SERVICING PRECAUTIONS
AIR RECHARGING IN COMPRESSOR
Test the refrigeration system connecting it electrfaally before
refilling operation. It is necessary to ascertain the function
of the motor*compressor and identity the defects
immediately, if defects have been found, empty the old
system of possible R-134a residue by breaking off the end
of the extension piece at its narrow point. (Figure 1)
Replace the filter and any damaged components. Unsolder
and pull off the piece remaining inside the service tube and
then attach an complete extension with male Hansen and
at last, solder it to the same tube again. (Figure 2)
POINT TO BE BROKEN
SERVICE TUBE EXTENSION
Figure I
It is necessary to executethe soldering operation with
valve open so that the fumes caused by oil residue can
come out freely without blowholes between two tubes
during the heating the of the point to be soldered.
The extension fitted with the male Hansen is connected to
the female fitting of the vacuum pump tube. (Figure 3)
CHARGE TUBE FEMALE
EXTENSION RANSEN
MALE HANSEN
SOLDERING POINT
Figure 2
vacuum operation is over, add the quantity in grams of
R-134a to the refrigeration system. Remember that every
system has an exact quantity of R-134a that can be added
with a tolerance of +5 grams. (Figure 4)
TO THE R-t34a CYLINDER
1
SYSTEM
TO THE REFRIGERATION
1
Before performing this operation (if the vacuum pump and
refilling cylinder are connected), make sure that the valve
placed between the vacuum pump and the refilling tube is
dosed in order to keep the Freen for addition to the system.
(Figure 5)
FILLING OR VALVE TO BE OPENED
CHARGE TUBE WHEN REFILLING
r_;_-- _J Figure 4
L3_
GAUGE
Air evacuating from the system begins as soon as the
pump starts. The refrigeration system must be kept under
vacuum until the reading on the low-pressure gauge
indicates vacuum (0 absolute, -1 aim., -760 mm hg). In any
case it is advisable to keep the pump running for about 30
minutes. (Figure 3)
If considerable leakage occurs, it will be necessary to stop
the vacuum pump and to add a small quantity of Freon to
the system. If vacuum should not be obtained (pressure
gauge can't fall to 1 atmosphere), start the refrigeration
unit and find the leakage with special leak-finder. When the
defective soldering point is visible, repair it after opening
the extension tube valve and reestablishing the normal
outside pressure inside the group.
Because the melted alloy is sucked into the tubes and
blocks them, the pressure must be rebalanced when
vacuum is in the system when soldering, As soon as the
TO THE REFRIGERATION TO THE CHARGE
SYSTEM CYLINDER
VALVE TO BE CLOSED
AFTER VACUUM
TO THE
VACUUM _ Figure 5
PUMP
In addition, check the graduated scale on the cylinder for
the quantity of R-134a to be added, for example, ifwe have
750 grams of Freon in the cylinder and must add 140
grams to the group, this amount will be reached when
R-134a has dropped to 610 grams, remembering thai the
indicator shows a lower limit of meniscus. Do this after
choosing the scale corresponding to the gas pressure
different scales reported as the same gas pressure
indicated by the pressure gauge on the top of the column.
To make R-134a flow i_o the system, open the valve
placed at the base of the cylinder connected to the filling
tube. The amount of Freen cannot be added to the system
all at once because it may cause a blocking of motor-
compressor. Therefore, proceed by adding the original
quantity of about 20-30 grams and close the valve
immediately.
The pressure rises and the motor compressor must start
sucking the gas and lowering the pressure again. Open the
valve again, maintaining the same manner until reaching to
the quantity of R-134a established for the system being
charged. When the system is running, the suction pressure
must be stabilized between 0.30 to 0.6 (0.10 to 0.4)
atmosphere.
-3-
T
2001.06.01 1601120
CIRCUITDIAGRAM
THERM(_TAT I_FRO6T,1111R
_,,,-Io ° I
_11_ SUPI_YlNGIBIE CONIROL
_W_'_ _
I t I-----
J I I _ I
I ,,: ,, . -,
_ , , ,_ =_=--',
I I I- E
i ' ' ,_._m-"-I',
.. _,: ',,_ ',__.--',
L_--I ! I Ii : ;_ _;JK
€,_i_ITOR pART p.T,O 8TARTER
t LAMP.FpART,CAP/,CITORS.THEPLUGTfPE, ENTrH pNtT N_ ICEMAK]_tOP'i_ PART0t__
IX_._%_I N_ 8UBJECTTOC.HN_61EIN0FFI_t _ LOC,N.I/1ES.
WH:WHITE BL:BLUE RD:RED Gy : GRAYPURPLEYL:YBJ.OW BO: BRIGHTOflkN_
BK:B.AO( BN:BRO_ PR:PURPLE pK:pIIe( GN:GREEN 3854JD1046C
8W1 SW2 5W_
OFF OFF OFF 10.5 s_
ON OFF OFF 9 8eC
OFF ON OFF 10 se_
ON ON OFF 11 SeC
OFF OFF ON 12 sec
ON OFF ON 13 sec
OFF ON ON 14 sec
ON ON ON 15sec
WITCHOFF 2 3
SWI SW2 SW3
TIME
ON
2. PARTS IDENTIFICATION
FREEZER
COMPARTMENT
Freezer Shelf
Automatic Ice Maker
Ice Cube Box
Freezer Temperature
REFRIGERATOR
COMPARTMENT
Push the grilletoward
Control Dial
Temperature
Control Dial
Lamp
Shelves
Egg Box
Snack Comer
Crisper
Used to keep fruits
and vegetables
fresh and crisp.
Base Grille
the refrigerator
until it snaps
into place.
Freezer Door Bin
Door Cooling
On the refrigerator door,
the cold air passageway is
installedto supply
coldair to the doorside of
the refrigerator
compartment.
Can Server
Dairy Corner
Wine Rack
Adjustable
Door Bin
Refrigerator Door
Rack
Leveling Screw
(Inside)
-5-
3. DISASSEMBLY
3-1 DOOR
• Freezer Door
1. Remove the hinge cover by pulling it upwards.
2. Loosen hexagonal bolts fixing the upper hinge to the
body and lift the freezer door.
HINGE COVER
HINGE
BOLT
Figure 6
3. Pull out the door gasket to remove from the door foam
assembly.
GASKET
3-2 DOOR SWITCH
1. To remove the door switch, pull out it with a slotted type
driver as shown in (figure g).
2. Disconnect the lead wire from the switch.
LEAD WIRE
DOOR SWITCH
Figure 9
3-3 THERMOSTAT
1. Remove Control Box-R by loosening 2 screws attached to
ceiling of Refitgerator comparb'nent (Figure 10)
2. Separate the thermostat and dial knob F.
3. Remove the thermostat by disconnecting the lead wire.
Figure 7
• Refrigerator Door
1. Loosen hexagonal bolts attaching the lower hinge to the
body to removethe refrigeratordoor only.
_:_ LOWER HINGE
BOLT
Figure 8
2. Pull out the door gasket to remove from the door foam
assembly.
Figure 10
-6-
3-4 FAN AND FAN MOTOR
1. Remove the freezer shelf. (If your refrigerator have an
Ice Maker, disassemble the Ice maker first)
2. Remove the grille by pulling it out and by loosening a
screw.
3. Remove the Fan Motor assembly by loosening 4 screws
and disassemble the shroud.
4. Pull out the fan and separate the Fan Motor and Bracket,
3-6 REFRIGERATOR ROOM LAMP
REFRIGERATOR ROOM LAMP
Figure 16
SHROUD
Figure 12
3-5 DEFROST CONTROL ASSEMBLY
Defrost control assembly consists of Defrost Thermostat
and FUSE-M.
Defrost Thermostat functions to defrost automatically and it
is attached to metal side of the Evaporator and senses
Temp.
Fuse-M is a safety device for preventing over-heating of the
Heater when defrosting.
At the temperature of 77°C, it stops the emission of heat
from the Heater.
1. Pull out the grille assembly.
2. Separate the connector connected with the Defrost
Control assembly and replace the Defrost Control
assembly after cutting the Tie Wrap. (Figure 14)
1. Unplug the power cord from the outlet,
2. Remove refrigerator shelves.
3. Release the hooks on both ends of the lamp shield and
pull the shield downward to remove it.
4. Turn the lamp counterclockwise.
5. Assemble in reverse order of disassembly. Replacement
bulb must be the same specification as original.
(Max 40 W)
3-7 CONTROL BOX-R
1. First, remove all shelves in the refrigerator and Control
Box-R by loosening 2 screws.
1
COVER LAMP_@ Figure 17
2. Remove the Control Boxer by pulling it downward.
3. Disconnect the lead wire on the right pusibon and
seperate timer, themostat, Lamp socket, etc.
SHROUD-F
Figure 13
DEF-THERMO
FUSE-M
HOLDER FUSE Figure 14
-7-
4. ADJUSTMENT
_ICOMPRESSOR
4-1-1 Role
The compressor intakes low temperature and low pressure
gas evaporated from evaporator of the refrigerator, and
condenses this gas to high temperature and high pressure
gas, and then plays delivering role to condenser.
4-1-2 Composition
The compressor includes overload protection. The PTC
starter and OLP (overload protector) are outside the
compressor. Since the compressor is manufactured to
tolerances of 1 micron, and is sealed in a dust - and
moisture - free environment, use extreme caution when
repairing it.
4-1-3 Note for Usage
(1) Be careful not to allow over-voltage and over-currant.
(2) No Strike
If applying forcible power or strike (dropping or careless
handling), poor operation and noise may occur.
(3) Use proper electric components eppmpdata to the
Compressor.
(4) Note to Keep Compressor.
if Compressor gets wet in the rain and rust in the pin of
Hermetic Terminal, the result may be poor operation
and poor contact may cause.
(5) Be careful that dust, humidity, and welding flux don't
contaminate the compressor inside when replacing the
Compressor. Dust, humidity, and flux due to welding
which contaminates the cylinder may cause Iockege
and noise.
4-2 PTC-STARTER
4-2-1 Composition of PTC-Starter
(1) PTC (Positive Temperature Coefficient) is a no-contact
semiconductor starting device which uses ceramic
matedal consisting of 8aTiO3.
(2) The higher the temperature is, the higher the resistance
value. These features are used as starting device for
the Motor,
4-2-2 Role of PTC-Starter
(1) PTC is attached to Hermetic Compressor used for
Refrigerator, Show Case, and starting Motor.
(2) Compressor for household refrigerator applies to
single-phase induction Motor.
For normal operation of the single-phase induction
motor, in the starting operation flows in both main coil
and sub-coil. After the starting is over, the current in
subcoil is cut off. The proper features of PTC play all
the above roles. So, PTC is used as a motor starting
device.
4-2-3 PTC-Appltad Circuit Diagram
• According to Starting Method for the Motor
OVERLOAD PROTECTOR(O.L.P)
-=_ C
[-- _-C -] ,= /_'_ COMPRESSOR
PTC STARTER HERMETIC
RSlR
4-2-4 Motor Restarting and PTC Cooling
(1) For restarting after power off during normal
Compressor Motor operation, plug the power cord after
5 rain. for pressure balance of Refrigerating Cycle and
PTC cooling.
(2) During normal operation of the Compressor Motor, PTC
elements generate heat continuously. Therefore,
if PTC isn't cooled for a while after the power has been
shut off, the motor will not restart.
4-2-5 Relation of PTC-Starter and OLP
(1) If the power is off during operation of Compressor and
the power is on before the PTC is cooled, (instant shut-
off within 2 min. or unplugging and reconnecting), the
PTC isn't cooled and a resistance value grows. As a
result, current can't flow to the sub-coti, the Motor con't
operate, and the OLP operates by flowing over currant
in only in the main-coil.
(2) While the OLP repeats on and off operation about 3-5
times, PTC is cooled and Compressor Motor performs
normal operation.
If OLP doesn't operate when PTC is not cooled,
Compressor Motor is worn away and causes circuit-
short and tire. Therefore, always use a properly
attached OLR
4-2-6 Note to Use PTC-Starter
(1) Be careful not to allow over-voltage and over-current.
(2) Do not strike
Don't apply a forcible power or strike.
(3) Keep apart from any liquid.
If liquid, such as oil or water away enters the PTC,
PTC materials may fail due to insulation breakdown of
the material itself.
(4) Don't change PTC at your convenience.
Don't disassemble PTC and case. If the exterior to the
PTC-atarter is damaged, resistance value is altered and
it may cause poor starting of the compressor motor may
cause.
(5) Use a properly attached PTC.
TERMINAL
Figure 19
-8-
4-30LP (OVERLOAD PROTECTOR)
4-3-1 Definition of OLP
(1) OLP (OVERLOAD PROTECTOR) is attached to the
Compressor and protects the Motor by cutting the
current to the Motor ifthe temperature rises and
activates the bimetal spring in the OLP.
(2) When over-voltage flows to Compressor motor, the
Bimetal works by heating the heater inside the OLP,
and the OLP protects Motor by cutting off current which
flows to the Compressor Motor.
4-3-2 Role of the OLP
(1) The OLP is attached to the Hermetic Compressor used
for the Refrigerator and prevents the Motor Coil from
being started inthe Compressor.
(2) Do not turn the Adjust Screw of the OLP in any way for
normal operation of the OLR
(Composition and connection diagram of OLP)
5. CIRCUIT DIAGRAM
CONTACTING
POINT
SCREW
ADJUST _
COVER
BIMETAL
BIMETAL
HEATER
[ i co.=]
Figure 21
BL
WH:WH;TE BL :_.UE RD: RED GY: GRA'tPURPLE "ft.:'t'RIOW BO:BRIGHTORN_E
BK:Bt,ACK BN:BROWN PR:PU_:t,E PK:PINK GN:G_EN
I_"_: Ple=emplu9thepo_r =_1
fromthev_loulef.
SWg'(_N0
awl SW3
OFF OFF 10.5Se
ON OFF 9 sec
OFF OFF lOsec
ON OFF 11se(
OFF O_ 12se(
ON ON 13se(
OFF ON 14se{
SWITCHOFF 2 3
L_J L-_J _
SW1SW2 SW3
TIME
15see
3854JD1046C
-9-
6. TROUBLESHOOTING
6-1 COMPRESSOR AND ELECTRIC COMPONENTS
.._ Remove the PTC-
[_ [ Power Source.
Starter from the
Compressor and
measure the voltage
between Terminal C of
Compressor and
Terminals 5 or 6 of PTC.
)_No Voltage. _ OLP disconnected?
._ (Rating Voltage YES
_+10%)? I "[_
Replace OLR
condition.
Check connection __]
L_ Reconnect. I
Check the
resistance of
Motor
Compressor.
Check the
resistance of
PTC-Starter.
Check OLR
Check
starting state.
_. in the range of Rating ,_to use a regular _,
Voltage ±10%. | transformer.
_ heck the resistance
amongM-C, S-C and
M-S in Motor
Compressor.
of two terminals in
-_ heck the resistance
PTC-Starter.
a regular OLR _ [30 sec. in forcible OLP
_._ Check if applying _,,10LP works within ___ YES i .[_
NO t_"
_ Replace Compressor.
YEs
NO _- Replace
YES
I I Ioperation by turning Replace OLR
I I instant power on and
I
PTC-Starter.
II°" f
NO
starting voltage after 5
rain, for balancing cycle
pressure and cooling the
]_ easura minimum ___
PTC.
the voltage of Rating
Voltage _+10%
Components start in _-_ O.K. I
below. NO _-[_
-10-
6-2 PTC AND OLP
11
Normal operation of
Compressor is -_
impossible or poor.
/
Separate the PTC-
Starter from
Compressor and
measure the
resistance between
No. 5 and 6 of PTC-
Starter with a Tester or
Wheatstone Bridge.
(Figure 21)
-]P
Compressor and check I Vl electric components. I
the resistance value I I
between two terminals J r
I Separate the OLP freml YES_[ Check another
of OLP with a Tester. _ I
(Figure 22) _ Replace OLR
._}1_ Observation value is _ Check another |
220VISOHz: 22_±30% electric components, I
115V/60Hz : 6.8__+30%
240VI50 HZ: 33_±30%
127.220V!60Hz : 22_
±30%
is 0 or several Starter I
hundred _.
The value is _o.
=
=
!
6-3 DEFROST TIMER
Normal operation of
the Defrost Timer is
impossible.
No defrosting.
Poor cooling.
_/Fl'igure 21_igure 22
the point of first click
sound and check the
Position the Cam Shaft to
current flowing between
terminals No. t(brown)
and No. 2(boght orange).
I__ Next, posi0on the Cam
__ No. 1 (brown) and
Shaft to the point of
second click sound and
check the current flowing
between terminals
No. 4 (black)
(Figure 23).
-_ Turn the Cam Shaft.
-_ with holding the Cam
f Shake about 3 times
Shaft and Body softly.
_--_ The resistanceis _. t_ DRePlroa_tethmeer. I
._The resistance is
0_2or variable.
220V/50Hz :2OK.Q
The resistanceis about
115V/60Hz :7.8K&_
I "°
-_ Loud click sound,
I__ Replace the
Defrost Timer. I
_ Check the another ]
electric components. I
Replace the
Defrost Timer.
Defrost Timer.
Replace the I
Figure 23
-11 -