LG LB-C366GTA0 Installation Manual

LG

LG Ceiling Duct-Type

Air Conditioner

INSTALLATION MANUAL

MODELS: LB-C246HSA0

LB-C306GTA0

LB-C366GTA0

LB-C428GTA0

LB-C488ETA0

LB-C608ETA0

IMPORTANT

Please read this instruction sheet completely before installing the product.

When the power cord is damaged, replacement work shall be performed by authorized personnel only.

Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

Ceiling Duct Type Air Conditioner Installation Manual

TABLE OF CONTENTS

Installation

Required Parts Required Tools

Requirements

Safety Precautions..............

3

Introduction .........................

7

Installation of Indoor,

 

Outdoor Unit ........................

8

Connecting Pipes to the

 

Indoor Unit .........................

18

Connecting Pipes to the

 

Outdoor Unit ......................

20

Checking the Drainage .....

20

Connecting Cables

 

between Indoor Unit and

 

Outdoor Unit ......................

21

• Four Type “A” screws

• Level

• Connecting cable

 

• Screw driver

 

 

• Electric drill

 

 

• Hole core drill (ø70mm)

• Pipes: Gas side .....1/2", 5/8", 3/4"

• Flaring Tools set

Liquid side .............1/4", 3/8", 1/2"

 

• Insulated drain hose

 

 

• Insulation materials

 

 

• Additional Drain hose

 

(Inner Dia...............

25mm)

 

• Screw driver

Air Purging of the

• Hexagonal Wrench (4mm/5mm)

Connecting Pipes and the

• Gas-leak Detector

Indoor Unit .........................

24

Group Control....................

25

Two Thermistor system ....

25

E.S.P.(External Static

 

Pressure) Setting ..............

26

How to Set E.S.P? .............

27

High-Static Motor

 

Connection (For 48k/60k

 

Model).................................

28

External Static Pressure &

air Flow...............................

28

Checking the

 

Power Cord ........................

29

2 Ceiling Duct Type Air Conditioner

Safety Precautions

Safety Precautions

damage, the following instructions must be

.

they include important items related to safety.

cause harm or damage. The seriousness is classified

possibility of death or serious injury.

possibility of injury or damage.

shown below.

sure not to do.

to follow the instruction.

Do not damage or use an unspecified power Do not disassemble or repair the product. cable.

It will cause electric shock or fire.

Always earth the product.

It will cause fire or electric shock.

Do not install the product where flamable gas could leak.

Otherwise, it may cause esplosion or fire.

Be cautious when unpack and install the product.

Sharp edges could cause injury.

Do not install the product on an defected installation stand.

Otherwise, It may cause injury or accident.

Contact your dealer and service center.

Do not handle the flamable gas or explosive materials near the product.

Otherwise, it may cause fire or failure of product.

Do not install the product on the defected installation stand.

Otherwise, It may cause injury or accident.

For installation, always contact the dealer or service center.

Otherwise, it may cause fire, electric shock, explosion or injury.

For electric work, contact the dealer or service center.

Otherwise, It will cause fire or electric shock.

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 3

Do not modify power cable length.

• It will cause fire or electric shock.

Always intstall a circuit breaker and exclusive switching board.

No installation may cause fire and electric shock.

Use a rated breaker and fuse.

Do not use a defected circuit breaker and exclusive switching board.

• Otherwise, it may cause fire and electric shock. • Otherwise, it may cause fire and electric shock.

Operation

Do not touch(operate) product with wet hands.

• Otherwise, it may cause fire or electric shock.

If strange sound, smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable.

• Otherwise, it may cause electric shock or fire.

Do not place the heater, etc. near the power cable.

• Otherwise, it may cause fire and electric shock.

Do not put water into electric part.

Otherwise, it may cause fire or failure of product, and electric shock.

Ventilate the room frequently using with a stove, etc.

Otherwise, an ozygen shortage may occur.

Do not place heavy object on the power cable.

Otherwise, it may cause fire or electric shock.

When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.

Otherwise, it may cause failure of product or fire.

When the product is soaked, contact the service center.

Otherwise, it may cause fire or eletric shock.

Install the panel and the cover of control box securely.

Do not turn the breaker on/off or connect/disconnect the power supply plug during operation.

• Otherwise, it may cause fire and electric shock." • Otherwise, it may cause fire or electric shock.

Do not open the inlet grill of the product during operation.

• Otherwise, it may cause electric shock or

Do no touch the metal parts of the product when removing the air filter.

• Otherwise, it may cause personal injury.

Do not let children step on the product.

Otherwise, children may be seriously injured.

Do not step or put anyting on the product.

Otherwise, it may cause personal injury and failure of product.

Be cautious that water could not enter the product.

Otherwise, it may cause fire or electric shock.

4 Ceiling Duct Type Air Conditioner

Safety Precautions

Installation

Always inspect gas leakage after installation and repair of product.

Otherwise, it may cause failure of product.

Keep the level even when install the product.

Otherwise, it may cause vibration or water leakage.

Do not carry the product by oneself.

Otherwise it may harm to your health.

Install the drain hose to ensure that drain can be securely done.

Otherwise, it may cause water leakage.

Do not install the product where the noise or hot wind from the outdoor unit could give any damage to the neighborhoods.

Otherwise, it may cause dispute with the neighborhoods.

Do not install the product exposed to sea wind(salt) directly.

Otherwise, it may cause the rust on product.

 

 

 

 

 

 

Do not expose your skin directly to cool air

When flammable gas leaks, open the

for a long time.

window for ventilation before turn the

 

 

product on.

• Otherwise, it may harm to your health.

• Otherwise, it may cause explosion or fire.

Turn the main power off when cleaning the

Do not put a pet or houseplant where it is

product.

exposed to direct air flow.

• Otherwise, it may cause fire and electric shock. • This could injure the pet or plant.

Do not use the product for special purpose

Stop operation and close the window in

to preserve animals, vegetables, precision

strom or hurricane.

device, or works of art, etc.

 

Otherwise, it may cause loss of property.

Do not place obstacles aroud the inlet or outlet of air flow.

Othewise, it may cause failure of product.

Use a soft cloth to clean, Do not use wax, tinner or a strong detergent, etc.

Otherwise, it may change the appearance of the product.

Otherwise, it may cause failure of product or electric shock.

Always insert the filter securely. Clean the filter every two weeks.

Otherwise, it may cause failure of the product.

Do not drink drained water from the product.

Otherwise, it may harm to your health.

<![if ! IE]>

<![endif]>ENGLISH

Installation Manual 5

Do not insert your hand or bars, etc. into the air inlet/outlet.

• Otherwise, it may cause personal injury.

Do not use the product at the closed space for a long time.

Otherwise, it may cause suffocation due to poor oxygen.

Do not operate the product for a long time at high humid place, and leave a door or a window open.

Otherwise, water may drop and wet or damage

Replace the 2 batteries with new ones of same type.

Otherwise, it may cause fire or explosion.

If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water.

Otherwise it may harm to your health.

Do not step on an unstable bench when maintaining the product, etc.

Otherwise, it may cause personal injury.

Do not charge or disassemble the batteries and throw into a fire.

Otherwise, it may cause fire or an explosion.

6 Ceiling Duct Type Air Conditioner

Installation Parts Provided

Introduction

SymbolsUsedinthisManual

This symbol alerts you to the risk of electric shock.

This symbol alerts you to hazards that could cause harm to the air conditioner.

NOTICE This symbol indicates special notes.

Features

<![if ! IE]>

<![endif]>ENGLISH

Air outlet vents

Air filters

(Optional)

Air intake vents

 

Remote Controller

 

Air Intake

Connecting Wire

 

(side, rear)

Power Wire

 

 

 

Air Outlet

 

 

Vents

Connection Tube

Air outlet vents

(Side)

 

(Rear)

Drain Hose

Air intake vents

Control cover

Connecting wire

Piping

Drain hose

Installation Manual 7

LG LB-C366GTA0 Installation Manual

Installation of Indoor, Outdoor Unit

Installation of Indoor, Outdoor Unit

Selectionofthebestlocation

Indoor unit

Install the air conditioner in the location that satisfies the following conditions.

The place shall easily bear a load exceeding four times the indoor unit’s weight.

The place shall be able to inspect the unit as the figure.

The place where the unit shall be leveled.

The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)

The place shall easily connect with the outdoor unit.

The place where the unit is not affected by an electrical noise.

The place where air circulation in the room will be good .

There should not be any heat source or steam near the unit

Outdoor unit

If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.

There should not be any animals or plants which could be affected by hot air discharged.

Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.

Top view

 

 

 

 

 

Inspection hole

 

 

 

 

 

 

 

 

 

 

(600X600)

 

 

 

 

(unit: mm)

 

 

 

 

 

Control box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

 

<![if ! IE]>

<![endif]>1000

 

 

 

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front

Front view

 

 

 

H

More

 

Sunroof

 

30cm

 

 

 

 

 

Fence

 

 

 

or

 

More than

obstacles

 

 

30cm

 

 

 

More than

 

 

 

70cm

 

 

Fence or

than 120cm

 

 

obstacles

More than

 

 

 

90cm

 

 

 

Fence

or

 

More than

 

 

90cm

obstacles

 

More than 90cm

More than 90cm

8 Ceiling Duct Type Air Conditioner

 

 

 

 

 

 

Installation of Indoor, Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping length and the elevation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe Size

 

Length A(m)

Elevation B(m)

*Additional

 

 

 

 

 

 

(Diameter: Ø)

 

 

<![if ! IE]>

<![endif]>ENGLISH

Capacity

 

refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

Liquid

 

Standard

Max.

Standard

Max.

(g/m)

 

 

 

 

 

18K BTU/h

5/8"

1/4"

 

7.5

30

5

15

30

 

 

24K BTU/h

5/8"

1/4"

 

7.5

30

5

15

30

 

 

30K BTU/h

5/8"

1/4"

 

7.5

30

5

15

35

 

 

36K BTU/h

5/8"

1/4"

 

7.5

30

5

15

40

 

 

42K BTU/h

3/4"

3/8"

 

7.5

30

5

15

70

 

 

48K BTU/h

3/4"

3/8"

 

7.5

30

5

15

70

 

 

60K BTU/h

3/4"

1/2"

 

7.5

30

5

15

100

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

Outdoor unit

Indoor unit

 

A

Oil trap

 

 

Outdoor unit

B

Indoor

 

 

 

B

 

Indoor unit

 

 

 

If piping length is more than 5m

CAUTION:

If 24K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5) x 30g = 225g

Capacity is based on standard length and maximun allowance length is on the basis of reliability.

Improper refrigerant charge may result in abnormal cycle.

Oil trap should be installed every 10 meters.

Installation Manual 9