LG LG290N1CW-G4, LG280N1C-G4, LG290N1C-G4, LG295N1C-G4, LG295N1CW-G4 Installation Instructions Manual

...
Monocrystalline Solar Module
LGXXXN9C(W)-G4
LGXXXN1C(W,K)-G4
Installation Instructions
MFL69021104
Table of Contents
2
1. Safety 3
2. Before & After Installation 4
3. Electrical Installation 5
4. Mechanical Installation 6
5. Product Specifications 10
6. Disclaimer of Liability / Disposal 12
7. Transporting and Storage 12
Date Version RemarkDescription of change
1.0 (1stedition)2015.01.22
3
Safety
The instructions related to the safety indicated in the following are for preventing unexpected danger or damage in advance by safely and exactly using the product.
Non-compliance of the instructions may immediately cause serious injury or death.
Non-compliance of the instructions may cause death or serious injury to the user.
Non-compliance of the instructions may cause injury or property damage to the user.
Do not contact with electrically active parts of the panel, such as terminals, regardless of connection of the module. It may result in spark or lethal electric shock.
Please don’t use the module with the broken window or the torn back side. There is a danger of electric shock.
Please perform works in the dry condition and use only dry tools. Do not handle the wet panels without protection equipment. It may result in safety accident.
Damaged module must be treated with safety protection equipment. It may result in injury.
Do not approach the damaged or broken module unless you are an expert. It may result in serious injury.
No electrical parts like cables are located after installation between laminate and mounting structure.
Do not reconnect or repair Junction Box Cable. It may occur spark or electric shock.
Module Module
Installing structure (bent type)
Installing structure (Stralght type)
Product Deformation Occurrence of space
Please use proper equipment, connector, wire and buttress for system configuration of the module. It may result in damage or failure of the product.
Do not perform installation in rainy, heavily windy or snowy days. It may result in safety accident. Do not make holes in the frame or glass of the module. It may decrease the strength of the frame or break the glass. Do not touch the glass surface or frame of the solar module after installation of the module. It may result in injury. Do not locate a heavy object onto the module. Do not stand on or step on the module. Do not drop or suddenly lay down the module. It may result in injury. Do not scratch the coating surface of the frame. It may decrease the strength due to corrosion of the frame. Do not concentrate sunlight on the module surface. It may result in damage of the product. Do not apply a shock to the junction box of the module or pull the cable. Do not remove the labels attached to the module. It may result in damage of the product. If the installing structure has a curved surface e.g. arch type as shown in the below picture, do not forcefully modify the module in installation when connecting it with the structure. Please install the module in the place where the structure has been completely set up because deformation of the structure may cause deformation of the product when performing installation by using a crane, etc after assembling the module to the installing structure.
4
Before & After Installation
• Wear a safety belt if working high above the ground.
• Contact with electrically active parts of the panels, such as terminals, can result in burns, sparks and lethal shock whether the panel is connected or disconnected.
• Even partial shadowing can substantially reduce panel and system output.
• Care must be taken to avoid low tilt angles which may cause dirt to buildup on the glass against the frame edge.
• Dirt build-up on the surface of the panel can cause active solar cells to be shaded and electrical performance to be impaired.
• Always keep the back surface of the panel free from any foreign objects or structural elements which could come into contact with the panel, especially when the panel is under mechanical load.
• For permission to use mounting methods not described in the Mounting Guide please consult LG Solar. Failure to do so will void the warranty and panel certification.
After Installation
• Plug the connector in tightly and ensure that the wiring properly works.
• It is advisable to conduct periodic inspection of the panels for damage to front glass, back sheet, frame, junction box, or external electrical connections.
• Check electrical connections for loose connections and corrosion.
• PV panels can operate effectively without ever being washed, although removal of dirt from the front glass can increase output.
• Water, ethanol or a conventional glass cleanser with a micro-fiber cloth can be used for regular washing or rinsing of the front glass to remove dust, dirt or other deposits.
• No aggressive and abrasive cleansers or chemicals such as alkali chemicals including ammonia based solution should ever be used on the treated front glass.
• Always wear rubber gloves for electrical insulation while maintaining, washing or cleaning panels.
• Deposits of foreign material on the frame surface can be cleaned using a wet sponge or cloth and dried in air or by using a clean chamois.
• Perform the wiring work by connecting the connector and wires to the stand away from the roof or ground.
Before Installation
Please carefully read this manual before installation.
• Solar module installation should be performed by an authorized installer for the safety and maintenance of the system.
• All installation instructions should be clearly understood before attempting installation.
• Do not twist, pull, or scratch the cable attached to the solar module.
• Do not touch the solar module with bare hands. It may result in a burn or injury.
• Do not drop the solar module and cause an excessive load on solar module.
• Do not disassemble the solar module.
• After installation or repair, check whether solar module operates properly or not.
• In case the currently used solar module or the parts applied to the solar module have been replaced, check whether the changed solar module is properly operated or not. The newly replaced solar module and its parts must be the same solar module(module name) and parts with the current solar module.
• Please contact the local office to confirm the regulations and to obtain permission.
• Do not let anyone approach the solar module who has little knowledge of solar modules or on the measures to take when solar modules are damaged in order to avoid the risk of injury or electrical shock.
• Do not locate the solar module horizontally, as this may cause dirt or white efflorescence (glass deformation)
• Panels produce voltage even when not connected to an electrical circuit or load.
• Panels are intended for outdoors, land based applications only. Panels are not intended for use indoor use or application on moving vehicles of any kind.
• Reflection from external environments such as snow, water or other surfaces can increase the power generated by the panel.
• Industry standard rated specifications are made at conditions of 1000W/m2 irradiance and 25°C (77ºF) solar cell temperature. Colder temperatures can substantially increase voltage and power.
• Keep the solar module and system away from children when installing.
• Keep the module packed in the carton until the time of installation.
• Make sure flammable gases are not generated near the installation site.
• Do not work alone. Please work as part of a team of two or more people.
--
Parallel connection for more current
5
Electrical Installation
Parallel Connection
• The solar modules may be combined in parallel to produce the desired current output.
• When modules are combined in parallel, the total current is equal to the sum of currents from each module.
• The voltage of each module connected in parallel should be same.
• When connecting plural strings of modules in parallel every series string or solar module must be fused prior to combining with other strings. By pass diodes are factory installed in the solar modules.
• Please refer to the applicable regional and local codes for additional fusing requirements and limitations on the maximum number of solar modules in parallel.
• Maximum parallel strings without proper measures, e.g. fuse 20A and/or blocking diode : 1 string Parallel configuration is not limited if proper measures are taken to block the reverse current flow, e.g. fuses for the protection of the module and cables from over-current and/or blocking diodes for prevention of unbalanced string voltage.
• A multiplying factor is required for increased output of the PV modules. Under normal conditions, a PV module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions. Accordingly, the values of Isc and Voc marked on this PV module should be multiplied by a factor of 125% when determining component voltage ratings, conductor ampacities, fuse sizes, and size of controls to the PV output.
• Depending on national directives additional safety factors might be applicable for overcurrent protection.
Caution
• Avoid all electrical hazards when installing, wiring, operating and maintaining a panel.
• Do not use panels of different electrical or physical configurations in the same system.
• Match the polarities of cables and terminals when making the connections; failure to do so may result in damage to the panel.
• When reverse currents can exceed the value marked on the name plate, a properly rated and certified over-current device (fuse or circuit breaker) must be connected in series with each panel or string of panels.
• The rating of the over-current device shall not exceed the maximum series fuse rating marked on the name plate.
• The panel contains factory installed bypass diodes located inside the junction box.
• When installing the system, it is recommended to install the lightning rod to protect the system.
• The junction box should not be opened. Opening the junction box may void the warranty.
• Panels with a suspected electrical problem should be returned to LG Electronics for inspection and possible repair or replacement as per the warranty conditions provided by LG Electronics.
Electrical Connections
• Modules may be connected in series and/or parallel to achieve the desired electrical output as long as certain requirements are met.
• Please use only the same type of modules in a combined source circuit.
• Do not disconnect the module under load. Shock hazard can occur near the solar modules connection means.
Series Connection
• The solar modules may be wired in series to produce the desired voltage output.
• The current of each module connected in series should be same.
• The maximum number of series connected modules can be determined by basis on max. system voltage, the 125% safety factor, and the module Voc which can be checked in “Product Specifications” in this document.
Do not exceed 80% of maximum system voltage.
• The maximum solar module configuration can be found in “Product Specifications”.
Series connection for more voltage