Lg Lmvn240hv, Lmvn360hv Owner's Manual

Air Conditioner
SVC MANUAL(Exploded View)
Type : Vertical Air Handling Unit
MODEL : AMNW24GNJA0 [LMVN240HV]
AMNW36GNJA0 [LMVN360HV]
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
- 2 -
Specification
Copyright ©2013 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Specification
Notes:
1. All data are based on the following conditions
- Cooling Temperature : Indoor 27˚C(80.6˚F) DB / 19˚C(66.2˚F) WB Outdoor 35˚C(95˚F) DB / 24˚C(75.2˚F) WB
- Heating Temperature : Indoor 20˚C(68˚F) DB / 15˚C(59˚F) WB Outdoor 7˚C(44.6˚F) DB / 6˚C(42.8˚F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound measured at 1m(3.3ft) away from the center of the unit. The values depends on the ambient conditions and values are normally higher in actual operation.
Model Name
AMNW24GNJA0
[LMVN240HV]
AMNW36GNJA0
[LMVN360HV]
Power Supply V, Ø, Hz
208/230, 1, 60
220, 1, 60
208/230, 1, 60
220, 1, 60
Capacity
Nominal kW Class 7.03 10.6
Nominal Btu/h Class 24,000 36,000
Casing Color - Morning fog Morning fog
Dimensions Body
W x H x D mm 457 × 1236 × 540 457 × 1236 × 540
W x H x D inch 18 x 48-21/32 x 21-1/4 18 x 48-21/32 x 21-1/4
Net Weight Body kg (lbs) 53 (117) 55 (121)
Heat Exchanger
(Row x Column x Fins per inch) x No. - (2 x 24 x 18) x 2 (3 x 24 x 18) x 2
Face Area m2(ft2) 0.22 (2.37) x 2 0.22 (2.37) x 2
Fan
Type - Sirocco Fan Sirocco Fan
Air Flow Rate (0.3 inch)
H / M / L ft3/min 20.1 / 18.1 / 13.6 28 / 24.9 / 22.7
H / M / L ft3/min 710 / 640 / 480 990 / 880 / 800
Air Flow Rate (0.5 inch)
H / M / L ft3/min 20.1 / 18.1 / 13.6 28 / 24.9 / 22.7
H / M / L ft3/min 710 / 640 / 480 990 / 880 / 800
Fan Motor
Type - BLDC BLDC
Output W x No. 96 x 1 182 x 1
Running Current A 0.59 1.12
Sound Pressure Level (0.3 inch ESP) H / M / L dB(A) 43 / 42 / 41 45 / 44 / 43
Sound Power Level Cooling dB(A) - -
Piping Connections
Liquid mm(inch) 6.35 (1/4) 9.52 (3/8)
Gas mm(inch) 12.7 (1/2) 15.88 (5/8)
Drain_Primary (I.D.) mm(inch) 19.05 (3/4FPT) 19.05 (3/4FPT)
Drain_Secondary (I.D.) mm(inch) 19.05 (3/4FPT) 19.05 (3/4FPT)
Air Filter - - -
Safety Devices
- Fuse Fuse
- Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x AWG 4C x 18 4C x 18
- 3 -
Copyright ©2013 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
List of Functions
2. List of Functions
Note
1. * : These functions need to connect the wired remote controller.
O : Applied X : Not applied Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Category Functions
AMNW24GNJA0 [LMVN240HV] AMNW36GNJA0 [LMVN360HV]
Air flow
Air supply outlet 1 Airflow direction control (left & right) X Airflow direction control (up & down) X Auto swing (left & right) X Auto swing (up & down) X Airflow steps (fan/cool/heat) 3 / 3 / 3 Chaos wind(auto wind) X Jet cool/heat X / X Swirl wind X
Air purifying
Triple filter (Deodorizing) X Plasma air purifier X Allergy Safe filter X Long-life prefilter (washable / anti-fungus) X
Installation
Drain pump X E.S.P. control O Electric heater ANEH053B1(5kW) / ANEH103B2(10kW) High ceiling operation X Auto Elevation Grille X
Reliability
Hot start O Self diagnosis O Soft dry operation O
Convenience
Auto changeover X Auto cleaning X Auto operation(artificial intelligence) O Auto Restart O Child lock O Forced operation X Group control O Sleep mode O Timer(on/off) O Timer(weekly) O Two thermistor control O
Individual control
Standard Wired remote controller PREMTB10U Deluxe wired remote controller X Simple wired remote controller O Simple Wired remote controller(for hotel use) X Wireless remote controller* PQWRHQ0FDB
Network function
General central controller (Non LGAP) X Network Solution(LGAP) O Dry contact PQDSA(1) / PQDSB(1) / PQDSBC / PQDSBNGCM1 PI 485(for Indoor Unit) X
Special function kit
Zone controller X CTI(Communication transfer interface) X Electronic thermostat X
Others
Remote temperature sensor PQRSTA0 Group control wire PZCWRCG3 Telecom shelter controller X
Loading...