LG LMNH182BTG0 Installation Manual

ENGLISH
LG Multi Type Air Conditioner
(Ceiling Duct Type)
INSTALLATION MANUAL
LG
IMPORTANT
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
website http://www.lgservice.com e-mail http://lgservice.com/techsup.html
ESPAÑOL
2 Multi Type Air Conditioner
Multi Type Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions..............3
Introduction .........................6
Installation of Indoor...........7
Connecting Pipes to the
Indoor Unit.........................12
Connecting Pipes to the ..14
Checking the Drainage .....14
Connecting Cables
between Indoor Unit .........15
Group Control....................17
Two Thermistor system ....17
E.S.P.(External Static
Pressure) Setting...............18
How to Set E.S.P? .............19
Installation
Requirements
Required Parts Required Tools
Four Type “A” screws
Connecting cable
Level
Screw driver
Electric drill
Hole core drill (ø70mm)
Pipes: Gas side...........
1
/2", 3/8"
Liquid side...........................
1
/4"
Insulated drain hose
Insulation materials
Flaring Tools set
Additional Drain hose
(Inner Dia...............25mm)
Screw driver
Hexagonal Wrench (4mm/5mm)
Gas-leak Detector
Safety Precautions
Installation Manual 3
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Safety Precautions
Operation
4 Multi Type Air Conditioner
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Gasolin
Installation Manual 5
ENGLISH
Safety Precautions
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Installation
90˚
6 Multi Type Air Conditioner
Introduction
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Introduction
Symbols Used in this Manual
Features
Air filters
Air intake vents
Remote Controller
Air outlet vents
Installation Manual 7
ENGLISH
Installation of Indoor
Installation of Indoor
Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four times the indoor units weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit
H
600600
Top view
(unit: mm)
Front view
Inspection hole
(600X600)
Control box
Indoor unit installation
Installation of Unit
Install the unit above the ceiling correctly.
Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
CASE 1
POSITION OF SUSPENSION BOLT
(Unit:mm)
9/12k 708 678 434 51 537 455 230 172
18k 1058 1028 434 51 537 805 230 172 24k 1258 1228 434 51 537 1075 230 172
Dimension
Capacity
ABCDEFGH
Drainage hole
A B
CD
1-3 mm
F
H
G
E
8 Multi Type Air Conditioner
Select and mark the position for fixing
bolts.
Drill the hole for set anchor on the face of
ceiling.
Insert the set anchor and washer onto the
suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set
anchor firmly.
Secure the installation plates onto the
suspension bolts (adjust level roughly) using nuts, washers and spring washers.
CAUTION: Tighten the nut and bolt to prevent unit falling
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut 5 Suspension
bolts
Installation of Indoor
Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
A place where the unit will be leveled and
that can support the weight of the unit.
A place where the unit can withstand its
vibration.
A place where service can be easily
performed.
CASE 2
POSITION OF CONSOLE BOLT
M10 Nut M10 SP. washer M10 washer
X 4 X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4 X 4
(Local supply)
X 4
Installation Manual 9
ENGLISH
Installation of Indoor
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A 70mm B 2C C 2 x SP SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq A 70mm B 40mm C 20mm
A
Make sure to be closed.
Unit
Drainage pipe (Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Lay the drain hose with a downward inclination so water will drain out.
Front of view
Always lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part.
5mm or thicker formed thermal insulator shall always be provided for the drain pipe.
Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
Applied U-Trap Dimension
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
The unit must be horizontal or declined to the drain hose connected when finished
installation.
CORRECT
CORRECT
INCORRECT
INCORRECT
Upward routing not allowed
10 Multi Type Air Conditioner
Drill the piping hole with 70mm dia, hole core drill.
Piping hole should be slightly slant to the outdoor side.
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
REFRIGERANT PIPE
Insulate and tape both the gas pipe and liquid pipe.
After all workings are finished, check the working and operation.
Air distribution Is the air circulation good?
Drain Is the drainage smoothly and no sweating?
Gas leakage Is the piping connection correctly?
Wiring Is the wiring connection correctly?
Service Valve Lock-bolt Is the lock-bolt of Service Valve loosened?
THERMAL INSULATION
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose clip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply)
Hose clip for thermal insulator (Local supply)
Power cable
Liquid pipe
Thermal insulator
Gas pipe
Tape
Installation of Indoor
Indoor Outdoor
WALL
5~7mm
Installation Manual 11
ENGLISH
Installation of Indoor
INSTALLATION OF REMOTE CONTROLLER
Install the remote control box and cord correctly.
Although the room temperature sensor is in the indoor unit, the remote control box should be installed in such places away from direct sunlight and high humidity.
INSTALLATION OF THE REMOTE CONTROLLER
Select places that is not splashed by water.
Select control position after receiving customer approval.
The room temperature sensor of the thermostat for temperature control is built in the indoor unit.
This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see. (The standard height is 1.2~1.5m high)
ROUTING OF THE REMOTE CONTROL CORD
Keep the remote control cord away from the refrigerant piping and the drain piping.
To protect the remote control cord from electrical noise, place the cord at least 5cm away from other power cables. (Audio equipment, Television set, etc)
If the remote control cord is secured to a wall, provide a trap at the top of the cord to prevent water droplets from running.
POINT OF REMOTE CONTROLLER INSTALLATION
DISASSEMBLING THE REMOTE CONTROLLER
ELECTRICAL WIRING TO THE INDOOR UNIT
FIXING OF REMOTE CONTROL CORD
1. Fix the cord clamps on the wall by ø3 tapping screws(Local supply).
2. Fix the remote control cord.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the switch box by screws(Local supply). In this case, fit the under plate on the wall, and be careful of deformation.
2. Receive the remote control cord in the switch box.
3. Hook the remote control unit on the under plate.
WHEN THE REMOTE CONTROLLER IS INSTALLED WITH THE CORD BURIED.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the wall by self tapping screws (accessory).
2. Make a slit (Part A) at the top side of the remote controller by nipper.
3.Rout the cord as shown in the following figure. In
this case, push the cord into the around of case(Part B).
4. Hook the remote control unit on the under plate.
WHEN THE REMOTE CONTROLLER IS INSTALLED WITH THE CORD EXPOSED.
Remote controller
CN REMO
If the length of the cord exceeds 50m, use a wire size greater than 0.5mm
The maximum length of the cord is 100m.
(Main board)
CN REMO
Make sure that wire and terminal numbers are matched on unit side and remote controller side.
2
.
Front case
lo
w
e
r p
a
rt
Remote control
box body
Lever carefully
the box open
using a screw
driver, etc.
T
h
e
Face of wall Upper notch
Under plate Remote
control unit Screw
(Local supply) Remote
control cord Lower notch Switch box
(Local supply)
Remote
control cord
(Part A)
Remote
control unit
Face of wall
Upper notch
Under plate
Tapping screw (Local supply)
Upper flange
Push hand
(Part B)
Lower notch
Cord
clamp
12 Multi Type Air Conditioner
Connecting Pipes to the Indoor Unit
Connecting Pipes to the Indoor Unit
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
3) Putting nut on
Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
4) Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
5) Check
Compare the flared work with figure.
If flare is noted to be defective, cut off the
flared section and do flaring work again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Outside Diameter "A"
1/4" 0~0.5 3/8" 0.5~0.8 1/2" 0.5~0.8 5/8" 0.8~1.0 3/4" 1.0~1.3
Installation Manual 13
ENGLISH
Connecting Pipes to the Indoor Unit
6) Pipe bending
Annealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. In this case, secure large R(radius) for the bend section and gradually bend pipe. If annealed copper pipe is large in diameter (ø15.88 or ø19.05), bend pipe with bender. Use bender appropriate for the pipe diameter.
7)
Brazing
In refrigerant piping, bending (in particular, acute bending) must be minimized to reduce piping resistance. Bending is, however, necessary in some places by virtue of the installation position of devices auxiliary to the packaged air conditioner, or of the building structure, piping distance or finishing appearance. If a more acute bend is required than that attainable by pipe bender, perform brazing using ready-made elbow. Aside from this function, brazing also serves to connect straight pipes, generally using ready-made sockets. While brazing, protect piping against heat with wet cloth to avoid damaging valve packing or burning thermal insulator with burner heat. While brazing, blow inert gas (nitrogen gas or carbonic gas) to prevent formation of oxidation film in copper piping; otherwise, the refrigerant circuit will clog. The blowing of nitrogen gas (or carbonic gas) through 3-way valves is described in the following:
8)
Refrigerant piping(Flare piping)
When connecting piping, be sure to keep piping dry(keep piping away from water), clean (keep piping away from dust) and airtight (avoid refrigerant leakage). When connecting piping on rainy days or making a through-hole in wall, take due care to prevent water or plaster from entering piping.
CAUTION: This procedure is designed to prevent formation of oxidation film by filling piping with inert gas. Note that excessive gas pressure will generate pinholes at brazed points. (Nitrogen gas: Supply pressure
0.05~0.1kg/cm2G) When supplying inert gas, be sure to open one end of piping.
Water enters Plaster enters