LG L1006R, LWHD1006RY6, L1006RY6, LWHD1006R, HBLG1003R Service Manual

...
Page 1
LG
Room
Air Conditioner
SERVICE MANUAL
LG
CAUTION
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
MODEL: HBLG8003R,LB8000ER,LW8000ER,HBLG1003R,LWHD1006R,L1006R
LWHD1006RY6,L1006RY6
Page 2
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions..........................................................................................................................................3
Dimensions .....................................................................................................................................................5
Outside Dimensions...................................................................................................................................5
Product Specifications ..................................................................................................................................6
Installation .......................................................................................................................................................7
Select the Best Location ............................................................................................................................7
Installation Check.......................................................................................................................................7
How to Secure the Drain Pipe....................................................................................................................7
How to Install..............................................................................................................................................8
Operation ......................................................................................................................................................12
Function of Controls .................................................................................................................................12
Disassembly ..................................................................................................................................................14
Mechanical Parts......................................................................................................................................14
Air handling
Parts.....................................................................................................................................15
Elect
rical Parts .........................................................................................................................................16
Ref
rigerating Cycle...................................................................................................................................18
S
chematic Diagram.......................................................................................................................................21
Wi
ring Diagram.........................................................................................................................................21
Electronic Control D
evice.........................................................................................................................22
Components Location ..............................................................................................................................23
Trou
bleshooting Guide.................................................................................................................................24
Pipeing System ................................................................................................................
........................24
Trou
bleshooting Guide .............................................................................................................................25
Exploded Vi
ew ..............................................................................................................................................37
Replacement
Parts List ................................................................................................................................38
Electrical Parts Troubleshooting Guide......................................................................................................27
Electrical Parts ........................................................................................................................................31
Page 3
Safety Precautions
Safety Precautions
To prevent injury and property damage, follow these instructions. Incorrect operation due to ignoring instructions might cause harm or damage, the seriousness of which is indicated by the following symbols.
Precautions
WARNING CAUTION
This symbol shows the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
Never Do This
Always Do This
The following items are classified by these symbols.
WARNING
WARNING
Plug in the power plug properly.
• Doing so may cause electric shock or fire due to heat generation.
Do not modify power cord length or share the outlet with other appliances.
• Doing so may cause electric shock or fire due to heat generation.
Do not allow water to run into electric parts.
• Doing so may cause failure of machine or electric shock.
Do not use the socket if it is loose or damaged.
Do not operate or stop the unit by inserting or pulling out the power plug.
• Doing so may cause electric shock or fire due to heat generation.
Do not operate with wet hands or in damp environment.
• Doing so may cause electric shock.
Always install air leakage breaker and a dedicated switching board.
• Failure to install these may cause fire or electric shock accident.
Do not open the entrance during operation.
Do not damage or use an unspecified power cord.
• Doing so may cause electric shock or fire.
If the supply cord is damaged, it must be replaced by the manufacturer, the manufacturer's service agent, or a similarly qualified person in order to avoid a hazard. (Y attachment)
Always plug into a grounded outlet.
• No grounding may cause electric shock (See Installation Manual).
Unplug the unit if strange sounds, odors, or smoke comes from it.
• Such a unit may pose a risk of
fire or electric shock accident.
Keep firearms away.
• Doing so may cause fire or electric shock.
Do not use the power cord close to heating tools.
• Doing so may cause fire or electric shock. • Doing so may lead to an explosion or fire.
• It may cause electric shock.
Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc.
Service Manual 3
Page 4
Safety Precautions
WARNING
WARNING
Ventilate before operating air conditioner when gas goes out.
• Operating the air conditioner in the presence of gas vapors can lead to explosions and fire.
Never touch the metal parts of the unit when removing the filter.
• They are sharp and may cause injury.
When cleaning the unit, first make sure the cord is unplugged.
Since the fan rotates at high speed during operation, it may cause injury if activated while cleaning.
is off and the
Do not clean the air conditioner with water.
• Water may enter the unit and degrade the insulation. It also may cause an electric shock.
Do not put a pet or house plant where it will be exposed to direct air flow.
• This could injure the pet or plant. • It may cause damage of animals
• Doing so may cause failure or electric shock.
CAUTION
CAUTION
Do not disassemble or modify products randomly.
Operate only in a well ventilated area when using in the presence of a stove, etc.
• An oxygen shortage may otherwise occur.
Do not use appliance for special purpose such as climate control for animals or vegetables, precision machine, or conservation of art
or vegetables or loss of property.
articles.
Stop operation in storm or hurricanes.
• Operation with windows opened may cause wetting of indoor and soaking of household furniture.
Do not place obstacles around the absorption inlet or output.
• Doing so may cause failure of appliance or accident.
Do not use abrasives or strong detergent such as wax or thinner. Always use a soft cloth.
• Otherwise, the products appearance may
be damaged due to change of product color or scratching of its surface.
If water enters the product, turn off the the power switch of the main body of appliance. Contact service center after taking the power­plug out from the socket.
Hold the plug by the head when taking it out.
• Improper handling may cause electric shock or damage.
Ensure that an installation console of the outdoor appliance is not damaged due to extened use.
• If the previous air conditioner damaged the console, there is a risk of the new unit falling.
Do not place heavy object on the power cord and take care so that the cord is not pinched.
• Treating the power cord carelessly poses a danger of fire or electric shock.
Turn off the main power switch when not using it for a long time.
• Doing so can prolong the life of the product.
Always insert filters securely. Clean them every two weeks.
• Operation without filters will cause failure.
Do not drink water drained from air conditioner.
• It contains contaminants that would make you sick.
Do not direct airflow at room occupants only.
4 Room Air Conditioner
• This could damage your health.
Page 5
Dimensions
Dimensions
Outside Dimensions
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
490(19 / )
3
8"
29(1 / )
18( / )
unit: mm(inch)
31
126.5(4 / )
5
32"
23
32"
32"
510
20
3
32
DEFROST
HEAT
COOL
FAN
DRY
FAN
ENERGY SAVER
AIR
INDOOR DESIRED
PURYFIER
AUTO
RESTART
354(13 / ")
29
32
Service Manual 5
Page 6
6 Room Air Conditioner
Specfications
Product SpecificationsPrProduct Specificationsoduct SpecificationsProduct Specifications
MODELS
ITEMS
POWER SUPPLY
COOLING CAPACITY (Btu/h)
INPUT (W)
RUNNING CURRENT (A)
E.E.R (BTU/W.h)
OPERATING
CONDITION
REFRIGERANT (R-22) CHARGE
EVAPORATOR
CONDENSER
FAN, INDOOR
FAN, OUTDOOR
FAN SPEEDS, FAN/COOLING
FAN MOTOR
OPERATION CONTROL
INDOOR (°C)
OUTDOOR (°C)
HBLG8003R
8,000
820
7.4
9.8
300g(10.6oz)
2 ROW 11STACKS
LB8000ER
26.7(DB)* 19.4(WB)**
35(DB)* 23.9(WB)**
2 ROW 16STACKS
PROPELLER TYPE FAN WITH SLINGER RING
REMOTE CONTROLLER
LW8000ER
1ø, 115, 60Hz
8,200 10, 000
750 1 ,020
7.0 9.2
10 . .8
9
400g(14.1oz) 420
3 ROW 11STACKS
TURBO FAN
3/3
6 POLES
HBLG1003R LWHD1006R(Y6) L1006R(Y6)
9
g(14.6oz)
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
PROTECTOR
POWER CORD
DRAIN SYSTEM
NET WEIGHT (lbs/kg)
OUTSIDE DIMENSION (inch)
(W x H x D) (mm)
* DB:Dry Bulb **
WB:Wet Bulb
COMPRESSOR
FAN MOTOR
THERMISTOR
VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
SLIDE IN-OUT CHASSIS
OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
(3 WIRE WITH GROUDING)
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN PIPE OR SPLASHED BY FAN SLINGER
62/28
203/32x 137/8x 193/
510 x 35 3 x 490
8
71 /32
Page 7
Figure 2
Figure 3
Figure 1
Installation
Installation
Select the Best Location
1.To prevent vibration and noise, make sure the unit is installed securely and firmly.
2.Install the unit where the sunlight does not shine directly on the unit.
3.The outside of the cabinet must extend outward for at least 12" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.
4.Install the unit a little slanted so the back is slightly lower than the front (about1/2"). This will help force con-densed water to the outside.
5.Install the unit from the bottom about 30"~60" above the floor level.
The setting conditions must be checked prior to initial starting.
The undermentioned items are especially important checking points when the installation is finished.
1. Grounding wire (Green or Green and Yellow) is
provided in the power cord. The green wire must be grounded.
2. Connect to a single-outlet 15A circuit.
(or 20A circuit for Electric Heater Model)
3. To avoid vibration or noise, make sure the air
conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the
air inlet and outlet.
The air conditioner must be installed horizontally or tilted slightly to the outside for proper water drainage.
On exceptionally hot and humid days the air conditioner may overflow condensed water.
If the air conditioner is used in hot and a high humidity zone, exchange the HOLE RUBBER for the DRAIN PIPE.(See figure 2, figure 3.)
Installation CheckInstallation Check
CAUTION: All side louvers of the cabinet must
remain exposed on the outdside of the structure.
COOLED AIR
30"~60"
AWNING
RADIATION
ABOUT 1/2"
FENCE
HEAT
Over 20"
How to Secure the Drain Pipe
BASE PAN
BASE PAN
1
HOLE RUBBER
2
HOLE RUBBER
BOTTOM
BOTTOM
Service ManSerSer ual vice Manvice Man 7ual ual Ser 77vice Manual 7
Page 8
1. WHEN USING GASKET
2. WHEN USING INSTALLATION KITS
A. WINDOW REQUIREMENTS
This unit is designed for installation in standard double hung windows with actual opening widths from 25" to 36". The top and bottom window sash must open sufficiently to allow a clear vertical opening of 16" from the bottom of the upper sash to the window stool.
DEFROST
HEATCOOL
INDOORDESIRED
ENERGY SAVER AIR PURYFIER AUTO RESTART
FAN
FAN
DRY
DEFROST
HEATCOOL
INDOORDESIRED
ENERGY SAVER AIR PURYFIER AUTO RESTART
FAN
FAN
DRY
A
B
D
E
F
C
HJ
2
3
4
2
1
G
A
RIGHT SIDE
HORIZONTAL LINE
B
1. WINDOW (WIDTH-A, HEIGHT-B)
2. GASKET
3. WALL
4. DETAILS 5.1 x 30 ROUND HEAD WOOD SCREWS
ABCDE F HJK
535mm 366mm 250mm 30mm 0~25mm OVER 420mm 32 5~10mm 0~5mm
(211/2") (147/16") (10") (11/16") (0~1") (OVER 1617/32") (11/4") (3/16"~3/8") (0~3/16")
1
2 3 4
8 9
11
765
10
13
12
NO. NAME OF PARTS Q'TY
1 FRAME CURTAIN 2 2 SILL SUPPORT 2 3 BOLT 2 4 NUT 2 5 SCREW(TYPE A) 16 6 SCREW(TYPE B) 3 7 SCREW(TYPE C) 5 8 FOAM-STRIP 1
9 FOAM-PE 1 10 UPPER GUIDE 1 11 FOAM-PE 1 12 FRAME GUIDE 2 13
WINDOW LOCKING BRACKET
1
B. INSTALLATION KITS CONTENTS
25" to 36"
15" min
Stool
Interior wall
20
3
/32" min
(Without frame curtain)
Offset
1
/2" to 11/4"
Sill
Exterior
Installation
How to Install
8 Room Air Conditioner
Page 9
BEFORE INSTALLATION
1. Remove the screws which fasten the cabinet at both sides and at the back.
2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
3. Cut the window sash seal to the proper length. Peel off the backing and attach the Foam-Pe to the underside of the window sash.
4. Remove the backing from the top upper guide Foam PE
and attach it to the bottom of the Upper
Guide
.
5. Attach the upper guide onto the top of the cabinet with 3 type A screws.
6. Insert the Frame Guides into the bottom of the cabinet.
7. Insert the Frame Curtain into the upper guide and Frame Guides .
8. Fasten the curtains to the unit with 4 Type A screws at the both sides.
NOW START INSTALLATION
1. Open the window. Mark a line on center of the window stool (or desired air conditioner location). Carefully place the cabinet on the window stool and align the center mark on the front angle with the center line marked in the window stool.
2. Pull the bottom window sash down behind the upper guide until it meets.
Shipping Screws
C O O
L
I N D
O O R
D
E S I R E D
E
N E R
G Y
S A V E
R A I R
P U
R Y F
IE
R
A U T
O
R
E S T A
R
T
F A
N
F A
N
D
R Y
H E
A T DEFROST
9
10
13
(Type A)
(Type A)
5
5
11
11
9
5
C O O L
IN D OO
R
DESIRED
EN ERG
Y
SAVER AIR PURYFIER A UTO RE STA
RT
F A N
FAN
D R Y H
E A T
DEFRO
ST
EPS Material
Upper Guide
Window stool
Front Angle
Window Sash Upper guide
9
Frame Curtain
1
Foam-pe
10
Foam-pe
13
Cabinet
Figure 4
Figure 5
Service Manual 9
Installation
NOTICE
Do not pull the window sash down so tightly
that the movement of Frame Curtain is restricted.
Page 10
INDOOR OUTDOOR
Sill Support
Nut
Bolt
2
4
3
INDOOR OUTDOOR
12
7
5
Frame Guide
About 1/2"
Screw(Type A)
Cabinet
6
2
About 1/2"
Screw(Type B)5Screw(Type A)
Sill support
Type C
Sash track
Front Angle
Screw(Type B)
6
Sill support
2
3. Loosely assemble the sill support using the parts in
Figure
6.
4. Select the position that will place the sill support near the outer most point on sill (See
Figure
6)
5. Attach the sill support to the cabinet track hole in relation to the selected position using 2 Type A screws in each support (See
Figure 7).
6. The cabinet should be installed with a very slight
tilt (about
1
/2") downward toward the outside
(See Figure 8). Adjust the bolt and the nut of Sill Support for balancing the cabinet.
7. Attach the cabinet to the window stool by driving the screws (Type B: Length sixteen millimeters and below.) through the front angle into window stool (5/8").
8. Pull each Frame Curtain properly to each window sash track, and repeat step 2.
9. Attach each Frame Curtain to the window sash by using screws (Type C). (See Figure 9)
Figure 6
Figure 7
Figure 8
Figure 9
10 Room Air Conditioner
Installation
NOTICE
Be careful when you install the cabinet (frame
guides are broken so easily).
Page 11
DEFROST
HEATCOOL
INDOOR DESIRED
ENERGY SAVER AIR PURYFIER AUTO RESTART
FAN
FAN
DRY
Screw(Type A)
Screw(Type A)
Power cord
13
8
Foam-Strip
10. Slide the unit into the cabinet.(See Fig. 10)
11. Cut the Foam-Strip to the proper length and insert
between the upper and lower window sash. (See Fig. 11)
12. Attach the window Locking Bracket with a type C
screw. (See Fig. 12)
13. Attach the front grille to the cabinet by inserting the
tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place.(See Fig. 13)
14. Lift the inlet grille and secure it with a type A screw
through the front grille.(See Fig. 14)
Figure 10
Figure 11
Figure 12
Figure 15
Figure 14
Figure 13
Service Manual 11
Installation
CAUTION: For security purpose, reinstall screws (Type A) at cabinet's sides.
Page 12
The controls look like this:
Controls
Remote Control Operations
CAUTION: The Remote Controller will not function properly if strong light strikes
the sensor window of the air conditioner or if there are obstacles between the
Remote Controller and the air conditioner.
12 Room Air Conditioner
Installation
• Designed for COOLING ONLY.
• Powerful and quiet cooling.
• Slide-in and slide-out chassis for the simple installation and service.
• Low air-intake, top cooled-air discharge.
• Built-in adjustable Thermistor
• Washable one-touch filter
• Compact size
• Reliable and efficient rotary compressor is equipped.
Powe r
Temp
Fan Speed
Timer Mode
1
2
3
4
5
'
F
TIMER POWERMODE
TEMP
FAN
SPEED
F1 LOW F2 MED F3 HIGH
Dry Timer
Fan
Energy
Saver
Cool
1
2
6
3 45
Operation
Page 13
Service Manual 13
Operation
How to Insert Batteries
1
POWER
Operation starts when this button is pressed and stops when you press the button again.
2
TEMPERATURE CONTROL
The thermostat monitors room temperature to maintain the desired temperature. The thermostat can be set between 60°F~86°F (16°C~30°C). The unit takes an average of 30 minutes to adjust the room temperature by 1°F.
3
OPERATION MODE SELECTOR
Select cooling mode to cool the room. Select energy saver mode for energy saving operation. Select fan mode for basic ventilating fan operation. Select dry mode for dry operation.
4
FAN SPEED SELECTOR
For increased power while cooling, select a higher fan speed. 3 steps: High Low Med
5
ON/OFF TIMER
The timer can be set to start and stop the unit in hourly increments (up to 12 hours).
6
REMOTE CONTROL SENSOR
1
Push out the cover on the back of the remote control with your thumb
2
Pay attention to polarity and insert two new AAA 1.5V batteries.
3
Reattach the cover.
NOTICE
In order to prevent discharge, remove the batteries from the remote control if the air
conditioner is not going to be used for an extended period of time Keep the remote control away from extremely hot or humid places. To maintain optimal operation of the remote control, the remote sensor should not be exposed to direct sunlight.
:
Do not use rechargeable batteries. Make sure that both batteries are new.
Page 14
14 Room Air Conditioner
Disassembly
Disassembly
Mechanical Parts
— Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.
1. FRONT GRILLE
1. Open the lnlet grille downward and remove the air filter.
2. Remove the screw which fastens the front grille.(See Figure 16)
3. Pull the front grille from the right side.
4. Remove the front grille.(There are 4 hooks.)
5. Re-install the components by referring to the removal procedure, above.
2. CABINET
1. After disassembling the FRONT GRILLE, remove the 2 screws which fasten the cabinet at both sides.
2. Remove the 2 screws which fasten the cabinet at back.
3. Pull the base pan forward. (See Figure 17)
4. Remove the cabinet.
5. Re-install the components by referring to the removal procedure, above.
Figure 16
3. CONTROL BOX
1. Remove the front grille.
2. Remove the cabinet.
3. Remove the 2 screws which fasten the power cord.
4. Disconnect the grounding screw from the evaporator channel.
5. Remove the 1 screw which fasten the control box cover.
6. Remove the housing which connects PCB and motor wire in the control box.
7. Disconnect the housing which connects Plazma Air Purifier.(Optional)
8. Remove the screw at left cover of filter case and open the cover to remove inner screw. (Optional)
9. Remove the nut which fastens the terminal cover.
10. Remove the terminal cover.
11. Remove all the leads from the overload protector.
12. Discharge the capacitor by placing a 20,000 ohmresistor across the capacitor terminals.
13. Raise the control box upward completely. (See Figure 18)
14. Re-install the components by referring to the removal procedure, above. (Refer to the circuit diagram found on page 22 in this manual and on the control box.)
Figure 17
Figure 18
COOL
FAN
DRY
HEAT
FAN
D
IN
E F
D
R
O
O
O
S
R
T D E
S
E
IR
N
E
E
D
R
S
G
A
Y
V E
R
A P
IR U R
Y
F
IE A
R
U R
T E
O S
T
A
R T
Page 15
Service Manual 15
Disassembly
Air Handling Parts
4. AIR GUIDE AND TURBO FAN
1. Remove the front grille.
2. Remove the cabinet.
3. Remove the control box.
4. Remove the 4 screws which fasten the brace.
5. Remove the brace.
6. Remove the 2 screws which fasten the air guide upper.
7. Remove the air guide upper.(See figure 19)
8. Remove the 2 screws which fasten the evaporator.
9. Move the evaporator forward and pulling it upward slightly. (See Figure 20)
10. Pull out the hook of orifice by pushing the tabs
and remove it. (See Figure 21)
11. Remove the clamp with a hand plier which
secures the turbo fan.
12. Remove the turbo fan.
13. Remove the 2 screws which fasten the air guide
from the base pan.
14. Move the air guide backward, and pull out from
the base pan.(Move the air giude lower carefully.)
15. Re-install the components by referring to the
removal procedure, above.
5. FAN
1. Remove the cabinet.
2. Remove the brace.
3. Remove the 5 screws which fasten the condenser.
4. Move the condenser to the left carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan. (See Figure 22)
7. Re-install by referring to the removal procedure.
Figure 19
Figure 20
Figure 21
Figure 22
Page 16
16 Room Air Conditioner
Disassembly
6. SHROUD
1. Remove the fan.
2. Remove the shroud. (See Figure 23)
3. Re-install the components by referring to the removal procedure, above.
1. OVERLOAD PROTECTOR
1. Remove the cabinet.
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover. (See Figure 24)
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the removal procedure, above.
2. COMPRESSOR
1. Remove the cabinet.
2. Discharge the refrigerant system using a Freon
TM
Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
3. Remove the overload protector.
4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
5. Remove the 3 nuts and the 3 washers which fasten the compressor.
6. Remove the compressor. (See Figure 25)
7. Re-install the components by referring to the removal procedure, above.
Figure 23
Figure 24
Figure 25
Electrical Parts
Page 17
Service Manual 17
Disassembly
3. CAPACITOR
1. Remove the control box.
2. Open the top cover from the control box. (See Figure 26)
3. Pull out the capacitor from the control box.
4. Disconnect all the leads of capacitor terminals.
5. Re-install the components by referring to the removal procedure, above.
4. POWER CORD
1. Remove the control box.
2. Open the top cover from the control box.
3. Disconnect the front panel from the control box. (See Figure 27)
4. Disconnect two leads from the capacitor and relay.
5. Pull out the power cord.
6. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.)
7. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord attached at the unit.)
DEFROST
HEAT
C O
O L
IN
D O
O R
D E
S IR
E D
E N
E R G
Y
S A
V E R A IR
P U R
Y F IE
R
A
U T O
R E S
T A R
T
F A
N
FAN
D R
Y
H E
A T
D E F
R O S
T
Figure 27
Figure 26
Page 18
Disassembly
5. MOTOR
1. Remove the cabinet.
2. Remove the turbo fan.
3. Remove the fan.
4. Remove the 4 screws which fasten the motor from the air guide. (See Figure 28)
5. Remove the motor.
6. Re-install the components by referring to the removal procedure, above.(See Figure 28)
1. CONDENSER
1. Remove the cabinet.
2. Remove the 5 screws which fasten the brace.
3. Remove the 5 screws which fasten the condenser and shroud.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the condenser.
6. Re-install the components by referring to notes. (See Figure 29)
2. EVAPORATOR
1. Remove the control box.
2. Remove the air guide upper.
3. Remove the 2 screws which fasten the evaporator.
4. Move the evaporator sideways carefully.
5. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.
6. Remove the evaporator.
7. Re-install the components by referring to notes. (See Figure 30)
Figure 28
Figure 29
Figure 30
Refrigerating Cycle
CAUTION: Discharge the refrigerant system using a Freon
to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
TM
Recovery System. If there is no valve
18 Room Air Conditioner
Page 19
3. CAPILLARY TUBE
CAUTION: If high vacuum equip­ment is used, just crack valves A
and B for a few minutes, then open slowly with the two full turns counter­clockwise. This will keep oil from foaming and being drawn into the vacuum pump.
1. Remove the cabinet.
2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.(See caution above)
NOTES
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a Freon recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
31A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure 31B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
TM
Disassembly
3. Remove the capillary tube.
4. Re-install the components by referring to notes.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2) Connect the charging cylinder as shown in figure 31B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
Service Manual 19
Page 20
Disassembly
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable
of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
Figure 31A-Pulling Vacuum
Figure 31B-Charging
A
B
EXTERNAL VACUUM PUMP
A
CHARGING CYLINDER
LOW
HI
B
C
20 Room Air Conditioner
Page 21
Service Manual 21
Schematic Diagram
Schematic Diagram
33
22
11
HVB
5V
b
c
R04P
X
O
O
X
5V
R04P
8
EEPROMModel
1
EEPROM
A0
5V
S7136
IC01A
3.6V
2
1
R01A
20K
3
+
10V
1uF
C02A
CAT93C46
Vcc
Auto Restart
Non Auto Restart
20K
R03P
20K
576
R02P
Q03G
1K
R04P
A101S
Q01G
A101S
Q02G
SW03G
D03G
SW06G
D06G
TEMP UP
D02G
D05G
SW02G
MODE
SW05G
TEMP DOWN ON/OFF
D01G
D04G
FAN
SW01G
TIMER
SW04G
A101S
423
A2
GND
A1
10K
R06P
R05P
10K
Rx
SDA
SCL
Digit4 (Scan4)
0.001
C01F
R01F
10K
C02F
0.001
R03F
10K
Digit1 (Scan1)
SEG-c
SEG-a
SEG-b
Digit0 (Scan0)
Digit2 (Scan2)
Digit3 (Scan3)
SCL
SDA
WP
0.01
C01A
50V
1M
R01B
OSC01B
RT8.00MG
1%
12.1K
R02H
6.2K
1%
R04H
5V
2
1
CN-TH1
SMAW200-02
2
112
5V
12
TEST
14 13
8
9
10
11
1619 18
VSS
VAref
17 15
Osc in
Osc out
/Reset
21 2022
242526
23
5V
4WAY
SYNC
LOW
COMP
Pipe TH
Option1
Option2
Room TH
567
123
4
MICOM
TMP87CH47U
SEG-d
44
SEG-e
SEG-f
4342
VDD
40
SEG-g
3837
KEY0
39
SLIDE SW
41
27282931323330
ION
MED
HI
Receiver
LED out3
Buzzer
363534
LED out0
LED out1
LED out2
KEY1
HVB
R22H
1%
12.1K
R21H
12.1K
1%
OR2H
745
6
987
OR1H
131211
10
5V
1
2
9
8
IC01M
1K
R02E
20
GND
Vout
RECEIVER
Vcc
R01L
5
4
12V
+
5V
10V
220
C02L
ULN2004A
161514
3
6
680pF
C01L
R01P
20K
50V
3
Digit0
510
a
f
a
b
Digit1
a
3
9
b8c
d
f
d
e
d
c
7
e4f1g
e
6
g g
COOL
DEFROST
DRY/HEAT
TIMER
FAN
E/SAVER
R02G
R03G
R04G
R01G
680
680
680
680
R05G
R06G
R07G
12V
680
680
680
IC01G
151413
432
161
121110
765
98
ULN2004A
10K
5V
5V
R12F
R01E
1K
5V
C06D
BZ01E
PKM13EPY
-4002
+
C05D
50V
10V
220
0.01
10
12V
11
12
CN-AC/DC
51581-12(YEONHO)
52044-1245(MOLEX)
C05D
5V
12V
I
C04D
O
7805
IC02D
25V
25V
0.01
0.01
ANGLE
11
12
Rx
Tx
1K
Q03T
C104M
5V
5V
Q02T
A104M
Q01T
C104M
Q04T
A104M
C03T
0.001
R01T
25V
C02T
0.001
D01T
1N4148
C01T
0.1
50V
5V
(RD)
CN-TELE
CN-TH2
SMW200-03
SMW250-02
465
J7
RY-COMP
RY-4WAY
RY-LOW
9
8
CN-TH2
X
O
X
O
J07
O
X
X
O
RY-4WAY
RY-MED
RY-HI
CN-4WAY
7
J5
2
2
PIPE-TH
2
2
1
1
3
3
1
1
2
2
SW2
CN-HVB
SMW200-03(BL)
CN-CONT
SMW200-03(YL)
Model
RY-4WAY
3
3
3
3
1
1
2
2
SW1
33
11
CN-4WAY
YW396-03AV(YL)
SMW200-03(WH)
CN-12V
12V
Cool Only
Heat Pump
1
1
10
S/V-
4WAY
35V2
1
12V
CN-AC/DC
51580-12
52045-1245
+
I
7812
IC01D
C03D
C01D
D04D
+
O
C02D
16V
35V
50V
1000
1000
0.1
4
7
D02D
D03D
2
1
POWER TRANS
1N4004
D02D~D05D
D05D
STRAIGHT
RY-HI
RY-MED
RY-LOW
R01J
C01J
0.1/275V
1
3
1
3
579
579
33
11
CN-PWR
CN-MOTOR
YW396-09AV
YW396-03AV
SVC271D-14A
ZNR01J
SVC271D-14A
RY-COMP
G4A-1A-E-LG
FUSE
250VT3.15A
120 1/2W
CAPACITOR
C
MAIN POWER
MOTOR
FAN
COMP
FAN
HERM
ROOM-TH
88 SEGMENT
Electronic Control Device
Page 22
22 Room Air Conditioner
Schematic Diagram
Wiring Diagram
MOTOR ASSY
CAPACITOR
COMPRESSOR
OVERLOAD PROTECTOR
DC PCB ASSEMBLY
AC PCB ASSEMBLY
THERMISTOR
PLASMA FILTER ASSY
1
2
3
4
5
6
7
8
1
1
1
1
1
1
1
1
S
S
S
S
S
S
S
S
LOCATION
NO.
DESCRIPTION
REMARKS
Q'TY
PER SET
MOTOR
COMP.
CAPACITOR
DC PCB
ASSEMBLY
THERMISTOR
AIR FILTER ASSEMBLY
AC PCB
ASSEMBLY
WIRING DIAGRAM
SWITCH
H.V.
ASSEMBLY
BK
CN-MOTOR
CN-PWR
DC12V
ZNR01J
CN-12V
CN-HVB
RY-COMP
3
4
FUSE
250V/T2A
RY-LOW
RY-MED
RY-HI
CN-AC/DC
POWER
TRANS
CN-AC/DC
CN-TH1
BL RD
RDBK
BL
R
S
C
OLP
YL OR
YL
F
C
H
WH
(BL)
(
Ribbed
)
BK(BR
)
(
Plain
)
GN/YL
(GN)
GN/YL
(GN)
BK
RD
OR(BR
)
1
5
7
6
8
4
2
3
S: Service Parts N: Non Service Parts
Page 23
Service Manual 23
Schematic Diagram
Components Location
1. MAIN P.C.B ASSEMBLY
2. DISPLAY P.C.B. ASSEMBLY
R01T
Q01T
CN-CONCN-12V
CN-AC/DC
J1
J5
D02D
D03D
CN-HVB
HEAT SINK
D04D
C03T
D05D
IC01D
C01D
Q02T
J4
Q03T
C02D
J6
D01T
C02T
QIC02DT
J2
C04D
CN-TELE
Q04T
J3
C05D
J7
RY-HI
RY-MEDRY-LOWRY-4WAY
CN-TH2
CN-PWR
ZNR01J
R01J
PCB:6870A90068D
E03J
E02JJ8E01J
CN-MOTOR
CN-4WAY
C01J
RY-COMP
ASSEMBLY:6871A20417C
POWER
TRANS FUSE 250V/T3.15A
PCB:6870A90067C ASSEMBLY:6871A20418A
E04J
E05J
Page 24
Troubleshooting Guide
Troubleshooting Guide
Piping System
Figure 32 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LINE COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR
LIQUID REFRIGERANT
LOW PRESSURE VAPOR
ROOM AIR CONITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 32
24 Room Air Conditioner
CONDENSER COIL
FAN
CAPILLARY TUBE
MOTOR
COMPRESSOR
TURBO FAN
EVAPORATOR COIL
Page 25
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling
Check outdoor coil (heat exchanger) & the fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air ;
44~50°F(7~10°C)
Check heat load increase.
Clean condenser.
Not on separate circuit.
Check inside gas pressure.
Adjusting of refrigerant charged.
Malfunction of compressor.
Replacement of compressor.
Check cold air circulation for smooth flow.
Dirty indoor coil (Heat exchanger)
Correct above trouble
Check clogging in refrigera­tion circuit.
Repair clogging in refrigera­tion circuit.
Obstruction at air outlet
Clogged of air filter.
Malfunction of fan
Service Manual 25
Page 26
Troubleshooting Guide
Fails to Start
Check circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat
Check of control switch.
Fan only fails to start.
Improper wiring.
Defect of fan motor capacitor.
Irregular motor resistance (
). Irregular motor insulation (
).
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor (locking of rotor, metal).
Improper thermostat setting.
Loose terminal connection.
Improper wiring.
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor (Motor damaged)
Drop of power voltage.
Capacitor check.
Replacement
Compressor only fails to start.
Defect of compressor capacitor.
Check of power source.
Check of control switch setting.
26 Room Air Conditioner
Page 27
Troubleshooting Guide
Check the Fuse.
Check the wiring diagram.
Is the
Trans input power AC 115V?
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
Is output Voltage of IC01D
DC 12V?
Is output Voltage of IC02D
DC 5V?
Is the voltage No.18 of Micom
DC 5V?
Replace AC PCB Ass'y.
Is the
connection between
AC and DC
OK?
Is the reset circuit good?
(The No.14 of
Micom is 5V.)
• Check the Fuse.
• Check the wiring diagram.
• Check the Main PCB pattern.
• Replace the Trans.
Replace
D02D~D05D.
• Replace IC01D.
• Replace IC02D.
Replace
IC01A, C02A.
• Connect connector exactly.
• Check the PCB pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
Possible Trouble 1 The unit does not operate.
Electrical Parts Troubleshooting Guide
Service Manual 27
Page 28
Troubleshooting Guide
Possible Trouble 2 The compressor does not operate.
Possible Trouble 3 The compressor always operate.
Is setting
Temp. set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
• Replace IC01M.
• Select the setting Temp. to lower Number.
• Wait 3 Minutes.
Does the Unit delay
for 3 minutes?
• Replace MAIN PCB Ass'y.
Is the voltage N0.9 of
IC01M DC 12V?
• Check the RY-COMP.
• Check the wiring Diagram.
NO
NO
NO
YES
YES
YES
YES
Is the wire connection of
RY-COMP OK?
• Check the RY-COMP.
• Connect LEAD Wire to RY-COMP again.
NO
YES
NO
28 Room Air Conditioner
Page 29
Troubleshooting Guide
Possible Trouble 4 FAN does not operate.
Possible Trouble 5
The function of Energy Saver does not operate.
• Replace IC01M.
• Replace IC01M.
Is the voltage NO.1 or 2 or 4
of IC01M DC 12V?
Is the voltage NO.16 or 15 or 13
of IC01M 0V?
• Check the RY-Hi or RY-Med or RY-Lo.
Check the wiring diagram.
NO
NO
YES
YES
NO
NO
YES
YES
Is the mode
key pushed once more from
cool mode?
Is the voltage No.3 of
CN-AC/DC of AC PCB
Ass'y DC 5V?
• Reference to OWNER'S MANUAL.
• Set the mode key to Energy Saver mode.
• Check the Energy Saver mode key.
• Check the pattern of AC & DC PCB.
Service Manual 29
Page 30
30 Room Air Conditioner
Troubleshooting Guide
Possible Trouble 6 Remote controller does not operate.
Possible Trouble 7 It displays abnormally on DC PCB Ass’y.
NO
NO
NO
NO
YES
YES
YES
Is IC01G good?
Is the connection of
CN-AC/DC
OK?
• Replace the DC PCB Ass'y.
• Replace IC01G.
• Replace IC03G (Q01G, Q02G, Q03G
for Delux Model).
• Connect connector to
CN-AC/DC
exactly.
Does the IC03G
(Q01G, Q02G, Q03G for Delux Model)
operate normally on DC
PCB Ass'y?
Check the PCB pattern.
Is the voltage of Battery
over 2.3V?
• Replace Receiver Ass'y.
Is the connection of
CN-AC/DC
OK?
Is the voltage No.10
of CN-AC/DC on DC PCB
Ass'y DC 5V?
• Replace the battery.
• Check the PCB pattern.
• Connect connector to CN-AC/DC
exactly.
NO
NO
NO
YES
YES
YES
Page 31
Check the Fuse.
Check the wiring diagram.
Is the
Trans input power AC 115V?
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
Is output Voltage of IC01D
DC 12V?
Is output Voltage of IC02D
DC 5V?
Is the voltage No.40 of Micom
DC 5V?
Replace AC PCB Ass'y.
Is the
connection between
AC and DC
OK?
Is the reset circuit OK?
(The No.14 of
Micom is 5V.)
• Check the Fuse.
• Check the wiring diagram.
• Check the AC PCB pattern.
• Replace the Trans.
Replace
D02D~D05D.
• Replace IC01D.
• Replace IC02D.
Replace
IC01A, C01A.
• Connect connector exactly.
• Check the PCB pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
Possible Trouble 1 The unit does not operate.
Electrical Parts
Troubleshooting Guide
Service Manual 31
Page 32
Possible Trouble 2 The compressor does not operate.
Possible Trouble 3 The compressor always operate.
Is desired
Temp. set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
• Replace IC01M.
• Select the desired Temp. to lower Number.
• Wait 3 Minutes.
Is the Unit for 3 minutes
delay?
• Replace AC PCB Ass'y.
Is the voltage N0.9 of
IC01M DC 12V?
• Check the RY-COMP.
• Check the wiring Diagram.
NO
NO
NO
YES
YES
YES
YES
Is the wire connection of
RY-COMP OK?
• Check the RY-COMP.
• Connect LEAD Wire to RY-COMP again.
NO
YES
NO
32 Room Air Conditioner
Troubleshooting Guide
Page 33
Possible Trouble 4 FAN does not operate.
Possible Trouble 5
Remote controller does not operate.
• Replace IC01M.
• Replace IC01M.
Is the voltage NO.1 or 2 or 4
of IC01M DC 5V?
Is the voltage NO.16 or 15 or 13
of IC01M 0V?
• Check the RY-Hi or RY-Med or RY-Lo.
Check the wiring diagram.
NO
NO
YES
YES
Check the PCB pattern.
Is the voltage of Battery
over 2.3V?
• Replace Receiver Ass'y.
Is the connection of
CN-AC/DC OK?
Is the voltage No.10
of CN-AC/DC on AC PCB
Ass'y DC 5V?
• Replace the battery.
• Check the PCB pattern.
• Connect connector to CN-AC/DC exactly.
NO
NO
NO
YES
YES
YES
Service Manual 33
Troubleshooting Guide
Page 34
Possible Trouble 6 It displays abnormally on DC PCB Ass’y.
NO
NO
NO
NO
YES
YES
YES
Are IC01G and IC02G
OK?
Is the connection of
CN-AC/DC OK?
• Replace the DC PCB Ass'y.
• Replace IC01G, IC02G.
• Replace IC03G.
• Connect connector to CN-AC/DC exactly.
Does the IC03G
operate normally on AC
PCB Ass'y?
34 Room Air Conditioner
Troubleshooting Guide
Page 35
COMPLAINT CAUSE REMEDY
Check voltage at outlet. Correct if none.
Check voltage to Control Box. If none, check power supply cord. Replace cord if circuit is open.
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using slinger ring for condenser fan must have
1
/4to 5/16inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. If not within limits, call an electrician.
Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
If cracked, out of balance, or partially missing, replace it.
If cracked, out of balance, or partially missing, replace it.
Tighten it.
If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Check voltage. If not within limits, call an electrician.
Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
No power
Power supply cord
Wire disconnected or con­nection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload.
Fan
Turbo
Loose clamper
Worn bearings
Voltage
Wiring
Fan motor will not run.
Fan motor runs intermittently
Fan motor noise.
Compressor will not run, but fan motor runs.
Service Manual 35
Troubleshooting Guide
Page 36
COMPLAINT CAUSE REMEDY
Check the TEMP control. If not at the lowest number, set TEMP control to this setting and restart the unit. Check the continuity of the thermistor. Replace the thermistor if the circuit is open.
Check the capacitor. Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor overload, if externally mount­ed. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Check the voltage. If not within limits, call an electrician.
Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vac­uum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Straighten the fins or replace the coil.
Test capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean of replace.
Close if open.
Determine if the unit is properly sized for the area to be cooled.
Check the set screw or clamp. If loose or missing, correct. If the turbo or fan is hitting air guide, rearrange the air handling parts.
Remove the cabinet carefully and rearrange tubing not to contact cabinet, compressor, shroud, and barri­er.
Thermistor
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload
Voltage
Overload
Fan motor
Condenser air flow restric­tion
Condenser fins (damaged)
Capacitor
Wiring
Refrigerating system
Air filter
Exhaust damper door
Unit undersized
Turbo or fan
Copper tubing
Compressor will not run, but fan motor runs.
Compressor cycles on overload.
Compressor cycles on overload.
Compressor cycles on overload.
Insufficient cooling or heat­ing
Excessive noise
36 Room Air Conditioner
Troubleshooting Guide
Page 37
130910
149980
346811
359012
W48602
349001
268711-2
W0CZZ
135500
249950
147581
147582-1
559011
349480
552113
352113
263230
268711-1
238310
148000
354210
152302
264110
237200
130410
550140
35211A
554160
567502
135312
135303
352115
Exploded View
Exploded View
Service Manual 37
267110
352390-1
352390-2
55 40 30
731273
552102
147582-2
Page 38
38 Room Air Conditioner
Replacement Parts List
Replacement Parts List
LOCATION
NO
.
130410 130910
135312 135313 135500 147581
147582 148000 149980 152302 237200 238310 249950 261704 263230 264110 267110 268712 268714 346811 349001 349480 35211A 352113 352115 352390-1 352390-2 354210 359012 550140 554030 554031 554160 559010 567502 W0CZZ W48602
DESCRIPTION
BASE ASSEMBLY,SINGLE
CABINET ASSEMBLY,SINGLE GRILLE ASSEMBLY,FRONT(SINGLE) GRILLE ASSEMBLY,INLET COVER,CONTROL(INDOOR) LOUVER,HORIZONTAL LOUVER,VERTICAL BRACE SHROUD FILTER(MECH),A/C PANEL,CONTROL ESCUTCHEON CONTROL BOX ASSEMBLY,SINGLE TRANSFORMER,POWER THERMISTOR ASSEMBLY POWER CORD ASSEMBLY REMOTE CONTROLLER PWB(PCB) ASSEMBLY,DISPLAY PWB(PCB) ASSEMBLY,MAIN MOTOR ASSEMBLY,SINGLE DAMPER,VENTILATION ORIFICE TUBE ASSEMBLY,SUCTION SINGLE TUBE ASSEMBLY,DISCHARGE SINGLE TUBE ASSEMBLY,EVAPORATOR IN AIR GUIDE ASSEMBLY AIR GUIDE ASSEMBLY EVAPORATOR ASSEMBLY,FIRST FAN,TURBO ISOLATOR,COMP CONDENSER ASSEMBLY,FIRST CONDENSER ASSEMBLY,BENT COMPRESSOR FAN ASSEMBLY,AXIAL O.L.P CAPACITOR CLAMP,SPRING
PART NO.
HBLG8003R
3041A20021V
3091AR2317M 3531A20160A 3530A20075A
4998A10023A
3831A10021E 4995A20278R
6411A20011F
6711A20056S
4681A20069G
5211A20708B 5211A20559K 5211A20228R
5421A10026E
5403A20092B
--­ 5416A90007A
6750A30001N
0CZZA20005B
LB8000ER
3041A20021N
3091AR2317N 3531A20097A 3530A20038A 3550A30114A 4758A20019A 4758A20040A 4800A30002C
4998A10012A
5231A20006A 3720A10111C 3831A10021L 4995A20278U 6170A30003C 6323A20004P
6711A20034G 6871A20418A 6871A20417C 4681A20027X 4900A20003A 4948A10014A 5211A10074D 5211A20470B 5211A20228F 5239A20005B 5239A20012A 5421A10026J 5900A20020A
4830AR4335A 5403A20043L 5403A20043M
5900AR1167B
3H02932B
LW8000ER
HBLG1003R
3091AR2317M 3531A20160A 3530A20075A
3831A10021E 4995A20278S
6411A20011R 6711A20056S
4681A20069H
5211A10074J 5211A20470F 5211A20228S
5421A10026G
2520UCDK004
6750U-L031A 0CZZA20001N
REMARK
R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Page 39
Replacement Parts List
Service Manual 39
Replacement Parts List
LOCATION
NO
.
130410
130910
135312
135313
135500
147581
147582-1
147582-2
148000
159980
152302
237200
249950
268712
238310
268714
263230
264110
346811
349001-1
349001-2
349480
352115
35211A
352113
552111
552102
352390
354212
554030
550140
554160
559010
359012
267110
W48602
W0CZZ
DESCRIPTION
BASE ASSEMBLY,WELD[SINGLE]
CABINET ASSEMBLY,SINGLE
GRILLE ASSEMBLY,FRONT(SINGLE)
GRILLE,INLET
COVER
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
BRACE
SHROUD
FILTER ASSEMBLY,AIR CLEANER
PANEL,CONTROL
CONTROL BOX ASSEMBLY,SINGLE
PWB(PCB) ASSEMBLY,MAIN(AC)
ESCUTCHEON
PWB(PCB) ASSEMBLY,MAIN(DC)
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
MOTOR ASSEMBLY,SINGLE
DAMPER,VENTILATION
DAMPER,VENTILATION
ORIFICE
TUBE ASSEMBLY,EVAPORATOR IN
TUBE ASSEMBLY,SUCTION SINGLE
TUBE ASSEMBLY,DISCHARGE SINGLE
TUBE ASSEMBLY,CONDENSER OUT
TUBE ASSEMBLY,CAPILLARY
AIR GUIDE ASSEMBLY
EVAPORATOR ASSEMBLY,FIRST
CONDENSER ASSEMBLY,FIRST
ANTI-VIBRATION BUSH
COMPRESSOR SET
FAN, AXIAL
FAN, TURBO
REMOTE CONTROLLER ASSEMBLY
CLAMP, SPRING
CAPACITOR, DRAWING
PART NO.
LWHD1006R L1006R
3041A20021N
3091AR2317M
3531A20160C
3530A20075B
3550A30226A
4758A20019D
4758A20040A
4758A20040B
4800A30002C
4998A10023C
5231A20006A
3720A10111C
4995A11014A
6871A20417C
3831A10021E
6871A20418A
6323A20004P
6411A20056E
4681A20069H
4900A20003A
4948A10014A
5211A20470L
5211A21786A
5211A10074J
5211A30275M
5239A20012A
5421A10026P
ACG32514901
5040AR4195A
TBZ30826701
5900AR1167B
5900A20020A
6711A20034G
3H02932B
2H01451M
3041A20021V
3091AR2317M
3531A20097A
3530A10238A
3550A30226A
4758A20019A
4758A20040A
4758A20040B
4800A30002C
4998A10012A
5231A20006A
3720A10111C
4995A10113T
6871A20417C
3831A10021L
6871A20418A
6323A20004P
6411A20056F
4681A20069H
4900A20003A
4948A10014A
5211A20470L
5211A21786A
5211A10074J
5211A30275M
5239A20012A
5421A10026P
5403A20043M
5040AR4195A
2520UCDK004
5900AR1167B
5900A20020A
6711A20034G
3H02932B
0CZZA20001N
LWHD1006RY6
3041A20021V
3091AR2317M
3531A20160A
3530A20075A
3550A30226A
4758A20019A
4758A20040A
4758A20040B
4800A30002C
4998A10023C
5231A20006A
3720A10111C
4995A11014A
6871A20417C
3831A10021L
6871A20418A
6323A20004P
6411A20056E
4681A20069H
4900A20003A
4948A10014A
5211A20470L
5211A21786A
5211A10074J
5211A30275M
5239A20012A
5421A10026P
ACG32514902
4830AR4335A
2520UCDK004
5900AR1167B
5900A20020A
6711A20034G
3H02932B
0CZZA20001N
REMARK
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Page 40
Replacement Parts List
Service Manual 40
Replacement Parts List
LOCATION
NO
.
130410
130910
135312
135313
135500
147581
147582-1
147582-2
148000
159980
152302
237200
249950
268712
238310
268714
263230
264110
346811
349001-1
349001-2
349480
352115
35211A
352113
552111
552102
352390
354212
554030
550140
554160
559010
359012
267110
W48602
W0CZZ
DESCRIPTION
BASE ASSEMBLY,WELD[SINGLE]
CABINET ASSEMBLY,SINGLE
GRILLE ASSEMBLY,FRONT(SINGLE)
GRILLE,INLET
COVER
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
BRACE
SHROUD
FILTER ASSEMBLY,AIR CLEANER
PANEL,CONTROL
CONTROL BOX ASSEMBLY,SINGLE
PWB(PCB) ASSEMBLY,MAIN(AC)
ESCUTCHEON
PWB(PCB) ASSEMBLY,MAIN(DC)
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
MOTOR ASSEMBLY,SINGLE
DAMPER,VENTILATION
DAMPER,VENTILATION
ORIFICE
TUBE ASSEMBLY,EVAPORATOR IN
TUBE ASSEMBLY,SUCTION SINGLE
TUBE ASSEMBLY,DISCHARGE SINGLE
TUBE ASSEMBLY,CONDENSER OUT
TUBE ASSEMBLY,CAPILLARY
AIR GUIDE ASSEMBLY
EVAPORATOR ASSEMBLY,FIRST
CONDENSER ASSEMBLY,FIRST
ANTI-VIBRATION BUSH
COMPRESSOR SET
FAN, AXIAL
FAN, TURBO
REMOTE CONTROLLER ASSEMBLY
CLAMP, SPRING
CAPACITOR, DRAWING
L1006RY6
3041A20021V
3091AR2317M
3531A20097A
3530A20038A
3550A30226A
4758A20019A
4758A20040A
4758A20040B
4800A30002C
4998A10023C
5231A20006A
3720A10111C
4995A11014A
6871A20417C
3831A10021L
6871A20418A
6323A20004P
6411A20056E
4681A20069H
4900A20003A
4948A10014A
5211A20470L
5211A21786A
5211A10074J
5211A30275M
5239A20012A
5421A10026P
ACG32514902
4830AR4335A
2520UCDK004
5900AR1167B
5900A20020A
6711A20034G
3H02932B
0CZZA20001N
PART NO.
REMARK
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Page 41
P/NO:3828A29003C
March, 2007
Printed in China
Loading...