PARTS IDENTIFICATION ....................................................................................................................................................... 4
TO REMOVE THE DISPENSER ...........................................................................................................................................6
FAN AND FAN MOTOR........................................................................................................................................................ 7
DEFROST CONTROL ASSEMBLY...................................................................................................................................... 7
CONTROL BOX-REFRIGERATOR ...................................................................................................................................... 7
MULTI DUCT........................................................................................................................................................................ 7
TO REMOVE THE COVER PTC...........................................................................................................................................9
COMPRESSOR AND ELECTRIC COMPONENTS............................................................................................................ 11
PTC AND OLP.................................................................................................................................................................... 12
OTHER ELECTRICAL COMPONENTS ............................................................................................................................. 13
SERVICE DIAGNOSIS CHART.......................................................................................................................................... 14
OPERATION PRINCIPLE & REPAIR METHOD OF ICEMAKER .................................................................................. 17-20
DESCRIPTION OF FUNCTION & CIRCUIT OF MICOM ............................................................................................... 21-43
EXPLODED VIEW & REPLACEMENT PARTS LIST ..................................................................................................... 44-54
SAFETY PRECAUTIONS
Please read the following instructions before servicing your
refrigerator.
1. Check the refrigerator for current leakage.
2. To prevent electric shock, unplug before servicing.
3. Always check line voltage and amperage.
4. Use standard electrical components.
5. Don't touch metal products in the freezer with wet
hands. This may cause frostbite.
6. Prevent water from spiling onto electric elements or the
machine parts.
- 2 -
7. Before tilting the refrigerator, remove all materials from
on or in the refrigerator.
8. When servicing the evaporator, wear gloves to prevent
injuries from the sharp evaporator fins.
9. Service on the refrigerator should be performed by a
qualified technician. Sealed system repair must be
performed by a CFC certified technician.
Page 3
1. SPECIFICATIONS
22 cu. Ft. (22.4 cu. Ft.)
ITEMSSPECIFICATIONS
DOOR DESIGNSide Rounded
DIMENSIONS
NET WEIGHT
COOLING SYSTEMFan Cooling
TEMPERATURE CONTROL Micom Control
DEFROSTING SYSTEM
DOOR FINISHVCM, Stainless
HANDLE TYPE Bar
INNER CASEABS Resin
INSULATIONPolyurethane Foam
W(836)x D(870)x H(1764) mm
W(32.91)x D(34.25)x H(69.45) in
128.4 Kg
283.29 pounds
Full Automatic
Heater Defrost
ITEMSSPECIFICATIONS
VEGETABLE TRAYOpaque Drawer Type
COMPRESSORPTC Starting Type
EVAPORATORFin Tube Type
CONDENSERWire Condenser
REFRIGERANTR-134a (115 g)
LUBRICATING OILISO10 (220 ml)
DEFROSTING DEVICESHEATH HEATER
REFRIGERATOR60 W (2EA)
LAMP
FREEZER60 W (1EA)
- 3 -
Page 4
2. PARTS IDENTIFICATION
- 4 -
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
I
A
Digital Sensor Control*
B
Refrigerator Light
C
Shelves
D
Chef Fresh
E
Can Dispenser
F
Optibin Crisper
Keeps fruits and vegetable fresh and crisper
G
Customcube Icemaker
H
Ice Bin
I
Full Widht Wire Basket
J
Wire Durabase
K
Filter (inside)*
L
Dairy Bin
M
Egg Box
N
Design-A-Door Bins
O
Freezer Light
P
Wire Basket
*On some models
Page 5
3. DISASSEMBLY
3-1 DOOR
Left Door
Disconnect water supply tube by pushing back
on the disconnect ring (3).
Loosen the cover screw (1).
Disconnect door switch wire (2).
Attach the tube on the door with door.
Pull out the tube (4).
Disconnect wire harness (5).
Loosen screws (6) and lift off the top hinge (7).
Place the door on a non-scratching surface with
the inside up.
Right Door
Loosen the cover screw (1).
Disconnect door switch wire (2).
Disconnect wire harness (4).
Remove the ground screw (8).
Loosen screws (6) and lift off the top hinge (7).
Place the door on a non-scratching surface with
the inside up.
2. Remove gasket bracket clips
There are two clips on each door. Start bracket removal
near one of the middle clips.
1) Pull gasket back to expose gasket bracket clip and
door frame.
2) Insert a flat tip screwdriver into seam between gasket
bracket and door frame and pry back until clips snaps
out.
3) Continue prying back along seam until all clips snap
out.
Door
Frame
Flat Tip
Screwdriver
3. Remove gasket
Pull gasket free from gasket channel on the three
remaining sides of door.
Gasket
Bracket Clip
Figure 3
Gasket
Bracket
Left
Figure 1
Door Gasket Removal
1. Remove door frame cover
Starting at top of cover and working down, snap cover
out and away from door.
Frame Cover
Handle
Right
Figure 2
Figure 4
Door Gasket Replacement
1. Insert gasket bracket clips
1) Insert gasket bracket edge beneath door frame edge.
2) Turn upper gasket bracket spring so that both spring
ends are in the door channel.
3) Push in clip until you hear it snap securely into place.
Gasket
Bracket Clip
Spring
Door
Frame
4) Push in remaining two clips until you hear each snap
securely into place.
Note: Make sure that no part of gasket bracket edge
protrudes from beneath door frame edge.
CorrectIncorrect
Figure 5
- 5 -
Page 6
2. Insert gasket into channel
1) Snap gasket assembly into the door bracket.
<Inserting the Gasket Assembly into the Bracket Door>
Correct
Incorrect
Figure 6
3-2 TO REMOVE THE DISPENSER
1. Use fiat tip screwdriver to pry back hooks on botton
underside of cover dispenser.
Figure 9
2. Pry off cover dispenser.
2) Press gasket into channels on the three remaining
sides of door.
Figure 7
3. Replace door frame cover
Starting at top of cover and working down, snap cover
back into door.
Figure 10
Disconnect wire harness.
3. Replace cover dispenser in opposite manner and order
of removal.
Figure 8
- 6 -
Page 7
3-3 FAN AND FAN MOTOR
GRILLE ASSEMBLY
DEFROST-CONTROL
ASSEMBLY
CONTROL BOX
COVER LAMP
1. Remove the freezer shelf. (If your refrigerator has an
icemaker, remove the icemaker first)
2. Remove the plastic guide for slides on left side by
unscrewing phillips head screws.
3. Remove the grille by removing one screw and pulling the
grille forward.
4. Remove the Fan Motor assembly by loosening 2 screws
and disassembling the shroud.
5. Pull out the fan and separate the Fan Motor and Bracket.
FAN MOTOR
BRACKET
MOTOR
3-5-1 Refrigerator Compartment Lamp
1. Unplug the power cord from the outlet.
2. Remove refrigerator shelves.
3. Release the hooks on both ends of the lamp shield and
pull the shield downward to remove it.
4. Turn the lamp counterclockwise.
5. Assembly is the reverse of disassembly. Replacement
bulb must be the same specification as the original
(Max. 60 W2EA).
FAN
GRILLE
Figure 11
3-4 DEFROST CONTROL ASSEMBLY
Defrost Control assembly consists of Defrost Sensor and
FUSE–M.
The Defrost Sensor works to defrost automatically. It is
attached to the metal side of the Evaporator and senses its
temperature. At 72°C, it turns the Defrost Heater off.
Fuse-M is a safety device for preventing over-heating of
the Heater when defrosting.
1. Pull out the grille assembly. (Figure 12)
2. Separate the connector with the Defrost Control
assembly and replace the Defrost Control assembly
after cutting the Tie Wrap. (Figure 13)
Figure 15
3-5-2 Freezer Compartment Lamp
1. Unplug refrigerator or disconnect power.
2. Reach behind light shield to remove bulb.
3. Replace bulb with a 60-watt appliance bulb.
4. Plug in refrigerator or reconnect power.
3-6 CONTROL BOX-REFRIGERATOR
1. First, remove all shelves in the refrigerator, than remove
the Refrigerator control Box by loosening 2 screws.
Figure 16
2. Remove the Refrigerator Control Box by pulling it
downward.
3. Disconnect the lead wire on the right position and
separate the lamp sockets.
3-5 LAMP
Figure 12
Figure 13
Figure 14
3-7 MULTI DUCT
1. Remove the upper and
lower Caps by using a flat
screwdriver, and remove 2
screws. (Figure 17)
2. Disconnect the lead wire
on the bottom position.
Figure 17
- 7 -
Page 8
4. ADJUSTMENT
PTC STARTER
SEALED
TERMINAL
COMPRESSOR
MOTOR
C
M
S
M
2
5
6
3
S
PTC
N
L1
OVERLOAD PROTECTOR
Resistance Starter Capacitor Running
4-1 COMPRESSOR
4-1-1 Role
The compressor intakes low temperature and low pressure
gas from the evaporator of the refrigerator and compresses
this gas to high-temperature and high-pressure gas. It then
delivers the gas to the condenser.
4-1-2 Composition
The compressor includes overload protection. The PTC
starter and OLP (overload protector) are attached to the
outside of the compressor. Since the compressor is
manufactured to tolerances of 1 micron and is hermetically
sealed in a dust and moisture-free environment, use
extreme caution when repairing it.
4-1-3 Note for Usage
(1) Be careful not to allow over-voltage and over-current.
(2) If compressor is dropped or handled carelessly, poor
operation and noise may result.
(3) Use proper electric components appropriate to the
Particular Compressor in your product.
(4) Keep Compressor dry.
If the Compressor gets wet (in the rain or a damp
environment) and rust forms in the pin of the Hermetic
Terminal, poor operation and contact may result.
(5) When replacing the Compressor, be careful that dust,
humidity, and soldering flux don’t contaminate the inside
of the compressor. Contamination in the cylinder may
cause noise, improper operation or even cause it to
lock up.
4-2 PTC-STARTER
4-2-1 Composition of PTC-Starter
(1) PTC (Positive Temperature Coefficient) is a no-contact
semiconductor starting device which uses ceramic
material consisting of BaTiO
(2) The higher the temperature is, the higher the resistance
value. These features are used as a starting device for
the Motor.
4-2-2 Role of PTC-Starter
(1) The PTC is attached to the Sealed Compressor and is
used for starting the Motor.
(2) The compressor is a single-phase induction motor.
Durign the starting operation, the PTC allows current
flow to both the start winding and main winding.
4-2-3 PTC-Applied Circuit Diagram
● Starting Method for the Motor
Figure 18
4-2-4 Motor Restarting and PTC Cooling
(1) It requires approximately 5 minutes for the pressure to
equalize before the compressor can restart.
(2) The PTC device generates heat during operation.
Therefore, it must be allowed to cool before the
compressor can restart.
4-2-5 Relation of PTC-Starter and OLP
(1) If the compressor attempts to restart before the PTC
device is cooled, the PTC device will allow current to
flow only to the main winding.
(2) The OLP will open because of the over current
condition. This same process will continue (3 to 5
times) when the compressor attempts to restart until
the PTC device has cooled. The correct OLP must be
properly attached to prevent damage to the
compressor.
Parts may appear physically identical but could have
different electrical ratings. Replace parts by part
3.
number and model number. Using an incorrect part
could result in damage to the product, fire, injury, or
possibly death.
4-2-6 Note for Using the PTC-Starter
(1) Be careful not to allow over-voltage and over-current.
(2) Do not drop or handle carelessly.
(3) Keep away from any liquid.
If liquid such as oil or water enters the PTC,
PTC materials may fail due to breakdown of their
insulating capabilities.
(4) If the exterior of the PTC is damaged, the resistance
value may be altered. This can cause damage to the
compressor and result in a no-start or hard-to-start
condition.
(5) Always use the PTC designed for the compressor and
make sure it is properly attached to the compressor.
Parts may appear physically identical but could have
different electrical ratings. Replace parts by part
number and model number. Using an incorrect part
could result in damage to the product, fire, injury, or
possibly death.
Compressor and protects the Motor by opening the
circuit to the Motor if the temperature rises and
activating the bimetal spring in the OLP.
(2) When high current flows to the Compressor motor, the
Bimetal works by heating the heater inside the OLP,
and the OLP protects the Motor by cutting off the
current flowing to the Compressor Motor.
4-3-2 Role of the OLP
(1) The OLP is attached to the Sealed Compressor used
for the Refrigerator. It prevents the Motor Coil from
being started in the Compressor.
(2) For normal operation of the OLP, do not turn the Adjust
Screw of the OLP in any way.
4-4 TO REMOVE THE COVER PTC
(1) Remove the Cover Back M/C.
(2) Disconnect two housing upper side of comp connected
in.
(3) Loosen two screws on comp base.
Figure 19
(4) Use a L-shaped flap tool to pry off the cover.
(5) Assembly in reverse order of disassembly.
- 9 -
Page 10
5. CIRCUIT DIAGRAM
- 10 -
5. CIRCUIT DIAGRAM
- 10 -
Page 11
6. TROUBLESHOOTING
1
2
3
4
5
2
5
5
3
5
1
43
YES
NO
YES
The range of resistance is between 1~50Ω(ok)
Open or short
YES
YES
NO
NO
6-1 COMPRESSOR AND ELECTRIC COMPONENTS
Power Source.
Remove PTC-Starter
from Compressor and
measure voltage
between Terminal C of
Compressor and
Terminal 5 or 6 of PTC.
No Voltage.
Applied voltage isn't
in acceptable range.
(115V ±10%)
(Rated Voltage
±10%)?
OLP disconnected?
Advise customer that
power supply needs to be
checked by an electrician.
Replace OLP.
Check connection
condition.
Reconnect.
Check
resistance of
Motor
Compressor.
Check
resistance of
PTC-Starter.
Check resistance
between M-C, S-C and
M-S in Motor
Compressor.
Check resistance of
two terminals in
PTC-Starter.
Replace
Compressor.
Reference Page12.
Check OLP.
Check resistance of two
terminals in OLP.
Reference Page12.
Check
starting state.
Check the power supply
under load.
(Compressor attempting
to re-start after being off
for 5 minutes).
Supply
voltage rating
with ±10%.
Did
compressor
start?
Compressor
is OK
Replace the
compressor
- 11 -
Page 12
6-2 PTC AND OLP
65
Shows continuity
Open
Normal operation of
Compressor is
impossible or poor.
Separate PTC-Starter
from Compressor and
measure resistance
between No. 5 and 6
of PTC-Starter with a
Tester.
(Figure 20)
Separate OLP from
Compressor and check
resistance value
between two terminals
of OLP with a Tester.
(Figure 21)
Observation value is
115V/60Hz : 6.8Ω±30%
The resistance value
is 0Ω (short) or
∞ (open).
Check another
electric component.
Replace OLP.
Replace PTCStarter.
Figure 20
Figure 21
- 12 -
Page 13
6-3 OTHER ELECTRICAL COMPONENTS
▼ Not cooling at all
Compressor
doesn't run.
▼ Poor cooling performance
Compressor runs
poorly.
Check for open short or
incorrect resistance readings
in the following components
a. Starting devices
b. OLP
c. Compressor coil
d. Wiring harness
Check starting
voltage.
Check voltage at
starting devices.
Cause
Short, open, or broken.
Poor contact
or shorted.
Coil open or shorted.
Poor contact
or shorted.
Low voltage.
Poor or broken or
open contact.
Replace
indicated component.
Advise customer that
the Power supply
needs to be checked
by an electrician.
Replace
indicated component.
Fan motor
doesn't run.
Heavy frost buildup on
EVAPORATOR.
Check current flowing
in sub-coil of
Compressor.
Check rating of OLP.
Check wiring circuit.
Check Fan Motor.
Check current flow in
the following
components:
Sensor
Fuse-M
Check current flow in
the Defrost Heater.
Shorted.
Lack of capacity.
Wire is open or
shorted.
Coil is shorted
or open.
Open.
Open.
Replace
indicated component.
Replace
indicated component.
Replace
Defrost Heater.
- 13 -
Page 14
6-4 SERVICE DIAGNOSIS CHART
COMPLAINTPOINTS TO BE CHECKEDREMEDY
No Cooling.
Cools poorly.
Food in the
Refrigerator
is frozen.
Condensation or ice
forms inside
the unit.
Condensation forms
in the Exterior Case.
There is abnormal
noise.
• Is the power cord unplugged from the outlet?
• Check if the power switch is set to OFF.
• Check if the fuse of the power switch is shorted.
• Measure the voltage of the power outlet.
• Check if the unit is placed too close to the wall.
• Check if the unit is placed too close to the stove,
gas cooker, or in direct sunlight.
• Is the ambient temperature too high or
the room door closed?
• Check if food put in the refrigerator is hot.
• Did you open the door of the unit too often
or check if the door is sealed properly?
• Check if the Control is set to Warm position.
• Is food placed in the cooling air outlet?
• Check if the control is set to colder position.
• Is the ambient temperature below 41°F(5°C)?
• Is liquid food sealed?
• Check if food put in the refrigerator is hot.
• Did you open the door of the unit too
often or check if the door is sealed properly?
• Check if the ambient temperature and humidity
of the surrounding air are high.
• Is there a gap in the door gasket?
• Is the unit positioned in a firm and even place?
• Are any unnecessary objects placed
in the back side of the unit?
• Check if the Drip Tray is not firmly fixed.
• Check if the cover of the compressor enclosure
in the lower front side is taken out.
• Plug into the outlet.
• Set the switch to ON.
• Replace the fuse.
• If the voltage is low, correct the wiring.
• Place the unit about 4 inches (10 cm) from the wall.
• Place the unit away from these heat sources.
• Lower the ambient temperature.
• Put in foods after they have cooled down.
• Don't open the door too often and close
it firmly.
• Set the control to Recommended position.
• Place foods in the high-temperature section.
(front part)
• Set the control to Recommended position.
• Set the control to Warm position.
• Seal liquid foods with wrap.
• Put in foods after they have cooled down.
• Don't open the door too often and close
it firmly.
• Wipe moisture with a dry cloth. It will disappear
in low temperature and humidity.
• Fill up the gap.
• Adjust the Leveling Screw, and position the
refrigerator in a firm place.
• Remove the objects.
• Fix the Drip Tray firmly in the original position.
• Place the cover in its original position.
Door does not
close well.
Ice and foods
smell unpleasant.
● Other possible problems:
Check if frost forms in
the freezer.
Check the
refrigeration system.
Check the
Thermistor.
• Check if the door gasket is dirty with
an item like juice.
• Is the refrigerator level?
• Is there too much food in the refrigerator?
• Check if the inside of the unit is dirty.
• Are foods with a strong odor unwrapped?
• The unit smells of plastic.
Not
defrosting
The system
is faulty.
The operation of
the Thermistor is
incorrect.
• Clean the door gasket.
• Position in a firm place and level the
Leveling Screw.
• Make sure food stored in shelves does not prevent
the door from closing.
• Clean the inside of the unit.
• Wrap foods that have a strong odor.
• New products smell of plastic, but this
will go away after 1-2 weeks.
Check Components
of the defrosting
circuit.
Perform sealed
system repair.
Replace the
Thermistor.
- 14 -
Page 15
6-5 REFRIGERATION CYCLE
▼ Troubleshooting Chart
CAUSE
PARTIALFreezer Low flowing sound ofA little higher• Refrigerant level is low due
LEAKAGEcompartment and Refrigerant is heard andthan ambient• to a leak.
LEAKAGE
COMPLETE Freezer Flowing sound of refrigerantEqual to ambient• No discharging of Refrigerant.
LEAKAGEcompartment andis not heard and frost isn'ttemperature.• Normal cooling is possible by
CLOGGED BY DUST
PARTIALFreezer Flowing sound of refrigerantA little higher• Normal discharging of the
CLOGcompartment andis heard and frost formsthan ambient • refrigerant.
WHOLE
CLOG
MOISTURECooling operationFlowing sound of refrigerantLower than• Cooling operation restarts
CLOGstops periodically.is not heard and frost melts.ambient• when heating the inlet of the
COMPRESSION
COMP-Freezer andLow flowing sound ofA little higher • Low pressure at high side
DEFECTIVE
RESSIONRefrigeratorrefrigerant is heard andthan ambient• of compressor due to low
STATE OF
THE UNIT
Refrigerator don't frost forms in inlet only.temperature.• Normal cooling is possible by
cool normally.• restoring the normal amount of
Refrigerator don't formed.• restoring the normal amount of
cool normally.• refrigerant and repairing the leak.
Refrigerator don't in inlet only.temperature.• The capillary tube is faulty.
cool normally.
Freezer
compartment and
Refrigerator don't cool.
don't cool.frost forms in inlet only.temperature.• refrigerant level.
STATE OF THE
EVAPORATOR
Flowing sound of refrigerantEqual to ambient• Normal discharging of the
is not heard and frost isn'ttemperature.• Refrigerant.
formed.
TEMPERATURE
OF THE
REMARKS
COMPRESSOR
• refrigerant and repairing the leak.
temperature.• capillary tube.
NO COMP-No compressingFlowing sound of refrigerantEqual to ambient• No pressure in the high
RESSIONoperation.is not heard and there istemperature.• pressure part of the
no frost.• compressor.
- 15 -
Page 16
6-5-1 SEALED SYSTEM DIAGNOSIS
“Not Cooling” Complaint
All components operating, No airflow problems, Not frosted up as a defrost problem
problem has been isolated to sealed system area
Frost
Pattern?
Equalization
Test
Partial
Very Fast
Inefficient
Compressor
Partial
Restriction
Complete
Restriction
Equalization
Test
Condenser
Temperature
None
Very Fast
Very SlowVery Slow
Hotter than Normal
Air/Low Side
Leak
Loss of Change
Compressor Not
Pumping
Cap Tube
Sound
Room Temperature
Trace of Oil
Undercharge
Leak
Yes
No
Faint
Fast
None to Weak
(The equalization test is trying to restart a compressor using a start kit after it has been operating.)
- 16 -
Page 17
7. OPERATION PRINCIPLE AND REPAIR METHOD OF ICEMAKER
• Adjusts EJECTOR to Start Position with power on.
Power On
Start Position
Ice Making
Mode
Harvest
Mode
Park Position
Fill
Test Mode
• Waits until water becomes cold after starting the
ice making operation.
• Runs MOTOR to drop ice from the tray into the ICE BIN.
• Performs Ice Making Mode after supplying water by operating
the SOLENOID in ICE VALVE.
• To operate LINE and SERVICE, press and hold the Fill Key
for 3 seconds. The ice maker will run through 3 stages:
Harvest Fill Icemaking.
• With the detect lever, checks if the ICE BIN is full.
Power (On/ Off) Switch
Fill Key
7-1 OPERATION PRINCIPLE
7-1-1 Operation Principle of IceMaker
1. Turning the Icemaker stop switch off (O) stops the ice making function.
2. Setting the Icemaker switch to OFF and then turning it back on will reset the icemaker control.
- 17 -
Page 18
7-2 ICE MAKER FUNCTIONS
Heater
on
off
on
0V
5V
off
30 sec.
10 sec.
Motor
Hall IC
Ice removing
completion point
2 ms
Ice making sensor temperature is 50°F(10˚C)
or more
Max. 18 minutes
After detect LEVER rises
7-2-1 Start Position
1. After POWER OFF or Power Outage, check the EJECTOR's position with MICOM initialization to restart.
2. How to check if it is in place:
- Check HIGH/LOW signals from HALL SENSOR in MICOM PIN.
3. Control Method to check if it is in place:
(1) EJECTOR is in place,
- It is an initialized control, so the mode can be changed to ice making control.
(2) EJECTOR isn't in place:
A. If EJECTOR is back in place within 2 minutes with the motor on, it is being initialized. If not, go to Step B.
B. If EJECTOR is back in place within 18 minutes after the heater turns from ON to OFF, it is being initialized. If not, it is
not functioning. Repeat Step B with Heater and Motor off.
7-2-2 Ice Making Mode
1. Ice Making refers to the freezing of supplied water in the ice trays. Complete freezing is assured by measuring the
temperature of the Tray with Ice-Making SENSOR.
2. Ice Making starts after completion of the water fill operation.
3. The Ice Making function is completed when the sensor reaches 19°F(-7°C), 60 to 240 minutes after starting.
4. If the temperature sensor is defective, the ice-making function will be completed in 4 hours.
NOTE : After Icemaker Power is ON, the Icemaker heater will be on for test for 9 sec.
7-2-3 Harvest Mode
1. Harvest (Ice removing) refers to the operation of dropping cubes into the ice bin from the tray when ice-making has
completed.
2. Harvest mode:
(1) The Heater is ON for 30 seconds, then the motor starts.
(2) After performing Step 1 (the Heater is turned OFF), the Ejector will be back in place wthin 18 minutes. (Hall SENSOR
sign = OV). Ice removal is then complete. Then the Ice Maker cycles to the Fill Mode. The water supply fails to start, it
is not functioning. Put the Heater and Motor in the off position. Restart every 2 hours. (Refer to fig.1)
NOTE : If the motor malfunctions and starts before the detect lever rises, MICOM regards the Ice-Removing phase as
completed. Water then starts flowing. To prevent this, MICOM doesn’t switch to water-supply mode, but restarts the iceremoving mode. If this happens 3 times, the motor is malfunctioning and you should stop the loads (Heater, Motor). Then
restart the Ice-Removing mode every 2 hours. (See Step 2 above.)
<fig1. Harvest mode Process>
- 18 -
Page 19
7-2-4 Fill / Park Position
1. Once a normal harvest mode has been completed, the water solenoid will be activated.
2. The amount of water is adjusted by pressing the Fill Key repeatedly. This changes the time allowed for fill as illustrated in
the table below.
<Water supply amount TABLE>
STAGETIME TO SUPPLYINDICATIONSREMARKS
1
2
3
4
5
6 sec.
6.5 sec.
7 sec.
7.5 sec.
8 sec.
The water amount will vary depending
on the water control Switch setting, as
well as the water pressure of the
connected water line.
- 19 -
Page 20
7-2-5 Function TEST
1. This is a compulsory operation for TEST, SVC, cleaning, etc. It is operated by pressing and holding the Fill Key for 3 seconds.
2. The test works only in the Ice Making Mode. It cannot be entered from the Harvest or Fill mode. (If there is an ERROR, it
can only be checked in the TEST mode.)
3. Caution! If the test is performed before water in the Maker is frozen, the Ejector will pass through the water. When the Fill
mode begins (Stage 4), unless the water supply has been shut off, added water will overflow into the ice bin. If the control
doesn’t operate normally in the TEST mode, check and repair as needed.
4. After water is supplied, the normal CYCLE is followed: ice making → Harvest → Fill → Park Position.
5. Five seconds after Stage 5 is completed, the Ice Maker returns to MICOM control. The time needed to supply water
resets to the pre- test setting.
<Diagnosis TABLE>
STAGEITEMSINDICATORREMARKS
Five seconds after heater starts, heater will
1
2
HEATER
MOTOR
go off if temperature recorded by sensor is
10°C or lever is in up position.
Five seconds after heater starts, you can
confirm that motor is moving.
HALL IC I
3
4
5
6
(detection of
position)
VALVE
HALL IC II
(detection of full-
filled Ice)
Reset
Return to Status prior to
TEST MODE
You can confirm Hall Ic detection of position.
Two seconds after detection of initial
position, you can confirm that valve is on.
You can check whether hall is sensing Full
ice condition. (If there is a full-filled error, the
fifth LED is not on.)
Five seconds after fifth stage is completed,
the icemaker resets to initial status.
7-3 DEFECT DIAGNOSIS FUNCTION
7-3-1 ERROR CODES shown on Ice Maker water supply control panel
NODIVISIONINDICATORCONTENTSREMARKS
1
2
Normal
Ice-Making
Sensor
malfunction
Mark time to
supply
None
Open or short-circuited wire
Display switch
operates properly
Make sure that the wire
on each sensor is
connected.
3
ERROR indicators in table can be checked only in TEST mode.
Ice Maker Kit
malfunction
When ejector blades don’t reach
park position over 18 minutes after
- 20 -
Harvest Mode starts.
Check
HALL IC/MOTOR/
HEATER/RELAY
Page 21
8. DESCRIPTION OF FUNCTION & CIRCUIT OF MICOM
LOCK CONTROL
Ex) In selecting
"LOCK"
Ex) In selecting
"LOCK" again
DISPENSER & BUTTON
LOCK
DISPENSER & BUTTON
In initial Power On
/ Filter RESET
Replace indicator
light on
Classification
Filter Status
Display
FILTER RESET
HOLD 3SECS
EXPRESS FRZ
Control range -6°F ~ 8°F
-21°C ~ -13°C
32°F ~ 47°F
0°C ~ 8°C
Control range
8-1 FUNCTION
8-1-1 Function
1. When the appliance is plugged in, it is set to 37°F for Refrigerator and 0°F for freezer.
You can adjust the Refrigerator and the Freezer control temperature by pressing the ADJUST button.
2. When the power is initially applied or restored after a power failure, it is automatically set to “37” & “0”.
8-1-2 How to Toggle the Display between °F & °C
1. The display temperature mode can be changed from °F to °C or °C to °F by pressing and holding the FRZ TEMP and the
REF TEMP keys at the same time for over one second.
2. The initial setting is °F. Whenever the mode is changed, the LED lights are changed.
8-1-3 Lock function (dispenser and display button lock)
1. When the refrigerator is first turned on, the buttons are not locked. The display panel shows the padlock
unlocked icon.
2. To lock the display, the dispenser, and the control panel, press
and hold the LOCK button for 3 seconds. The locked padlock
icon is displayed with the word "LOCK" printed beside it.
3. The LOCK button is the only control feature that remains active
in the locked state. The buzzer sound, other control buttons,
and the dispenser are deactivated.
4. To release from the locked state, press and hold the LOCK
button again for 3 seconds.
8-1-4 Filter condition display function
1. There is a replacement indicator light for the water
filter cartridge on the dispenser.
2. Water filter needs replacement once six months or
about 28,000 seconds of using water filter.
3. Water filter light and “FILTER RESET HOLD 3 SECS”
text turn on to tell you need to replace the filter soon.
4. After replace the filter, press and hold the lock button
more than 3 seconds.
Then water filter light and “FILTER RESET HOLD 3
SECS” text turn off with reset status.
8-1-5 Express freezing selection
Please select this function for quick freezing.
• Function is repeated following below whenever pressing Express FRZ button.
• Expressing freezer function automatically turns off after a fixed time passes.
- 21 -
Page 22
8-1-6 CONTROL OF FREEZER FAN MOTOR
ClosedOpenClosedOpen
3 Times3 Times3 Times3 Times
Closed
Within 1 min.1 min.
30 sec30 sec30 sec
Freezer Door
or Refrigerator
Door
Buzzer
1. Freezer fan motor has high and standard speeds.
2. High speed is used at power-up, for express freezing, and when refrigerator is overloaded.
Standard speeds is used for general purposes.
3. To improve cooling speed, the RPM of the freezer fan motor change from normal speed to high.
4. High speed (2700RPM) : Initial power on or load corresponding operation, express freezing.
Normal speed (2400RPM) : General working conditions.
5. Fan motor stops when refrigerator or freezer door opens.
8-1-7 EXPRESS FREEZING
1. The purpose of this function is to intensify the cooling speed of freezer and to increase the amount of ice.
2. Whenever selection switch is pressed, selection/release, the LED will turn ON or OFF.
3. If there is a power outage and the refrigerator is powered on again, EXPRESS FREEZING will be canceled.
4. To activate this function, press the Express Freezing key and the LED will turn ON. This function will remain activated for
24 hrs. The first three hours the compressor and Freezer Fan will be ON. The next 21 hours the freezer will be controlled
at the lowest temperature. After 24 hours or if the Express Freezing key is pressed again, the freezer will return to its
previous temperature.
5. During the first 3 hours:
(1) Compressor and freezer fan (HIGH RPM) run continuously.
(2) If a defrost cycle begins during the first 90 minutes of Express Freezing, the Express Freeze cycle will complete its
cycle after defrosting has ended.
If the defrost cycle begins when Express Freeze has run for more than 90 minutes, Express Freeze will run for two
hours after the defrost is completed.
(3) If EXPRESS FREEZING is pressed during defrost, EXPRESS FREEZING LED is on but this function will start seven
minutes after defrost is completed and it shall operate for three hours.
(4) If EXPRESS FREEZING is selected within seven minutes after compressor has stopped, the compressor (compressor
delays seven minutes) shall start after the balance of the delay time.
(5) The fan motor in the freezer compartment runs at high speed during EXPRESS FREEZING .
6. For the rest of the 21 hours, the freezer will be controlled at the lowest temperature.
8-1-8 REFRIGERATOR LAMP AUTO OFF
1. To avoid heat damage caused by the lamp, it is turned off automatically when the refrigerator door is open for more than 7
minutes.
8-1-9 Alarm for Open Door
1. This feature sounds a buzzer when the freezer or refrigerator door is not closed within 1 minute after it is opened.
2. One minute after the door is opened, the buzzer sounds three times each for 1/2 seconds. These tones repeat every 30
seconds.
3. The alarm is cancelled when the freezer or the refrigerator is closed while the buzzer sounds.
- 22 -
Page 23
8-1-10 Buzzer Sound
When the button on the front Display is pushed, a Ding~ Dong~ sound is produced.
(Refer to the Buzzer Circuit 8-2-4 No. 3)
8-1-11 Defrosting (removing frost)
1. Defrosting starts each time the COMPRESSOR running time reaches 7 hours.
2. For initial power on or for restoring power, defrosting starts when the compressor running time reaches 4 hours.
3. Defrosting stops if the sensor temperature reaches 46.4°F(8°C) or more. If the sensor doesn’t reach 46.4°F(8°C) in
2 hours, the defrost mode is malfunctioning. (Refer to the defect diagnosis function, 8-1-14.)
4. Defrosting won’t function if its sensor is defective (wires are cut or short circuited)
8-1-12 Filter Replacement Indication
1. In 6 months after the UNIT (refrigerator) is power on, or after 28,000 seconds of dispenser use, the water filter Indicator
LED will be ON.
2. When the water filter indicator LED is illuminated, you should change the water filter. After this, you must press the water
filter button for three seconds and you will hear a ding-dong sound.
The LED will be OFF. This operation will indicate that the UNIT is reset to its initial conditions, so this process is restarted.
8-1-13 Electrical Parts Are Turned On Sequentially
Electrical parts such as COMP, defrosting heater, freezer FAN, etc. are turned on in the following order to prevent noise and
parts damage. Several parts are started at the same time at initial power on and are turned off together when TEST is
completed.
OPERATINGORDERS
Temperature of Defrosting
Sensor is 113°F(45°C) or
more (when unit is newly
Initial power on
purchased or when moved)
Temperature of defrosting
sensor is lower than
113 °F(45°C)
(when power cuts, SERVICE)
Reset to normal operation
from TEST MODE
POWER
in 1/2 secondin 1/2 second
ON
POWER
in 1/2 second
ON
in 1/2 secondin 1/2 second
COMP
COMP
ON
Defrosting
heater ON
ON
Total load
OFF
in 7 minute
COMP
ON
Freezer FAN
in 10 second
Freezer FAN
ON
in 1/2 second
ON
Defrosting
heater OFF
Freezer FAN
ON
- 23 -
Page 24
8-1-14 Defect Diagnosis Function
1. Automatic diagnosis makes servicing the refrigerator easy.
2. When a defect occurs, the buttons will not operate; but the tones. such as ding. will sound.
3. When the defect CODE removes the sign, it returns to normal operation (RESET).
4. The defect CODE shows on the Refrigerator and Freezer Display.
ERROR CODE on display panel
Note 1) Freezer room notch temperature display and refrigerator room notch temperature display (Failure code
indication part) are normally indicated in abnormal ambient sensor, and “Er” indicated on the amvient
temperature display.
✽ LED check function: If simultaneously pressing express freezer button and freezing temperature adjustment
button for a second, display LED graphics on. If releasing the button, the LED graphic
displays the previous status.
NOITEM
Failure of freezer
1
sensor
Failure of
2
Refrigerator sensor
Failure of defrost
3
sensor
Failure of Room
Temperature
4
sensor
Failure of defrost
5
mode
Failure of BLDC
Fan Motor at
6
Freezing
Compartment.
ERROR CODE
Er
Er
Er
When Display check mode
Er
Er
FS
rS
dS
dH
FF
CONTENTSREMARKS
Cut or short circuit wire
Cut or short circuit wire
Inspect Connecting wires
Cut or short circuit wire
Cut or short circuit wire
When defrost sensor
doesn’t reach 46°F within 2
hours after starting defrost.
If there is no fan motor
signal for more than 65sec
in operation fan motor
Snapping of defrost heater
or Temperature fuse, pull-
out of connector (indicated
minimum 2 hours after
Poor motor, hooking to
wires of fan, contact of
structures to fan, snapping
or short circuit of Lead wires
on each sensor
failure occurs)
- 24 -
Page 25
8-1-15 TEST Mode
1. The Test mode allows checking the PCB and the function of the product as well as finding out the defective part in case of
an error.
2. The test mode is operated by pressing two buttons at Display panel.
3. While in the test mode, the function control button is not recognized, but the recognition tone (beep~) sounds.
4. After exiting the test mode, be sure to reset by unplugging and then plugging in the appliance.
5. If an error, such as a sensor failure, is detected while in the test mode, the test mode is cleared and the error code is
displayed.
6. While an error code is displayed, the test mode will not be activated.
MODEMANIPULATIONCONTENTSREMARKS
TEST1
TEST2
TEST3
Reset
Push FREEZER
Key and LOCK KEY at the
same time for 3 seconds
OR Push TEST S/W(on
the main Board) once.
Push FREEZER
Key and LOCK KEY at the
same time for 3 seconds
in TEST MODE 1 OR
Push TEST S/W once in
TEST MODE 1
Push FREEZER
Key and LOCK KEY at the
same time for 3 seconds
in TEST MODE 2 OR
Push TEST S/W once in
TEST MODE 2
Push FREEZER
Key and LOCK KEY at the
same time for 3 seconds
in TEST MODE 3 OR
Push TEST S/W once in
TEST MODE 3
1) Continuous operation of the
COMPRESSOR and the Freezer fan
2) Stepping DAMPER OPEN
3) Defrosting HEATER OFF
4) DISPLAY LED all ON
1) Continuous operation of the
COMPRESSOR and the Freezer fan
2) Stepping DAMPER CLOSE
3) Defrosting HEATER OFF
4) DISPLAY LED shows no. 2
1) COMPRESSOR and the Freezer fan
OFF
2) Stepping DAMPER CLOSE
3) Defrosting HEATER ON
4) DISPLAY LED shows no. 3
Reset to the previously setting
Before TEST MODE.
Reset if the
Temperature of the
Defrosting Sensor is
46°F(8°C) or more.
The compressor will
Start after a 7-minute
Delay.
* Freezer Fan RPM Variable Check:
In case the freezer fan is in operation when the express freezer button and freezing temp. button. Control are pressed for
more than one second at the same time freezer fan RPM changes. (for example if high speed, to normal speed or if
normal speed, to high speed for 30 seconds)
After 30 seconds, it turns to its original RPM.
* Demonstration MODE:
1. When the Express Freezing Temp. Control button and the Refrigerator Temp. Control button are pushed and hold for 3 seconds
or longer, it converts to Demostration Mode.
2. The Display shows the Demo graphic.
3. In this status, all Loads are off (Compressor / Fan / Damper / Heater)
(Even is Demonstration Mode, the refrigerator Lamp automatic off function warks normally and can be demonstrated)
4. Exit the Demo mode and reset the Display by pressing the Express Freezing Temp. Control button and the Refrigerator Temp.
Control button for 3 seconds or longer.
- 25 -
Page 26
8-2 PCB FUNCTION
8-2-1 Power Circuit
The secondary part of the TRANSFORMER is composed of the power supply for the display, the BLDC FAN Motor drive
(15.5 V), the relay drive (12 Vdc) and the MICOM and IC (5 Vdc).
The voltage for each part is as follows:
VA1 is a part for preventing over voltage and noise. When 385V or higher power is applied, the inside elements are shortcircuited and broken, resulting in blowout of the fuse in order to protect the elements of the secondary part of the
TRANSFORMER.
PARTVA 1CE 3CE 4CE 5
VOLTAGE115 Vac12 Vdc15.5 Vdc5 V
- 26 -
6.8
100
Page 27
8-2-2 Oscillation Circuit
This circuit generates the base clock for calculating time and the synchro clock for transmitting data from and to the inside
logic elements of the IC1 (MICOM). Be sure to use specified replacement parts, since calculating time by the IC1 may be
changed. If changed, the OSC1 SPEC will not work.
8-2-3 Reset Circuit
The RESET circuit allows all the functions to start at the initial conditions by initializing various parts, including the RAM
inside the MICOM (IC1) when the power is initially supplied or the power supply to the MICOM is restored after a
momentary power failure. For the initial 10ms of power supply, LOW voltage is applied to the MICOM RESET terminal.
During a normal operation, 5V is applied to the RESET terminal. (If a malfunction occurs in the RESET IC, the MICOM will
not operate.)
- 27 -
Page 28
8-2-4 Load / Buzzer Drive & Open Door Detection Circuit
1. Load Drive Condition Check
LOAD TYPE
COMP
NO.13NO.14NO.16NO.12NO.15
1V or below
12V
DEFROSTING
HEATER
LAMPVALVE
FRENCH DOOR
HEATER 1, 2 /
DEW HEATER
Measurement Location (IC6)
Condition
ON
OFF
- 28 -
2.1 Fan motor driving circuit (freezing compartment fan)
1. This circuit makes standby power 0 by cutting off power supplied to ISs inside of the fan motor in the fan motor OFF.
2. This is a circuit to perform a temporary change of speed for the fan motor and applies DC voltage up to 7.5V ~ 16V to motor.
3. This circuit prevents over-driving the fan motor by cutting off power applied to the fan motor in the lock of fan motor by
sensing the operation RPM of the fan motor.
2. Motors driving circuit
CON1
POWER
ICE MAKER
RUNNING CAPACITOR
STARTING CAPACITOR
DEF-HEATER
LAMP-F
LAMP-R
WATER VALVE
FRENCH DOOR
HEATER
L1
5mH/4A
CM1
470nF
VA1
COMP
CON2
OLP
M
FUSE-M
com
nc
com
nc
com
nc
com
nc
CON3
275VAC
5
3
1
1
3
5
7
5
3
1
RY1
ALZ21B12
RY2
G5NB-1A
RY3
G5NB-1A
RY4
G5NB-1A
RY5
G5N-1A
RY6
G5N-1A
IC6
KID65003AP
D7
1N4004
9
4
13
3
14
6
11
1
16
10
P06
11
P05
14
P02
13
P03
I C 1
(MICOM)
2
15
5
12
8
12
P04
9
P07
PTC START
RC-FILTER
VALVE II
RC-FILTER
9
7
COOLING-FAN
A
B
DOOR S/W-F
C
D
DOOR S/W-R1&R2
M
M
Page 29
partpartpart
ab
MOTOR OFF2V or less0V5V
MOTOR ON13V~15V0V2V~3V
2.2 Cooling motor driving circuit (machine room)
c
1. This circuit makes standby power 0
by cutting off power supplied to ISs inside of the fan motor in the fan motor OFF.
2. This circuit prevents over-driving the fan motor by cutting off power applied to the fan motor in the lock of fan motor by
sensing the operation RPM of the fan motor.
Partpart
ab
MOTOR OFF2V or less0V
MOTOR ON13V~15V0V
A
R46
4.7KJ
CC20*
102
CON4
4
5
6
3
4
1
C-FAN
I C 1
(MICOM)
P14
(PPG)
P11
(INT1)
R43
Q4
330J
KTB1151
R40
4.7KJ
R41
35
3.9KJ
R42*
10KJ
R44
1.5KJ
1/2W
Q5
KTC3198
32
RJ1*
R45
2KJ
D9
FR107
D8
FR107
1mH
L4
220uF
/25V
CE12
CC19*
223
- 29-
Page 30
3. Open Door Detection Circuit Check
Measurement
Freezer/
Location
Refrigerator Door
Closed5 V
Open0 V
8-2-5 Temperature Sensor Circuit
7
1
2
(PIN NO.30 & PIN NO.37)
7
5
6
The upper CIRCUIT reads REFRIGERATOR temperature, FREEZER Temperature, and DEFROST-SENSOR temperature
for defrosting and the indoor temperature for compensating for the surrounding temperature into MICOM.
OPENING or SHORT state of each TEMPERATURE SENSOR are as follows:
SENSORCHECK POINTNORMAL (-30¡C ~ 50¡C)
Freezer SensorPOINT Voltage
Refrigerator SensorPOINT Voltage
A
B
SHORT-CIRCUITED
OPEN
0.5 V ~ 4.5 V0 V5 V
Defrosting SensorPOINT Voltage
Room Temperature sensor
POINT Voltage
C
D
- 30-
Page 31
8-2-6 Refrigeration Compartment Stepping Motor Damper Circuit
* The circuit shown below is the damper circuit to regulate the refrigerator temperature.
2
4
3
8-2-7 Dispenser Input
7
3
4
- 31-
Page 32
8-2-8 Temperature Compensation & Overcooling/Undercooling Compensation Circuit
1. Refrigerator Temperature Compensation
Refrigerator
ResistanceTemperature Remark
(RCR)Compensation
180 KΩ+2.5°CCompensation by
56 KΩ+2.0°C
33 KΩ+1.5°C
18 KΩ+1.0°C
12 KΩ+0.5°C
10 KΩ0 °C
8.2 KΩ-0.5°CCompensation by
5.6 KΩ-1.0°C
3.3 KΩ-1.5°C
2 KΩ-2.0°C
470 Ω-2.5°C
2. The temperature compensation for refrigerator compartment is in the following table:
➧ Table of Temperature Compensation by adjusting the
resistance (difference from the current temperature)
e.g., If the refrigerator compensation resistance
(RCR) is changed from 10K (the current resistance)
to 18K (the adjustment resistance), the temperature
of the refrigerator rises 33.8°F(+1°C).
NOTE: This circuit is designed to input the necessary temperature compensation values into the MICOM. This adjusts the
refrigerator temperature, which is different in each model.
- 32 -
Page 33
8-2-9 Key Button Input & Display Light-On Circuit
The circuit shown above determines whether a function control key on the operation display is pushed. It also turns on the
corresponding function indication LED Module SEVEN SEGMENT DISPLAY. The drive type is the scan type.
4
3
2
1
CON 6
- 33-
Page 34
8-3 RESISTANCE SPECIFICATION OF SENSOR
TEMPERATURE
- 20 ˚C22.3 KΩ77 KΩ
- 15 ˚C16.9 KΩ60 KΩ
- 10 ˚C13.0 KΩ47.3 KΩ
- 5 ˚C10.1 KΩ38.4 KΩ
0 ˚C7.8 KΩ30 KΩ
+ 5 ˚C6.2 KΩ24.1 KΩ
+ 10 ˚C4.9 KΩ19.5 KΩ
+ 15 ˚C3.9 KΩ15.9 KΩ
+ 20 ˚C3.1 KΩ13 KΩ
+ 25 ˚C2.5 KΩ11 KΩ
+ 30 ˚C2.0 KΩ8.9 KΩ
+ 40 ˚C1.4 KΩ6.2 KΩ
+ 50 ˚C0.8 KΩ4.3 KΩ
RESISTANCE OF FREEZER
SENSOR
RESISTANCE OF REFRIGERATOR &
DEFROST SENSOR & ROOM SENSOR
• The resistance of the SENSOR has a ±5% common difference.
• Measure the resistance of the SENSOR after leaving it for over 3 minutes in the measuring temperature.
This delay is necessary due to sensor response speed.
• Measure the F-SENSOR, SUPER FROST SENSOR, R1, R2-SENSOR after disconnect CON5 of PWB ASSY, MAIN.
- 34 -
Page 35
COOLING is poor.NO COOLING.1. If the COMPRESSORUSE TEST MODE1 COMPRESSOR locked orReplace COMPRESSOR.
INDUCTOR,RADIAL LEAD
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,FIXED CARBON FILM
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,FIXED CARBON FILM
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,METAL GLAZED(CHIP)
RESISTOR,FIXED METAL FILM
RESISTOR,FIXED METAL FILM
RESISTOR,FIXED METAL FILM
RESISTOR,FIXED METAL OXIDE FILM
RESISTOR,FIXED METAL OXIDE FILM
RESISTOR,FIXED METAL OXIDE FILM
RESISTOR,FIXED METAL OXIDE FILM
TRANSISTOR
TRANSISTOR,BIPOLARS
TRANSISTOR,BIPOLARS
FILTER(CIRC),EMC
FILTER(CIRC),EMC
FILTER(CIRC),EMC
SWITCH,TACT
DIODE,ZENERS
JUMP WIRE
FUSE,DRAWING
SCREW TAP TITE(S),BINDING HEAD
HEAT SINK
SOLDER,SOLDERING
FLUX
SOLDER(ROSIN WIRE) RS0
SPEC
BEST BRAVO-PJT
DL-PJT 2.9MH/20W
YW396-09AV
YW396-07AV
YW396-05AV
SMW250 YEONHO 6P 2.5MM STRAIGHT SN
SMW250 YEONHO 12P 2.5MM STRAIGHT SN
SMW250 YEONHO 4P 2.5MM STRAIGHT SN
SMW250 YEONHO 7P 2.5MM STRAIGHT SN
TMP87C846N 42P SDIP BK MASK BRAVO33-PJT BEST/BETTER
STR-G6351 5PIN BK SMPS 2,4PIN FORM
PS2561L1-1-V NEC 4P,DIP BK = TLP721F
KIA431 3 PIN TP - KIA7805PI 3DIP BK 5V 1A REFORM
KID65003AP 16P,SDIP BK DRIVE IC
KIA7042P KEC 3P BK RESET
TA7774AP 16,SDIP BK DRIVE,IC STEPPING MOTOR
ALZ12B12 NAIS 250VAC 16A 12VDC 1A NO VENTING
G5N-1A OMRON 250VAC 1.5A 12VDC 1A JAPAN
G5NB-1A-E(CHINA) OMRON 250VAC 5A 12VDC 1A NO VENTING
G5SB-14 OMRON 250VAC 5A 12VDC 1C NO VENTING
CSTS0400MG03 MURATA 4MHZ . TP -
INR14D621 ILJIN UL/VDE BK 620V
INR14D331K IL JIN UL/CSA/VDE BK
262E SCREW ASSEMBLY4001JA3005A4001JA3005A4001JA3005A
262H HINGE ASSEMBLY,C4775JJ2017R4775JJ2017D4775JJ2017H
271A HINGE ASSEMBLY,U4775JJ2018B4775JJ2018B4775JJ2018B
271C HINGE ASSEMBLY,U4775JJ2018A4775JJ2018A4775JJ2018A
276A HOLDER,BUTTON4930JJ3016A4930JJ3016A4930JJ3016A