LG LB-C366GTA0 Installation Manual

LG Ceiling Duct-Type Air Conditioner
INSTALLATION MANUAL
LG
MODELS: LB-C246HSA0
LB-C306GTA0 LB-C366GTA0 LB-C428GTA0 LB-C488ETA0 LB-C608ETA0
• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
2 Ceiling Duct Type Air Conditioner
Ceiling Duct Type Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions..............3
Introduction .........................7
Installation of Indoor,
Outdoor Unit ........................8
Connecting Pipes to the
Indoor Unit .........................18
Connecting Pipes to the
Outdoor Unit ......................20
Checking the Drainage .....20
Connecting Cables between Indoor Unit and
Outdoor Unit ......................21
Air Purging of the Connecting Pipes and the
Indoor Unit .........................24
Group Control....................25
Two Thermistor system ....25
E.S.P.(External Static
Pressure) Setting ..............26
How to Set E.S.P? .............27
High-Static Motor Connection (For 48k/60k Model)
.................................28
External Static Pressure &
air Flow...............................28
Checking the Power Cord
........................29
Installation
Requirements
Required Parts Required Tools
Four Type “A” screws
Connecting cable
Level
Screw driver
Electric drill
Hole core drill (ø70mm)
Pipes: Gas side .....
1
/2", 5/8", 3/4"
Liquid side .............
1
/4", 3/8", 1/2"
Insulated drain hose
Insulation materials
Flaring Tools set
Additional Drain hose
(Inner Dia...............25mm)
Screw driver
Hexagonal Wrench (4mm/5mm)
Gas-leak Detector
Safety Precautions
Installation Manual 3
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified
by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Do not damage or use an unspecified power cable.
It will cause electric shock or fire.
Do not disassemble or repair the product.
Contact your dealer and service center.
Always earth the product.
It will cause fire or electric shock.
Do not handle the flamable gas or explosive materials near the product.
Otherwise, it may cause fire or failure of product.
Do not install the product where flamable gas could leak.
Otherwise, it may cause esplosion or fire.
Do not install the product on the defected installation stand.
Otherwise, It may cause injury or accident.
Be cautious when unpack and install the product.
Sharp edges could cause injury.
For installation, always contact the dealer or service center.
Otherwise, it may cause fire, electric shock, explosion or injury.
Do not install the product on an defected installation stand.
Otherwise, It may cause injury or accident.
For electric work, contact the dealer or service center.
Otherwise, It will cause fire or electric shock.
4 Ceiling Duct Type Air Conditioner
Safety Precautions
Do not modify power cable length.
It will cause fire or electric shock.
Always intstall a circuit breaker and exclusive switching board.
No installation may cause fire and electric shock.
Use a rated breaker and fuse.
Otherwise, it may cause fire and electric shock.
Do not use a defected circuit breaker and exclusive switching board.
Otherwise, it may cause fire and electric shock.
Operation
Do not touch(operate) product with wet hands.
Otherwise, it may cause fire or electric shock.
If strange sound, smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
Otherwise, it may cause electric shock or fire.
Do not place the heater, etc. near the power cable.
Otherwise, it may cause fire and electric shock.
Do not put water into electric part.
Otherwise, it may cause fire or failure of product, and electric shock.
Ventilate the room frequently using with a stove, etc.
Otherwise, an ozygen shortage may occur.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
Otherwise, it may cause failure of product or fire.
Do not place heavy object on the power cable.
Otherwise, it may cause fire or electric shock.
When the product is soaked, contact the service center.
Otherwise, it may cause fire or eletric shock.
Install the panel and the cover of control box securely.
Otherwise, it may cause fire and electric shock."
Do not turn the breaker on/off or connect/disconnect the power supply plug during operation.
Otherwise, it may cause fire or electric shock.
Do not open the inlet grill of the product during operation.
Otherwise, it may cause electric shock or failure.
Do no touch the metal parts of the product when removing the air filter.
Otherwise, it may cause personal injury.
Do not let children step on the product.
Otherwise, children may be seriously injured.
Do not step or put anyting on the product.
Otherwise, it may cause personal injury and failure of product.
Be cautious that water could not enter the product.
Otherwise, it may cause fire or electric shock.
Safety Precautions
Installation Manual 5
ENGLISH
Operation
Installation
Always inspect gas leakage after installation and repair of product.
Otherwise, it may cause failure of product.
Install the drain hose to ensure that drain can be securely done.
Otherwise, it may cause water leakage.
Keep the level even when install the product.
Otherwise, it may cause vibration or water leakage.
Do not install the product where the noise or hot wind from the outdoor unit could give any damage to the neighborhoods.
Otherwise, it may cause dispute with the neighborhoods.
Do not carry the product by oneself.
Otherwise it may harm to your health.
Do not install the product exposed to sea wind(salt) directly.
Otherwise, it may cause the rust on product.
Do not expose your skin directly to cool air for a long time.
Otherwise, it may harm to your health.
When flammable gas leaks, open the window for ventilation before turn the product on.
Otherwise, it may cause explosion or fire.
Turn the main power off when cleaning the product.
Otherwise, it may cause fire and electric shock.
Do not put a pet or houseplant where it is exposed to direct air flow.
This could injure the pet or plant.
Do not use the product for special purpose to preserve animals, vegetables, precision device, or works of art, etc.
Otherwise, it may cause loss of property.
Stop operation and close the window in strom or hurricane.
Otherwise, it may cause failure of product or electric shock.
Do not place obstacles aroud the inlet or outlet of air flow.
Othewise, it may cause failure of product.
Always insert the filter securely. Clean the filter every two weeks.
Otherwise, it may cause failure of the product.
Use a soft cloth to clean, Do not use wax, tinner or a strong detergent, etc.
Otherwise, it may change the appearance of the product.
Do not drink drained water from the product.
Otherwise, it may harm to your health.
6 Ceiling Duct Type Air Conditioner
Safety Precautions
Do not insert your hand or bars, etc. into the air inlet/outlet.
Otherwise, it may cause personal injury.
Do not use the product at the closed space for a long time.
Otherwise, it may cause suffocation due to poor oxygen.
Do not operate the product for a long time at high humid place, and leave a door or a window open.
Otherwise, water may drop and wet or damage furniture, etc.
Do not step on an unstable bench when maintaining the product, etc.
Otherwise, it may cause personal injury.
Replace the 2 batteries with new ones of same type.
Otherwise, it may cause fire or explosion.
Do not charge or disassemble the batteries and throw into a fire.
Otherwise, it may cause fire or an explosion.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water.
Otherwise it may harm to your health.
Installation Parts Provided
Installation Manual 7
ENGLISH
Air filters
(Optional)
Air outlet vents
Air intake vents
Remote Controller
Air Intake
(side, rear)
Connecting Wire
Drain Hose
Power Wire
Connection Tube
Air Outlet
Vents
(Side)
(Rear)
Air intake vents
Air outlet vents
Piping
Drain hose
Control cover
Connecting wire
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Introduction
Symbols Used in this Manual
Features
8 Ceiling Duct Type Air Conditioner
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Indoor unit
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four times the indoor unit’s weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
There should not be any animals or plants which could be affected by hot air discharged.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Selection of the best location
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
More than 90cm
More than 90cm
More than 120cm
More than 90cm
More than 90cm
Fence or
obstacles
Fence or
obstacles
Fence or
obstacles
More than 30cm
Fence or
obstacles
Sunroof
More than 30cm
More than 70cm
Installation of Indoor, Outdoor Unit
Installation Manual 9
ENGLISH
Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 5m
30 30 35 40 70 70
100
Capacity
Gas 5/8" 5/8" 5/8" 5/8"
3/4" 3/4" 3/4"
Liquid
1/4" 1/4" 1/4" 1/4" 3/8" 3/8" 1/2"
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
7.5
7.5
7.5
7.5
7.5
7.5
7.5
Standard
5 5 5 5 5 5 5
Max.
30 30 30 30 30 30 30
Max.
15 15 15 15 15 15 15
18K BTU/h 24K BTU/h 30K BTU/h 36K BTU/h 42K BTU/h 48K BTU/h 60K BTU/h
CAUTION:
If 24K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5) x 30g = 225g
Capacity is based on standard length and maximun allowance length is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.