Unit Nomenclature...........................................................................................................................................................................................................4
LG Air Conditioner Technical Solution (LATS)..........................................................................................................................................................5-6
High Efciency Standard Product Data...................................................................................................................................................................7-36
General Data ......................................................................................................................................................................................................... 9
Electrical Data ............................................................................................................................................................................................................ 11
Functions, Controls, and Options .......................................................................................................................................................................... 12
Acoustic Data ........................................................................................................................................................................................................ 18-21
Air Flow, External Pressure, Temp. Distribution ...................................................................................................................................................... 31-34
High Efciency Standard Performance Data--------------------------------------------------------------------------------------------------------------------------------37-45
Cooling Capacity Data ........................................................................................................................................................................................... 38-396
Heating Capacity Data ........................................................................................................................................................................................... 40-41
Maximum Heating Capacity Data .......................................................................................................................................................................... 42-43
High Efciency Standard Application Guidelines................................................................................................................................................. 46-55
LG Air Conditioner Technical Solution (LATS) Software
A properly designed and installed refrigerant piping system is critical to the optimal performance of LG air-conditioning systems. To assist
engineers, LG offers, free of charge, LG Air Conditioner Technical Solution (LATS) software—a total design solution for LG air conditioning
systems. Contact your LG Rep for the best software program for your application.
To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all projects.
Formats
LATS is available to LG customers in three user interfaces: LATS HVAC, LATS CAD2, and LATS Revit. All three LATS formats are available
through www.myLGHVAC.com, or contact an LG Sales Representative.
LATS HVAC is a Windows®-based application that aids engineers in designing LG Variable Refrigerant Flow (VRF), Multi F / Multi F MAX,
Single-Zone, and Energy Recovery Ventilator (ERV) systems.
*Windows® is a registered mark of Microsoft® Corporation.
LATS CAD2 combines the LG LATS program with AutoCAD®
software**. It permits engineers to layout and validate LG Multi V
Variable Refrigerant Flow (VRF), Multi F / Multi F MAX, Single-Zone,
and Energy Recovery Ventilator (ERV) systems directly into CAD
drawings.
LATS Revit integrates the LG LATS program with Revit® software**.
It permits engineers to layout and validate Multi V VRF systems
directly into Revit drawings.
**AutoCAD® and Revit® are both registered marks of Autodesk, Inc.
Figure 1: Example of LATS CAD2.
Features
All LG product design criteria have been loaded into the program,
making LATS simple to use: double click or drag and drop the
component choices. Build systems in Tree Mode where the
refrigerant system can be viewed. Switch to a Schematic diagram to
see the electrical and communications wiring.
LATS software permits the user to input region data, indoor and outdoor design temperatures, modify humidity default values, zoning, specify
type and size of outdoor units and indoor units, and input air flow and external static pressure (ESP) for ducted indoor units.
The program can also:
• Import building loads from a separate Excel file.
• Present options for outdoor unit auto selection.
• Automatically calculate component capacity based on design
conditions for the chosen region.
• Verify if the height differences between the various system
components are within system limits.
• Provide the correct size of each refrigerant piping segment and LG
Y-Branches and Headers.
• Adjust overall piping system length when elbows are added.
• Check for component piping limitations and flag if any parameters
are broken.
• Factor operation and capacity for defrost operation.
• Calculate refrigerant charge, noting any additional trim charge.
• Suggest accessories for indoor units and outdoor units.
• Run system simulation.
Introduction
Features depend on which LATS program is being used, and the type of system being designed.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
LATS software also generates a report containing project design parameters, cooling and heating design data, system component
performance, and capacity data. The report includes system combination ratio and refrigerant charge calculations; and provides detailed bill
of material, including outdoor units, indoor units, control devices, accessories, refrigerant pipe sizes segregated by building, by system, by
pipe size, and by pipe segments. LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system.
Proper Design to Install Procedure
LG encourages a two report design-to-install-procedure. After the
design engineer determines building / zone loads and other details,
the engineer opens the LATS program and inputs the project’s
information. When the design is complete, the “Auto Piping” and
“System Check” functions must be used to verify piping sizes,
limitations, and if any design errors are present. If errors are found,
engineers must adjust the design, and run Auto Piping and System
Check again. When the design passes the checks, then the engineer
prints out a project “Shop Drawing” (LATS Tree Diagram) and
provides it to the installing contractor. The contractor must follow the
LATS Tree Diagram when building the piping system, but oftentimes
the design changes on the building site:
• Architect has changed location and/or purpose of room(s).
• Outdoor unit cannot be placed where originally intended.
• Structural elements prevent routing the piping as planned.
• Air conditioning system conflicts with other building systems (plumbing, gas lines, etc.).
The contractor must mark any deviation from the design on the Shop Drawing, including as-built straight lines and elbows. This “Mark Up”
drawing must be returned to the design engineer or Rep, who must input contractor changes into the LATS file. (Copy the original LATS
software file, save and rename as a separate file, and modify all piping lengths by double-clicking on each length and editing information.)
Like the shop drawing, the Auto Piping and System Check must also be run on this new “As Built” drawing. The design engineer or Rep must
then provide the final As Built file to the contractor. The Mark Up version must be compared to the As Built version for:
Figure 2: Example of a LATS Tree Diagram.
• Differences in pipe diameter(s). If incorrect diameters have been installed, the piping must be changed out. If pipe diameters have changed,
check to see if Y-Branches will also need to be changed.
• Changes to outdoor unit and indoor unit capacities. Capacities changes may impact line length changes.
• Additional refrigerant charge quantity (“Trim Charge”). Trim charge will change if piping lengths and diameters change. The As Built version
must reflect installed piping lengths to ensure correct trim charge.
All documents submitted by the contractor, as well as the Shop Drawing and the As Built Drawing files must be provided for commissioning
purposes. Model and serial numbers for all system components must also be submitted. If the steps previously detailed are not followed,
and all documents are not provided to the commissioning agent, the project runs the risk of not being commissioned and voiding any limited
warranty LG offers on the equipment.
Single Zone High Efciency Standard Wall Mount Engineering Manual
Contact your LG representative for the best software program for your application.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
“Air Flow, External Pressure, and Temperature
Distribution” on page 31
“Accessories” on page 35
Page 8
MECHANICAL SPECIFICATIONS
General
LG Single Zone High Efficiency Wall Mount systems are comprised
of a single outdoor unit connected to a single indoor unit with a
single refrigerant circuit.
These single zone systems can operate in either cooling or heating
mode. These systems are capable of changing mode within a
maximum time of three (3) minutes to ensure temperature can be
properly maintained.
LG Single Zone High Efficiency systems are manufactured in
a facility registered to ISO 9001 and ISO 14001, which is a set
of standards applying to environmental protection set by the
International Organization for Standardization (ISO). The units are
listed by Intertek Electrical Testing Laboratories (ETL) and bear the
ETL label. Wiring in these units are in accordance with the National
Electrical Code (NEC).
Temperature Ranges
Outdoor Unit
Operating ranges for outdoor units of 14°F to 118°F DB for cooling
and -4°F to +65°F WB for heating.
Indoor Unit
Operating ranges for indoor units of 53°F to 75°F WB for cooling and
60°F to 86°F DB for heating.
Figure 3: Single Zone High Efciency Wall Mount Indoor Unit.
Frequency ranges for the outdoor units are as follows:
LSU090HSV5 = 10-84 Hz
LSU120HSV5 = 10-92 Hz
LSU180HSV5 = 10-93 Hz
Overcurrent protection and vibration isolation are integrated with the
compressor.
Outdoor Unit Coil
Heat pump outdoor unit coils are made of a nonferrous construction
with louvered fins on copper tubing, and are protected with an
integral coil guard. Coil fans have a factory applied corrosion
resistant GoldFinTM material with hydrophilic coating. Drain pan
heaters are also available for the outdoor units—9,000 and 12,000
Btu/h outdoor units include factory-installed drain pan heaters; the
drain pan heater for the 18,000 Btu/h outdoor unit is offered as an
optional accessory
Installing an optional Low Ambient Wind Bafe Kit will allow operation
down to 0°F in cooling mode for these single zone systems.
Casing / Frame
Outdoor unit is constructed with pre-coated metal (PCM). Indoor unit
is constructed of heavy duty Acrylonitrile Butadiene Styrene (ABS)
and High Impact Polystyrene (HIPS) plastic.
Refrigerant System
The refrigeration system consists of a single refrigeration circuit and
uses R410A refrigerant. The outdoor unit is provided with factory
installed components, including a refrigerant strainer, four-way
reversing valve, electronic controlled expansion valve (EEV), high and
low side charging ports, service valves, and interconnecting piping.
Single Zone High Efciency Standard Wall Mount Engineering Manual
Refrigeration Oil Control
Heat pump outdoor units have a centrifugal oil separator and
controls to ensure sufficient oil supply is maintained, and that oil
does not travel with the refrigerant.
Compressors
The outdoor unit is equipped with one hermetic digitally controlled
inverter driven twin rotary compressor to modulate capacity
(modulation in 1 Hz increments).
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
The outdoor unit includes one direct fan drive, variable speed
propeller type fan. The Brushless Digitally Controlled (BLDC)
fan motor shall have inherent protection, permanently lubricated
bearings, and variable speed with a maximum speed up to 950 rpm.
Raised guards are provided to limit contact with moving parts. The
outdoor unit has horizontal discharge airflow.
Electrical
These units are available in 208-230V, 60 Hz, 1-phase power supply.
These units are capable of operating within voltage limits of ±10%
rated voltage, and include overcurrent protection.
Controls
The indoor unit casing has a factory-standard, integral, infrared
sensor designed to communicate with the supplied LG wireless
handheld remote controller. An optional LG supplied wired controller
is available as an additional accessory. Communication between the
indoor unit and the outdoor unit is accomplished through 18 AWG
four-core, stranded, shielded power / communication cable. HSV5
indoor units have built-in Wi-Fi and can be controlled by LG’s Smart
ThinQ™ app on a smart device. A field-supplied Wi-Fi network and
smart device are required. The Smart ThinQ app is free, and is
available for Android™ and iOS. (Android is a trademark of Google
LLC.)
Page 9
Table 1: Single Zone High Efciency Standard Wall Mount Unit Pairing Table.
Outdoor Unit ModelIndoor Unit ModelWireless Remote Controller
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Optional low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
5
All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied
and must be a minimum of four-conductor, 18 AWG, stranded, shielded or unshielded (if shielded, it
must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and
national codes. For detailed electrical information, please refer to electric characteristics on page 11.
6
Piping lengths are equivalent.
Page 11
ELECTRICAL DATA
Electrical Data
Table 3: Single Zone High Efciency Standard Wall Mount System Electrical Data.
Nominal
Tons
Unit Model No. HertzVoltage
3/4LS090HSV5
1LS120HSV510.015.017.07.00.0430.40.4
60208 - 230187 - 253
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
10.015.017.07.00.0430.40.4
1-1/2LS180HSV513.020.019.69.60.1240.250.4
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
Compressor Motor
RLA
CoolingHeating
RLA = Rated Load Amps.
FLA = Full Load Amps.
Outdoor Fan Motor
kWFLAFLA
Indoor
Fan Motor
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Table 4: Indoor Units—Functions, Controls and Options.
Indoor Unit TypeLS090HSV5LS120HSV5LS180HSV5
Air Supply Outlet
Airflow Direction Control (Left / Right)
Airflow Direction Control (Up / Down)
Auto Swing (Left / Right)
Auto Swing (Up / Down)
Figure 5: High Efciency Standard Wall Mount Indoor Unit Sound Level
Measurement.
• Measurements are taken 3.3 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of
±3.
• Data is valid at nominal operation conditions. Operating conditions
are assumed to be standard.
• Reference acoustic pressure 0dB=20μPa
• Sound pressure levels are tested in an anechoic chamber under
ISO Standard 3745, and may be different according to the test
condition or equipment.
• Sound level will vary depending on a range of factors including the
construction (acoustic absorption coefficient) of a particular room in
which the unit was installed.
Indoor Unit Sound Pressure Levels
Table 6: High Efciency Standard Wall Mount Indoor Unit Acoustic Data.
Figure 8: High Efciency Standard Wall Mount Outdoor Unit Sound
Level Measurement.
Outdoor Unit Sound Pressure Levels
Table 7: High Efciency Standard Wall Mount Outdoor Unit Acoustic Data.
Model
LSU090HSV54548
LSU120HSV54548
LSU180HSV55353
Sound Pressure Levels (dB[A])
Cooling (Max.)Heating (Max.)
• Measurements are taken 3.3 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of
±3.
• Data is valid at nominal operation conditions. Operating conditions
are assumed to be standard.
• Reference acoustic pressure 0dB=20μPa
• Sound pressure levels are tested in an anechoic chamber under
ISO Standard 3745, and may be different according to the test
condition or equipment.
• Sound level will vary depending on a range of factors including the
construction (acoustic absorption coefficient) of a particular room in
which the unit was installed.
LSU090HSV5 Sound Pressure Levels
Figure 9: Sound Pressure Level Diagrams for LSU090HSV5 Outdoor Units.
LSU090HSV5
CoolingHeating
80
▲ Front
●
70
60
50
40
Single Zone High Efciency Standard Wall Mount Engineering Manual
30
Octave Band Sound Pressure Level (dB re 20μPa )
20
Approximate
Hearing
Threshold
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Back
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
60
50
40
30
Octave Band Sound Pressure Level (dB re 20μPa )
20
Approximate
Hearing
Threshold
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
▲ Front
●
Back
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
20 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
General Power Wiring / Communications Cable Guidelines
• Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover.
• Have a separate power supply for the indoor units.
• Provide a circuit breaker switch between the power source and the indoor unit.
• Confirm power source specifications.
• Properly ground the outdoor unit and the indoor unit per National Electrical Code (NEC) and local codes.
• Connect the wiring firmly so that the wires cannot be easily pulled out.
• Confirm that the electrical capacity is sufficient.
• Power supply to the outdoor unit must be selected based on NEC and local codes. Maximum allowable voltage fluctuation ±10% or nameplate rated value.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system. Add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Any openings where the field wiring enters the cabinet must be completely sealed.
Do not install power wiring to the outdoor unit and the communication / connection (power) cable to the indoor unit in the same conduit.
Use separate conduits.
Power Wiring / Communications Cable Specifications
• Power wiring to the outdoor unit must be solid or stranded, and must comply with the applicable local and national electric codes.
• Communication / connection (power) cable from the outdoor unit to the indoor unit must be a minimum of 18 AWG, four (4) conductor,
stranded, shielded or unshielded (if shielded, must be grounded to chassis at the outdoor unit only) and must comply with applicable local
and national codes.
• Communication cable from the indoor unit to optional remote controller is to be 22 AWG, three (3) conductor, twisted, stranded, unshielded.
Wiring must comply with all applicable local and national codes.
• Terminal screws may become loose during transport. Properly tighten the terminal connections during installation or risk electric shock,
physical injury, or death.
• Loose wiring may cause unit to malfunction, overheat, and catch fire, resulting in severe injury or death.
• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk equipment malfunction or
property damage.
• Loose wiring may cause unit malfunction, the wires to burnout or the terminal to overheat and catch fire. There is a risk of equipment malfunction or property damage.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Figure 11: LS090HSV5 and LS120HSV5 General Power / Communications System Schematic.
Figure 12: LS180HSV5 General Power / Communications System
Schematic.
• Use a conduit for the communications cable / power wiring from the outdoor unit to the indoor units.
• Make sure the communications cable / power wiring from the outdoor units to the indoor units, and the power wiring to the outdoor unit are
separate, otherwise, the outdoor unit operation may be affected by electrical noise and will malfunction or fail.
Figure 13: LS090-120HSV5 System Electrical Connections.Figure 14: LS180HSV5 System Electrical Connections.
Single Zone High Efciency Standard Wall Mount Engineering Manual
28 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Single Zone High Efficiency Standard Wall Mount systems include a wireless handheld remote controller
(Model No. AKB74955602), but optional LG-suppled wired controllers are available. See “Functions,
Controls, Options”, or contact an LG representative for more information.
Wireless Handheld Remote Controller features:
• Display Panel: Displays operation conditions.
• On / Off Button: Turns system operation on and off.
• Mode Button: Selects the operation mode: Cooling, Heating, Auto, Dry
(Dehumidification), or Fan.
• Temp Up / Down Buttons: Adjusts the desired room temperature in the different modes.
• Fan Speed Button: Sets desired fan speed.
• Reset: Initializes the handheld remote control settings.
Wired Controller Connections
Optional controllers (see “Functions, Controls, Options”, or contact an LG representative for more
information) can connect to the Single Zone High Efficiency Standard Wall Mount indoor unit in one of
two different ways.
1. LG Wired Remote Extension Cable with Molex plug (PZCWRC1; sold separately) that connects to the
CN-REMO terminal on the indoor unit PCB.
2. Field-supplied controller cable that connects to the indoor unit terminal block (must be at least
UL2547 or UL1007, and at least FT-6 rated if local electric and building codes require plenum cable
usage). Communication cable from indoor unit to remote controller(s) is to be 22 AWG, 3-conductor,
twisted, stranded, unshielded. Wiring must comply with all applicable local and national codes.
Figure 17: AKB74955602 Wireless Handheld Remote Controller.
Buttons may differ depending on
model type.
Product Data
Figure 15: PZCWRC1 LG Wired Remote Extension Cable.
Figure 16: Wired Controller Connection on the Indoor Unit Terminal Block.
Indoor Unit Terminal Block
GND
1(L1 )2(L2)
3
CN-REMO
BR
BL
RD
When using eld-supplied controller cable, make sure to connect the yellow to yellow (communications wire), red to red (12V power wire), and
black to black (ground wire) terminals from the remote controller to the
indoor unit terminal blocks.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Figure 18: Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature.
To maintain comfort levels in the conditioned space, the wired
controller must be installed in a location away from direct sunlight,
high humidity, and where it could be directly exposed to cold air.
Controller must be installed four (4) to five (5) feet above the floor
where its LED display can be read easily, in an area with good air
circulation, and where it can detect an average room temperature.
Do not install the wired controller near or in:
• Drafts or dead spots behind doors and in corners.
• Hot or cold air from ducts.
• Radiant heat from the sun or appliances.
• Concealed pipes and chimneys.
• An area where temperatures are uncontrolled, such as an outside
wall.
Assigning the Thermistor for Temperature Detection
Each indoor unit includes a return air thermistor assigned to sense the temperature. If a wired controller is installed, there is a choice
of sensing temperature with either the indoor unit return air thermistor or the thermistor in the wired controller. It is also an option to set
both thermistors to sense temperature so that indoor unit bases its operation on the first thermistor to reach the designated temperature
differential.
Single Zone High Efciency Standard Wall Mount Engineering Manual
30 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Discharge Angle : 45˚ (From the floor)
Vertical Louver : Left & Right
Fan Speed : Power
0.5(1.6)
1(3.3)
2(6.6)
0
0
3.3
1
6.6
2
9.8
3
13.1
4
16.4
5
0201468
Page 35
ACCESSORIES
LG Monitoring View (LGMV) Diagnostic Software and Cable
LGMV software allows the service technician or commissioning agent to connect a computer USB port
to the outdoor unit main printed circuit board (PCB) using an accessory cable without the need for a
separate interface device. The main screen for LGMV allows user to view the following real time data on
one screen:
• Actual inverter compressor speed
• Target inverter compressor speed
• Actual outdoor fan speed
• Target outdoor unit fan speed
• Actual superheat
• Target superheat
• Actual subcooler circuit superheat
• Target subcooler circuit superheat
• Main EEV position
• Subcooling EEV position
• Inverter compressor current transducer
value
• Outdoor air temperature
• Actual high pressure/saturation temperature
• Actual low pressure/saturation temperature
• Suction temperature
• Inverter compressor discharge temperature
• Constant speed compressor discharge
Additional screens can be accessed by tabs on the main screen:
1. Cycleview: Graphic of internal components including:
• Compressors showing actual speeds
• EEVs
• Indoor Units
• Liquid injection valves
2. Graph: Full screen graph of actual high and low pressures and high and low pressure limits. A
sliding bar enables user to go back in time and view data.
3. Control IDU: Enables user to turn on all IDU’s default setpoints of 86°F in heat mode or 64°F in
cool mode.
4. Setting: Converts metric values to imperial values.
5. Making Data: Recording of real time data to a separate file created to be stored on the user’s computer.
6. Loading Data: Recorded data from a saved “.CSV” file can be loaded to create an LGMV session.
7. Electrical Data: The lower half of main screen is changed to show the following:
• Pressure graph showing actual low pressure and actual high pressure levels
• Error code display
• Operating mode indicator
• Target high pressure
• Target low pressure
• PCB (printed circuit board) version
• Temperature and pressure sensors
• Four-way reversing valve
• Outdoor fans showing status and speeds
• Constant compressor
- Current transducer value
- Phase
• Software
version
• Installer
name
• Model no.
of outdoor units
• Site name
• Total number of connected indoor units
• Communication indicator lights
• Indoor unit capacity
• Indoor unit operating mode
• Indoor unit fan speed
• Indoor unit EEV position
• Indoor unit room temperature
• Indoor unit inlet pipe temperature
• Indoor unit outlet pipe temperature
• Indoor unit error code
Product Data
Figure 19: Sample Cycleview.
In lieu of connecting to the outdoor unit, user has the option to connect to the indoor unit with the use of a USB to RS-485 connector kit.
When connected through the indoor unit, user will not be able to record data.
This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a “.CSV” file
and emailed to an LG representative to assist with diagnostic evaluations.
Recommended Minimum PC Configuration:
• CPU: Pentium
• Operating System: Windows® NT/2000/XP/Vista
• Main Memory: 256 MB
LGMV is available in different formats, including Mobile LGMV, which is a app for use on wireless devices. Contact your LG
Sales Representative for more information.
®
IV 1.6 GHz
• Hard Disk: 600 MB when operating
• Web Browser: Internet Explorer® 5.0
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
SIMS can be used to display and graph operational data for single zone systems and respective
components (indoor unit and outdoor unit). SIMS also displays error codes and a troubleshooting guide.
SIMs consists of a hardware Wireless Local Area Network (WLAN) module, an interface cable, and a
free downloadable application (app) for iOS® or Android™. The user must supply either an Apple® or an
Android smart phone; SIMs is not optimized for tablets, and only be used with LG single zone and Multi F
systems.
Only trained HVAC service technicians familiar with variable refrigerant flow (VRF) systems in general
and with LG’s DFS products can use SIMS. The technician must understand inverter air conditioning
operation cycles, the meaning of the data displayed by SIMS, and how to use the data to troubleshoot
the system.
iOS is a registered trademark of Cisco in the U.S. and other countries. Android is a trademark of Google Inc.
Apple is a trademark of Apple Inc., registered in the U.S. and other countries.
Contact your LG Sales Representative for system requirements, the latest version of SIMS,
how to download the app, or other information.
LG Smart ThinQ
LG Smart ThinQ is a built-in Wi-Fi module, along with a free smart phone app that provides monitoring
and remote control capabilities for certain LG single zone systems. The app has the following features
and benefits:
Figure 20: LG SIMS WLAN
Module.
Figure 21: Example of an LG
Smart ThinQ Screen (appearances my differ depending on version
of software).
• Sign in to the app using LG credentials, or using Google® or Facebook® login credentials. Users only
have to log in to the app once; the app remembers login details for subsequent logins.
• View current temperature settings of the air conditioning unit and change temperature, fan speed,
and air flow direction from anywhere in the house or at a remote location (through the use of wireless
connection). Multiple users can control the household air conditioning unit remotely.
• Monitor filter usage of the unit.
• Set up weekly schedules to start and stop air conditioner activity.
• Set up the unit to run in different Modes, depending on the user’s schedule. Set up specific temperatures for when the user is home, away on vacation, or sleeping.
• Troubleshoot problems, and view tips on general maintenance of the system using the Smart Diagnosis
function.
*Google is a registered trademark of Google Inc.; Facebook is a registered trademark of Facebook.
Single Zone High Efciency Standard Wall Mount Engineering Manual
Contact your LG Sales Representative or visit www.lg-dfs.com for system requirements, how
to download the app, a user’s manual, or other information.
36 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan motor and
outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling range with the Low Ambient Baffle Kit (sold separately) is 0°F to +122°F.
3. Grey shading indicates reference data. When operating the unit at this temperature, these values
can be different by discontinuous operation.
38 | PERFORM ANCE DATA
64 / 5368 / 5772 / 6177 / 6480 / 6786 / 7290 / 75
TCSHCPITCSHCPITCSHCPITCSHCPITCSHCPITCSHCPITCSHCPI
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
4. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
0.87 14.26 10.96 0.87 14.99 11.84 0.88
Page 39
PERFORMANCE DATA
Cooling Capacity
LS180HSV5
Cooling Capacity Table for LS180HSV5 (LSU180HSV5 + LSN180HSV5)
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan motor and
outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling range with the Low Ambient Baffle Kit (sold separately) is 0°F to +122°F.
3. Grey shading indicates reference data. When operating the unit at this temperature, these values
can be different by discontinuous operation.
64 / 5368 / 5772 / 6177 / 6480 / 6786 / 7290 / 75
TCSHCPITCSHCPITCSHCPITCSHCPITCSHCPITCSHCPITCSHCPI
Indoor Air Temperature (°F DB / °F WB)
4. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
1.28 21.39 15.78 1.30 22.48 17.06 1.30
Performance Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Page 41
PERFORMANCE DATA
Heating Capacity
LS180HSV5
Heating Capacity Table for LS180HSV5 (LSU180HSV5 + LSN180HSV5)
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate. Nominal capacity as rated: 0 ft. above sea
level with 25 ft. of refrigerant piping.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Page 43
PERFORMANCE DATA
Maximum Heating Capacity
LS180HSV5
Maximum Heating Capacity Table for LS180HSV5 (LSU180HSV5 + LSN180HSV5)
Table 19: LSN180HSV5 / LSU180HSV5 Maximum Heating Capacities.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate. Nominal capacity as rated: 0 ft. above sea
level with 25 ft. of refrigerant piping.
60646870727586
TCPITCPITCPITCPITCPITCPITCPI
Indoor Air Temperature (°F DB)
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Performance Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
For Single Zone High Efficiency Standard Wall Mounted systems, calculate the equivalent length of the liquid line from the outdoor unit to the
indoor unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating
capacity correction factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity
tables using design conditions. The resultant is the corrected cooling or heating capacity.
Refrigerant Line Length Derates
For air-cooled systems, a capacity correction factor may have to be applied to account for the length of the system’ s refrigerant pipe. Rate of
change in capacity due to increased piping lengths is shown below.
Cooling Capacity Coefficient Factors
Table 20: Single Zone High Efciency Standard Wall Mounted Unit Cooling Capacity Coefcient Factors.
Single Zone High Efciency Standard Wall Mount Engineering Manual
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted
altitude correction factors using ASHRAE guidelines must be applied.
44 | PERFORMANCE DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
The outdoor unit heating capacity may need to be adjusted for frost accumulation on air-cooled systems. If design day conditions are below
the dewpoint of the surrounding air, frost may not be a problem and no correction factor is needed. In certain weather conditions, however,
frost may form and accumulate on the air-cooled outdoor unit coil and impact the coils ability to transfer heat. If significant frost accumulates
on the outdoor unit coil, a defrost algorithm will start automatically. The timing between defrost periods is determined by the system’s ability
to achieve a target head pressure value.
Capacity and AHRI ratings tables do not factor in capacity reduction when frost has accumulated on the condenser coil, nor during defrost
operation.
Integrated heating capacity values can be obtained using the formula:
A = B x C
Where:
A = Integrated Heating Capacity.
B = Value found in the Capacity Table.
C = Correction Factor for Frost Accumulation Factor (from table at
right).
Table 23: Outdoor Unit Frost Accumulation Factor (Heating)1.
Entering DB (ºF)
Derate factor
1
At 85% outdoor air relative humidity.
The frost accumulation factor does not account for effects of snow accumulation restricting airflow
through the outdoor unit coil.
19.4 23.0 26.6 32.0 37.4 41.0 44.6
0.98 0.95 0.93 0.86 0.93 0.96 1.0
There will be a temporary reduction in capacity when frost / ice accumulates on the outside surface of the outdoor unit heat exchanger. The level of
capacity reduction depends on a number of factors, for example, outdoor temperature (°F DB), relative humidity (RH), and the amount of frost present.
Check the Indoor and Outdoor Unit Selection(s)
Compare the corrected cooling and heating capacities to the load calculations. Is each capacity sufficient for the zone it serves?
For each indoor unit, the corrected capacity must be at least equal to the total of the cooling design load (plus ventilation load, if applicable)
for the space served by the indoor unit. For each indoor unit, the corrected capacity also must be at least equal to the total of the heating
design load (plus ventilation load, if applicable) for the space(s) and / or thermal zones served by the indoor unit.
The outdoor unit selected must be large enough to offset the total cooling load for all spaces it serves (account for ventilation air cooling
load if the ventilation air has not been pretreated to room neutral conditions). The outdoor unit must also be large enough to offset the total
heating load for all spaces it serves.
If the corrected heating capacity ratio exceeds 100%, reselect the equipment, or change the system design by moving some of the load to
another system.
• Reference load calculations for actual cooling and heating capacities (applies in 99% of applications – consider total load when latent load
is greater than 30%).
• Verify that the sensible load of the zone is satisfied.
• Use caution when sizing to meet listed capacity specifications for the scheduled manufacturer’s equipment.
If further system design assistance is needed, or you have a unique application you would like to discuss, contact your LG sales rep.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Figure 22: Single Zone High Efciency Standard Wall Mount Indoor Unit
Follow recommended best practices when choosing an indoor location for
the single zone indoor unit.
Dos
• Follow the table at right for minimum clearance of indoor unit from
the top of the unit to the ceiling.
• Clearance gap between any wall or enclosure and the left or right
side of the unit must be greater than 4 inches. Ensure there is
sufficient maintenance space.
• Unit must be at least 6.5 feet from the floor for adequate clearance.
• Place the unit where drainage can be obtained easily. Condensation drain must be conveniently routed away from the unit.
• Locate the indoor unit in a location where it can be easily connected to the outdoor unit within allowable limits.
• Use a metal detector to locate studs in the walls. Anchor unit
following stud location to prevent damage to the wall.
Clearance Requirements.
Table 24: Single Zone High Efciency Standard Wall Mount Indoor Unit
Ceiling Clearances.
Indoor Unit
Application Guidelines
Dont’s
• Do not install the unit near a heat or steam source, or where consid-
erable amounts of oil, iron powder, or flour are used. (These materials may generate condensate, cause a reduction in heat exchanger
efficiency, or the drain to malfunction. If this is a potential problem,
install a ventilation fan large enough to vent out these materials.)
• Ensure there are no obstacles to air circulation around the unit; keep proper distances from ceilings, doorways, floor, walls, etc.
• Do not install in an area where operation sound will disturb occupants--place the unit where noise prevention is taken into consideration
• Do not install near doorway.
• Avoid installing the unit near high-frequency generators.
The unit must not be installed where sulfuric acid and ammable or corrosive gases are generated, vented into, or stored. There is risk of re,
explosion, and physical injury or death.
The unit may be damaged, may malfunction, and / or will
not operate as designed if installed in any of the conditions
listed.
• Indoor units (IDUs) must not be placed in an environment where the IDUs may be exposed to harmful volatile organic compounds (VOCs) or
in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the environment
where the IDUs are installed, proper air make up or supply and/ or adequate ventilation must be provided. Additionally, in buildings where
IDUs will be exposed to VOCs consider a factory-applied epoxy coating to the fan coils for each IDU.
• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken for
the unit and all installation parts.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air (room may be above or next to an
unheated garage or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet may increase the temperature by three [3] degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
“A” Ceiling Clearance (inches)Indoor Unit Model(s)
5LSN090HSV5, LSN120HSV5
8LSN180HSV5
Figure 23: Installing Near a Heat or Steam Source.
Indoor Unit
Include enough
distance
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Install a ventilation fan
with sufficient capacity
APPLICATION | 47
Page 48
DANGER
PLACEMENT CONSIDERATIONS
Outdoor Unit
Selecting the Best Location for the Outdoor Unit
• Do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. These conditions can cause a fire, resulting
in bodily injury or death.
•
Do not install the unit in a location where acidic solution and spray (sulfur) are often used as it can cause bodily injury or death.
• Do not use the unit in environments where oil, steam, or sulfuric gas are present as it can cause bodily injury or death.
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks
or driveways, which may create unsafe conditions. Properly install and insulate any drain hoses to prevent the hose from freezing, cracking, leaking,
and causing unsafe conditions from frozen condensate.
Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it. Vermin and unauthorized individuals may
cause a fire, electric shock, physical injury or death. Follow the placement guidelines set forth in “Clearance Requirements”.
Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it. Vermin and unauthorized individuals may
damage the unit. Follow the placement guidelines set forth in “Clearance Requirements”.
Select a location for installing the outdoor unit that will meet the following conditions:
• Where there is enough strength to bear the weight of the unit.
• A location that allows for optimum air flow and is easily accessible for inspection, maintenance, and service.
• Where piping between the outdoor unit and indoor unit is within allowable limits.
• Include space for drainage to ensure condensate flows properly out of the unit when it is in heating mode. Avoid placing the outdoor unit in
a low-lying area where water could accumulate.
• If the outdoor unit is installed in a highly humid environment (near an ocean, lake, etc.), ensure that the site is well-ventilated and has a lot
of natural light (Example: Install on a rooftop).
Dont’s
• Where it will be subjected to direct thermal radiation from other heat sources, or an area that would expose the outdoor unit to heat or steam
like discharge from boiler stacks, chimneys, steam relief ports, other air conditioning units, kitchen vents, plumbing vents, and other sources
of extreme temperatures.
• Where high-frequency electrical noise / electromagnetic waves will affect operation.
• Where operating sound from the unit will disturb inhabitants of surrounding buildings.
• Where the unit will be exposed to direct, strong winds.
• Where the discharge of one outdoor unit will blow into the inlet side of an adjacent unit (when installing multiple outdoor units).
Outdoor Unit Condensate Drain Piping
Outdoor unit requires condensate drain piping. Condensate drain pipe is constructed with materials approved by local code. See page 51 for
information in reference to outdoor unit placement.
Planning for Snow and Ice
To ensure the outdoor unit operates properly, certain measures are required in locations where there is a possibility of heavy snowfall or
Single Zone High Efciency Standard Wall Mount Engineering Manual
severe windchill or cold:
1. Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these are unusual phenomena.
2. Position the outdoor unit so that its airflow fans are not buried by direct, heavy snowfall. If snow piles up and blocks the airflow, the
system may malfunction.
3. Remove any snow that has accumulated four (4) inches or more on the top of the outdoor unit.
4. In climates that may experience significant snow buildup, mount the outdoor unit on a raised, field-provided platform or stand. The raised
support platform must be high enough to allow the unit to remain above possible snow drifts, and must be higher than the maximum
anticipated snowfall for the location.
5. Design the mounting base to prevent snow accumulation on the platform in front or back of the unit frame.
6. Provide a field fabricated snow protection hood to keep snow and ice and/or drifting snow from accumulating on the coil surfaces.
7. To prevent snow and heavy rain from entering the outdoor unit, install the condenser air inlets and outlets facing away from direct winds.
8. Consider tie-down requirements in case of high winds or where required by local codes.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks
or driveways, which may create unsafe conditions. Properly install and insulate any drain hoses to prevent the hose from freezing, cracking, leaking,
and causing unsafe conditions from frozen condensate.
Underground Refrigerant Piping
Refrigerant pipe installed underground must be routed inside a vapor
tight protective sleeve to prevent insulation deterioration and water
infiltration. Refrigerant pipe installed inside underground
casing must be continuous without any joints. Underground
refrigerant pipe must be located at a level below the frost line.
Table 25: Utility Conduit Sizes (Inches).
Liquid Pipe
1/4 (1.0)
3/8 (1-1/8)
1
OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket.
2
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may
vary based on surrounding ambient conditions and must be calculated and specified by the design
engineer.
3
Insulation thickness (value in parenthesis) = 3/8 inch.
4
Insulation thickness (value in parenthesis) = 3/4 inch.
1
3/8 (1-1/8
4
4
2,3
444
444
Vapor Pipe
)1/2 (2.0
1
2,4
)5/8 (2-1/8
2,4
Figure 24: Typical Arrangement of Refrigerant Pipe and Cable(s) in a
Utility Conduit.
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
)
Material
Min. 18 Gauge
Power/Communication
Cable
Table 26: Outdoor Unit Refrigerant Pipe Connections (All Brazed Type).
Model
Liquid Conn.
(inches)
LSU090HSV5, LSU120HSV51/43/8
LSU180HSV53/85/8
Vapor Conn.
(inches)
Application Guidelines
Tie-Downs and Lightning Protection
Tie-Downs
Figure 25: Lightning Protection Diagram.
Lightning rod
Lightning rod
• The strength of the roof must be checked before installing the
outdoor units.
• If the installation site is prone to high winds or earthquakes, when
installing on the wall or roof, securely anchor the mounting base
using a field-provided tie-down configuration approved by a local
professional engineer.
• The overall tie-down configuration must be approved by a local
professional engineer.
Always refer to local code when using a wind restraint system.
Lightning Protection
• To protect the outdoor unit from lightning, it must be placed within
the specified lightning safety zone.
Table 27: Safety Zone Specifications.
Building Height (feet)
Protection Angle (˚)
• Power cable and communication cable must be installed five (5) feet away from lightning rod.
• A high-resistance ground system must be included to protect against induced lightning or indirect strike.
6698148197
55453525
Ground
Protection Angle (25˚~55˚)
5 feet
Safe zone
If the building does not include lightning protection, the outdoor unit may be damaged from a lightening strike. Inform the customer of this possibility
in advance.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Ocean winds may cause corrosion, particularly on the condenser and
evaporator ns, which, in turn could cause product malfunction or
inefcient performance.
• Avoid installing the outdoor unit where it would be directly
exposed to ocean winds.
• Install the outdoor unit on the side of the building opposite from
direct ocean winds.
• Select a location with good drainage.
• Periodically clean dust or salt particles off of the heat exchanger
with water.
• If the outdoor unit must be placed in a location where it would
be subjected to direct ocean winds, install a concrete windbreak
strong enough to block any winds.
• Windbreak must be more than 150% of the outdoor unit’s height.
There must be 2 to 3-1/2 inches of clearance between the outdoor
unit and the windbreaker for purposes of air flow.
Use of a Building to Shield from Sea Wind
If a windbreak is not possible, a building or larger structure must be
used to shield the outdoor unit from direct exposure to the sea wind.
The unit must be placed on the side of the building directly opposite
to the direction of the wind as shown in Figure 31.
Figure 26: Oceanside Placement Using Windbreak.
Windbreak
Sea wind
Additional anti-corrosion treatment may need to be applied to the outdoor
unit at oceanside locations.
Figure 27: Placement Using Building as Shield.
Building
Sea wind
Single Zone High Efciency Standard Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
50 | APPLICATION
Sea wind
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Minimum Allowable Clearance and Service Access Requirements
Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet,
and minimum allowable space requirements as illustrated in the diagrams below.
• Include enough space for airflow and for service access. If installing multiple outdoor units, avoid placing the units where the discharge of
one unit will blow into the inlet side of an adjacent unit.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that the discharge air of the outdoor unit isn’t restricted.
• No obstacles to air circulation around the unit; keep proper distances from ceilings, fences, floor, walls, etc. (Install a fence to prevent
pests from damaging the unit or unauthorized individuals from accessing it.)
Single Zone High Efficiency Standard Wall Mount Outdoor Unit (9,000, 12,000, 18,000 Capacities) Service Access and
Allowable Clearances
Specific clearance requirements in the diagram below are for 9,000, 12000, 18,000 Btu/h capacities. Figure 32 shows the overall minimum
clearances that must be observed for safe operation and adequate airflow around the outdoor unit.
When placing the outdoor unit under an overhang, awning, sunroof or other “roof-like structure”, observe the clearance requirements (as
shown in Cases 1 and 2) for height in relation to the unit. To have successful service access to the outdoor unit, see Figure 32 for minimum
spacing. When installing multiple outdoor units, see Cases 4 and 5 for correct spacing requirements.
If the outdoor unit is installed between standard and minimum clearances, capacity decreases approximately 10%.
Figure 28: Single Zone High Efciency Standard Wall Mount 9,000, 12,000, 18,000 Capacity Outdoor Unit Service Access and Allowable Clearances
Diagram.
1/16 inch
20 inches or less
G
20 inches or less
G
Application Guidelines
A
Case 4
B
D
C
Case 5
D
C
Do not place the unit where animals
and/or plants will be in the path of the warm
F
E
D
B
air, or where the warm air and/or noise will
disturb neighbors.
B
D
Table 28: Single Zone High Efciency Standard Wall Mount 9,000, 12,000, 18,000 Outdoor Unit Service Access and Allowable Clearances Diagram
Legend.
Unit: InchABCDEFG
Case 1
Case 2
Case 3
Case 4
Case 5
Standard
Minimum
Standard
Minimum
Standard
Minimum
Standard
Minimum
Standard
Minimum
1224-12---
410-4--40
--20----
--14---40
--2012---
--144---
---1224--
---4879-
-24-12---
-10-4---
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Single Zone High Efficiency Standard Wall Mount outdoor units are engineered to be mounted outdoors and include technology designed to
minimize the negative effects of winter weather’s freezing rain, sleet, and snow. Some building projects, however, necessitate placing the
HVAC outdoor units indoors:
• Lack of ground space.
• Lack of an appropriate outdoor location that meets system design requirements.
• When mounting on the roof is not an option due to a lack of roof space.
• Roof warranty will be voided if mechanical equipment is placed on the membrane.
• On retrofit projects, a former chiller / boiler / air handler equipment room, mechanical area, or penthouse already exists.
• To curtail the potential need for redundant zone heating devices such as wall-fin radiators or duct heaters.
• In extremely cold environments where there is a significant amount of run-time at temperatures well below freezing outside the outdoor unit
ambient air temperature range published in this engineering manual.
Benefits of Installing Outdoor Units Indoors
• Shelters the outdoor unit from direct exposure to prevailing winds that decrease the heating capability of the outdoor unit.
• Protects equipment from freezing precipitation and / or potential ice build-up that could hinder unit operation.
• Maintains coil heat transfer efficiency by reducing the number of and shortening the cycle time for defrost operation.
• Easier maintenance and servicing during inclement weather.
• When mounted in a fully enclosed space, limiting the ambient air temperature may allow the Single Zone High Efficiency Standard Wall
Mount system designer to eliminate oversizing.
• The outdoor unit to compensate for loss of capacity at low ambient temperatures.
• May also curtail the need to provide inefficient redundant zone heating devices such as wall-fin radiators and second-stage ancillary heat-
ing devices.
Design Considerations Include:
• Enclosure types and elements such as louvers (see next page), rain hoods, dampers and controls, heating methods and sizing of heating
devices.
• Heating strategies.
• Duct design.
• Condensate handling.
General Guidelines
• Follow ASHRAE 62.1 design guidelines.
• Depending on the project / application, a roof over the outdoor units in combination with a wind break may be all that is necessary.
• Consider the potential for snow accumulation near louvers / roof openings. Outside air intakes and discharge ducts/louvers must be engi-
neered to clear anticipated snow accumulation levels by at least one (1) foot.
• In situations where operation is anticipated at temperatures lower than the product’s minimum operating temperature, ancillary heat must
be provided to heat the outdoor unit coils to ensure continuous compressor operation and heating.
It may be necessary to use a field-fabricated air guide to prevent discharge air from short-cycling back to the coil inlet.
Single Zone High Efciency Standard Wall Mount Engineering Manual
• Consider the direction of prevailing winds and opening placement. If possible, locate inlet openings upwind of discharge openings and other
exhaust outlets.
• When inlet and outlet openings are placed on the same wall, minimum distance between the two openings must be approximately three (3)
feet (minimum distance varies significantly with variations in outlet opening face velocity).
• If roof-mounted ventilation openings are used, strategically locate the inlet ventilation opening(s) upwind of the outlet opening(s).
• Discharge and supply ductwork must be designed to avoid weather related long periods of water entrainment and the potential for microbial
growth.
52 | APPLICATION
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
Provide a means to drain the condensate generated during heating mode and defrost cycle in addition to rainwater that infiltrates the inlet
louver enclosed area.
• Install a field-provided drain pan under the outdoor units and provide a path to a nearby floor drain.
• If the ambient air temperature is expected to drop below 32°F in the enclosure, heat the bottom surface of the pan, drain line, and floor
drain so that the condensate does not freeze before reaching the drain.
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost will not accumulate and freeze on sidewalks or driveways which may create unsafe conditions.
Allow for ventilation intake and exhaust air based on maximum outdoor unit fan capacity.
• Select the size, type and orientation of architectural louvers with adequate “net free area” face velocity to ensure the total external static
pressure from the outdoor unit fan does not exceed design limitations (see specification data tables).
• No obstructions must be placed in front of the louver that could hamper the free flow (throw) of air.
• Roof top openings and / or discharge and supply louvers must be equipped with screens to prevent bird and insect infiltration.
For louver recommendations, see below and on the next page.
Application Guidelines
As always, the best solution for each project balances acceptable heating performance (considering local weather conditions), capital costs,
life cycle energy consumption, and limitations set forth by local building codes.
Louver Recommendations for Outdoor Unit Enclosure
1. Outdoor Unit Enclosure: Manual Door Open Type.
2. Louver Angle: No More Than 15° Horizontally.
3. Space Between Louvers: More than 4 inches (Recommend).
4. Louver Shape: Wing or Plane Type.
• Open Rate and Inlet must be taken into consideration when design-
ing the louvered outdoor unit enclosure.
• Do not use “S” type louvers.
If the Louver Open Rate is Too Small
1. Noise can occur because of the increased air velocity passing
through the louver blade.
2. Noise can occur from louver blade vibrations.
3. A drop in outdoor unit fan performance (excess static pressure
can cause a drop in outdoor unit performance and heat exchanger
efficiency).
4. If the louver open rate is too small or there is insufficient air flow
exchange, the air conditioner might stop operating.
Figure 29: Louver Recommendations.
Figure 30: Using “S” Type Louvers.
Air flow passing through
the louver blade backwards
can generate noise.
Outside
Inside
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Engl ewood Cliffs , NJ. All rights re served. “LG” is a registe red trademark of LG Corp.
A single-zone system consists of one outdoor unit and one indoor
unit. One of the most critical elements of a single-zone system is
the refrigerant piping. If the connection piping is not within allowable
limits, there will be reliability, performance, noise, and vibration
issues. Table 29 below lists pipe length limits that must be followed
in the design of a Single Zone High Efficiency Wall Mount refrigerant
pipe system, and Table 30 includes additional refrigerant charge
necessary for longer piping lengths. Refer to the figure for maximum
length and elevation of piping.
Table 29: Single Zone High Efciency Refrigerant Piping System Limitations.
LS090HSV5
Model Numbers
Pipe Sizes
Pipe Length
(ELF = Equivalent Length of
pipe in Feet)
Elevation
(All Elevation Limitations are
Measured in Actual Feet)
Additional Refrigerant Needed (oz/ft)
Vapor
Liquid
Standard Piping Length
Piping Length with No
Additional Refrigerant
Longest total equivalent
piping length
Shortest total equivalent
piping length
Distance between fittings
and indoor units or outdoor
units
If outdoor unit is above
indoor unit
If outdoor unit is below
indoor unit
(LSN090HSV5/
LSU090HSV5)
Ø3/8Ø3/8Ø5/8
Ø1/4Ø1/4Ø3/8
24.624.624.6
414124.6
8282114.8
9.89.89.8
≥20 inches≥20 inches≥20 inches
49.249.249.2
49.249.249.2
0.220.220.38
Figure 33: Single Zone High Efciency Wall Mount System Layout.
LS120HSV5
(LSN120HSV5/
LSU120HSV5)
LS180HSV5
(LSN180HSV5/
LSU180HSV5)
Application Guidelines
Table 30: Single Zone High Efciency Refrigerant Piping System Additional Refrigerant Charge.
(LSN090HSV5 / LSU090HSV5)
(LSN120HSV5 / LSU120HSV5)
(LSN180HSV5 / LSU180HSV5)
• Capacity is based on standard length.
• Equivalent Pipe Length = Actual Pipe Length + Number of Bends x 0.3.