To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the follow-
ing indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n Meanings of symbols used in this manual are as shown below.
Be sure to disconnect all remote electric power supplies before servicing. Internal
components and circuit boards are at main potential when the equipment is connected to the power cables. This voltage is extremely dangerous and may cause
death or severe injury if come in contact with it.
Do not touch the discharging refrigerant gas during the repair work.
The refrigerant gas can cause frostbite.
Release the refrigerant gas completely at a well-ventilated place first.
Otherwise, when the pipe is disconnected, refrigerant gas or refrigerating machine
oil discharges and it can cause injury.
When the refrigerant gas leaks during work, execute ventilation. If the refrigerant
gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen
occurs. Be sure to execute ventilation.
When removing the front panel or cabinet, execute short-circuit and discharge
between high voltage capacitor terminals. If discharge is not executed, an electric
shock is caused by high voltage resulted in a death or injury.
Be sure to provide the grounding when repairing the equipment in a humid or wet
place, to avoid electrical shocks.
Do not use a defective or underrated circuit breaker. Use the correctly rated
breaker and fuse. Otherwise there is a risk of fire or electric shock.
Install the panel and the cover of control box securely. Otherwise there is risk of
fire or electric shock due to dust, water etc.
Indoor/outdoor wiring connections must be secured tightly and the cable should be
routed properly so that there is no force pulling the cable from the connection terminals. Improper or loose connections can cause heat generation or fire.
Do not touch, operate, or repaire the product with wet hands. Hoding the plug by
hand when taking out. Otherwise there is risk of electric shock or fire.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge.
Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it
may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Do not turn on the breaker or power under condition that front panel, cabinet, top
cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
Be sure to earth the air conditioner with an earthing conductor connected to the
earthing terminal.
Conduct repair works after checking that the refrigerating cycle section has cooled
down sufficiently. Otherwise, working on the unit, the hot refrigerating cycle section
can cause burns.
Do not tilt the unit when removing panels. Otherwise, the water inside the unit can
spill and wet floor.
Do not use the welder in a well-ventilated place. Using the welder in an enclosed
room can cause oxygen deficiency.
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Check to see if the parts are mounted correctly and wires are connected. Improper installation and connections can cause an electric shock or an injury.
Check the installation platform or frame has corroded. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Be sure to check the earth wire is correctly connected.
After the work has finished, be sure to do an insulation tset to check the resistance is 2[Mohm] or more between the charge section and the non-charge metal
section (Earth position). If the resistance value is low, a disaster such as a leak or
electric shock is caused at user’s side.
Check the drainage of the indoor unit after the repair. If drainage is faulty the
water to enter the room and wet floor.
Check to see if the power cable plug is not dirty or loose. If the plug is dust or
loose it can cause an electrical shock or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances. otherwise, it can cause an electrical shock,
excessive heat generation or fire.
Do not insert hands or other objects through the air inlet or outlet while the product is operating. There are sharp and moving parts that could cause personal injury.
Do not block the inlet or outlet of air flow. It may cause product failure
Basic A
Basic+4Way B
Basic+Deodorizing Filter (Carbon filter) C
Plasma+(A/changeove)+A/clean+2Way+Ion E
Plasma+(A/changeove)+A/clean+4way+Ion+Lamp F
Plasma+(A/changeove)+A/clean+Low A G
Plasma+(A/changeove)+A/clean+4way+Low A H
Plasma+(A/changeove)+A/clean L
Plasma+(A/changeove)+A/clean+4way M
Plasma+(A/changeove)+A/clean+PTC N
Plasma+(A/changeove)+Autoclean+4way+PTC P
Plasma+(A/changeove)+A/clean+4way+Low A+PTC Q
Smart(Robot) Cleaning R
Eco eye+Plasma+Allergy Filter+4way S
Plasma+Allergy Filter+4way U
Allergy Filter+4way V
Allergy Filter+2way W
Basic+Low Ambient Y
Basic+(A/clean)+4way+Low A Z
[Note]
O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
[Note]
O : Applied, × : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
The PLASMA Air Purifying System not only removes microscopic contaminants and dust, but also removes house mites,
pollen, and pet fur to help prevent allergic diseases like asthma. This filter that can be used over and over again by simply washing with water.
This is the function that decides the strength of the wind for each wind level and because this function is to make
the installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during the setup of the E.S.P value,
the E.S.P value of previous air flow rate will be maintained by remembering the E.S.P value prior to the shift.
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and button
1
simultaneously for more than 3 seconds, the system will be
entered into the installer setting mode.
- After entering into the installer setting mode, select the
E.S.P code value by pressing the button.
* E.S.P code value : 03
Select the desired air flow rate with
2
3
4
FAN
SPEED
the button. Whenever pressing
FAN
the button, [SLo
SPEED
Select the desired air flow rate value with the temperature
up(▲), down(▼) button.
* E.S.P value range : 0~255
E.S.P value will be indicated at the upper right section of the
-
display window.
When pressing the button, currently established E.S.P
value will be set up.
→Lo→
Med→Hi→Po] will be indicated.
OPER
MODE
OPER
MODE
When pressing the button and button simultaneously for
5
more than 3 seconds after the setting has been completed, the
setting mode will be released.
- If there isn’t any button input for more than 25 seconds, the
• When heating is started, the indoor fan is stopped or very slow to prevent the cold air carry out
• When the temp. of heat exchanger reach 30°C(model by model), indoor fan is started.
5.2 Self-diagnosis Function
• The air conditioner installed can self-diagnosed its error status and then transmits the result to the central control.
Therefore, a rapid countermeasure against failure of the air conditioner allows easy management and increases the
usage life of air conditioner.
• Refer to trouble shooting guide.
5.3 Soft dry operation
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and
the setting temp is automatically set according to the intake air temperature.
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat.
Compressor ON Temp. ‘ Setting Temp+0.5°C
Compressor OFF Temp. ‘ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
5. Reliability
Intake air Temp. Setting Temp.
26°C ≤ intake air temp. 25°C
24°C ≤ intake air temp.< 26°C intake air temp. -1°C
22°C ≤ intake air temp. < 24°C intake air temp. -0.5°C
18°C ≤ intake air temp. < 22°C intake air temp.
• Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
• If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30
seconds. ( not emergency conditions)
• Compressor turned off when
- intake air temperature is in between ±0.5°C of the setting temp. limit for three minutes continuously.
- intake air temperature reaches below 1.0°C of the temperature of setting temp..
• Compressors three minutes time delay.
- After compressor off, the compressor can restart minimum 3 minutes later.
6. Convenience Functions & Controls
6.1.2 Heating Mode
• Operating frequency of compressor depend on the load condition, The difference between the room temp. and set
temp., frequency restrictions.
• If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature reaches +4°C above the setting temperature.
• Condition of compressor turned on
- When intake air temperature reaches +2°C above the setting temperature.
* Condition of indoor fan turned off
- While in compressor on : indoor pipe temp. < 20°C
- While in compressor off : indoor pipe temp. < 30°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
CST/Duct type indoor unit matched with
Universal Outdoor unit
CST/ Duct/CVT type indoor unit
matched with Single Outdoor unit/Multi
Outdoor unit/Multi V Outdoor unit
Thermo ON : +2 °C above setting temp.
Thermo OFF : +4 °C above setting temp.
Thermo ON : Setting temp.
Thermo OFF : +3 °C above setting temp.
NOTE: Some Models are different by temperature of thermo ON/OFF.
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C ≤ Inatake Air Temp ‘ Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp < 24°C ‘ Fuzzy Operation for Dehumidification
Inatake Air Temp < 21°C ‘ Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or
longer before Fuzzy operation, the mode before Fuzzy operation is operated.
6.3.1 Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ‘ Setting Temp + 0.5°C
Compressor OFF Temp ‘ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air
temp at that time.
26°C≤ Intake Air Temp ‘ 25°C
24°C≤ Intake Air Temp<26°C ‘ Intake Air Temp + 1°C
22°C≤ Intake Air Temp<24°C ‘ Intake Air Temp + 0.5°C
18°C≤ Intake Air Temp<22°C ‘ Intake Air Temp
Intake Air Temp<18°C ‘ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key
value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
6.2 Auto cleaning operation
• Function used to perform Self Cleaning to prevent the Unit from Fungus and bad odor.
• Used after the Cooling Operation before turning the unit off, clean the Evaporator and keep it dry for the next operation.
• The function is easy to operate as it is accessed through the Remote controller.
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ‘ Setting Temp + 0.5°C
Compressor OFF Temp ‘ Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air
temp at that time.
26°C ≤ Intake Air Temp ‘ 25°C
24°C ≤ Intake Air Temp<26°C ‘ Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C ‘ Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C ‘ Intake Air Temp
Intake Air Temp<18°C ‘ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key
value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
6.3.3 Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting
temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp ‘ Setting Temp
Compressor OFF Temp ‘ Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air
temp at that time.
20°C≤Intake Air Temp ‘ Intake Air Temp + 0.5°C
Intake Air Temp<20°C ‘ 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key
value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air
temperature and the setting temperature.
Notes: The Temp. of Comp. Turn ON and OFF is different in heating mode and fuzzy operation for heating. Please,
refer 6.1
6.4 Auto restart Operation
• Whenever there is electricity failure to the unit, and after resumption of the power, unit will start in the same mode prior
to the power failure. Memorized condition are on / off condition, operating mode (cooling/ heating), set temperature and
fan speed. The unit will memorize the above conditions and start with same memorized condition.
• To operate the appliance by force in case when the remote control is lost, the forced operation selection switch is on
the main unit of the appliance, and operate the appliance in the standard conditions.
• The operating condition is set according to the outdoor temp. and intake air temperature as follows.
• The unit select the last operation mode in 3 hours.
• Operating procedures when the remote control can't be used is as follows :
- The operation will be started if the ON/OFF button is pressed.
- If you want to stop operation, re-press the button.
Indoor temp.
over 24°C
21~24°C
below 21°C
Setting temp.
22°C
23°C
24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Heating
It is the function to use preventing children or others from careless using.
FAN
SPEED
FAN
SPEED
FAN
SPEED
During the operation, when pressing the button and
button for approx. 3 seconds, the ‘Child Lock’ Function can
be used.
- At the time of initial setting of the ‘Child Lock’, the ‘CL’ Will
be indicated approx. 3 seconds at the temperature Display
section before resuming to the previous mode.
After the setting of the ‘CL’, if another button is setup, the
button can not be recognized as the ‘CL’ is indicated at the
temperature display section for approx. 3 seconds.
1
If the ‘CL’ function is wanted to be used under the operation
standby state, press the
button and Button for approx.
3 seconds under the standby mode state and the system will
be the ‘CL’ state.
2
As for the releasing method, when pressing the Button and
button for approx. 3 seconds, the ‘CL’ function can be
released.
1. When installing more than 2 units of air conditioner to
one wired remote controller, please connect as the
right figure.
• If it is not event communication indoor unit, set the unit
as slave.
• Check for event communication through the product
manual.
2. When installing more than 2 wired remote controllers to one
air conditioner, please connect as the right picture.
• When installing more than 2 units of wired remote controller to one
air conditioner, set one wired remote controller as master and the
others all as slaves, as shown in the right picture.
• You cannot control the group as shown in the right for some prod-
ucts.
•
Refer to the product manual for more detail.
When controlling multiple indoor units with event communication function with one remote controller, you must change the
master/slave setting from the indoor unit.
- Indoor units, the master/slave configuration of the product after completion of indoor unit power ‘OFF’ and then ‘ON’ the
power after 1 minutes elapsed sign up.
- For ceiling type cassette and duct product group, change the switch setting of the indoor PCB.
- For wall-mount type and stand type product, change the master/slave setting with the wireless remote controller. (Refer to
wireless remote controller manual for detail)
h When installing 2 remote controllers to one indoor unit with event communication function, set the master/slave of the re-
mote controller. (Refer to remote controller master/slave selection)
When controlling the group, some functions excluding basic operation setting, fan level Min/Mid/Max, remote controller
lock setting and time setting may be limited.
<When simultaneously connecting
2 sets of wired remote controller>
• When controlling in groups, set the master/slaver of the remote controller. Refer to Installer setting section on how to set master/slave for more detail.
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by
1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the
medium.
6.9 Timer(On/Off)
6.9.1 On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
6.9.2 Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
6.10 Weekly Program
• If necessary, an operator can make an On/Off reservation of the product for a period of one week.
- On/Off schedule of operation for a period of ONE week.
• No need to turn the unit On/OFF manually during working days.
On/Off time is scheduled in micom of the wired remote control.
When pressing the button and button
simultaneously for more than 3 seconds, the system will be
entered into the installer setting mode.
- After entering into the installer setting mode, select the
thermistor sensor setting code value by pressing the
button.
* Thermistor sensor selection code value : 04
1
Select the desired setting value with the temperature up(▲),
down(▼) button.
2
When pressing the button, currently established
thermistor sensor location will be set up.
3
When pressing the button and button
simultaneously for more than 3 seconds after the setting
has been completed, the setting mode will be released.
- If there isn’t any button input for more than 25 seconds,
the installer setting mode will also be released.
4
OPER
MODE
OPER
MODE
Code value
*Setting value
01: Remote
controller
02: Indoor unit
03: 2TH
OPER
MODE
Value
TEMP
FAN
SPEED
OPER
MODE
h The function of 2TH has different operation characteristics according to the product.
<Thermistor Table>
This is the function to select the temperature sensor to judge the room temperature.
Temperature sensor selectionFunction
01Remote controllerOperation in remote controller temperature sensor
02Indoor unitOperation in indoor unit temperature sensor
032TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote
controller’s temperature.
(There are products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's and wired remote
controller's temperature.
Vanes angle can be controlled by pair, considering its
installation environment.
• For example direct drafts can be annoying, leading to
discomfort and reduced productivity vane control
helps to eliminate this problem.
• Easily controlled by wired remote control.
• Air Flow can be controlled easily regarding any space
environment.
7.3 Auto Elevation Grille
• Auto Elevation Grille is automatically down to height
of max. 3.1 m. So it enables to install the Indoor unit
at high ceiling space. And Auto Elevation Grille
makes you cleaning the filter easily.
7.1 Low Ambient control
• This Function is for cooling operating in outdoor low temperature .
• If outdoor temperature drops below certain temperature, liquid back is prevented by reducing outdoor fan speed.
• It can prevent frosting of evaporator and keep cooling operation
As for operation of Remote Controller, use it by directing the transmitter part of Remote Controller to the receiver part of front panel
directly under front panel.
• Do not drop it down or into water. Or else there is worry about trouble failure.
• Do not press hard the Remote Controller button with nail (ballpoint
pen or other sharp substance). Or else there is worry about trouble
failure.
• In case when obstacle such as curtain hides the signal reception
part of receiver in between the space interval, Remote Controller
operation is infeasible.
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -11°C after starting of heating operation and
more than 10 minutes operation of compressor.
• Defrost ends after 15 minutes passed from starting of defrost operation when the outdoor rises over 40°C even before
12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below – 6°C after from ending of the first defrost and more than 10 minutes operation of compressor.
Automatic stop distance
S
If you want to change automatic distance setting,
consult with your sale agency.
Automatic Stop Distance of Grill
Ceiling height
Low
Medium
High
(
Height: 3~4 m)
Automatic stop distance
1.5±0.5 m 2.5±0.5 m 3.5±0.5 m
- Depress the down button( ).
Then suction grill descends and stops automatically at a certain
distance.
- You may stop it at wanted distance point by depressing the stop but-
ton ( ) when descending.
- Depress the up button( ).
Then suction grill goes up and enters into the front panel.
1. Stop the Air Conditioner Operation
2. Descend the Suction Grill
3. Raise the Suction Grill
- Depress the stop button( ).
Make use of this when you want to stop it at your wished position.
4. Stop the Suction Grill during Rising
• Always stop the air conditioner operation for safety before operating lift grill.
• Take heed _ there is worry about dust fall etc. when suction grill descends.
• In case when the set automatic stop distance goes wrong, check the set value of operation panel and confirm if there is neither obstacle nor mankind.
• When you are not to remove obstacle, stop the operation before touching the obstacle.
Basic principle is to control the rpm of the motor by changing the working frequency of the compressor.
Three phase voltage is supplied to the motor and the time for which the voltage will supplied is controlled by IPM
(intelligent power module).
Switching speed of IPM defines the variable frequency input to the motor.
1. Normal operation
Fuzzy control : Maintain evaporating temperature (Te) to be constant on cooling mode and constant condensing temper-
ature (Tc) on heating mode by fuzzy control to ensure the stable system performance.
2. Compressor control
ActuatorCooling operationHeating operationStop state
CompressorFuzzy controlFuzzy controlStop
FanFuzzy controlFuzzy controlStop
EEV
Super heating
fuzzy control
Super heating & Sub cooling
fuzzy control
Min. Pulse
EEV operates with fuzzy control rules to keep the degree of superheat (about 2~3℃) at the evaporator outlet status.
The degree of superheat = Tsuction – Tevaporation
Tsuction : temperature at suction pipe sensor(℃)
Tevaporation : evaporation temperature (℃)
3. EEV( Electronic Expansion Valve) control
Linear control
System capacity
Cooling and heating load
Inverter linear control as cooling and heating load increasing
Oil return operation recovers oil amount in compressor by collecting oil accumulated in pipe.
Each cycle component operates as shown on the below table during oil return operation.
4. Oil return control
Defrost operation eliminates ice accumulated on heat exchanger, recovering performance of heat exchanger.
Each cycle component operates as shown on the below table during defrost operation.
5. Defrost control
ComponentStartingRunningEnding
CompressorNormal controlSetting valueNormal control
FanNormal controlOffNormal control
EEV (Thermo on)Normal controlSetting valueNormal control
EEV (Thermo off)Min. PulseSetting valueMin. Pulse
4 way valveOnOffOn
ComponentStartingRunningEnding
FanNormal controlOffNormal control
Defrost signalOffOnOff
Outdoor unit
ComponentStartingRunningEnding
CompressorNormal controlSetting valueNormal control
FanNormal controlOffNormal control
EEV (Thermo on)Normal controlSetting valueNormal control
Check to see whether there is any refrigerant leakage, and check whether the power or transmission
cable is connected properly.
Check liquid pipe and gas pipe valves are fully opened.
NOTE: Be sure to tighten caps.
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal block and
ground. Do not operate in the case of 2.0 MΩ or less.
NOTE: Never carry out mega ohm check over terminal control board.
Otherwise the control board may break.
Immediately after mounting the unit or after leaving it turned off for an extended length of
time, the resistance of the insulation between the power supply terminal board and the
ground maydecrease to approx. 2.0 MΩ as a result of refrigerant accumulation in the internal
compressor.
If the insulation resistance is less than 2.0 MΩ, turn on the main power supply.
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
CAUTION:
① For test run, carry out the cooling operation first even during winter season. If heating operation is carried out
first, it leads to the trouble of compressor.
② Carry out the test run more than 5 minutes without stopping.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer button for 3 seconds
at the same time.
• To cancel the test run, press any button.
3.2.2 CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured data, etc.
• Measuring data are room temperature, outside temperature, suction temperature, blow out temperature,
air velocity, air volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping
temperature.
• As to the structure and appearance, check following items.
o Is the circulation of air adequate?
o Is the drainage OK?
o Is the heat insulation complete
(refrigerant and drain piping)?
o Is there any leakage of refrigerant?
o Does the romote controller works properly?
o Is there any error on wiring?
o Aren't terminal screws loosened?
This function gathers the refrigerant present in the system to ODU
Use this function to store refrigerant of system in ODU for leakage or IDU replacement.
• Procedure
n
This function start Dip switch setting status of ODU PCB.
(1) Set the Dip switch as follow after shutting the power source down.
(2) Reset the power.
(3) Check that the Red LED of PCB is on during work.(The indoor unit is operated by force.)
(4) Pump down during forced cooling operation.
CAUTION
1. Use pump down function within guaranteed temperature range
IDU : 20~32C
ODU : 0~40C
2. Make certain that IDU doesn't run with thermo off mode during operation
3. After the compressor is starting operation, please complete Pump Down within 4 minutes.
4. Pump Down can be stopped (The compressor is turned off), because of compressor protection.
In this case, reset the power.
turn off the vacuum pump, and confirm that
the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
WARNING
Use a vacuum pump or lnert (nitrogen) gas when
doing leakage test or air purge. Do not compress
air or Oxygen and do not use Flammable gases.
Otherwise, it may cause fire or explosion.
nected from the vacuum pump to the valve at
the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
–
Stopping partway will allow the gas to be discharged.
–
If the system has been charged with liquid refrigerant while operating the air conditioner turn off
the air conditioner before disconnecting the hose.
(5)
Mount the valve stem nuts and the service port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
WARNING
When installing or relocation the unit, make sure
that no substance other than the specified refrigerant(R410A) enter the refrigerant circult.
- Any presence of foreign substance such as air can
cause an abnormal pressure rise and may result in
explosion or injury.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
1. Check temperature difference between intake and discharge air, and check for the operating current too.
CaseSymptomSupposed Caused
Temp. difference : approx. 0°C
Current : less than 80% of rated current
Temp. difference : approx. 8°C
Current : less than 80% of rated current
Temp. difference : less than 8°C
Current : over the rated current
Temp. difference : over 8°C
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle
Defective Compressor.
Excessive amount of refrigerant
Normal
Case 1
Case 2
Case 3
Case 4
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is
relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference
is larger.
2. Check temperature and pressure of refrigeration cycle in cooling mode.
1. The suction pressure is usually 8.5~9.5kg/cm2G(Cooling) at normal condition.(R410A)
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Suction pressure
(Compared with Cause of Trouble Description
the normal value)
Defective compressor Current is low.
Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
* The voltage of main power supply.
* The voltage applied to the unit.
* The connecting method of Indoor/Outdoor connecting cable (each color)
* The PCB Assembly (Fuse, Noise Filter, Power Module, Bridge Diode, etc.)
’ The Voltage is about [input voltage x 1.414]
’ if the Voltage does not come with the above Voltage,
’ Check the power input
’ Replace the PCB & Motor
2. Check the Voltage Black line to White
’ the Voltage is DC 15V
’ Check the Power input
’ Replace the motor
Check the Motor
1. Check the shaft
’ if the shaft is not turn smoothly, the Motor Power IC is defected
’ replace the motor
2. Check the motor resistance(if the shaft is turn smoothly, check the resistance)
’ Check Red line to Black line, Blue line to Black line
’ The resistance should infinite
’ replace the motor
- Overcharging of refrigerant Pipe length.
Outdoor Fan is stop
• Poor insulation of compressor
Display
code
TitleCause of errorCheck point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
n Comp checking method
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Input over current
(18,24,30kBtu/h class 19A↑
36,42kBtu/h class 37A ↑)
1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...
Display
code
TitleCause of errorCheck point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
5. Check the CT Sensor Output signal
(18/24/30 kBtu/h class - Check output the CT Sensor : DC 2.5±0.2V)
(36/42 kBtu/h class - Check output pin 1.2 of the CT Sensor : 5V )
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
No
Is input voltage normal ?
Yes
No
Is Inverter PCB assembly
Power connection normal?
Check L1~L2 Voltage is 230V±15%
Check connection from terminal block to
Inverter PCB assembly CN(L), CN(N)
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
5. Inverter PCB assembly Damage (input current
sensing part)
Display
code
TitleCause of errorCheck point & Normal condition
h PFCM Moudle checking method
① Set the multi tester to diode mode.
② Check short between input signal pin which are
placed below PFC Module.
③ Replace PCB assembly if it is short between pins
except No.4,5 pins.
CAUTION
PFCM module No.4,5 pins are internal short state.
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
High temperature in Discharge pipe of the inverter
compressor
• Overload operation (Outdoor fan constraint,
screened, blocked)
• Refrigerant leakage (insufficient)
• Poor INV Comp Discharge sensor
• LEV connector displaced
/ poor LEV assembly
• Check outdoor fan constraint/ screened/ flow
structure
• Check refrigerant leakage
• Check if the sensor is normal
• Check the status of EEV assembly
CN- DISCHARGE
(BLACK 3Pin Connector)
Replace the Thermistor
Yes
CN_TH3
(RED 4Pin Connector)
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
• Covering / clogging (outdoor unit covering during
the cooling mode / indoor unit filter clogging during heating mode)
• SVC valve clogging
• Defective outdoor unit PCB
• Defective indoor unit pipe sensor
n Error diagnosis and countermeasure flow chart
Is service valve
opened?
Yes
Are communication cable/
piping normal?
No
Open service valve
check communication/
piping correction.
Yes
Is amount of refrigerant
normal?
[refer refrigerant part]
Yes
Is strainer Ok?*
Yes
Are the value of manifold
gauge and pressure
sensor same?
(Is the low pressure value
actually low?)
Yes
Check indoor / outdoor unit LEV
Check Indoor unit PCB
Check indoor / outdoor unit
installation conditions
No
No
No
Is there pipe crack or trace
of refrigerant leakage?
Yes
Weld / reconnect the cracked
portion and recharge refrigerant
Replace the strainer
Replace the pressure sensor
No
Adjust the amount of
refrigerant (Additive charge)
* If the temperature difference between inlet and outlet of strainer
is so large that frost or ice formation can be seen or confirmed
then clogging of strainer should be checked
(Notice: it is not full ice forming of strainer, in case that there is
not at inlet portion but at outlet portion)
2. Check Input Voltage Sensor output voltage (2.5Vdc±10%)
n Error Diagnosis and Countermeasure Flow Chart
40
C/T
Sensor Error
• Initial current error
•
Malfunction of current detection circuit.
(Open / Short)
•
Check CT Sensor output voltage :
2.5Vdc ±5%
Display
code
TitleCause of errorCheck point & Normal condition
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
1. Estimate the resistance of each sensor.(Unplugged)
2. Check the value of the resistor of thermistor.
D-pipe sensor (Inverter): Normal Value of the resistor is 200kΩ at 25℃
Air sensor: Normal Value of the resistor is 10kΩ at 25℃
Cond. Mid-pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
Suction pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
Condenser Out-pipe sensor: Normal Value of the resistor is 5kΩ at 25℃
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Display
code
TitleCause of errorCheck point & Normal condition
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire Confirm the wire of "Live", "Neutral"
3. Check the resistance between communication line and GND. (Normal :
Over 2MΩ)
4. Check the connector for communication is correctly connected.
5. If one indoor unit is operated normally, outdoor PCB is no problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at
outdoor unit.
6. If all indoor unit is displayed CH05 but outdoor PCB not
display
CH53 : Check the CN_COM and CN_POWER is correctly connected.
• 18,24,30kBtu/h class
1. In Case of CH53, Check the Connection
’ L1,L2 at the terminal block
• 36,42kBtu/h class
1. In Case of CH05, Check the Connection ’ CN_POWER,
CN_COMM at the Main PCB
2.
In Case of CH53, Check the Connection ’ CN_COMM at the
Main PCB ’ L1, L2 at the terminal block
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
• Overload operation (Outdoor fan constraint,
screened, blocked)
• Outdoor unit heat exchanger contaminated
• EEV connector displaced
/ poor EEV assembly
• Poor Cond. Pipe sensor
assembly / burned
• Check outdoor fan constraint / screened / flow
structure
• Check if refrigerant overcharged
• Check the status of EEV assembly
• Check the status of sensor assembly / burn
CN- C/PIPE
(Violet 3Pin Connector)
Replace the Thermistor
Yes
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.