrigerant
g/m(oz/ft)
Max.
Elevation
B m(ft)
Standard
Length
m(ft)
In case more than 5m(16.4ft)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
9k
3/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
1/2" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
12k 1/2" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
18k
1/2" 1/4" 7.5(25) 15(49) 30(98) 20(0.22)
5/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
24k 5/8" 1/4" 7.5(25) 7.5(25) 15(49) 20(0.22)
Installation Manual 15
ENGLISH
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by
aligningthecenterlineusingalevel.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
How To Mount Installation Plate
Chassis
Hook
Installation Plate
Type A
Drill the piping hole with a ø70mm(2.76in) hole core drill. Drill the piping hole at either the right or the left with the hole slightly slantedtotheoutdoorside.
Drill a Hole In The Wall
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
ABCD S4 50 105 59 105 SE 65 110 85 110 S5 95 122 235 122
CHASSIS
(Grade)
Distance (mm)
D
C
Ø70mm
Left rear piping Right rear piping
Installation plate
A
B
Ø70mm
16 Room Air Conditioner
Installation
Flaring Work
Cut the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m(59.1in) longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Carry out flaring work using flaring tool as
shown below.
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
mm inch mm inch
Ø6.35 1/4 0~0.5 0~0.020 Ø9.52 3/8 0~0.5 0~0.020 Ø12.7 1/2 0~0.5 0~0.020
Ø15.88 5/8 0~1.0 0~0.039
Outside diameter A
Copper
pipe
90¡
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Pipe
Reamer
Point down
Firmly hold copper pipe in a die in the dimension shown in the table above.
Flare nut
Copper tube
Installation Manual 17
ENGLISH
Installation
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by) and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.
Route the indoor tubing and the drain hose in the direction of rear left.
Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is
recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of
the installation plate.(Engage the three hooks of the rear top and rear lower of the indoor unit with the upper edge and lower edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Connecting the Piping
For left rear piping
Connecting The Piping
1 2
Indoor unit
Installation plate
8cm
Spacer
Connecting
cable
Drain pipe
18 Room Air Conditioner
Installation
Wrap the insulation material around the connecting portion.
Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Plastic bands
Insulation material
Connection pipe
Flare nut
Indoor unit tubing
Torque wrench
Spanner (fixed)
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
When extending the drain hose at the indoor unit, install the drain pipe.
Mount the clamp on the boss with a type "B" screw.(SE-H/P: 9k, 12k C/O: 12k)
Tighten the flare nut with a wrench.
Wrap the area which accommodates the rear
piping housing section with vinyl tape.
For right rear piping
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Indoor unit tubing Flare nut Pipings
Drain hose
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6
Outside diameter
mm inch
Torque
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Type "B" screw
Clamp
Boss
Drain hose
Installation Manual 19
ENGLISH
Installation
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
Tape the drain hose and the connecting cable.
Connecting cable
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
Indoor unit tubing Flare nut Pipings
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the three hooks of the rear top and rear lower of the indoor unit with the upper edge and lower edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Wrap the insulation material around the connecting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Plastic bands
Insulation material
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
When extending the drain hose at the indoor unit, install the drain pipe.
Connecting pipe
Connecting cable
Tape
Drain hose
Drain hose
Connecting
cable
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6
Outside diameter Torque
Mounttheclamponthebosswithatype"B" screw.(SE-H/P: 9k, 12k C/O: 12k)
Type "B" screw
Clamp
Boss
Drain hose
20 Room Air Conditioner
Installation
Reroute the pipings and the drain hose across the back of the chassis.
Reroute the pipings and the drain hose across the back of the chassis.
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Piping for passage through piping hole
Drain hose
Connecting
cable
Wrap the area which accommodates the rear piping housing section with vinyl tape.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Installation Manual 21
ENGLISH
Installation
Installation Information. For left piping. Follow the instruction below.
Correct case
Press on the upper side of clamp and unfold the tubing to downward slowly.
Incorrect case
Following bending type from right to left may cause damage to the tubing.
22 Room Air Conditioner
Installation
Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
The drain hose can be connected at two different positions. Use the most convenient position and, if necessary, exchange the position of the drain pan, rubber cap and the drain hose.
Drain panRubber capDrain hoseExchange if necessary
Remove the drain hose.
Securely insert both the rubber plug and drain
hose into the drain outlets. Be sure the rubber the cap is securely fastened so that there is no leakage.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Suction Line piping (Bigger diameter)
Evaporator Line piping (Smaller diameter)
Torque wrench
1
2
3
4
Connecting the PipingConnection Of The Drain Hose
Connecting the PipingConnection Of Piping -Outdoor
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2 Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter
mm inch
Torque
Installation Manual 23
ENGLISH
Installation
Connecting the PipingConnection Of The Cable
1
Indoor Unit Outdoor Unit
2
3
4
1
2
3
4
5
6
G
To branch circuit
Ground
Power supply
a
L1
*
L2
Connecting cable(Low voltage)
b
Terminal
(4P)
Terminal
(6P)
Outdoor unit
Wiring Diagram
Terminal block
Over 5mm
(0.2")
Cover control
Conduit panel
Connecting
cable
Power supply
cord
*
L1 is neutral for 115V models.
1. Remove the cover control from the unit by loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit panel.
4. Properly connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
1. shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of withstanding temperatures up to 167°F.
4. Use outdoor and waterproof connection cable
rated more than 300V for the connection between indoor and outdoor unit. (For example, Type STOW)
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Everywiremustbeconnectedfirmly.
No wire should be allowed to touch
refrigerant tubing, the compressor or any moving parts.
Connector trade size for this unit is 1/2" for instructions on connecting depending on thewiretypeyouareusing.
WARNING
NOTE
Power Supply
Model
Powe r sour ce
9K 1ø, 115V 14 18 15A 12K 1ø, 115V 14 18 20A 18K 1ø, 230/208V 14 18 20A 24K 1ø, 230/208V 12 18 25A
AWG(MI N.)
Fuse or breaker
Capacity
NOTE
24 Room Air Conditioner
Installation
After the confirmation of the above conditions, prepare the wiring as follows:
1)
Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) Confirm that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.
7) Always install an GFCI circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, open fuse, disturbance of the
normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm(0.12in) in each active(phase) conductors.
CAUTION
Installation Manual 25
ENGLISH
Installation
Checking The Drainage
Pour a glass of water on the drain pan.
Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain
exit.
Drain piping
The drain hose should point downward for easy drain flow.
Avoid these situations.
Drain pan
Drain
hose
Leakage checking
Connecting area
drain hose
Leakage checking
Downward slope
Water leakage
Accumulated drain water
Waving
Air
Do not raise
Water leakage
Water leakage
Tip of drain hose dipped in water
Ditch
Less than 50mm gap
26 Room Air Conditioner
Installation
Forming The Piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using saddle or equivalent.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form atraptopreventwaterenteringtheroom.
Fix the piping onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Installation Manual 27
ENGLISH
Air Purging
Air purging With Vacuum Pump
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Preparation
Check that each tubing(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
CAUTION
CAUTION
Installation
28 Room Air Conditioner
Installation
Evacuation
Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter­clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the gas side and
liquid side valves.
(2) Remove the service-port cap from the gas
side valve.
(3) To open the gas side valve turn the valve
stem counterclockwise approximately 90°, wait for about 2~3 seconds, and close it.
(4) Apply a soap water or a liquid neutral
detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Suction Line
Evaporator Line
Cap
Hexagonal wrench
3-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h
vacuum pump is used
10 min. or more 15 min. or more
If tubing length is less
than 10m (33 ft)
if tubing length is longer
than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Loading...
+ 64 hidden pages