Lg Lauk2430hl Installation Guide

INSTALLATION INSTRUCTIONS
SINGLE SPLIT WALL MOUNTED AIR CONDITIONER
1. Type "A" screw
2. Installation Plate
3. Type "B" screw
4. Holder Remote Control
Air filter
Putty(Gum Type Sealer)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
Installation parts you must purchase
Vinyl tape (Wide)
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Saddle
Gas side piping (Optional Parts) Liquid side piping (Optional Parts) Additional drain pipe
Vinyl tape (Narrow) Connecting cable
(Optional Parts)
P/No.: 3828A20196X
(Split - Series)
• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Installation Parts Provided
• This illustration is for explanation purposes only.
• The indoor unit will actually face a different way.
• Copper lines must be insulated independently.
ENGLISH FRANÇAIS ESPAÑOL
INSTALLATION OVERVIEW
2
The following should be always observed for safety
....................
3
Installation of indoor, outdoor unit
................................................
4
Flaring work and connection of piping
...........................................
6
Connection of piping(Indoor)
......
7
For right rear piping For left rear piping Connection of piping(Outdoor)
................................................
10
Connecting the cable between indoor unit and outdoor unit
......
....................................................
11
Checking the drainage and Forming the piping
..................
14
Air purging
...............................
15
Test running
.............................
17
Installation plateFour type "A" screwsConnecting cable
Pipes: Gas side .........1/2"(9K,12K)
5/8"(18K,24K)
Liquid side......1/4"(9K,12K,18K)
3/8"(24K)
(Refer to page 4)
Insulation materialsAdditional drain pipe
(Outer Diameter.........15.5mm)
Level gaugeScrew driverElectric drillHole core drill ø70mm(2.79")
Flaring tool setSpecified torque wrenches
Liquid side -1.8kg.m(13ft.lbs):9K,12K,18K
4.0kg.m(28.9ft.lbs):24K
Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K
6.6kg.m(47.7ft.lbs):18K, 24
K
Spanner......................Half union
A glass of waterScrew driver
Hexagonal wrench(4mm: 5.32")Gas-leak detectorVacuum pumpGauge manifold
Owner's manualThermometerHolder Remote Control
Installation
Requirements
Required Parts Required Tools
ENGLISH
THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY
3
Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
The indications and meanings are as follows.
After reading this instructions, be sure to keep it together with the owner's manual in a handy place on the customer's site.
WARNING
: Could lead to death, serious injury, etc.
CAUTION
: Could lead to serious injury in particular environments when operated
incorrectly.
WARNING
Incorrect installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
Do not install it yourself (customer).
When installed in an insufficiently strong place, the unit could fall causing injury.
Install the unit securely in a place which can bear the weight of the unit's.
Incorrect connection and attachment could cause fire.
Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal board connecting sections so the stress of the wires is not applied to the sections.
If the electrical part covers of the indoor unit and/or the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely.
The use of defective parts could cause an injury due to a fire, electric shock, the unit's falling, etc.
Be sure to use the part provided or specified parts for the installation work.
Check that the refrigerant gas does not leak after installation is completed.
Incorrect installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
Perform the installation securely referring to the installation instruction.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
Perform electrical work according to the installation manual and be sure to use a dedicated circuit.
CAUTION
If there is a defect in the drainage/piping work, water could leak from the unit and household goods could come wet and be damaged.
Perform the drainage/piping work according to the installation instruction.
If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
Do not install the unit in a place where a flammable gas leaks.
4
INSTALLATION OF INDOOR, OUTDOOR UNIT
Read completely, then follow step by step.
Select the best location
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
Piping length and elevation
More than "A"
More than "B"
More than 2.3m
More than "B"
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
If case more than 5m
A
C
B
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
CAUTION
Pipe Size
MODEL
(Cooling Capa.)
GAS LIQUID
Max.
length
A
Max.
Elevation
B
9K, 12K 1/2" 1/4" 15m(50ft) 8m(26ft)
18K 5/8" 1/4" 15m(50ft) 8m(26ft) 24K 5/8" 3/8" 15m(50ft) 8m(26ft)
ENGLISH
5
How to fix installation plate
The wall you select should be strong and solid enough to prevent vibration
Mount the installation plate on the wall with 6 type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation Plate
Type "A" screw
A,B
A,B,C
C
D
D
A,B,D
C
A
B,D
C
ø70m
m
(2.76")
Left rear piping Right rear piping
Hole Center Installation plate
ø70m
m
(2.76")
Left rear piping Right rear piping
Hole Center Installation plate
A,B
A,B,C
C
D
D
A,B,D
C
A
B,D
C
ø85m
m
(3.35")
Left rear piping Right rear piping
Hole Center Installation plate
9K Btu
12K Btu
18K, 24K Btu
A
B
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Drill a hole in the wall
6
Connection of piping -- Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the
original position.(Optional)
FLARING WORK AND CONNECTION OF PIPING
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes
purchased locally.
Measure the distance between the indoor and
the outdoor unit.
Cut the pipes a little longer than the measured
distance.
Cut the cable 1.5m longer than the pipe length.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
A
B
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
C
Carry out flaring work using flaring tool as shown below.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared section and re-flare it.
E
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5 Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Outside diameter A
Flare nut
Copper tube
To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.
Tubing holder
Pull
Press
2
1
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
CAUTION
When install, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
D
Copper
pipe
Point down
Slanted Uneven Rough
90°
Pipe
Reamer
Bar
"A"
Copper pipe
Clamp handle
Bar
Handle
Yoke
Cone
Red arrow mark
Loading...
+ 12 hidden pages