Lg Lmu186hv, Lmu185hv Installation Template

ENGLISH
P/No: MFL39817310
FLEX MULTI SPLIT INSTALLATION
INSTRUCTIONS
FRANÇAIS ESPAÑOL
2 Multi Air Conditioner
TABLE OF CONTENTS
Installation Parts Provided ...................................................3
Product Introduction .............................................................4
Indoor Unit.........................................................................4
Outdoor Unit......................................................................4
Safety Precautions ................................................................5
Installation of Indoor, Outdoor Unit .....................................8
Select the best location ....................................................8
Seaside Applications and Installation .............................10
Piping length and elevation.............................................11
Installation............................................................................12
Connecting the piping .....................................................12
How To Fix.......................................................................15
Wiring Connection...........................................................16
Conduit connection .........................................................16
Ceiling dimension and hanging bolt location ..................17
How to Fix .......................................................................18
Wiring Connection...........................................................18
Conduit connection .........................................................18
Installation of wired Remote Controller ...........................20
Wired remote controller switch information.....................21
Trial Operation .................................................................22
Celsius/Fahrenheit Switching..........................................23
Setting the Central-Control Address ...............................24
ESP Function ..................................................................25
Ceiling dimension and hanging bolt location ..................26
Wiring Connection...........................................................27
Conduit connection .........................................................27
Installation of Wired Remote Controller(Optional)...........28
Installation of Decorative Panel.......................................30
Drain Piping.....................................................................32
Flaring Work and Connection of Piping ............................35
Flaring work.....................................................................35
Connection of piping - Outdoor .......................................36
Connecting the Cable between Indoor Unit and
Outdoor Unit.........................................................................37
Connect the cable to the Indoor unit...............................37
Connect the cable to the Outdoor unit. ...........................38
Connection method of the connecting cable(Example) ..39
Checking the Drainage, Insulating the Pipe and Special
Piping Applications .............................................................40
Insulating the Pipe and Special Piping Applications .......40
Long Pipe Setting ................................................................41
Air Purging and Evacuation ...............................................42
Leak Checking.................................................................42
Evacuation.......................................................................43
Charging ...............................................................................44
Combination indoor units...................................................45
Level gaugeScrew driverElectric drillHole core drill (ø50mm)
Flaring tool setSpecified torque wrenches
1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m (different depending on model No.)
Adjustable wrench
A glass of waterScrew driver
Hexagonal wrench(4mm)Refrigerant Gas Leak DetectorVacuum pumpGauge manifold
Owner's manualThermometerRemote Control Holder
Installation Requirements
Required Tools
Installation Manual 3
ENGLISH
Installation Parts Provided
Installation Parts Provided
[Standard /Artcool Mirror Type]
[Cealing Concealed Duct Type]
[Cealing Cassette Type]
Type "A" screw (6 EA) Type "A" screw (8 EA)
Type "B" screw Type "B" screw
Remote control holderRemote control holder
Type 1 Type 2
Installation plate Installation plate
Name
Quantity
Shape
for gas pipe
for liquid pipe
Clamp metal
1 EA
Insulation for
fitting
1 set
Clamp
8 EA
Screws for
duct flanges
1 set
Conduit Bracket
Screw(M4) 2EA
Conduit Bracket
1 EA
Name
Quantity
Shape
for gas pipe
Conduit Bracket
Screw(M4) 2EA
for liquid pipe
Clamp metal
1 EA
Insulation for Remote
control holder
fitting
1 SET 1 EA
Drain hose
1 EA
Clamp
Conduit Bracket
8 EA
Washer for
hanging backet
8 EA 1 EA
Here is a brief introduction of the indoor and outdoor units. Please see the information specific to your indoor unit type.
Product Introduction
4 Multi Air Conditioner
Product Introduction
more than
70 cm
(27.6 inch)
more than
60 cm
(23.6 inch)
more than
30 cm
(11.8 inch)
more than
30 cm
(11.8 inch)
Air Outlet
Air Intake
(side, rear)
Connection pipe Drain hose
Connecting wire
Control cover
more than 30 cm
(11.8 inch)
Signal receiver
Front panel
Air discharge
ON/OFF button
Power cord
Plasma filter
Air inlet Air filter
Air inlet
Plasma filter (Optional)
Air filter
Air outlet
Front grille ON/OFF button
Signal
receiver
Grille tab
Flap
(Horizontal blade)
Louvers
(Vertical blades)
Cabinet
Air Discharge
Air Inlet
Signal receiver
Front Panel
Air outlet vents
Air Inlet
[Standard Type]
[Cealing Concealed Duct Type]
[Artcool Mirror Type]
[Ceiling Cassette Type]
Air outlet vents
Base plate
Connection pipe
Drain hose
Connecting wire
Control cover
Air intake vents
Indoor Unit
Outdoor Unit
Installation Manual 5
ENGLISH
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
The meanings of the symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
WARNING
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Always perform grounding.
Otherwise, it may cause electrical shock.
Don’t use a power cord, a plug or a loose socket which is damaged.
Otherwise, it may cause a fire or electrical shock.
For installation of the product, always contact the service center or a professional installation agency.
Otherwise, it may cause a fire, electrical shock, explosion or injury.
Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Always install an air leakage breaker and a dedicated switching board.
No installation may cause a fire and electrical shock.
Do not keep or use flammable gases or combustibles near the air conditioner.
Otherwise, it may cause a fire or the failure of product.
Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
It may cause injury or an accident.
Do not disassemble or repair the product randomly.
It will cause a fire or electrical shock.
WARNING
CAUTION
6 Multi Air Conditioner
Safety Precautions
Do not install the product at a place that there is concern of falling down.
Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
Sharp edges may cause injury.
Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
Otherwise, it may cause a fire or electrical shock.
Do not use the power cord near the heating tools.
Otherwise, it may cause a fire and electrical shock.
Do not open the suction inlet of the indoor/outdoor unit during operation.
Otherwise, it may electrical shock and failure.
Do not allow water to run into electrical parts.
Otherwise, it may cause the failure of machine or electrical shock.
Hold the plug by the head when taking it out.
It may cause electric shock and damage.
Never touch the metal parts of the unit when removing the filter.
They are sharp and may cause injury.
Do not share the outlet with other appliances.
It will cause an electric shock or a fire due to heat generation.
Do not use the damaged power cord.
Otherwise, it may cause a fire or electrical shock.
Do not modify or extend the power cord randomly.
Otherwise, it may cause a fire or electrical shock.
Take care so that the power cord may not be pulled during operation.
Otherwise, it may cause a fire or electrical shock.
Unplug the unit if strange sounds, smell, or smoke comes from it.
Otherwise, it may cause electrical shock or a fire.
Keep the flames away.
Otherwise, it may cause a fire.
Do not step on the indoor/outdoor unit and do not put anything on it.
It may cause an injury through dropping of the unit or falling down.
Do not place a heavy object on the power cord.
Otherwise, it may cause a fire or electrical shock.
When the product is submerged into water, always contact the service center.
Otherwise, it may cause a fire or electrical shock.
Take care so that children may not step on the outdoor unit.
Otherwise, children may be seriously injured due to falling down.
Operation
Installation Manual 7
ENGLISH
Safety Precautions
CAUTION
Installation
Install the drain hose to ensure that drain can be securely done.
Otherwise, it may cause water leakage.
Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
Otherwise, it may cause dispute with the neighbors.
Always inspect gas leakage after the installation and repair of product.
Otherwise, it may cause the failure of product.
Keep level parallel in installing the product.
Otherwise, it may cause vibration or water leakage.
Avoid excessive cooling and perform ventilation sometimes.
Otherwise, it may do harm to your health.
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles.
Otherwise, it may damage your properties.
Do not place obstacles around the flow inlet or outlet.
Otherwise, it may cause the failure of appliance or an accident.
Operation
8 Multi Air Conditioner
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Read completely, then follow step by step.
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
6. Use a Metal Detector or Metal Scanner to locate studs to prevent unnecessary damage to the wall.
Select the best location
Top view
Front view
600(23 19/32)
600(23 19/32)
7 5/16
Front
1000(39 3/8)
H=13/16 or more
A
B
Capacity(Btu/h class)
AB
9/12k 600(23 5/8) 900(35 15/32)
18k 600(23 5/8) 1100(43 5/16)
Unit:mm(inch)
Ceiling
False ceiling
False ceiling
20(13/16) or more
1500
(59 1/16)
or more
1500(59 1/16) or
more
Above 2500(98 7/16)
3300(129 15/16) or less
1500(59 1/16)or
more
Floor
[Cealing Concealed Duct Type] [Cealing Cassette Type]
[Standard /Artcool Mirror Type]
More than
100(3 15/16)
More than 2300(90 9/16)
More than 200(7 7/8)
More than
100(3 15/16)
Unit:mm(inch)
Installation of Indoor, Outdoor Unit
Installation Manual 9
ENGLISH
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5.
Select a place so that the warm air and sound from the air conditioner does not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
more than 700
(27 9/16)
more than 300
(11 7/16)
more than 300
(11 7/16)
more than 600
(23 21/32)
Unit:mm(inch)
10 Multi Air Conditioner
Seaside Applications and Installation
Installation of Indoor, Outdoor Unit
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3.
If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2)
In case, to install the outdoor unit on the seaside, set up a windbreaker/barrier, to lessen the unit's exposure to sea air
3) Select a well-drained place.
It should be strong enough (like concrete) to obstruct the wind from the sea.
The height and width should be more than 150% of the outdoor unit.
A minimum of 70cm (27 1/16 inches)
of space between outdoor unit and the windbreak
for easy air flow.
Sea wind Sea wind
Sea wind
Windbreaker/Barrier
Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger using water is recommended.
1. Selecting the location(Outdoor Unit)
Installation Manual 11
ENGLISH
Installation of Indoor, Outdoor Unit
Multi Piping Type
Piping length and elevation
18k 50(164) 25(82) 3(10) 15(49) 7.5(25) 24k
24k 75(246) 25(82) 3(10) 15(49) 7.5(25) 33k
36k 75(246) 25(82) 3(10) 15(49) 7.5(25) 48k
Outdoor Unit
Capacity
(Btu/h class)
Max total length
of all pipes
(A+B)/(A+B+C)/
(A+B+C+D)
Max length of
each pipe (A/B/C/D)
Min length of
each pipe
(A/B/C/D)
Max Elevation between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
Max.Combination
of Indoor unit
(Btu/h class)
h2
A
B
C
D
h1
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.
9k 9.52(3/8) 6.35(1/4) 7.5(25) 20(0.22)
12k 9.52(3/8) 6.35(1/4) 7.5(25) 20(0.22)
18k 12.7(1/2) 6.35(1/4) 7.5(25) 20(0.22)
Gas Liquid
Standard
Pipe Length
Unit : m(ft)
Additional
Refrigerant
Unit : g/m(oz/ft)
Indoor unit
Capacity
(Btu/h class)
Pipe Diameter
Unit : mm(inch)
Unit : m(ft)
12 Multi Air Conditioner
Installation
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration on the right) and pull the tubing and drain hose away from chassis.
3. Route the indoor tubing and the drain hose to the required piping hole position.
4. Insert the piping, drain hose, and the connecting cable into the piping hole.
5.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
6. Tape the drain hose and the connecting cables.
7. Indoor unit installation
Hang the indoor unit from the hooks at the
top of the installation plate.
Insert the spacer etc. between the indoor
unit and the installation plate and separate the bottom of the indoor unit from the wall.
For right rear piping For left rear piping
Installation
Connecting the piping
[Standard /Artcool Mirror Type]
Connecting
cable
Drain pipe
Tape
Connecting pipe
Drain hose
Connecting cable
Indoor unit
Spacer
Installation plate
80(33/16)
Installation
Installation Manual 13
ENGLISH
8. Connecting the piping to the indoor unit and drain hose to drain pipe.
1) Align the center of the pipes and sufficiently tighten the flare nut by hand.
2) Tighten the flare nut with a wrench.
3) Next, extend the indoor unit's drain hose. Then attach the drain pipe.
Indoor unit tubing Flare nut Pipes
mm inch kgf.m (lbf·ft)
Ø6.35 1/4 1.8~2.5 (13~18) Ø9.52 3/8 3.4~4.2 (24~30) Ø12.7 1/2 5.5~6.6 (40~48)
Outside diameter Torque
Installation Information. For left piping. Follow the instruction below.
Good case
Press on the upper side of clamp and unfold the tubing to slowly downward.
Bad case
Bending the pipe from right to left may cause damage to the tubing.
Wrench
Indoor unit tubing
Drain pipe
Adhesive
Vinyl tape(narrow)
Open-end wrench (fixed)
Flare nut
Connection pipe
Indoor unit drain hose
14 Multi Air Conditioner
Installation
9. Wrap the insulation material around the connecting portion.
1) Overlap the connection pipe insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
2) Wrap the area which accommodates the rear piping housing section with vinyl tape.
3) Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
10. Reroute the pipings and the drain hose across the back of the chassis.
11. Indoor unit installation
1) Remove the spacer.
2) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
3) Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Plastic bands
Insulation material
Connection pipe
Vinyl tape (wide)
Connecting cable
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Indoor unit piping
Drain hose
Piping for passage through piping hole
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape(wide)
Connecting
cable
Drain hose
Installation
Installation Manual 15
ENGLISH
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by
aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Chassis
Hook
Installation Plate
Type A
Left rear piping Right rear piping
Ø70mm
Ø70mm
110(4 11/32)
110(4 11/32)
90(3 17/32)
70(2 3/4)
Left rear piping Right rear piping
Ø70mm
133mm
Ø70mm
100mm
How To Fix
<9/12 kBtu/h class>
<18 kBtu/h class>
Chassis
Hook
Installation Plate
Type A
Installation
16 Multi Air Conditioner
Wiring Connection
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
2. Attach the Grille onto the cabinet.
Grasp the lower left and right side of the Grille and engage four tabs on the top inside edge of the chassis.
Press the Grille toward the chassis until it goes back into place.
Connecting cable
Conduit connection
1. Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the conduit bracket to the indoor unit.
2. Join the conduit and the conduit bracket together.
Connecting cable
Lock nut
Conduit
Conduit bracke
t
Terminal Block in Indoor
1(L1) 2(L2) 3
Connected to Outdoor Unit
4
Installation
Installation Manual 17
ENGLISH
[Cealing Concealed Duct Type]
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
Install the unit leaning to a drainage hole side as
a figure for easy water drainage.
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CE
G
D
A
B
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
1/100
I
F
H
Drainage hole
CASE 2
POSITION OF CONSOLE BOLT
Dimension
Capacity Btu/h class
9/12k
18k
Unit:mm(inch)
ABCDEFGH I
850 900 383 570 93.5 190 20.6 795 163
(33 15/32) (35 15/32) (15 3/32) (22 7/16) (3 11/16) (7 1/2) (13/16) (31 5/16) (6 13/32)
1130 1180 383 570 93.5 190 20.6 1065 163
(44 1/2) (46 1/2) (15 3/32) (22 7/16) (3 11/16) (7 1/2) (13/16) (41 15/16) (6 13/32)
18 Multi Air Conditioner
Installation
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension bolts
How to Fix
CAUTION :Tighten the nut and bolt to prevent unit falling.
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Wiring Connection
B1/B2 Series
Conduit connection
1. Remove the busing rubber product attached on the indoor unit.
2. Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the conduit bracket to the indoor unit.
3. Join the conduit and the conduit bracket together.
Lock nut
Conduit mounting plate
Conduit
Terminal Block of Indoor Unit
1(L1) 2(L2) 3
Connected to outdooor unit
Installation
Installation Manual 19
ENGLISH
CAUTION
Ceiling
Drain Pump use
Drainage hole
Front of view
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 19mm(1/32 inch).
The unit must be horizontal or declined to the drain hose connected when finished installation.
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
After all workings are finished, check the working and operation.
Air distribution ............... Is the air circulation good?
Drain ............................. Is the drainage smoothly and no sweating?
Gas leakage ................. Is the piping connection correctly?
Wiring ........................... Is the wiring connection correctly?
Lock-bolt ....................... Is the lock-bolt of compressor loosened?
Insulation....................... Is the unit fully insulated?
Ground .......................... Is the unit safely grounded?
THERMAL INSULATION
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose clip for thermal insulator(Local supply)
Felt
Rubber
Insulation
No clearance
Cabinet
Refrigerant pipe and thermal
insulator(Local supply)
Hose clip for thermal insulator
Thermal insulator for refrigerant pipe
(Local supply)
(Local supply)
Union for gas pipe
Union for liquid pipe
20 Multi Air Conditioner
Installation
Installation of wired Remote Controller
1
Put the installation paper on the place and determine the position and height of the fixing screws of the wired remote controller.
Refer to the printed side of the installation paper.
2
Plug the connecting cable into the indoor unit.
The product is being shipped with the cable connected only to the remote controller. Fix the connecting cable with the cable rack.
3
Remove the installation paper before installing the remote controller so that it can fit at the right place.
* Do not embed the remote controller into the wall.
(It may cause the breakdown of the temperature sensor.)
* If you want to install a number of remote
controller at the same place in a vertical line, install them at regular intervals of 20mm(1/32 inch). (It may cause the breakdown of the temperature sensor.)
* Do not install the cable with a distance of 50m(164ft) or longer.
(This can cause communication error.)
* When installing the cable, check whether the connector between the remote controller and the
product is installed properly. The connector will not be connected when installed in opposite sides.
Supply the power after connecting wired remote controller.
When you need to change wired remote controller, switch off the main power and change it. If the wired remote controller is changed before switching off the main power, the option function of the indoor unit can't be used. (option function like "slo" fan speed selection)
The position of the fixing screws
Side of
remote Controller
Side of
Indoor Unit
Main frame
Fixing the
remote controller
Main
indoor unit
CN-M CN-ZONEC
J15
C01K
IC01A
CN-DISP
LO1K
J14
CN-REMO
Red Yellow Brown
C07D
LO1D
LO2K
20mm(1/32 inch)
Installation
Installation Manual 21
ENGLISH
Wired remote controller switch information
Group control switch
1. For individual control/Master use
2. For group control/Slave use
Ceiling height selection switch
1. Low ceiling
2. Standard ceiling
3. High ceiling
Product selection switch
1. Cooling Only product
2. Heat Pump product
Indoor temperature sensor selection switch
1. Use the temperature sensor on the remote controller.
2. Use the temperature sensor on the product.
3. Use the sensors on the product and remote controller.
When changing the product selection switch and group control switch, the power must be reconnected to reflect the changes.
The central control could operate inappropriately depends on indoor unit type, when the remote controller is set as slave.
Group Control
2 1
Ceiling Height/Default E.S.P
3 2 1
S/W 1
Select Product
2 1
Room Temp. Sensing
SW±GR
SW±PD
321
SW±HI
SW±TH
22 Multi Air Conditioner
Installation
Trial Operation
The trial operation is to check the installation status of the product. The temperature will not be controlled during trial operation. Instead the product will operate in several modes such as cooling, strong wind, comp-on.
1
If you want to set the trial operation mode, press the mode button and the Fan speed button same time for three seconds.
2
Then the product will begin the trial operation and the display will be like as shown on left side picture.
3
If you want to cancel the trial operation mode, just press the On/Off button.
4
The trail operation will be shut down
automatically after 18 minutes and system will go to the standby mode.
Necessary functions before using
PQRCUCS0C
Defrost Preheat
MODE
TEMP
FAN
SPEED
TEMP
Out door
Room Temp
Total on
Central Run
Installation Manual 23
ENGLISH
Installation
Celsius/Fahrenheit Switching
1
If you want to change the temperature unit as the Celsius or Fahrenheit, press the Temperature control button(
) and the Fan speed button same time for three seconds to enter the setting Mode.
2
Press the temperature control button to change the unit. Ex) Setting unit as Fahrenheit.
3
After setting, press the Temperature control button(
) and the Fan speed button same time for three seconds to exit the setting Mode. The system will automatically release without input after 30 seconds.
PQRCUCS0C
Defrost Preheat Out door
Room Temp
Total on
Central Run
MODE
TEMP
FAN
SPEED
TEMP
Defrost Preheat
Out door
Room Temp
Central Run
Total on
Defrost Preheat
Out door
Room Temp
Central Run
<Setting as Celsius> <Setting as Fahrenheit>
Defrost Preheat Out door
Room Temp
Total on
Central Run
Total on
24 Multi Air Conditioner
Installation
Setting the Central-Control Address
Note : The remote controller displays 'HL' if central controller has locked the remote controller .
1
If you want to set the address on the display panel, press both temperature control buttons (/) same time for three seconds.
2
Press the temperature-increasing button to change the group number. Press the temperature-decreasing button to change the indoor unit number. e.g. As shown on the left side panel, it displays 23.
Group No. : 2 Indoor Unit No. : 3
3
Set the address by pressing both temperature control buttons again(s/t) at the same time for three seconds.
If you connect the indoor unit to the central controller, you should set the network address of the indoor unit so that the central controller could recognize it.
The center-control address is composed of the group number and the indoor-unit number.
Please set the address while using the central controller.
You don't need to set address if you don't use central controller.
PQRCUCS0C
Defrost Preheat
Out door
Room Temp
Total on
Central Run
Group No.
Indoor Unit No.
MODE
TEMP
FAN
SPEED
TEMP
MODE
TEMP
FAN
SPEED
TEMP
Installation
Installation Manual 25
ENGLISH
ESP Function
1
Press the mode button and the temperature increasing button() same time for three seconds.
2
Set the volume of each fan speed(Low, Medium, Hi) by using the temperature control button. Press the fan speed button to select the fan speed. The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP function, it will be canceled. (The picture on the left side is the example of setting the Hi wind to ESP
10.)
4
Press the mode button and the temperature increasing button () same time for three seconds. Then the ESP setting will be activated after the temperature display flashes three times.
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is recommended that you should not use this function while using the remote controller.
EX)
The E.S.P value is set at the proper value at the
factory. So it is highly recommended that you should not change the E.S.P value at your discretion.
PQRCUCS0C
Defrost Preheat
Out door
Room Temp
Total on
Central Run
MODE
TEMP
FAN
SPEED
TEMP
Lo
Med
Static pressure(mmAq)
Model name
AMNW09GB1A0
[LMDN095HV]
AMNW12GB1A0
[LMDN125HV]
AMNW18GB2A0
[LMDN185HV]
200
Setting the Low wind to 210 Setting the Medium wind to 175
100
01234
Step(H/M/L)
8.5 CMM(300cfm) 75 84 94 104 114
7.5 CMM(265cfm) 69 77 88 99
6.5 CMM(230cfm) 62 71 83 95
9.5 CMM(336cfm) 82 90 99 109
8.5 CMM(300cfm) 75 84 94 104
7.5 CMM(265cfm) 69 77 88 99
15 CMM(530cfm) 90 97 105 114
13.5 CMM(477cfm) 82 90 99 109 119
11.5 CMM(406cfm) 75 84 93 103
Setting value
110
106
118
114
110
122
114
26 Multi Air Conditioner
Installation
[Cealing Cassette Type]
Ceiling dimension and hanging bolt location
Level gauge
Ceiling
Ceiling board
Unit: mm(inch)
585~660(23 1/16~26) (Ceiling Opening)
517(20 3/8)
461(18 5/32)
517(20 3/8)
585~660(23 1/16~26) (Ceiling Opening)
523(20 19/32)
570(22 15/32)
Unit Size
570(22 15/32) Unit Size
319(12 9/16)
The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily
steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
NOTICE
CAUTION :
This air-conditioner uses a drain pump.
Install the unit horizontally using a level gauge.
During the installation, care should be taken not to damage electric wires.
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
Installation
Installation Manual 27
ENGLISH
Set screw of
paper model (4 pieces) Paper model for installation
Ceiling board
150mm
(5-7/8 inch)
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm(1-1/2 inch)
Open the ceiling board along the outer edge of the paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut (W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
Keep the length of 15~18mm(5/8~3/4 inch) between the air conditioner bottom surface and the ceiling surface
The following parts are local purchasing.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
CAUTION :Tighten the nut and bolt to prevent unit from falling off.
Wiring Connection
How to Fix
Conduit connection
Remove the busing rubber product attached on the indoor unit.
Join the conduit and the conduit bracket together using nut.
Set the connecting cable into the terminal block of indoor unit, and tighten set screw to lock the
conduit bracket to the indoor unit.
Open the control box cover and connect the remote control cord and indoor power wires.
TQ/TR series
Terminal Block of Indoor Unit
1(L1) 2(L2) 3 4 5
TO AIR FRESH
Connected to outdoor unit
KIT
OPTION
Connecting Cable
Conduit
Conduit bracket
Screw
28 Multi Air Conditioner
Installation
Installation of Wired Remote Controller(Optional)
1. Connect the wired remote controller cable to the wired remote controller installation board as shown in the right picture.
2. After fixing the cable to the guide slot, attach the wired remote controller installation board at the desired location.
Before fixing the wired remote controller cable
to the guide slot, remove any clogged part of the case in the direction to install before the installation.
3. After locating the wired remote
controller installation board at the desired location, screw the unit firmly. (When there is a buried box, install the wired remote controller board to fit the
buried box.)
Use the screw provided.
4. After fixing the top part of the wired
remote controller to the installation board as shown in beside picture, press the bottom part to assemble the controller to it’s board.
When disassemble the wired remote controller from the installation board, use the driver as shown in the right picture and insert it into the hole with the arrow. And when you pull the driver in the front direction, the wired remote controller will be separated.
12V Red wire
SIG Yellow wire
GND Black wire
The wired remote controller cable is connected as factory default.
12V SIG GND
Red Yellow Black
Remote Controller Cable
Guide slot
Fixate the remote controller cable to the guide slot.
Use the screws for fixate the unit firmly on the wall.
Installation board
<Front side of
installation board>
<Rear side of
installation board>
Top
Bottom
Wall Side
Wall Side
Wall Side
Wall Side
Wall
Side
Installation
Installation Manual 29
ENGLISH
5. Use the connecting cable to connect the indoor unit and the wired remote controller.
6. When the distance between the wired remote controller and the indoor unit is 10m and above, use the extension cable.
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
If you install the extension cable in the opposite direction, the connector will not be connected.
Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
CAUTION
Check whether the connector is connected correctly.
Connecting cable
Indoor unit side
30 Multi Air Conditioner
Installation
Installation of Decorative Panel
The decorative panel has its installation direction. Before installing the decorative panel, always remove the paper template.
1. Remove the packing and take out air inlet grille from front panel.
2. Remove the Corner covers of the panel.
3. Fit the panel on the unit by inserting hooks as shown in picture.
4. Insert two screws on diagonal corners of panel. Do not tighten the bolts completely. (The fixing screws are included in the indoor unit box.) Check the alignment of panel with the ceiling. Height can be adjusted using hanging bolts as shown in picture. Insert the other two screws and tighten all screws completely.
Front grille
Coner cover
Hook clip
Hook