1. Specification
Nominal Capacity Cooling kW (Min~Rating~Max) Btu/h
Heating kW
Btu/h Nominal Input Cooling kW (Min~Rating~Max) Heating kW Testing Combination
Running Current(Rating) Cooling A
Heating A Starting Current Cooling/Heating A Power Supply Ø / V / Hz Power Supply Cable(Outdoor) No. x mm
2
Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD) No. x mm
2
Power and Transmission Cable(BD to Indoor) No. x mm
2
Dimensions W x H x D mm(inch) Net Weight kg(lbs) Max. Number of Connectable Indoor Units Compressor (#1) Type
Qty x Model
Motor type
Oil charge volume cc
Oil Type Compressor (#2) Type
Qty x Model
Motor type
Oil charge volume cc
Oil type Compressor (#3) Type
Qty x Model
Motor type
Oil charge volume cc
Oil type Refrigerant Cycle A Charge (at 7,5m) g(oz)
Cycle B Charge (at 7,5m) g(oz)
Type
Control Additional Refrigerant Charge g/m(oz/ft) Heat Exchanger (Rows x Column x FPI) No.
Defrosting Method Fan Capacitor μF/Vac
Drive
Discharge Direction(Side/Top)
Air Flow RateNo. of Fan CMM(cfm) Sound Level(H/L) Sound Pressure dB(A)+3 Piping Connections Liquid(Cycle A) mm(inch)
Gas(Cycle A) mm(inch)
Liquid(Cycle B) mm(inch)
Gas(Cycle B) mm(inch)
High Pressure Gas mm(inch) Max. Interunit Total Piping m Piping Length Main Piping m
Total Branch Piping m
Each Branch Piping m Max. Elevation Outdoor Unit~Indoor Unit m Difference Indoor Unit~Indoor Unit m Operation Range Cooling °C(°F) (Outdoor) Heating °C(°F)
3.52~28.72
12,000~98,000
-
-
2.5~9.75
­Cycle 1 : LMNC122D4A0 + LMNC36GTNA0 Cycle 2 : LMNC24GTPA0 + LMNC242D5A0
8.5~30.5
-
-
3/220/60 4 x 13.3 (Including Earth) 4 x 0.75 (Including Earth) 4 x 0.75 (Including Earth)
1,280 x 1,520 x 730 (50.4 x 59.8 x 28.7)
260 (551)
8
Rotary
2 x QP348RAA
Single Phase Induction Motor
1,130
NM56 or SUNISO 4GSI
Rotary
2 x QP348RAA
Single Phase Induction Motor
1,130
NM56 or SUNISO 4GSI
-
-
-
-
­4,300 (151.9) 4,300 (151.9)
R22
EEV / Short tube
Ø12.7 : 20(0.2) / Ø15.88 : 30(0.3) / Ø19.05 : 50(0.5)
(2R x 14C x 17) x 2 + (1R x 28C x 17) x 2
Reversing Cycle
10/370
Direct Drive
Top
53x2 (3,179)
60/60
9.52(3/8)
19.05(3/4)
9.52(3/8)
19.05(3/4)
-
110
50 60 15 45 10
21 (69.8) ~ 54 (129.2)
-
L8UC100BFA3/ L8UC100BFE3
Outdoor Unit
Note :
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80,6°F) DB/19°C(66,2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75,2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44,6°F) DB/6°C(42,8°F) WB
Piping Length - Interconnecting Piping Length 7,5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula kW = Btu/h × 0.0002931 cfm = CMM × 35.3
2. List of Functions
- 3 -
Copyright ©2014 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Defrost / deicing High pressure switch Low pressure switch Phase reverse Phase failure protection Restart delay (3-minutes) Self diagnosis Soft start Test function Auto operation(Artificial intelligence) Auto restart operation Central control(LGAP) PDI(Power Distribution Indicator) PI485 Low Ambient Kit Thermistor
X X X O O O O X O O O O
PQNUD1S00
PMNFP14A0 / PMNFP14A1
X
-
FunctionCategory
L8UC100BFA3 L8UC100BFE3
Reliability
Convenience
Special Function Kit Others
CAC Network Function
O : Applied X : Not applied - : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied
with separate package
H : These safety switcher are standard or optional features defending on region & country.