Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
INSTALLATION MANUAL
AIR
CONDITIONER
P/NO : MFL68681805
For more information, Refer to the CD or LG Web site (www.lg.com).
[
Representative
] LG Electronics Inc. EU Representative : LG Electronics European Shared
Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu,
This installation manual is to present information and guide about understanding, installing,
and checking .
Your careful reading before installation is highly appreciated to make no mistake and to prevent potential risks.
The manual is divided into nine chapters. These chapters are classified according to installation procedure.
See the table below to get summarized information.
• Warning and Caution concerned with safety.
• This chapter is directly related with human safety. We strongly recommend
reading this chapter carefully.
• Items Inside product Box
• Before starting installation, please make it sure that all parts are found
inside the product box.
• Fundamental knowledge about
• Model identification, accessories information, refrigerant and water cycle diagram, parts and dimensions, electrical wiring diagrams, etc.
• This chapter is important to understand
• Installation about the outdoor unit.
• Installation location, constraints on installation site, etc
• Installation about the indoor unit.
• Installation location, constraints on installation site, etc
• Constrains when accessories are installed
• How to perform piping (for refrigerant) and wiring at the outdoor unit.
• Refrigerant pipe connection between the indoor unit and the outdoor unit.
• Electrical wiring at the outdoor unit.
• How to perform piping (for water) and wiring at the indoor unit.
•
Water pipe connection between the indoor unit and pre-built under floor water loop pipe.
• Electrical wiring at the indoor unit.
• System set-up and configuration.
• As many control parameters of is adjustable by control panel,
deep understanding about this chapter is required to secure the operation
flexibility of
• For more detailed information, please read the separate operation manual to
use control panel and adjust control parameters.
• Information about supported accessories
• Specification, Constraints, and wiring are described.
•
Before purchasing accessories, please find supported specification to buy proper one.
• Test operation and check point while test running.
• Check points before starting operation are explained.
•
Troubleshooting, maintenance, and error code list are presented to correct problems.
Chapters Contents
Chapter 1
Chapter 2
Chapter 4
Chapter 3
Chapter 5
Chapter 6
Chapter 7
Chapter 8
Chapter 9
Chapter 10
REMARK : ALL CONTENTS OF THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE.
TO GET THE LATEST INFORMATION, PLEASE VISIT LG ELECTRONICS WEB SITE.
Safety Precautions
6 Air-to-Water Heat Pump
1. Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
n Be sure to read before installing the unit.
n Be sure to observe the cautions specified here as they include important items related to safety.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified
by the following indications.
n Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
WARNING
Be sure not to do.
Be sure to follow the instruction.
Do not use a defective
or underrated circuit
breaker. Use this appliance on a dedicated
circuit.
• There is risk of fire or
electric shock.
For electrical work,
contact the dealer,
seller, a qualified electrician, or an Authorized Service Center.
• There is risk of fire or
electric shock.
Always ground the unit.
• There is risk of fire or
electric shock.
Install the panel and
the cover of control
box securely.
• There is risk of fire or
electric shock.
Always install a dedicated circuit and
breaker.
• Improper wiring or installation may cause fire or
electric shock
Use the correctly rated
breaker or fuse.
• There is risk of fire or
electric
n Installation
Safety Precautions
Installation Manual 7
ENGLISH
Do not install the water
pipe system as Open
loop type.
• It may cause failure of
unit.
Use a vacuum pump or
inert (nitrogen) gas
when doing leakage
test or purging air. Do
not compress air or
oxygen and do not use
flammable gases.
• There is the risk of
death, injury, fire or explosion.
Make sure the connected condition of
connector in product
after maintenance.
• Otherwise, it may cause
product damage.
For installation, always
contact the dealer or an
Authorized Service
Center.
• There is risk of fire, electric shock, explosion, or
injury.
Do not install the unit
on a defective installation stand.
• It may cause injury, accident, or damage to the
unit.
Be sure the installation
area does not deteriorate with age.
• If the base collapses, the
unit could fall with it,
causing property damage, unit failure, and personal injury.
Do not modify or extend the power cable.
• There is risk of fire or
electric shock.
Do not install, remove,
or reinstall the unit by
yourself (customer).
• There is risk of fire, electric shock, explosion, or
injury
For antifreeze, always
contact the dealer or an
authorized service center.
• Almost the antifreeze is
a toxic product.
Do not touch leaked refrigerant directly.
• There is risk of frostbite.
8 Air-to-Water Heat Pump
Safety Precautions
Take care to ensure
that power cable could
not be pulled out or
damaged during operation.
• There is risk of fire or
electric shock.
Do not place anything
on the power cable.
• There is risk of fire or
electric shock.
Do not plug or unplug
the power supply plug
during operation.
• There is risk of fire or
electric shock.
Do not touch (operate)
the unit with wet hands.
• There is risk of fire or
electric shock.
Do not place a heater
or other appliances
near the power cable.
• There is risk of fire or
electric shock.
Do not allow water to
run into electric parts.
• There is risk of fire, failure of the unit, or electric
shock.
n Operation
Do not store or use
flammable gas or combustibles near the unit.
• There is risk of fire or
failure of unit.
Do not use the unit in a
tightly closed space for
a long time.
• It may cause damage to
the unit.
When flammable gas
leaks, turn off the gas
and open a window for
ventilation before turning the unit on.
• There is risk of explosion
or fire.
If strange sounds, or
small or smoke comes
from unit, turn the
breaker off or disconnect the power supply
cable.
• There is risk of electric
shock or fire.
Stop operation and
close the window in
storm or hurricane. If
possible, remove the
unit from the window
before the hurricane arrives.
• There is risk of property
damage, failure of unit,
or electric shock.
Do not open the front
cover of the unit while
operation. (Do not
touch the electrostatic
filter, if the unit is so
equipped.)
• There is risk of physical
injury, electric shock, or
unit failure.
Installation Manual 9
ENGLISH
Safety Precautions
Turn the main power on
6 hours ago before the
product starting operation.
• Otherwise, it may cause
compressor damage.
Do not touch electric
parts for 10 minutes
after main power off.
• There is risk of physical
injury, electric shock.
The inside heater of
product may operate
during stop mode. It is
intended to protect the
product.
Be careful that some
part of the control box
are hot.
• There is risk of physical
injury or burns.
When the unit is
soaked (flooded or submerged), contact an
Authorized Service
Center.
• There is risk of fire or
electric shock.
Be cautious that water
could not be poured to
the unit directly.
• There is risk of fire, electric shock, or unit damage.
Do not touch any electric part with wet
hands. you should be
power off before touching electric part.
• There is risk of electric
shock or fire.
Do not touch refrigerant pipe and water pipe
or any internal parts
while the unit is operating or immediately after
operation.
• There is risk of burns or
frostbite, personal injury.
If you touch the pipe or
internal parts, you
should be wear protection or wait time to return to normal
temperature.
• Otherwise , it may cause
burns or frostbite, personal injury.
10 Air-to-Water Heat Pump
For installation, always
contact the dealer or an
Authorized Service
Center.
• There is risk of fire, electric shock, explosion, or
injury.
If the unit is not used
for long time, we
strongly recommend
not to switch off the
power supply to the
unit.
• There is risk of water
freezing.
Ventilate the unit from
time to time when operating it together with a
stove, etc.
• There is risk of fire or
electric shock.
Turn the main power off
when cleaning or maintaining the unit.
• There is risk of electric
shock.
Take care to ensure
that nobody could step
on or fall onto the unit.
• This could result in personal injury and unit
damage.
Safety Precautions
Installation Manual 11
ENGLISH
n Installation
Always check for gas
(refrigerant) leakage
after installation or repair of unit.
• Low refrigerant levels
may cause failure of unit.
Keep level even when
installing the unit.
• To avoid vibration or
water leakage.
Use two or more people
to lift and transport the
unit.
• Avoid personal injury.
n Operation
Do not use the unit for
special purposes, such
as preserving foods,
works of art, etc.
• There is risk of damage
or loss of property.
Use a soft cloth to
clean. Do not use
harsh detergents, solvents, etc.
• There is risk of fire, electric shock, or damage to
the plastic parts of the
unit.
Do not step on or put
anything on the unit.
• There is risk of personal
injury and failure of unit.
CAUTION
Use a firm stool or ladder when
cleaning or maintaining the unit.
• Be careful and avoid personal injury.
Do not turn on the breaker or power
under condition that front panel cabinet, top cover, control box cover are
removed or opened.
• Otherwise it may cause fire, electric
shock, explosion or death
Safety Precautions
12 Air-to-Water Heat Pump
2. Installation Part
Thank you for choosing LG Electronics Air-to-Water Heat Pump
Before starting installation, please make it sure that all parts are found inside the product box.
INDOOR UNIT BOX
Indoor unit 1
1
1
Shut-off valve 2
1
1
ItemImageQuantityItemImageQuantity
Installation
Manual
Installation
plate
Owner's Man-
ual
Installation
Sheet
Outdoor Unit
U4
Chassis
(Product heating capacity :
5kW, 7kW, 9kW)
Item Image Quantity
OUTDOOR UNIT BOX
1
1
1
Outdoor Unit
U3 Chassis
(Product heating capacity :
12kW, 14kW, 16kW)
Outdoor Unit
UE Chassis
(Product heating capacity : 3kW)
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
INSTALLATION MANUAL
AIR
CONDITIONER
www.lg.com
Please read this manual carefully before operating
your set and retain it for future reference.
OWNER’S MANUAL
AIR
CONDITIONER
Installation Part
Installation Manual 13
ENGLISH
General Information
3. General Information
Model Information
With advanced inverter technology, is suitable for applications like under floor heating,
under floor cooling, and hot water generation. By Interfacing to various accessories user can customize the range of the application.
In this chapter, general information of is presented to identify the installation procedure. Before beginning installation, read this chapter carefully and find helpful information on installation.
Model number nomenclature
AH
AH N W 0 9 A0 6 A2
—
W096A2
Series Number
Function
A : General heating heat pump
H : Domestic Hot heating only
T : High temperature heating heat pump
Electrical ratings
6 : 1 phase 220-240V AC 50Hz 8 : 3 phase 380-415V AC 50Hz
If is installed with pre-existing boiler, the boiler and should not be operated together. If entering water temperature of is above 55°C, the system will stop
operation to prevent mechanical damage of the product. For detailed electric wiring and water piping, please contact authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual figures, installer should optimize the installation scene according to the installation conditions.
CAUTION
CASE 1:
Connecting Heat Emitters for Heating and Cooling
(Under floor loop, Fan Coil Unit, and Radiator)
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loopFan coil unit
Radiator
High TemperatureRoom Thermostat(Field supply)
2way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Shut-off valve
Typical Installation Example
Note:
• Room thermostat
- Type of thermostat and specification should be complied with chapter 4 and chapter 7 of
installation manual.
• 2way valve
- It is important to install 2way valve to prevent dew condensation on the floor and radiator while
cooling mode.
- Type of 2way control valve and specification should be complied with chapter 4 and chapter 7 of
installation manual.
- 2way valve should be installed at the supply side of the collector.
• By-pass valve
- To secure enough water flow rate, by-pass valve should be installed at the collector.
- By-pass valve should guarantee minimum water flow rate in any case. Minimum water flow rate is
described in water pump characteristics curve.
CASE 2:
Connecting Sanitary Water Tank
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loopFan coil unit
Sanitary
water
tank
Hot water
City water
Radiator
High Temperature
Room Thermostat(Field supply)
2way valve
(Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Shut-off valve
Note:
• Sanitary water tank
- It should be equipped with internal electric heater to generate sufficient heat energy in very cold
season.
• 3way valve
- Type of 3way valve and specification should be complied with chapter 4 and chapter 7 of
installation manual.
General Information
16 Air-to-Water Heat Pump
General Information
CASE 3: Connecting Solar thermal system
Solar heat source
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loopFan coil unit
Sanitary
water
tank
Hot water
City water
Radiator
High Temperature
Room Thermostat(Field supply)
2way valve
(Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Shut-off valve
Pump(Field supply)
Note:
• Sanitary water tank
- It should have additional indirect heat exchanger to utilize heat energy by solar thermal system.
• Pump
- Maximum power consumption of pump should be less than 0.25kW.
Installation Manual 17
ENGLISH
18 Air-to-Water Heat Pump
Cycle Diagram
Description
General Information
CategorySymbolMeaning
PCB
Connector
Remarks
Indoor
Unit
Th1Remote air temperature sensorCN_ROOM
- Optional accessory (being sold separately)
- Not shown in diagram
Th2Inlet evaporator temperature sensorCN_PIPE
- Meaning is expressed based on Cooling
mode.
Th3Outlet evaporator temperature sensorCN_PIPE/O
Outdoor
Unit
Th4Compressor-suction pipe temperature sensorCN_TH3
- Th4 and Th5 are connected at 4 pin type connector CN_TH3.
Th5Compressor-discharge pipe temperature sensorCN_TH3
Th6Condenser temperature sensorCN_TH2
- Description is expressed based on Cooling
mode
- Th6 and Th7 are connected at 4 pin type
connector CN_TH2
Th7Outdoor air temperature sensorCN_TH2
Th8Condenser middle temperature sensorCN_TH3
- Th8 is connected at 4 pin type connector
CN_TH3
EEVElectronic Expansion ValveCN_LEV1
INDOOR UNITOUTDOOR UNIT
LIQUID SIDE
Th2
Indoor Unit
Plate Heat
Exchanger
Th3
Th1
(Accessories)
Service Valve
GAS SIDE
Service Valve
3-Way
3-Way
Th4
Accumulator
EEV
Pressure
sensor
COMPRESSOR
Th6
Th7
Th8
Outdoor Unit
Heat Exchanger
Reversing Valve
Th5
COOLING
HEATING
General Information
Water cycle
Sanitary water tan
k is installed
(Sanitary water tan
k kit is necessary)
Solar thermal syst
em is connected
(Solar thermal kit i
s necessary)
Basic installation
(IDU + ODU)
Solar
Thermal
Componets
Fan
Coil
Unit
Underfloor
Heating
Radiator
Installation Manual 19
ENGLISH
General Information
Description
20 Air-to-Water Heat Pump
CategorySymbolMeaningPCB ConnectorRemarks
Indoor Unit
Water
Heating
Solar
Heating
TH1
TH2
TH3
TH4
TH5
F/S
E/HT
W_PUMP1
EXP/TANK
TH8
CTR/PNL
2WAY V/V_1
W/TANK
B/HT
3WAY V/V_1
CITY WATER
SHOWER
TH6
TH7
3WAY V/V_2
W_PUMP/2
SOLAR THER-
MAL SYSTEM
Refrigerant temperature sensor
(Gas side)
Refrigerant temperature sensor
(Liquid side)
Entering Water temperature sensor
Interim Water temperature sensor
Leaving Water temperature sensor
Flow Switch
Electric Heater
Internal Water Pump
Expansion Tank
Remote Air temperature sensor
Control Panel (or
‘Remote Controller’)
To control water flow for Fan Coil Unit
Sanitary Water Tank
Electric Heater
- Flow control for water which is leaving from
indoor unit.
- Flow direction switching between underfloor and water tank
Water to be heated by Indoor unit and B/HT
of W/TANK
Water supplied to end-user
W/TANK water temperature sensor
Solar-heated water temperature sensor
- Flow control for water which is heated and
circulated by SOLAR THERMAL SYSTEM.
- Flow direction switching between SOLAR
THERMAL SYSTEM and W/TANK
External Water Pump
- This system can include following components : Solar panel, Sensors, Thermostats,
Interim heat exchanger, Water pump, etc.
- To utilized hot water heated by SOLAR
THERMAL SYSTEM, end-user must by LG
AWHP Solar-Kit.
CN_PIPE/OUT
CN_PIPE
CN_TH3
CN_FLOW1
CN_E/HEAT(A)
CN_E/HEAT(B)
CN_W/PUMP(A)
(no connector)
CN_ROOM
CN_REMO
CN_2WAY(A)
(no connector)
CN_B/HEAT(A)
CN_3WAY(A)
(no connector)
(no connector)
CN_TH4
CN_3WAY(B)
CN_W/PUMP(B)
(no connector)
- Meaning is expressed based on Cooling
mode.
- TH3, TH4, and TH5 are connected at 6 pin
type connector CN_TH3.
- Heating capacity is divided into two level :
partial capacity by E/HEAT(A) and full
capacity by E/HEAT(A) + E/HEAT(B).
- Operating power(230V AC 50Hz) of
E/HEAT(A) and E/HEAT(B) are supplied by
external power source via relay connector
and ELB.
- Operating power(230V AC 50Hz) of internal
water pump is supplied by the connector.
- Absorb volume change of heated water,
- Optional accessory (sold separately)
- Model : PQRSTA0
- Pre built-in at indoor unit
rd
party accessory and Field installation
- 3
(sold separately)
- 2 wire NO or NC type 2way valve is
supported.
rd
party accessory and Field installation
- 3
(sold separately)
- Generating and storing sanitary hot water by
AWHP or built-in electric heater-
rd
- 3
party accessory and Field installation
(usually built-in at W/TANK)
- Supplying additional water heating capacity.
rd
- 3
party accessory and Field installation
(sold separately)
- SPDT type 3way valve is supported.
- Field installation
- Field installation
- TH6 and TH7 are connected at 4 pin type
connector CN_TH4.
- TH6 is a part of sanitary water tank kit.
(Model:PHLTA)
- TH7 is a part of solar thermal kit
(Model:PHLLA)
rd
- 3
party accessory and Field installation
(sold separately)
- SPDT type 3way valve is supported.
rd
- 3
party accessory and Field installation
(sold separately)
If water pump of SOLAR THERMAL SYSTEM
is incapableof circulation,external water pump
can be used.
- 3rd party accessory and Field installation
(sold separately)
General Information
Parts and Dimensions
Indoor unit(External)
Description
(unit:mm)
Installation Manual 21
ENGLISH
490
850
315
315.3
474
NoNameRemarks
1DoorControl panel is shown after this door is opened.
2HandleUsed to cover or uncover the front case
General Information
Description
Indoor unit(Internal)
NoNameRemarks
1Refrigerant PipeØ15.88mm(5~16kW), Ø12.7mm (3kW)
2Refrigerant PipeØ9.52mm(5~16kW), Ø6.35mm (3kW)
3Entering Water PipeMale PT 1 inch
4Leaving Water PipeMale PT 1 inch
5Control PanelBuilt-in Remote Controller
6Water PumpMax Head 9 / 7 / 6 m
7Safety ValveOpen at water pressure 3 bar
8
8'
T
Thermal switch
hermal switch
Cut-off power input to electric heater at 90 °C (manual return at 55C)
(1Ø Electric Heater is applied)
Cut-off power input to electric heater at 90 °C (manual return at 55 C)
(3Ø Electric Heater is applied)
9Control BoxPCB and terminal blocks
Minimum operation range at 12 LPM.(5~9kW)
Minimum operation range at 15 LPM.(12~16kW)
※ 3kW IDU has not a flow switch.
11Plate Heat ExchangerHeat exchange between refrigerant and water
12Pressure GageIndicates circulating water pressure
13Expansion TankAbsorbing Volume change of heated water
14Air VentAir purging when Charging water
15Electric Heater
Please refer to the below Page
‘Model name and related information’
16
17
Strainer
Shut-off valve
18
Carrying handle
Filtering and stacking particles inside circulating water
To drain or to block water when pipe connecting
To carry the product
Flow Switch10
(unit:mm)
22 Air-to-Water Heat Pump
848
474
305
66
52
109
474
39
75.11008176
General Information
Outdoor unit(External)
Description
Product Heating
Capacity :
12kW,14kW,16kW
U3 Chassis
(unit:mm)
Installation Manual 23
ENGLISH
Supporter
NoName
1
2
3
Liquid-side Service Valve
Gas-side Service Valve
Air discharge Grill
490
Description
General Information
Product Heating
Capacity : 3kW
UE Chasis
(unit:mm)
24 Air-to-Water Heat Pump
NoName
1
2
3
Liquid-side Service Valve
Gas-side Service Valve
Air discharge Grill
General Information
Description
Product Heating
Capacity : 5kW,7kW,9kW
U4 Chassis
(unit:mm)
Installation Manual 25
ENGLISH
Supporter
NoName
1
2
3
Liquid-side Service Valve
Gas-side Service Valve
Air discharge Grill
General Information
Control Parts
Control Box : Indoor Unit
Description
1Ø Electric Heater3Ø Electric Heater
26 Air-to-Water Heat Pump
77
8
6
54
32
6
10
8
NoNameRemarks
1
2
3
4
5
6
7
8
9
10
Terminal blocks
Unit ELB
Water tank heater
ELB(optional)
Magnetic switch
Magnetic switch
(optional for water tank heater)
Main PCB
Dry ContactSupporter
Magnet Contact
Unit MCCB
Water tank heater
MCCB(optional)
The terminal blocks allow easy connection of field wiring
The ELB protects the unit against overload or short circuit
The ELB protects the water tank heater in sanitary water tank
against overload or short circuit
The main PCB(Printed Circuit Board) controls the functioning of the unit
Supporter to install Dry Contact(sold separately)
The MCCB protects the unit against overload
The MCCB protects the water tank heater in sanitary water tank
against overload
5
1
9
8
1
-
-
General Information
Control Panel
WATER
TEMP
OPER
HEATING
MODE
Wiring Diagram : Indoor Unit
- Refer to the wiring diagram inside the control box.
Circuit Diagram : Indoor Unit
- Refer to the circuit diagram inside the front panel.
Wiring Diagram : Outdoor Unit
- Refer to the attached wiring diagram in the outdoor unit.
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 1Ø, Outdoor : 1Ø)
28 Air-to-Water Heat Pump
General Information
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 3Ø 380-415V, Outdoor : 3Ø)
Installation Manual 29
ENGLISH
Installation of Outdoor Unit
4. Installation of Outdoor Unit
The outdoor unit of is installed outside to exchange heat with ambient air. Therefore, it
is important to secure proper space around the outdoor unit and care for specific external conditions.
This chapter presents a guide to install the outdoor unit, make a route to connect with the indoor, and
what to do when installed around seaside.
• If a sunroof is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the heat exchanger is not
restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the weight of the outdoor unit into account
and select a place where noise and vibration
are minimum.
• Select a place so that the warm air and noise
from the outdoor unit do not disturb neighbors.
Conditions where Outdoor Unit is Installed
300
Fence or
obstacles
700
300
600
Sunroof
• If making a hole to the wall is required to connect pipe between the indoor unit and the outdoor unit, please follow below descriptions.
- Drill the piping hole with a ø70mm hole core
drill.
- Piping hole should be slightly slant to the outdoor side to prevent raindrop into indoor side.
Drill a Hole in the Wall
Minimum service space (unit:mm)
30 Air-to-Water Heat Pump
Wall
IndoorOutdoor
5~7mm
Installation of Outdoor Unit
Installation at Seaside
Seasonal wind and cautions in winter
Sea windSea wind
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole,
the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 500 mm than the average snowfall (annual average snowfall)
if it is installed at the area with much snowfall.
•
Where snow accumulated on the upper part of the Outdoor Unit by more than 100 mm, always remove snow for operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
Installation Manual 31
ENGLISH
CAUTION
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
3) Select a well-drained place.
Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
• It should be strong enough like concrete to prevent
the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
• It should be keep more than 700 mm of space
between outdoor unit and the windbreak for easy
air flow.
Installation of Indoor Unit
5. Installation of Indoor Unit
The indoor unit of is installed inside where terminal of under floor water pipe cycle and
refrigerant pipe from the outdoor unit are accessible at the same time.
In this chapter conditions for installation place is described. In addition, considerations when installing accessories or 3rd party accessories are described, too.
Conditions where Indoor Unit is Installed
Specific conditions are required for installation place such as service space, wall mounting, water
pipe length and height, total volume of water, adjusting expansion vessel, and water quality.
General Considerations
Followings are should be considered before the installation of the indoor unit.
- The installation place should be free from outdoor weather conditions such as rain, snow, wind,
frost, etc.
- Choose the place where is water-resistant or good drainage.
- Service space should be secured.
- No flammable materials around the indoor unit.
- Mice can not be appeared to prevent entering the indoor unit or attacking wires.
- Do not place anything in front of the indoor unit to ensure air circulation around the indoor unit.
- Do not locate anything under the indoor unit to be free from unexpected water out.
- In case of water pressure increasing to 3 bar, water drainage should be treated when water is
drained by safety valve.
Service Space
• Ensure that the spaces indicated by arrows around bottom,
side, and top side.
• Wider spaces are preferred for easy maintenance and piping.
• If minimum service space is not secured, air circulation can
be troubled and internal parts of the indoor unit can be damaged by overheating.
Minimum service space
(unit : mm)
32 Air-to-Water Heat Pump
200
250
200
1300
Installation of Indoor Unit
Mounting to Wall
Step 1. After releasing eight screws, detach front cover from the indoor unit. While detaching the
front cover, grab the carrying handles at left and right sides of the front cover. Then pull into
upward direction. When assemble the front cover, remove detached side brackets of the
front cover and ONLY tighten two screws of bottom.
Step 2. Attach "Installation Sheet" to the wall and mark
the location of bolts. This sheet helps to find
correct location to the bolts.
Step 3. Detach the Installation sheet. Screw bolts with
supporting plate at the hole marks on the wall.
When screwing bolts, use M8 ~ M11 anchor
bolts to secure hanging the indoor unit.
Bottom
screws
Remove
(Hall marks)
The sheet should be attached level. If not, the supporting plate and the indoor unit will not be mounted
correctly.
CAUTION
Eight small holes around four large hole marks can be used as alternatives of M8 ~ M11 anchor bolts. But M8 ~ M11 anchor bolts are
more preferred.
NOTICE
Step 4. Hang the indoor unit at the supporting plate.
Also, catch the carrying handles at left and
right sides of the indoor unit.
While lifting the indoor unit, at least two persons
should be joined. Weight of the indoor unit is almost
55kg.
CAUTION
Installation Manual 33
ENGLISH
Installation of Indoor Unit
34 Air-to-Water Heat Pump
Water volume and pump capacity
The water pump is three speed-adjustable (Maximum / Medium / Minimum), so it may be required to
change default water pump speed in case of noise by water flow. In most case, however, it is
strongly recommended to set speed as Maximum.
Water pump speed
To secure enough water flow rate, do not set water pump speed as "Min."
It can lead unexpected flow rate error CH14.
AHNW03604A2
Pump model : Yonos Para 25/6
AHNW09604A2
Yonos Para 25/7
NOTICE
: Operation cutoff range
Δp-v (variable)
H/m
6
5
4
3
2
1
0
00,51,01,52,02,53,0
00,20,40,60,8
02468
P
/W
1
40
30
20
10
0
00,51,01,52,02,53,0
Tolerances of each curve according to EN 1151-1:2006
Wilo-Yonos PARA RS
15/6, 20/6, 25/6, 30/6
1~230 V - Rp½, Rp¾, Rp 1, Rp 1¼
Δp-v
4m
5m
6m
max.
10
max.
2m
3m
Q/m ³/ h
Q/l/s
Q/Igpm
Q/m ³/ h
p/kPa
60
50
40
30
20
10
0
Constant speed I, II, III
H/m
4350 1/min
6
5
4
3060 1/min
3
2
2180 1/min
1
800 1/min
0
00,51,01,52,02,53,0
00,20,40,60,8
0246810
P
/W
1
40
30
3060
20
10
0
00,51,01,52,02,53,0
Tolerances of each curve according to EN 1151-1:2006
Wilo-Yonos PARA RS
15/6, 20/6, 25/6, 30/6
1~230 V - Rp½, Rp¾, Rp 1, Rp 1¼
1
/min
II
I
max.
III
Q/m³/ h
Q/l /s
Q/Igpm
Q/m³/ h
p/kPa
60
50
40
30
20
10
0
p-v (variable)
Δ
H/m
7
6
5
4
3
2
1
0
00,51,01,52,02,53,0
00,20,40,60,8
0246810
/W
P
1
40
20
0
00,51,01,52,02,53,0
Wilo-Yonos PARA RS
15/7.0, 25/7.0, 30/7.0
1~230 V - Rp½, Rp 1, Rp 1¼
Δ
p-v
max
.
max.
Q/m³/ h
Q/l/s
Q/Igpm
Q/m³/ h
p/kPa
70
60
50
40
30
20
10
0
Constant speed I, II, III
H/m
4660 1/min
7
6
5
3400 1/min
4
3
2390 1/min
2
1
800 1/min
0
00,51,01,52,02,53,0
00,20,40,60,8
0246810
P
/W
1
40
20
0
00,51,01,52,02,53,0
Wilo-Yonos PARA RS
15/7.0, 25/7.0, 30/7.0
1~230 V - Rp½, Rp 1, Rp 1¼
max.
max.
Q/m³/ h
Q/l/s
Q/Igpm
Q/m³/ h
/kPa
p
70
60
50
40
30
20
10
0
Installation Manual 35
ENGLISH
AHNW16606A2, AHNW16809A2
Pump model : Stratos Para 25/1-9
: Operation cutoff range
WARNING
Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
Installation of Indoor Unit
36 Air-to-Water Heat Pump
Installation of Indoor Unit
Pressure Drop
When installing the product, install additional pump in consideration of the pressure loss and pump
performance.
If flow-rate is low, overloading of product can occur.
The water pump is operating according to below curves.
Inside expansion vessel is included which is 8 liter capacity with 1 bar pre-pressure.
That means, according to the volume-pressure graph, total water volume of 230 liter is supported as
default. If total water volume is changed because of installation condition, the pre-pressure should be
adjusted to secure proper operation.
- Minimum total water volume is 20 liter.
- Pre-pressure is adjusted by the total water volume. If the indoor unit is located at the highest position of the water circuit, adjustment is not required.
- To adjust pre-pressure, use nitrogen gas by certificated installer.
Adjusting pre-pressure of expansion vessel is as following :
Step 1. Refer "Volume-Height" table.
If installation scene is belong to Case A, go to Step 2.
Otherwise, if it is Case B, do nothing. (pre-pressure adjustment is not required.) Otherwise, if it is Case C, go to Step 3.
Step 2. Adjust pre-pressure by following equation.
Pre-pressure [bar] = (0.1xH+0.3) [bar]
where H : difference between indoor unit and the highest water pipe
0.3 : minimum water pressure to secure product operation
Step 3. Volume of expansion vessel is less than installation scene.
Please install additional expansion vessel at the external water circuit.
H : difference between indoor unit and the highest water pipe
V : total water volume of installation scene
V < 230 liter V ≥ 230 liter
H < 7m Case B Case A
H ≥ 7m Case A Case C
Volume-Height Table
Installation Manual 37
ENGLISH
2.4
2.1
1.7
1.4
1.0
0.7
Pre-pressure in Expansion vessel (bar)
0.3
2060100140180220260300340
Maximum total water volume (liter)
Installation of Indoor Unit
Water Quality
Water quality should be complied with EN 98/83 EC Directives. Requirement for resolved chemical
ingredients is following table. Detailed water quality condition can be found in EN 98/83 EC Directives.
Parameter Value
Fluoride 1.5 mg/l
Lead 10 μg/l
Mercury 1.0 μg/l
Nickel 20 μg/l
Nitrate 50 mg/l
Nitrite 0.50 mg/l
Pesticides 0.10 μg/l
Pesticides — Total 0.50 μg/l
Polycyclic aromatic hydrocarbons 0.10 μg/l
Selenium 10 μg/l
Tetrachloroethene and Trichloroethene 10 μg/l
Trihalomethanes — Total 100 μg/l
Vinyl chloride 0.50 μg/l
• If the product is installed at existing hydraulic water loop, it is important to clean hydraulic pipes to remove sludge and scale.
• Installing sludge strainer in the water loop is very important to prevent performance degrade.
• Chemical treatment to prevent rust should be performed by installer.
CAUTION
38 Air-to-Water Heat Pump
Frost protection
In areas of the country where entering water temperatures drop below 0 °C, the water pipe must be
protected by using an approved antifreeze solution. Consult your AWHP unit supplier for locally
approved solutions in your area. Calculate the approximate volume of water in the system. (Except
the AWHP unit.)
And add six litters to this total volume to allow for the water contained in AWHP unit.
1. Use only one of the above antifreeze.
2. If a antifreeze is used, pressure drop and capability degradation of the system can be
occurred.
3. If one of antifreezes is used, corrosion can be occurred. So please add corrosion inhibitor.
4. Please check the concentration of the antifreeze periodically to keep same concentration.
5. When the antifreeze is used (for installation or operation), take care to ensure that antifreeze
must not be touched.
6. Ensure to respect all laws and norms of your country about Anti-freeze usage.
Antifreeze type
Antifreeze mixing ratio
0°C -5°C -10°C -15°C -20°C -25°C
Ethylene glycol 0% 12% 20% 30% - -
Propylene glycol 0% 17% 25% 33% - -
Methanol 0% 6% 12% 16% 24% 30%
CAUTION
Piping and Wiring for Outdoor Unit
6. Piping and Wiring for Outdoor Unit
Procedures about refrigerant piping and electric wiring at the outdoor are described in this chapter. Most of
procedures are similar to those of LG Air Conditioner.
Before starting refrigerant piping, constraints in pipe length and elevation should be examined. After resolving all constraints, some preparations are required to proceed. Then connecting pipe to the outdoor and
the indoor unit is beginning.
Refrigerant Piping
Constraints in Pipe Length and Elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A trap is not necessary
when the outdoor unit is
installed in a higher
position than the indoor
unit.
1. Standard pipe length is 7.5m If the pipe length is longer than 7.5m, additional charge of the refrigerant is required according to the table.
• Example : If 16kW model is installed at a distance of 50m, 1,700g of refrigerant should be
added according to following formula : (50-7.5) x 40g = 1,700g
2. Rated capacity of the product is based on standard length and maximum allowable length is
based on the product reliability in the operation.
3. Improper refrigerant charge may result in abnormal operation.
CAUTION
Note:
Fill in the f-gas Label attached on outdoor about the quantity of the fluorinated greenhouse gases (This note about
f-gas label may not apply depending on your product type or market.)
① Manufacturing site (See Model Name label)
② Installation site (If possible being placed adjacent to the service points for the addition or removal of refrigerant)
③ The total Charge (① + ②)
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor unit and
the outdoor unit.
• Cut the pipes a little longer than measured distance.
Step 2. Burrs removal.
• Remove all burrs completely from cut cross section of the pipe.
• Put the end of the pipe to downward direction in
order to prevent drop of burrs into the pipe.
Step 3. Insert flare nut.
• Take out flare nuts attached at the indoor unit and
the outdoor unit.
• Insert flare nuts into burr-removed pipe.
• If flaring work is finished, it is impossible to insert
nuts into pipe.
Step 4. Flaring work.
• Carry out flaring work using dedicated flaring tool
for R-410A refrigerant as shown below.
• Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Step 5. Check
• Compare the flared work with right figure.
• If flare is seemed to be defective, cut off the flared
section and do flaring work again.
Preparation for Piping
Preparation for piping is five steps. As main cause of refrigerant leakage is defects in flaring work, please
carry out correct flaring work in the following steps.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
mm inch mm
6.35 1/4 1.1 ~ 1.3
9.52 3/8 1.5 ~ 1.7
12.7 1/2 1.6 ~ 1.8
15.88 5/8 1.6 ~ 1.8
19.05 3/4 1.9 ~ 2.1
Outside diameter"A"
40 Air-to-Water Heat Pump
Piping and Wiring for Outdoor Unit
Connecting Pipe to Indoor Unit
Connecting pipe to the indoor unit is two steps. Read following directions carefully.
Connecting Pipe to Outdoor Unit
(Product Heating Capacity : 9kW(U4 Chassis),12kW,14kW,16kW)
Connecting pipe to the outdoor unit is five steps including PCB setting.
Step 1. Pre-tightening.
• Align the center of the pipes and sufficiently
tighten the flare nut by hand.
Step 2. Tightening.
• Tighten the flare nut with a wrench.
• Tightening torque is as following.
Step 1. Determine direction of pipes.
• The pipes can be connectable in four directions
• The directions are expressed in below figure.
• The pipes cannot be connected in downward direction.
mm inch kgf·m
6.35 1/4 1.8 ~ 2.5
9.52 3/8 3.4 ~ 4.2
12.7 1/2 5.5 ~ 6.6
15.88 5/8 6.6 ~ 8.2
19.05 3/4 9.9 ~ 12.1
Outside diameterTorque
Forward
Sideways
Backward
Installation Manual 41
ENGLISH
Indoor unit tubingFlare nutPipings
Torque wrench
Indoor unit tubing
Open-end wrench (fixed)
Flare nut
Connection pipe
Backward
Forward
Sideways
Piping and Wiring for Outdoor Unit
Step 2. Tightening
• Align the center of the pipes and sufficiently
tighten the flare nut by hand.
• Tighten the flare nut with a wrench until the
wrench clicks
• Tightening torque is as following.
Step 3. Preventing entering of foreign
objects
• Plug the pipe through-holes with putty or insulation material (procured locally) to fill up all
gaps as shown in right figure.
• If insects or small animals enter the outdoor
unit, it may cause a short circuit in the electrical
box.
• Finally, form the pipes by wrapping the connecting portion of the indoor unit with insulation
material and secure it with two kinds of vinyl
tape. Ensuring thermal insulation is very important.
mm inch kgf·m
6.35 1/4 1.8 ~ 2.5
9.52 3/8 3.4 ~ 4.2
12.7 1/2 5.5 ~ 6.6
15.88 5/8 6.6 ~ 8.2
19.05 3/4 9.9 ~ 12.1
Outside diameterTorque
Outdoor unit
Continuous
Torque wrench
Gas side piping
Liquid side piping
Putty or insulating material
(produced locally)
Drain hose
(if necessary)
Connecting wire
Connection pipe
42 Air-to-Water Heat Pump
Piping and Wiring for Outdoor Unit
Connecting Pipe to Outdoor Unit
(Product Heating Capacity : 9kW)
• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench
until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening follows the arrow on the wrench.
Align the center of the piping and sufficiently
tighten the flare nut by hand.
mm inch kgf.m
Ø6.35 1/4 1.8~2.5
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.6
Ø15.88 5/8 6.3~8.2
Ø19.05 3/4 9.9~12.1
Outside diameterTorque
Torque wrench
Outdoor unit
Gas side piping
Liquid side piping
Installation Manual 43
ENGLISH
Piping and Wiring for Outdoor Unit
Two kind of cables should be connected to the outdoor unit : One is ‘Power cable’, the other one is ‘Connecting cable’.
Power cable is a cable which is used to supply external electricity to the outdoor unit. This cable is generally connected
between external power source (such as main electric power distribution panel of user’s house) and the outdoor unit.
Connecting cable is, on the other hand, used to connect between the outdoor unit and the indoor unit to supply electric
power to the indoor unit and to establish the communication between the outdoor unit and the indoor unit.
Procedure for wiring to the outdoor unit is four steps. Before starting wiring, check if wire specification is suitable and
read following directions and cautions VERY carefully.
Wire Specification
Power Cable Specification : The power cord connected to the outdoor unit should be complied with
IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or H07RN-F)
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Terminal Specification of Power Cable and related Cautions :
Use round pressure terminals for connections to the power terminal block.
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
Connecting Cable Specification : The connecting cable, being used to connect the indoor unit and
outdoor unit, should be complied with IEC 60335-1 standard (This equipment shall be provided with
a cord set complying with the national regulation).
Point for attention regarding quality of the public electirc power supply
• In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to
consult the distribution network operator to ensure that the equipment is connected only to a supply
with Zsys≤Zmax, respectively Ssc ≥ minimum Ssc value.
20mm
GN/YL
1 Phase(Ø)3 Phase(Ø)
20mm
GN/YL
Round pressure terminal
Power wire
20mm
GN/YL
If the supply cable is damaged, it must be replaced by a special cable or assembly available from the manufacturer or its service agent.
Electrical Wiring
44 Air-to-Water Heat Pump
Piping and Wiring for Outdoor Unit
• European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.
• European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current ≤16A of ≻75A per phase.
Circuit Breaker Specification
• Select a power source that is capable of supplying the current required by the AWHP.
• Use a recognized circuit breaker between the power source and the unit.
A disconnection device to adequately disconnect all supply lines must be fitted.
• Capacity of circuit breaker recommended.
• Separate main power supply and heater supply.
Installation Manual 45
ENGLISH
Notes:
1. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
2. Select wire spec. based on the MCA
3.
Recommended circuit breaker is ELCB (Earth Leakage Circuit breaker)
4. RLA is measured during each individual compressor test condition.
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating Over current Protective device
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
S/Heater: Sanitary Water Tan Heater
After checking and confirming following conditions, start wiring work.
1. Secure dedicated power source for the Air-to-Water heat pump. The wiring diagram (attached
inside the control box of the indoor unit) is presenting related information.
2. Provide a circuit breaker switch between power source and the outdoor unit.
3. Although it is very rare case, sometimes the screws used to fasten internal wires can be loosen
due to the vibration while product transportation. Check these screws and make it sure if they
are all fastened tightly. If not tightened, burn-out of the wire can be occurred.
4. Check the specification of power source such as phase, voltage, frequency, etc.
5. Confirm that electrical capacity is sufficient.
6. Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7. Confirm that the cable thickness is as specified in the power sources specification. (Particularly
note the relation between cable length and thickness.)
8. Provide an ELB(electric leakage breaker) when the installation place is wet or moist.
9. The following troubles would be caused by abnormal voltage supply such as sudden voltage increasing or voltage drop-down.
• Chattering of a magnetic switch (frequent on and off operation)
• Physical damage of parts where magnetic switch is contacted
• Break of fuse
• Malfunction of overload protection parts or related control algorithms.
• Failure of compressor start up
10. Ground wire to ground outdoor unit to prevent electrical shock.
CAUTION
When connecting power cable, make sure the
rubber bushes are properly attached in knock-out
holes after removing the Insulation pad.
Control Terminal
(Terminal for
Connecting Cable)
Main Power
Terminal
(Terminal for
Power Cable)
Cable Clamp
(or Cord Clamp)
Cable Clamp
(or Cord Clamp)
Insulation pad
Side Panel
Water
Inlet
Water
Outlet
46 Air-to-Water Heat Pump
Wiring Procedure for Power Cable and Connecting Cable
Step 1. : Disassemble the side panel from the outdoor unit by loosing screws.
Step 2. : Connect Power cable to Main Power Terminal and Connecting cable to Control Termi-
nal, respectively.
See below figure for detailed information. When connecting earth cable, the diameter
of cable should be bigger than 1.6mm
2
to secure safety. The earth cable is connected
to the terminal block where earth symbol is marked.
Step 3. : Use cable clamps (or cord clamps) to prevent unintended move of Power cable and
Connecting cable.
Step 4. : Reassemble the side panel to the outdoor unit by fastening screws.
Piping and Wiring for Outdoor Unit
After pipes are connected and electric cables are wired, pipe forming and some tests are remained. Especially,
careful attention is required while proceeding leakage test because the leakage of the refrigerant effects degrade
of performance directly. Also, it is very hard to find leaked point after all installation procedures are finished.
Pipe Forming
Do pipe forming by wrapping the connecting
cable and refrigerant pipe (between the indoor
unit and outdoor unit) with thermal insulation material and secure it with two kinds of vinyl tape.
1. Tape the refrigerant pipe, power cable and connecting cable from down to up.
2. Secure the taped pipe is along with the exterior
wall. Form a trap to prevent water entering the
room and electrical part.
3. Fix the taped pipe onto the wall by saddle or
equivalent.
Taping Procedure
1. Tape the pipes, connecting cable and power cable from down to up. If taping direction is up to
down, rain drop may be sinking into the pipes or cables.
2. Secure the taped pipe along the exterior wall using saddle or equivalent.
3. Trap is required to prevent water from entering into electrical parts.
• Trap is required to prevent water from entering
into electrical parts.
Taping
Drain hose
(not used)
Refrigerat
Pipes
Connecting
cable
Power Cable
PlasticPlastic
bandband
Plastic
band
Seal a small Seal a small
opening around opening around
the pipings with the pipings with
gum type sealer.gum type sealer.
Seal a small
opening around
the pipings with
gum type sealant.
Seal a small opening Seal a small opening
around the pipings around the pipings
with gum type sealer.with gum type sealer.
Seal a small opening
around the pipings
with gum type sealant.
Finalizing
Installation Manual 47
ENGLISH
The Power cord connected to the unit should be selected according to the following
specifications .
CAUTION
Drain hose
(not used)
Pipe
Vinyl tape(narrow)
Wrap with
vinyl tape(wide)
Piping and Wiring for Outdoor Unit
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been
properly connected and all wiring for the test run has been completed. Remove the service valve caps
from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port
with charge hoses.
Be sure to use a manifold valve for leakage test.
If it is not available, use a stop valve for
this purpose. The "Hi" knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 3.0
Mpa with dry nitrogen gas and close the
cylinder valve when the gauge reading
reached 3.0 Mpa Next, test for leaks with liquid soap.
To avoid nitrogen entering the refrigerant
system in a liquid state, the top of the cylinder must be higher than its bottom when you
pressurize the system. Usually, the cylinder is
used in a vertical standing position.
1. Do a leakage test of all joints of the
tubing(both indoor and outdoor) and both
gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
2. After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder. When the system pressure is reduced to
normal, disconnect the hose from the cylinder.
CAUTION
CAUTION
Leakage test and Evacuation
48 Air-to-Water Heat Pump
Indoor unit
Outdoor unit
Manifold valve
Lo Hi
Charge hose
Pressure
gauge
Nitrogen gas
cylinder(in vertical
standing position)
Piping and Wiring for Outdoor Unit
Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the
tubing and indoor unit.
Confirm the "Lo and Hi" knob of the manifold valve
is open. Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following table
shows the time required for evacuation.
2. When the desired vacuum is reached, close the "Lo
and Hi" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of
liquid side valve counter-clockwise to fully open the
valve.
2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with
an adjustable wrench. This process is very important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Required time for evacuation when 30 gal/h
vacuum pump is used
30 min. or more 60 min. or more
0.5 torr or less
If tubing length is less
than 10 m(33 ft)
If tubing length is longer
than 10 m(33 ft)
Installation Manual 49
ENGLISH
Manifold valve
Open
Vacuum pump
Outdoor unit
Open
Pressure
gauge
Lo Hi
Indoor unit
Piping and Wiring for Indoor Unit
7. Piping and Wiring for Indoor Unit
Procedures about water piping and electric wiring at the indoor unit are described in this chapter.
Water piping and water circuit connection, water charging, pipe insulations will be shown for water
piping procedures. For wiring, terminal block connection, connecting with the outdoor unit, electric
heater wiring will be introduced. Accessories connection, such as sanitary water tank, thermostat,
3way or 2way valves, etc will be dealt in separated chapter.
General Considerations
Followings are should be considered before beginning water circuit connection.
• Service space should be secured.
• Water pipes and connections should be cleaned using water.
• Space for installing external water pump should be provided if internal water pump capacity is
not enough for installation field.
• Never connect electric power while proceeding water charging.
Water Piping and Water Circuit Connection
Definition of terms are as follow :
• Water piping : Installing pipes where water is flowing inside the pipe.
• Water circuit connecting : Making connection between the product and water pipes or between
pipes and pipes. Connecting valves or elbows are, for example, in this category.
Configuration of water circuit is shown in Chapter 2. All connections should be complied with presented diagram.
While installing water pipes, followings should be considered :
• While inserting or putting water pipes, close the end of the pipe with pipe cap to avoid dust entering.
• When cutting or welding the pipe, always be careful that inner section of the pipe should not be
defective. For example, no weldments or no burrs are found inside the pipe.
• Drain piping should be provided in case of water discharge by the operation of the safety valve.
This situation can be happened when the internal pressure is over 3.0 bar and water inside the
indoor unit will be discharged to drain hose.
While connecting water pipes, followings should be considered.
• Pipe fittings (e.g. L-shape elbow, T-shape tee, diameter reducer, etc) should be tightened
strongly to be free from water leakage.
• Connected sections should be leakage-proof treatment by applying tefron tape, rubber bushing,
sealant solution, etc.
• Appropriate tools and tooling methods should be applied to prevent mechanical breakage of the
connections.
• Operation time of flow control valve(e.g. 3way valve or 2way valve) should be less than 90 seconds.
• Drain hose should be connected with drain piping.
Water Piping and Water Circuit Connection
50 Air-to-Water Heat Pump
Piping and Wiring for Indoor Unit
Installing shut-off valve
• While assembling two shut-off valves, that are found inside ‘AWHP Installation Kit
(AET69364401)’, pop sound will be heard when valve is open or close by rotating handles. It is
normal condition because the sound is due to leakage of charged nitrogen gas inside the valve.
The nitrogen gas is applied to secure quality assurance.
• Before starting water charging, these two shut-off valves should be assembled with water inlet
and outlet pipe of the indoor unit.
Water condensation on the floor
While cooling operation, it is very important to keep leaving water temperature higher than 16°C.
Otherwise, dew condensation can be occurred on the floor.
If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
While cooling operation, cold water may not flow to the radiator. If cold water enters to the radiator,
dew generation on the surface of the radiator can be occurred.
Drainage treatment
While cooling operation, condensed dew can drop down to the bottom of the indoor unit. In this
case, prepare drainage treatment (for example, vessel to contain condensed dew) to avoid water
drop.
WARNING
Installation Manual 51
ENGLISH
Piping and Wiring for Indoor Unit
Water Charging
For water charging, please follow below procedures.
Step 1. Open all valves of whole water circuit. Supplied water should be charged not only inside the
indoor unit, but also in the under floor water circuit, sanitary water tank circuit, FCU water circuit, and any other water circuits controlled by the product.
Step 2. Connect supply water into drain valve and fill valve located at the side of the shut-off valve.
No water-leakage permitted at the drain and fill
valve. Leakage-proof treatment which is described
in previous section should be applied.
Step 3. Start to supply water. While supplying water, following should be kept.
• Pressure of supplying water should be 2.0 bar approximately.
• For supplying water pressure, time to be taken from 0 bar to 2.0 bar should be more than 1
minute. Sudden water supply can yield water drain through safety valve.
• Fully open the cap of air vent to assure air purging. If air is exist inside the water circuit,
then performance degrade, noise at the water pipe, mechanical damage at the surface of
electric heater coil.
Step 4. Stop water supplying when the pressure gage located in front of the control panel indicates
2.0 bar.
Step 5. Close drain valve and fill valve. Then wait for 20~30 seconds to observe water pressure
being stabilized.
Step 6. If following conditions are satisfactory, then go to step 7(pipe insulation). Otherwise, go to
step 3.
• Pressure gage indicates 2.0 bar. Note that sometimes pressure in decreased after step 5
due to water charging inside expansion vessel.
• No air purging sound is heard or no water drop are popping out from air vent.
Pipe Insulation
Purpose of water pipe insulation is :
• To prevent heat loss to external environment
• To prevent dew generation on the surface of the pipe in cooling operation
CAUTION
Water In Water Out
52 Air-to-Water Heat Pump
Piping and Wiring for Indoor Unit
General Consideration
Followings are should be considered before beginning indoor unit wiring.
• Field-supplied electrical components such as power switches, circuit breakers, wires, terminal
boxes, etc should be properly chosen with compliance with national electrical legislation or regulation.
• Make it sure that supplied electricity is enough to operate the product including outdoor unit,
electric heater, water tank heater, etc. The capacity of fuse also selected according to the power
consumption.
• The main electricity supply should be dedicated line. Sharing main electricity supply with other
devices such as washing machine or vacuum cleaner is not permitted.
• Before starting wiring job, the main electricity supply should be turned off until wiring is completed.
• When adjusting or changing wiring, the main electricity supply should be turned off and ground
wire should be connected securely.
• Installation place should be free from the attack of wild animal. For example, mice’s wire attacking
or frog’s entering into the indoor unit may cause critical electrical accident.
• All power connections should be protected from dew condensation by thermal insulation.
• All electrical wiring should comply with national or local electrical legislation or regulation.
• The ground should be connected exactly. Do not earth the product to the copper pipe, steel fence
at the veranda, city water outlet pipe, or any other conductivity materials.
• Fix all cable using cord clamp tightly. (When cable is not fixed with cord clamp, use additionally
supplied cable ties.)
CAUTION
Hole A, B : for AC line (wire which is connected to the terminal block of the control box)
Hole C : for DC line (wire which is connected to the PCB of the control box)
Electrical Wiring
Installation Manual 53
ENGLISH
ABC
Piping and Wiring for Indoor Unit
Terminal Block Information (1Ø Electric Heater)
Symbols used below pictures are as follows :
- L, L1, L2 : Live (230V AC)
- N : Neutral (230V AC)
- BR : Brown , WH : White , BL : Blue , BK : Black
Terminal Block 1
Terminal Block 2
Terminal Block 3
54 Air-to-Water Heat Pump
energizing water
3WAY VALVE
(B)
1
2L13N4L5N6L7N8L9L110
L
BRWHBLBRBLBRBRWHBLBL
water flow switching between using
solar thermal heating and skipping
solar thermal heating
OUTDOOR UNIT
11
12
(2(N)
BL
13
3
BK
1(L)
(BR)
Power supply for Indoor
unit and communication
pump for solar
thermal system
WATER
PUMP
(B)
turn on or off sanitary
water tank heater
opening or closing
water flow for FCU
cooling
2WAY VALVE
(A)
14
15
L1
L2
BR
WH
water flow switching between
under floor heating and sanitary
water tank heating
WATER
TANK
HEATER
16
N
BL
Connection for thermostat
(230V AC)
Supporting type : Heating only or
Heating/Cooling
3WAY VALVE
THERMOSTAT
(Default : 230V AC)
17
18
BL
19
N
L1
WH
L
BR
(A)
N
20
L2
BK
Terminal
Block 1
Terminal
Block 2
EXTERNAL POWER
(INTERNAL E/HEATER)
1
L
BR
connecting external electric
power supply for internal
electric heater
connecting external electric
power supply for sanitary
water tank electric heater
EXTERNAL POWER
(W/TNK E/HEATER)
2
N
BL
BR
Terminal
Block 3
3
L
4
N
BL
Piping and Wiring for Indoor Unit
Terminal Block Information (3Ø Electric Heater)
Symbols used below pictures are as follows :
- L, L1, L2 : Live (230V AC)
- N : Neutral (230V AC)
- BR : Brown , WH : White , BL : Blue , BK : Black
Terminal Block 1
Terminal Block 2
Terminal Block 3
Installation Manual 55
ENGLISH
3WAY VALVE
(B)
1
L
BRWHBLBRBLBRBRWHBLBL
water flow switching between using
solar thermal heating and skipping
solar thermal heating
energizing water
pump for solar
thermal system
WATER
PUMP
2L13N4L5N6L7N8L9L110
(B)
turn on or off sanitary
opening or closing
water flow for FCU
cooling
water flow switching between
under floor heating and sanitary
water tank heating
WATER
TANK
HEATER
water tank heater
3WAY VALVE
(A)
N
Terminal
Block 1
OUTDOOR UNIT
11
12
(2(N)
BL
13
3
BK
1(L)
(BR)
Power supply for Indoor
unit and communication
connecting external electric
power supply for sanitary
water tank electric heater
EXTERNAL POWER
(W/TNK E/HEATER)
1
2
L
BR
N
BL
2WAY VALVE
(A)
14
15
L1
BR
EXTERNAL POWER
(INTERNAL E/HEATER)
3
R
BR
connecting external electric
power supply for internal
electric heater
16
L2
N
WH
BL
Connection for thermostat
(230V AC)
Supporting type : Heating only or
Heating/Cooling
4
S
BK
5
T
GY
THERMOSTAT
(Default : 230V AC)
17
18
BL
19
N
L1
WH
L
BR
BK
20
L2
Terminal
Block 2
Terminal
Block 3
Piping and Wiring for Indoor Unit
Connecting with Outdoor Unit
Electric Heater Wiring
N
L
S
RT
NL
N
L
External power supply (same
dedicated power supply for the
indoor unit and outdoor unit)
Power Cable Specification : The power cord connected to the outdoor unit should be complied
with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or H07RN-F)
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
CAUTION
20mm
GN/YL
1 Phase(Ø)3 Phase(Ø)
20mm
GN/YL
1Ø Electric Heater
1Ø Electric Heater
3Ø Electric Heater
3Ø Electric Heater
LN
Separation
Power SupplyCommunication Wiring
Shield cable
CAUTION
You should separate the communication
wiring, in case of communication wiring
length is over 40M
56 Air-to-Water Heat Pump
1(L) 2(N) 3
Terminal block at outdoor unit
123
Terminal block at outdoor unit
123
Accessories Installation
8. Accessories Installation
Installation Manual 57
ENGLISH
Accessories supported by LG Electronics
Accessories supported by 3
rd
party Companies
Item Purpose Specification
Solar Heating System
Thermostat
3way valve and actuator
2way valve and actuator
To generate auxiliary heating energy
for water tank
To control by air temperature
To control water flow for hot water
heating or floor heating
To control water flow for Fan Coil Unit
Heating-Only type (230V AC)
Cooling/Heating type (230V AC with
Mode selection switch)
3 wire, SPDT (Single Pole Double
Throw) type, 230V AC
2 wire,NO(Normal Open) or NC(Normal
Closed) type,230V AC
ItemPurposeModel
Sanitary Water Tank Install KitTo operate with sanitary water tank
PHLTA : 1Ø Indoor
PHLTC : 3Ø Indoor
Remote Air SensorTo control by air temperaturePQRSTA0
Dry ContactTo receive on & off external signalPQDSA
Solar Heating KitTo operate with solar heating system PHLLA (Limit Temperature : 96℃)
Sanitary Water TankTo generate and store hot water
PHS02060310 : 200 liter, Single Heating Coil,
1Ø 230V 50Hz 3kW Electric Heater
PHS02060320 : 200 liter, Double Heating Coil,
1Ø 230V 50Hz 3kW Electric Heater
PHS03060310 : 300 liter, Single Heating Coil,
1Ø 230V 50Hz 3kW Electric Heater
PHS03060320 : 300 liter, Double Heating Coil,
1Ø 230V 50Hz 3kW Electric Heater
Drain PanTo prevent drain water dropPHDPA
can interface to various accessories to extend its functionality and to improve user convenience. In this chapter, specifications about supported 3rd party accessories and how to connect
to is introduced.
It is noted that this chapter only deal with 3rd party accessories. For accessories supported by LG
Electronics, please refer to installation manual of each accessories.
58 Air-to-Water Heat Pump
Thermostat is generally used to control the product by air temperature. When thermostat is connected to the product, the product operation is controlled by the thermostat.
General Information
supports following thermostats.
Before Installation
Thermostat
Followings should be kept before installation
• Main power must be turned off during installing 3rd party accessories.
• 3rd party accessories should be comply with supported specification.
• Proper tools should be chosen for installation.
• Never do installation with wet hands.
WARNING
The Heat Pump supports following thermostats.
(1) There is no electric circuit inside the thermostat and electric power supply to the thermostat is
not required.
(2) Electric circuit such as display, LED, buzzer, etc is included in the thermostat and electric power
supply is required.
(3) Thermostat generates "Heating ON or Heating OFF" signal according to user"s heating target
temperature.
(4) hermostat generates both "Heating ON or Heating OFF" and "Cooling ON or Cooling OFF"
signal according to user"s heating and cooling target temperature.
Choosing heating / cooling thermostat
• Heating / cooling thermostat must have "Mode Selection" feature to distinguish operation mode.
• Heating / cooling thermostat must be able to assign heating target temperature and cooling
target temperature differently.
• If above conditions are not kept, the unit can not operation properly.
• Heating / cooling thermostat must send cooling or heating signal immediately when temperature
condition is satisfied. No delay time while sending cooling or heating signal is permitted.
CAUTION
Accessories Installation
SupportedOperating ModePowerType
Mechanical
(1)
Electrical
(2)
230 V~
230 V~
YesHeating Only (3)
YesHeating / Cooling (4)
YesHeating Only (3)
YesHeating / Cooling (4)
Installation Manual 59
ENGLISH
How to wire thermostat
Follow below procedures Step 1 ~ Step 5.
Step 1. Uncover front cover of the unit and open the control box.
Step 2. Identify the power specification of the thermostat. If it is 220-240 V~, go to Step 3.
Step 3. If it is Heating only thermostat, go to step 4. Otherwise, if it is Heating / cooling thermostat,
go to step 5.
Step 4. Find terminal block and connect wire as below. After connecting, go to step 5.
Mechanical type thermostat
Do not connect wire (N) as mechanical type thermostat does not
require electric power supply.
Do not connect external electric loads.
Wire (L) and (N) should be used only for operation electric type
thermostat.
Never connect external electric loads such as valves, fan coil units,
etc. If connected, Main PCB (Heater) can be seriously damaged.
(L) : Live signal from PCB to thermostat
(N) : Neutral signal from PCB to thermostat
(H) : Heating signal from thermostat to PCB
(L) : Live signal from PCB to thermostat
(N) : Neutral signal from PCB to thermostat
(C) : Cooling signal from thermostat to PCB
(H) : Heating signal from thermostat to PCB
Step 5. Find terminal block and connect wire as below.
Mechanical type thermostat
Do not connect wire (N) as mechanical type thermostat does
not require electric power supply.
Do not connect external electric loads.
Wire (L) and (N) should be used only for operation Electric
type thermostat.
Never connect external electric loads such as valves, fan coil
units, etc. If connected, Main PCB (Heater) can be seriously
damaged.
Thermostat
(L)(N)(C)(H)
THERMOSTAT
(Default : 230 V AC)
17
L
BR
18
N
BL
19
L1
BR
20
L2
BK
WARNING
CAUTION
WARNING
CAUTION
Accessories Installation
THERMOSTAT
(Default : 230 V AC)
17
L
BR
(L)(N)(H)
18
N
BL
Thermostat
19
L1
BR
20
L2
BK
Accessories Installation
60 Air-to-Water Heat Pump
Final check
• DIP switch setting :
Set DIP switch No. 8 to ‘ON’. Otherwise, the unit can not recognize the thermostat.
• Remote Controller :
- ‘Thermostat’ icon is displayed on the remote controller.
- Button input is prohibited.
Thermostat Icon
Thermostat Operation with Remote Controller
Following features are permitted when thermostat is installed :
•SET TEMP button
•VIEW TEMP button
•Temperature adjusting button(*)
•Sanitary water heating Enable / Disable
(*) : Adjusted temperature is only used to control electric heater on / off condition.
The unit does not turn on / off according to the setting temperature at the remote controller.
It turns on / off according to the thermostat signal.
Following features are NOT permitted when thermostat is installed :
To establish sanitary water circuit, 3way valve and sanitary water tank kit is required. If solar thermal
system is pre-installed at the installation field, solar thermal kit is required to interface solar thermal
system – to – sanitary water tank – to –
General Information
supports following 3way valve.
(1) : SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2
(for selecting Flow B), and Neutral (for common).
(2) : 'Flow A' means water flow from the indoor unit to under floor water circuit.
(3) : 'Flow B' means water flow from the indoor unit to sanitary water tank.
Sanitary Water Tank and Sanitary Water Tank Kit/Solar Thermal Kit
SupportedOperating ModePowerType
230V ACSPDT
3-wire
(1)
Selecting “Flow A” between
“ Flow A” and “ Flow B” (2)
Selecting “Flow B” between
“ Flow A” and “ Flow B” (3)
Yes
Yes
How to Install Sanitary Water Tank
For more detail information about installing sanitary water tank, please refer installation manual provided with sanitary water tank.
PHS02060310(LGRTV200E) / PHS03060310(LGRTV300E)
PHS02060320(LGRTV200VE) / PHS03060320(LGRTV300VE)
(unit : mm)
Accessories Installation
62 Air-to-Water Heat Pump
Accessories Installation
Installation Manual 63
ENGLISH
How to Install Sanitary Water Tank Kit
Fellow bellow procedures Spet 1 ~ Step 5
Step 1. Find magnetic switch and ELB(MCCB) in the kit. Fit
them into the indoor unit control box with enclosed a
braket and screws.(symbol
Ⓐ
at picture)
Step 2. Contact ‘CN_B/HEAT(A)’(white connector)of the indoor
unit PCB with magnetic switch contact using encolsed
cable(symbol
Ⓑ
at the picture). Connect magnetic
switch contactor port no. A1 and A2.
Step 3. Connect magnetic switch contactor port no.L1 and L3
with RLB(MCCB) port no. 2 and 4(symbol
Ⓒ
at the pic-
ture).
Check Poarity
• Connect magnetic switch contact port no. L1 to ELB(MCCB)
port no.2
• Connect magnetic switch contact port no. L3 to ELB(MCCB)
port no.4
Step 4. Connect magnetic switch contactor port no. T1 and T3
with terminal block 1 port 6 and 7(symbol Ⓓ at the picture).
Check Polarity
• Connect magnetic switch contact port no. T1 to terminal
block 1 port 6
• Connect magnetic switch contact port no. T3 to terminal
block 1 port 7
Step 5. 1Ø Electric Heater
’ Connect ELB(MCCB) port no.1 and 3 with block 3
port 3 and 4(symbol
Ⓔ
at the picture).
’ Connect ELB(MCCB) port no.1 and 3 with block 3
port 1 and 2(symbol Ⓔat the picture).
Check Polarity
- Connect ELB port no. 1 to terminal block 3 port 3
- Connect ELB port no. 3 to terminal block 3 port 4
- Connect MCCB port no. 1 to terminal block 3 port 1
- Connect MCCB port no. 3 to terminal block 3 port 2
CAUTION
Note:
Some models are using MCCB instead of ELB
3ø Electric Heater
1ø Electric Heater
ʶ
ʹ
ʶ
ʺ
ʸ
Terminal
Block 1
Terminal
Block 3
ʷ
13
24
Relay contactor
port no. assignment
ELB(MCCB) port no.
assignment
ʶ
ʸ
ʶ
ʹ
Terminal
Block 1
Terminal
Block 3
ʺ
Step 6. Find sanitary water tank sensor. Connect it to ‘CN_TH4’ (Red Connector) of the indoor unit
PCB (symbol
Ⓐ
at the picture). The sensor wire should be passed through holes for sensor (symbol Ⓑand Ⓒat the picture). The sensor should be mounted correctly to the sensor hole of sanitary water tank.
Sensor mounting
Insert sensor into sensor socket and bolt it tightly.
CAUTION
1Ø Electric Heater
3Ø Electric Heater
Accessories Installation
64 Air-to-Water Heat Pump
A
B
AB
C
D
Sanitary Water
Tank
C
D
Sanitary Water
Tank
Accessories Installation
Installation Manual 65
ENGLISH
How to Wire Sanitary Water Tank Heater
Step 1. Uncover heater cover of the sanitary water tank. It is located side of the tank.
Step 2. Find terminal block and connect wires as below. Wires are field-supplied item.
(L) : Live signal from PCB to Heater
(N) : Neutral signal from PCB to Heater
Wire specification
• Cross-sectional area of the wire should be 5mm
2
.
Adjusting thermostat temperature
• To guarantee proper operation, it is recommended to set temperature of thermostat to maximum
temperature (symbol at the picture).
WARNING
1Ø Electric Heater
3Ø Electric Heater
WATER
TANK
HEATER
6L7
N
BRBL
(L)(N)
WATER
TANK
HEATER
6L7
N
BRBL
(L)(N)
A
A
How to Install Solar Thermal Kit
Step 1. Check the diameter of pre-installed pipes. (symbol Ⓐ and Ⓑ)
Step 2. If the diameter of pre-installed pipes is different from diameter of solar thermal kit, it is neces-
sary to reduce or extend of pipe’s diameter.
Step 3. After Step 2., connect the pipe and solar thermal kit.
Step 4. Connect solar thermal sensor to ‘CN_TH4’(Red connector) of the indoor unit PCB.
If the sanitary tank sensor is connected, disconnect the sensor from PCB first.
LG Dry Contact is a solution for automatic control of air conditioning system at the owner's behest.
In simple words, it's a switch which can be used to turn the unit On/Off after getting the signal from
external sources like key-in lock, door or window switch etc specially used in Hotel rooms.
How to Install Dry Contact
• For more information about installing Dry Contact, Please refer installation manual provided with
Dry Contact.
• For system set-up, please read chapter 8.(Especially function code No.6)
Dry Contact
Remote temperature sensor can be installed any place a user wants to detect the temperature.
How to Install Remote Temperature Sensor
• For more information about installing Remote Temperature Sensor, Please refer installation manual
provided with Remote Temperature Sensor.
• For system set-up, please read chapter 8.(Especially function code No.3)
Remote Temperature Sensor
Accessories Installation
66 Air-to-Water Heat Pump
Solar Thermal Sensor
(less than 12 m)
Water Tank Sensor
(less than 12 m)
Water Out
Water In
Water Tank
3way valve
(Field Supply)
Pump
(Field Supply)
Water In
Water Out
Solar
Thermal
System
(Field Supply)
Solar
Collector
(Field Supply)
Accessories Installation
Installation Manual 67
ENGLISH
Final Check
• Flow direction :
- Water should flow from water outlet of the indoor unit to sanitary tank water inlet when sanitary
tank heating is selected.
- To verify the flow direction, check temperature at the water outlet of the indoor unit and water inlet
of sanitary water tank.
- If correctly wired, these temperatures should be almost equivalent if thermal insulation of water
pipe is well performed.
• Noise or water pipe vibration while 3way valve operation
- Due to surging effect or cavitation effect, noise or water pipe vibration can be occurred while
3way valve is operating.
- In that case, check followings :
• Is water circuit (both under floor water loop and sanitary water tank loop) fully charged? If not,
additional water charging is required.
• Fast valve operation yields noise and vibration. Appropriated valve operating time is 60~90 seconds.
• 3way valve should select water tank loop when electric power is
supplied to wire (W) and wire (N).
• 3way valve should select under floor loop when electric power is
supplied to wire (U) and wire (N).
WARNING
How to Wire 3Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
(W) : Live signal (Water tank heating) from PCB to 3way valve
(U) : Live signal (Under floor heating) from PCB to 3way valve
(N) : Neutral signal from PCB to 3way valve
3Way Valve
3way valve
(W)(U)(N)
3WAY VALVE
(A)
BRWHBL
8
L
9
L1
10
N
Dew Condensation
• Wrong wiring can yield dew condensation on the floor. If radiator is
connected at the under floor water loop, dew condensation can be
occurred on the surface of the radiator.
Wiring
• Normal Open type should be connected to wire (NO) and wire (N)
for valve closing in cooling mode.
• Normal Open type should be connected to wire (NO) and wire (N)
for valve closing in cooling mode.
WARNING
CAUTION
2way valve is required to control water flow while cooling operation. Role of 2way valve is to cut off
water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling operation.
General Information
supports following 2way valve.
(1) : Normal Open type. When electric power is NOT supplied, the valve is open. (When electric
power is supplied, the valve is closed.)
(2) : Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric
power is supplied, the valve is open.)
How to Wire 2Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
(NO) : Live signal (for Normal Open type) from PCB to 2way valve
(NC) : Live signal (for Normal Closed type) from PCB to 2way valve
(N) : Neutral signal from PCB to 2way valve
Final Check
• Flow direction :
- Water should not flow into under floor loop in cooling mode.
- To verify the flow direction, check temperature at the water inlet of the under floor loop.
- If correctly wired, this temperatures should not be approached to 6°C in cooling mode.
2Way Valve
YesClosing water flow230V ACNC 2-wire
(2)
YesOpening water flow
YesOpening water flow
YesClosing water flow230V ACNO 2-wire
(1)
SupportedOperating ModePowerType
2way valve
(NO)(NC)(N)
2WAY VALVE
(A)
14
L1
BR
15
L2
WH
16
N
BL
Accessories Installation
68 Air-to-Water Heat Pump
Accessories Installation
Installation Manual 69
ENGLISH
Thermostat
Conditions if Accessories are Installed
This section describes conditions about installation place where accessories are installed. Detailed
installation for accessories (including supported accessory specification, wiring, PCB setting for accessory configuration, etc) will be dealt in separated chapter.
Following location should be avoid to secure proper operation :
• Height from floor is approximately 1.5 m.
• Thermostat can not be located where the area may be hidden when door is open.
• Thermostat can not be located where external thermal influence may be applied. (such as
above heating radiator or open window)
1. NEVER USE 230V AC Thermostat and 24V AC Thermostat at the same time. If used together, it
causes short-circuit and yields power cut-off by circuit breaker.
2. Some electro-mechanical type thermostat has internal delay time to protect compressor. In that case,
mode change can takes time more than user's expectation. Please read thermostat manual carefully
if the product does not response quickly.
3. Setting temperature range by thermostat can be different with that of the product. The heating or cooling set temperature should be chosen within the setting temperature range of the product.
4. It is highly recommended that the thermostat should be installed where space heating is mainly applied.
CAUTION
Remote Air Temperature Sensor
Role and constraint while installation of remote air temperature sensor is very similar to that of thermostat.
• Distance between the indoor unit and the remote air temperature sensor should be less than 15 m
due to length of the connection cable of remote air temperature sensor.
• For other constraints, please refer to previous page where constraints about thermostat is described
ThermostatRemote Air Temperature Sensor
Direct
Sun ray contact area
Direct
Sun ray contact area
yes
no
5ft
(1.5m)
no
no
yes
no
5ft
(1.5m)
no
Connection cable
(less than 15m)
no
70 Air-to-Water Heat Pump
Sanitary Water Tank and Sanitary Water Tank Kit /
Solar Thermal Kit
Installing sanitary water tank requires following considerations :
• Sanitary water tank should be located at the flat place.
• Water quality should be complied with EN 98/83 EC Directives.
• As this water tank is sanitary water tank (indirect heat exchange), do not use anti water-freezing
treatment like ethylene grycol.
• It is highly recommend to wash out inside of the sanitary water tank after installation. It ensures
generating clean hot water.
• Near the sanitary water tank there should be water supply and water drain to easy access and
maintenance.
• Set the maximum value of the temperature control device of sanitary tank.
While installing sanitary water tank with sanitary water tank kit or solar thermal kit, there are some
constraints like below :
• Sanitary water tank should be located under the indoor unit or same height with the indoor unit.
• Sanitary water tank should be located under the solar thermal system.
• Distance between sanitary water tank sensor or solar thermal sensor should be less than 5 m.
• If there is AC power cable near the sensor cable, the sensor cable should be away from the AC
power cable at least 5 m to prevent electric noise.
Accessories Installation
Solar Thermal Sensor
(Less than 12 m)
3way valve
(Field Supply)
Water Tank Sensor
(Less than 12 m)
Water Out
Water In
Water Tank
Water In
Pump
(Field Supply)
Water Out
Solar
Thermal
System
(Field Supply)
Solar
Collector
(Field Supply)
Installation Manual 71
ENGLISH
Installing recirculation pump
When is used with sanitary water tank, it is STRONGLY recommended to install recirculation pump to prevent flooding out cold water at the end of hot water supply and to stabilize the water
temperature inside the sanitary water tank
- The recirculation pump should be operated when sanitary water demand is not required. Therefore, external time scheduler to determine when the recirculation pump should turn on and turn off is required.
- The operating duration time of the recirculation pump is calculated as follow :
Duration time [minute] = k x V x R
k : 1.2 ~ 1.5 is recommended. (If distance between pump and tank is far, then choose high number)
V : Volume of sanitary water tank [liter]
R : Water flow rate of pump [liter per minute], which is determined by pump performance curve
- The pump operating start time should be prior to the sanitary water demand.
WARNING
Accessories Installation
Hot water supply
Shower
(End of Hot
water supply)
Water Out
Water In
Sanitary
Water Tank
City water
Recirculation
Pump
Check Valve
External
Time Scheduler
72 Air-to-Water Heat Pump
2Way(3way) Valve
2Way(3way) valve should be located between the indoor unit and the water tank.
• If enough space is not secured, the 2Way(3way) valve can be partially located inside the indoor unit
by cutting out the bottom of the indoor unit.
Mice can not be appeared to prevent entering the indoor unit or attacking wires.
After cutting out the bottom of the indoor unit, remove all burrs completely. Burrs could cause personal
injury.
2Way valve should be located between the indoor unit and the water entering point to the under floor.
See below picture to identify clearly.
CAUTION
WARNING
Water In
Water Out
2way valve
(Field Supply)
domain where 2way
valve installed
Fan Coil Unit
Under floor
Before Cutting
After Cutting
Accessories Installation
Installation Manual 73
ENGLISH
9. System Set-Up
As is designed to satisfy various installation environment, it is important to set up system correctly. If not configured correctly, improper operation or degrade of performance can be expected.
DIP Switch Setting
Turn off electric power supply before setting DIP switch
• Whenever adjusting DIP switch, turn off electric power supply to avoid electric shock.
General Information
CAUTION
System Set-Up
OFF ON
1
2
3
4
5
6
7
8
OFF is selected
ON is selected
DIP Switch Information
System Set-Up
74 Air-to-Water Heat Pump
DescriptionSettingDefault
Role when central
controller is equipped
Accessory installation
information
Emergency operation
Level
External water pump
installation information
1
1
2
3
2
3
2
3
4
4
5
5
As Master
As Slave
Indoor unit + Outdoor unit
is installed
Indoor unit + Outdoor unit
+ Sanitary water tank
is installed
Indoor unit + Outdoor unit
+ Sanitary water tank
+ Solar thermal system
is installed
High temperature cycle
Low temperature cycle
External water pump is
NOT installed
External water pump is
installed
1
2
3
4
5
Selecting electric
heater capacity
Thermostat installation
information
6
7
6
7
6
7
8
8
Step 2 capacity is used
Step 1 capacity is used
Electric heater is not used
Thermostat is NOT installed
Thermostat is installed
6
7
8
System Set-Up
Installation Manual 75
ENGLISH
Emergency Operation
• Definition of terms
- Trouble : a problem which can stop system operation, and can be resumed temporally under
limited operation without certificated professional's assist.
- Error : problem which can stop system operation, and can be resumed ONLY after certificated
professional's check.
- Emergency mode : temporary heating operation while system met Trouble.
• Objective of introducing 'Trouble'
- Not like airconditioning product, Air-to-Water heat pump is generally operation in whole winter
season without any system stopping.
- If system found some problem, which is not critical to system operating for yielding heating energy, the system can temporarily continue in emergency mode operation with end user's decision.
• Classified Trouble
- Trouble is classified two levels according to the seriousness of the problem : Slight Trouble and
Heavy trouble
- Slight Trouble : a problem is found inside the indoor unit. In most case, this trouble is concerned with sensor problems. The outdoor unit is operating under emergency mode operation
condition which is configured by DIP switch No. 4 of the indoor unit PCB.
- Heavy trouble : a problem is found inside the outdoor unit. As the outdoor unit has problem, the
emergency mode operation is performed by electric heater located in the indoor unit.
- Option Trouble : a problem is found for option operation such as water tank heating. In this
trouble, the troubled option is assumed as if it is not installed at the system.
• Emergency operation level
- When system met trouble, it stops operation and wait for user’s decision : Calling service center
or starting emergency operation.
- To start emergency operation, user simply push ON / OFF button once more.
- Two different levels are prepared for emergency operation : High temperature cycle and low
temperature cycle.
- In emergency operation mode, user can not adjust target temperature.
NOTICE
High temperature cycle OFF 50°C 24°C 70°C
Low temperature cycle ON 30°C 19°C 50°C
DIP
Switch
Target
Leaving Water
Temperature
Target
Room Air
Temperature
Target
Sanitary Water
Temperature
System Set-Up
76 Air-to-Water Heat Pump
• Following features are permitted in emergency operation. :
- Operation On/Off
- VIEW TEMP button*
- Temperature adjust button*
- Sanitary water heating Enable / Disable
* : Temperature measured by failed sensor is displayed as ‘- -’.
* : Adjusted temperature is only used to control electric heater on / off condition.
The product does not turn on / off according to the setting temperature at the control panel. It turns
on / off according to the thermostat signal.
• Following features are NOT permitted in emergency operation. :
• Duplicated trouble : Option trouble with slight or heavy trouble
- If option trouble is occurred with slight (or heavy) trouble at the same time, the system puts higher
priority to slight (or heavy) trouble and operates as if slight (or heavy) trouble is occurred.
- Therefore, sometimes sanitary water heating can be impossible in emergency operation mode.
When sanitary water is not warming up while emergency operation, please check if sanitary water
sensor and related wiring are all Ok.
• Emergency operation is not automatically restarted after main electricity power is reset.
- In normal condition, the product operating information is restored and automatically restarted after
main electricity power is reset.
- But in emergency operation, automatic re-start is prohibited to protect the product.
- Therefore, user must restart the product after power reset when emergency operation has been
running.
System Set-Up
Installation Manual 77
ENGLISH
Installer Setting
How to enter installer setting mode
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it could cause problems to the unit, user injury or
property damage. This must be set by an certificated installer, and any installation or change that
is carried out by a non-certificated person should be responsible for the results. In this case, free
service cannot be provided.
?)<-:
<-58
78-:
0-)<16/
57,-
Press Function Setting button for 3 seconds
to enter the installer setting mode.
(When you enter the installer setting mode
initially, function code is displayed on the bottom
of the LCD screen.)
Repeat pressing button, and the function code
will be changed from 01 to 2B.
Please refer the code table on the next page.
CAUTION
1
?)<-:
0-)<16/
<-58
78-:
57,-
Function CodeValue
Summary
System Set-Up
78 Air-to-Water Heat Pump
Example of Fuction Code Display
Function Code Value #1Value #2
CodeItemDetailRemark
01FunctionAdditional refrigerant charging
DescriptionInstant cooling operation for charging additional refrigerant
Value #1Note-
Default01
Range-
Value #2Note-
DefaultRange-
02FunctionDisable 3 minute delay
DescriptionFactory use only
Value #1Note-
Default01
Range-
Value #2Note-
DefaultRange-
03FunctionRemote air sensor connection
DescriptionConnection information about remote air sensor
Value #1Note01:Remote air sensor is not connected and not used.
02:Remote air sensor is connected and used.
Default1
Range01 ~ 02
Value #2Note-
DefaultRange-
04FunctionCelsius / Fahrenheit switching
DescriptionDisplay temperature in Celsius or Fahrenheit
Value #1Note01:Celsius
02:Fahrenheit
Default1
Range01 ~ 02
Value #2Note-
DefaultRange-
System Set-Up
Installation Manual 79
ENGLISH
CodeItemDetailRemark
05FunctionSetting temperature selection
DescriptionSelection for setting temperature as air temperature or
leaving water temperature.
Value #1Note01:Air temperature
02:Leaving water temperature
Air temperature as setting temperature is ONLY available
when remote air sensor.
Connection is enabled and Function code 03 is set as 02.
Default2
Range01 ~ 02
Value #2Note-
DefaultRange-
06FunctionAuto dry contact
Description
If thermostat is used, value should be changed from "2" to "1".
Value #1Note01: Auto start off
Default2
Range01 ~ 02
Value #2Note-
DefaultRange-
07FunctionAddress setting
DescriptionAssigning address when central controller is installed
If thermostat is used, value should be changed from "2" to "1".
Value #1Note-
Default00
Range00 ~ FF
Value #2Note-
DefaultRange-
11FunctionSetting air temperature in cooling mode
DescriptionAdjusting range of 'Setting Air Temperature' in cooling mode
Value #1NoteUpper limit of setting range
Default30 °C
Range24 ~ 30 °C
Value #2NoteLower limit of setting range
Default18 °C
Range18 ~ 22 °C
12FunctionSetting leaving water temperature in cooling mode
DescriptionAdjusting range of 'Setting Leaving Water Temperature' in
Value #1NoteUpper limit of setting range
Default24 °C
Range20 ~ 25 °C
Setting dry contact auto start option.
02: Auto start on
cooling mode
'Setting Air
Temperature' is
used when user
wants to set target
temperature by
room air
temperature.
'Setting Leaving
Water Temperature'
is used when user
wants to set target
temperature by
leaving(from the
unit) water
temperature.
System Set-Up
80 Air-to-Water Heat Pump
CodeItemDetailRemark
12Value #2NoteLower limit of setting range(FCU is not equipped)
Default16 °C
Range16 ~ 18 °C
13FunctionSetting air temperature in heating mode
DescriptionAdjusting range of 'Setting Air Temperature' in heating mode
Value #1NoteUpper Limit of setting range
Default30 °C
Range24 ~ 30 °C
Value #2NoteLower Limit of setting range
Default16 °C
Range16 ~ 22 °C
14FunctionSetting
DescriptionAdjustin range of 'Setting
Value #1NoteUpper Limit of setting range
Default57 °C
Range35 ~ 57 °C
Value #2NoteLower Limit of setting range
Default15 °C (*20 °C)
Range15 ~ 34 °C (*20 ~ 34 °C)
15FunctionSetting DHW tank heating flow temperature for
Description
Value #1NoteUpper Limit of setting range
Default50 °C
Range50 ~ 80 °C
Value #2
18FunctionScreed drying mode
Description
Value #1Note
Value #2Note
NoteLower Limit of setting range
Default40 °C
Range30 ~ 40 °C
Default01
Range00 ~ 01
DefaultRange-
Adjusting range of 'Setting DHW tank heating flow Temperature'
After installing water pipes for under floor heating, user can select
00: Screed drying mode is not connected and not used.
Heating flow
in Domestic hot water tank heating mode
screed drying mode for curing the cement
01:Remote air sensor is connected and used.
temperature in heating mode
Heating flow
heating mode
Sanitary water heating
-
Temperature' in
'Setting air
temperature' is
used when user
wants to set
target
temperature by
room air
temperature.
'Setting Heating
flow temperature'
is used when
user wants to set
target tempera-
ture by
Heating flow
(from the unit)
temperature.
* : Electric heater
is not used
'Setting DHW
tank heating flow
Temperature' is
used when user
wants to set water
temperature of
Domestic hot
water tank.
System Set-Up
Installation Manual 81
ENGLISH
krameRliateDmetIedoC
edom gnilooc ni erutarepmet ffo-tuc gnitteSnoitcnuF22
(FCU setting included)
DescriptionDetermine leaving water temperature when the unit is turned off.
This function is used for preventing condensation
on the floor in cooling mode.
Value #1NoteCut-off temperature. Value #1 is valid when Value #2 is
'01 (that means, FCU is not installed)'."
C° 61tluafeD
C° 52 ~ 61egnaR
Value #2NoteDetermines if FCU is installed or not. '01' means 'FCU is
not installed', and '00' means 'FCU is installed.'
00tluafeD
Range00(Equipped) ~ 01(not Equipped)
23FunctionSetting outdoor temperature range for weather-dependent
operation
DescriptionSetting outdoor Max/Min temperature for weather-dependent
operation
egnar gnittes fo timiL reppUetoN1# eulaV
C° 01-tluafeD
C° 50 ~ 02-egnaR
egnar gnittes fo timiL rewoLetoN2# eulaV
C° 51tluafeD
C° 02 ~ 01egnaR
24FunctionSetting indoor air temperature range for weather-dependent
operation
DescriptionSetting indoor Max/Min temperature for weather-dependent
operation
egnar gnittes fo timil reppUetoN1# eulaV
C° 12tluafeD
C° 03 ~ 02egnaR
egnar gnittes fo timil rewoLetoN2# eulaV
C° 61tluafeD
C° 91 ~ 61egnaR
erutarepmet ffo / no retaeh cirtcele gnitteSnoitcnuF12
ffO = 6.oNffO = 6.oNhctiws PID
ffO = 7.oNnO = 7.
oNgnittes
DescriptionSetting for using Step 1 capacity
of electric heater
Outdoor air temperature where electric heater start operation.
-5°C
-5~33°C
Setting for using Step 2 capacity
of electric heater
Value #1Note
tluafeD
egnaR
DIP Switch
setting is
described in
Chapter 6 of
Installation
Manual.
System Set-Up
82 Air-to-Water Heat Pump
CodeItemDetailRemark
Function
25
DescriptionSetting Heating flow max / min temperature for
Value #1NoteUpper limit of setting range
Default57 °C
Range35 ~ 57 °C
Value #2NoteLower limit of setting range
Default15 °C (*20 °C)
Range15 ~ 34 °C (*20 ~ 34 °C)
26FunctionSetting pasteurisation operation
DescriptionSetting start/maintain time for pasteurisation
Value #1Note
Default00
Range00 ~ 01
Value #1
Value #2
27FunctionSetting pasteurisation Operation
DescriptionSetting pasteurisation temperature
Value #1NoteMaximum heating temperature
Value #2NoteMaximum heating duration in minute
28FunctionSetting control parameter for Domestic hot water heating operation
DescriptionSee below notes for each values
Value #1NoteTemperature gap from Value #2 of Function Code 28
Value #2Note
29FunctionSetting control parameter for Domestic hot water heating operation
DescriptionSee below notes for each values
Value #1
Value #2
NoteStarting date (Sunday:1,Monday:2, ···· ,Saturday:7)
Default06
Range01 ~ 07
NoteStarting time in 24 hours(00 ~ 23)
Default23
Range00 ~ 23
Default70 °C
Range40 ~ 80 °C
Default10 min
Range05 ~ 60 min
Default05 °C
Range01 ~ 20 °C
Default48 °C
Range40 ~ 48 °C
NoteTemperature gap from target Domestic hotwater temperature.
Default03 °C
Range02 ~ 04 °C
Note
Default00 : Sanitary water tank priority
Range01 : under floor heating
Setting Heating flow temperature range for weather-dependent operation
weather-dependent operation
* : Electric heater
is not used.
Domestic hot water
heating should be
Enable / Disable of pasteurisation operation(00:Disable , 01:Enable)
Maximum temperature generated by AWHP compressor cycle
(This value is required to frequent ON and OFF of water tank heater.)
Determining heating demand priority between Domestic hot water tank
heating and under floor heating
enable.
• If Domestic hot
water heating is
disable, the disinfectionmode will not
beoperated although
Value #1 of Code26
is set as '01'.
• To use
disinfection mode,
Domestic hot water
heating should be
enable.
Only available
when Domestic
hot Water
Tank is installed.
System Set-Up
Installation Manual 83
ENGLISH
Note: Some contents may not be displayed depending on DIP switch setting in the main PCB assembly 1.
CodeItemDetailRemark
FunctionMiscellaneous setting
2A
DescriptionDetermine electric heater and water heater on and off
Value #1Note00: Operate both electric heater and Domestic hot water tank heater
01: Operate only Domestic hot water tank heater
Default00
Range00 ~ 01
Value #2NoteNot used
DefaultRange-
2B
FunctionDomestic hot water heating timers
Description
Value #1Note
Default
Range5 ~ 95 min (step: 5 min)
Value #2Note
Default
Range0 ~ 600 min (step: 30 min)
Value #3Note
Default
Range20 ~ 95 min (step: 5 min)
2E
FunctionChanging thermal on / off room air temp
DescriptionSelect Thermal on / off Temperature gap.
Value #1Note
Default
Range
2F
FunctionChanging thermal on / off leaving water Ten
DescriptionSelect Thermal on / off Temperature gap.
Value #1Note
Default
Range
42
Function
Description
Default
Range
Determine following time duration : operation time of Domestic hot
water tank heating, stop time of Domestic hot water tank heating,
and delay time of sanitary tank heater operating.
This time duration defines how long time Domestic hot water tank
heating can be continued.
30 min
This time duration defines how long time Domestic hot water tank
heating can be stopped. It is also regarded as time gap between
Domestic hot water tank heating cycle.
180 min
This time duration defines how long time Domestic hot water tank
heater will not be turned on in Domestic hot water heating operation.
20 min
Thermal onThermal off
0
1
2
3
0
1
2
3
-0.5 °C
4 °C
2 °C
-1 °C
0
0 ~ 3
Thermal onThermal off
-2 °C
-6 °C
-2 °C
-1 °C
0
0 ~ 3
Setting mode lock function
Mode-lock is can operate only cooling
00 (Not use Mode-lock)
00~01
1.5 °C
6 °C
4 °C
1 °C
2 °C
4 °C
4 °C
1 °C
Common Setting
• Function Code 01 : Test Run
Test run should be performed when additional refrigerant charging is required. To charge the refrigerant, the product must run in Cooling mode. Test run instantly makes the product working in Cooling mode for 18 minutes.
Note: • If you press any kind of button during this mode, Test Run mode will be finished.
• After running 18 minutes under test run mode, system will automatically turn OFF.
• Function Code 02 : Disable 3 minute Delay
Factory use only.
• Function Code 03 : Remote Air Sensor Connection
If user connects remote air sensor to control the product by room air temperature, the connection
information should be notified to the product.
Note : If remote air sensor is connected but this function code is not set correctly, the product can
not be controlled by room air temperature.
• Function Code 04 : Celsius/Fahrenheit Switching
Temperature is displayed in Celsius or Fahrenheit.
• Function Code 05 : Setting Temperature Selection
The product can be operated according to air temperature or leaving water temperature. The selection for setting temperature as air temperature or leaving water temperature is determined.
Note : Air temperature as setting temperature is ONLY available when Remote Air Sensor Connec-
tion is enabled and Function Code 03 is set as 02.
• Function Code 06 : Auto Dry Contact
This function allows the Dry contact-indoor unit operate under Auto Run mode or Manual mode with
remote control panel.
If thermostat is used, value should be changed from "2" to "1"
• Function Code 07 : Address Setting
When Central Controller is installed, address assigning is set by this function.
System Set-Up
84 Air-to-Water Heat Pump
System Set-Up
Installation Manual 85
ENGLISH
Temperature range setting
• Function Code 11 : Setting air temperature in cooling mode
Determine cooling setting temperature range when air temperature is selected as setting
temperature.
Only available when remote air temperature sensor is connected.
• Accessory PQRSTA0 should be installed.
• Also, Function Code 03 should be set properly.
• Function Code 12 : Setting leaving water temperature in cooling mode
Determine cooling setting temperature range when leaving water temperature is selected as
setting temperature.
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than 16
°C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to the
radiator, dew generation on the surface of the radiator can be occurred.
NOTICE
NOTICE
NOTICE
• Function Code 14 : Setting leaving water temperature in heating mode
Determine heating setting temperature range when leaving water temperature is selected as
setting temperature.
• Function Code 15 : Setting sanitary tank leaving water temperature
Determine heating setting temperature range of water tank leaving water.
Only available when sanitary water tank feature is installed.
• Sanitary water tank and sanitary water tank kit should be installed.
• DIP switch No. 2 and 3 should be set properly.
• Function Code 18 : Screed drying mode.
After installing water pipes for under floor heating, user can select screed drying mode for curing the
cement.
• Function Code 13 : Setting air temperature in heating mode
Determine heating setting temperature range when air temperature is selected as setting
temperature.
Only available when remote air temperature sensor is connected.
• Accessory PQRSTA0 should be installed.
• Also, Function Code 03 should be set properly.
CAUTION
NOTICE
System Set-Up
86 Air-to-Water Heat Pump
1
Keep pressing programming button for 3 seconds to enter setting
screed drying mode.
2
Press programming button to select
function code 18.
3
Press left, right button to move to
screed drying setting part.
4
Press up, down button to adjust “01” or
“00”
(00: Not Used 01: Used)
5
If you finish the setting,
press OK / CLEAR button.
6
Press exit button to exit or system will automatically release without any
input 25 seconds.
7
During the screed drying mode, “dry” is
displayed.
Left days for completing the screed drying
mode are displayed.
Left days
System Set-Up
Temperature Control Parameter Setting
• Function Code 21 : Setting Electric Heater On/Off temperature
Using Half capacity of electric heater : when DIP Switch No. 6 and 7 is set as ‘OFF-ON’ :
- Value #1 : outdoor air temperature where half capacity of electric heater starts operation.
- Value #2 : not used.
- Example : If Value #1 is set as ‘-1’ and DIP Switch No 6. and 7 is set as ‘OFF-ON’, then half capacity of electric heater will start operation when outdoor air temperature is below -1°C and current leaving water temperature or room air temperature is much belower than target leaving water
temperature or target room air temperature.
Using Full capacity of electric heater : when DIP Switch No. 6 and 7 is set as ‘OFF-OFF’ :
- Value #1 : base outdoor air temperature.
- Value #2 : temperature gap (it means ‘how much colder than base outdoor air temperature?’)
- Example : If Value #1 is set as ‘-1’ and Value #2 is set as ‘3’ and DIP Switch No 6. and 7 is set as
‘OFF-OFF’, then full capacity of electric heater will start operation when outdoor air temperature is
below -4°C (-4 = Value #1 – Value #2) and current leaving water temperature or room air temperature is far much belower than target leaving water temperature or target room air temperature.
• Function Code 22 : Setting Cut-off Temperature in Cooling Mode (FCU setting included)
Determine leaving water temperature when the product is turned off. This function is used fr preventing condensation on the floor in cooling mode.
- Value #1 : cut-off temperature. Value #1 is valid when Value #2 is ’01 (that means, FCU is installed)’.
- Value #2 : determines if FCU is installed or not. ’01’ means ‘FCU is NOT installed’, and ’00’ means
‘FCU is installed.’
- Example : If Value #1 is set as ‘10’ and Value #2 is ’01’ and actually FCU is NOT installed in the
water loop, the product stop operation in cooling mode when the leaving water temperature is
below 10 °C.
- Example : If Value #1 is set as ‘10’ and Value #2 is ’00’ and actually FCU is installed in the water
loop, the Value #1 is not used and the product do NOT stop operation in cooling mode when the
leaving water temperature is below 10 °C.
FCU Installation
• If FCU is used, related 2way valve should be installed and connected to the indoor unit PCB.
• If Value #2 is set as ’00’ but FCU or 2way valve is NOT installed, the product can abnormal operation.
Function Code 23 and 24 : Setting Weather-dependent operation Mode
NOTICE
Installation Manual 87
ENGLISH
System Set-Up
• Function Code 23, 24, and 25 : Setting Weather-dependent operation
Weather-dependent operation is that the product automatically adjusts target temperature (leaving
water or room air) according to the outdoor air temperature.
- Value #1 and Value #2 of Function Code 23 : range of outdoor air temperature
- Value #1 and Value #2 of Function Code 24 : range of auto-adjustable target room air temperature
- Value #1 and Value #2 of Function Code 25 : range of auto-adjustable target leaving water temperature
Note : Weather-dependent operation is applied for heating mode only.
88 Air-to-Water Heat Pump
Auto-Adjustable
Target Temperature
Value #1 of
Function Code
24 or 25
Value #2 of
Function Code
24 or 25
Temperature profile
of Weather-dependent
operation
Value #1 of
Function Code 23
Value #2 of
Function Code 23
Outdoor
air temperature
System Set-Up
• Function Code 26 and 27 : Setting Disinfection operation
Disinfection operation is special sanitary tank operation mode to kill and to prevent growth of
viruses inside the tank.
- Value #1 of Function Code 26 : Selecting enable or disable of disinfection operation. ’00’ for disable, and ’01’ for enable.
- Value #2 of Function Code 26 : Determining the date when the disinfection mode is running. ’01’
for Sunday, ’02’ for Monday, … , and ’06’ for Saturday.
- Value #3 of Function Code 26 : Determining the time when the disinfection mode is running. ’00’
for 0:00am, ’01’ for 01:00am, … , ’22’ for 10:00pm, and ’23’ for 11:00pm.
- Sunday, ’02’ for Monday, … , and ’06’ for Saturday.
- Value #1 of Function Code 27 : Target temperature of disinfection mode.
- Value #2 of Function Code 27 : Duration of disinfection mode.
Vales of Function Code 26
• If Value #1 of Function Code 26 is set as ’00’, that is ‘disable disinfection mode’, Value #2 and
Value #3 is not used.
• When Value #1 is set as ’01’, that is ‘enable disinfection mode’,’ Value #2 is displayed at the position of Value #1 and Value #3 is displayed at the position of Value #2. It is due to limited width
of the control panel display.
Sanitary water heating should be enable
• If sanitary water heating is disable, the disinfection mode
will not be operated although Value #1 of Code 26 is set
as ’01’.
• To use disinfection mode, sanitary water heating should
be enable.(by button input or scheduler programming)
NOTICE
NOTICE
Time
Value #2 of
Function Code 26
Value #1 of
Function Code
27
Value #2 of
Function Code 27
Water temperature
(Inside sanitary water tank)
Temperature profile
of Disinfection operation
Press repeatedly Button to enable sanitary
tank heating
<Sanitary Water Heating Disable>
<Sanitary Water Heating enable>
Installation Manual 89
ENGLISH
System Set-Up
• Function Code 28 and 29 : Setting control parameter for Sanitary water heating operation
Descriptions for each parameters are as following.
- Value #1 of Function Code 28 : temperature gap from Value #2 of Function Code 28.
- Value #2 of Function Code 28 : maximum temperature generated by AWHP compressor cycle.
- Example : If Value #1 is set as ‘5’ and Value #2 is set as ’48’, then Session A (see the graph) will
be started when the water tank temperature is below 45°C. If temperature is above 48 °C, then
Session B will be started.
- Value #1 of Function Code 29 : temperature gap from target sanitary water temperature. This
value is required to frequent On and Off of water tank heater.
- Value #2 of Function Code 29 : Determining heating demand priority between sanitary water tank
heating and under floor heating.
- Example : If user’s target temperature is set as ’70’ and Value #1 is set as ‘3’, then the water tank
heater will be turned off when the water temperature is above 73 °C. The water tank heater will be
turned on when the water temperature is below 70 °C.
- Example : If Value #2 is set as ‘0’, that means heating priority is on sanitary water heating, sanitary water is heated by AWHP compressor cycle and water heater. In this case the under floor can
not be heated while sanitary water heating. On the other hand, if the Value #2 is set as ‘1’, that
means heating priority is on under floor heating, sanitary tank is ONLY heated by water heater. In
this case the under floor heating is not stopped while sanitary water is heated.
Sanitary water heating does not operate when it is disabled.
Enabling / Disabling of sanitary water heating is determined by pushing button.
When icon is displayed on the control panel, sanitary water heating is enabled.
(by button input or scheduler programming)
NOTICE
90 Air-to-Water Heat Pump
(Inside sanitary water tank)
Water temperature
Water heater off
temperature
Target sanitary water
temperature (set by user)
Value #2 of
Function Code 28
Starting temperature
of sanitary water heating
Value #1 of
Function Code 28
Session A
Session B
Session A : Heating by AWHP compressor cycle and water heater
Session B : Heating by water heater
Session C : No heating (Water heater is Off)
Session D : Heating by water heater
Session C
Session D
Value #1 of
Function Code 29
Time
System Set-Up
• Function Code 2A : Miscellaneous setting
- Value #1 of Function Code 2A : determine electric heater and sanitary tank heater on and off.
- Value #2 of Function Code 2A : not used.
- Example : If Value #1 is set as ‘0’, then electric heater and sanitary tank heater are on and off according to control logic. If Value #1 is set as ‘1’, then electric heater is never turned on and only
water heater is on and off according to control logic.
• Function Code 2B : Sanitary water heating timers
Determine following time duration : operation time of sanitary tank heating, stop time of sanitary
tank heating, and delay time of sanitary tank heater operating.
- Value #1 of Function Code 2B : This time duration defines how long time sanitary tank heating can
be continued.
- Value #2 of Function Code 2B : This time duration defines how long time sanitary tank heating can
be stopped. It is also regarded as time gap between sanitary tank heating cycle.
- Value #3 of Function Code 2B : This time duration defines how long time sanitary tank heater will
not be turned on in sanitary water heating operation.
- Example of timing chart :
Sanitary tank
heating is enabled
Sanitary tank heater
is enabled
Sanitary tank
heating is required
Sanitary tank
heating operation
Sanitary tank
heater operation
1=active / 0=not active
Time
2B.032B.03
2B.012B.012B.022B.022B.02
1
0
1
0
1
0
1
0
1
0
❈
Installation Manual 91
ENGLISH
Check Points, Maintenance and Troubleshooting
10. Check Points, Maintenance and Troubleshooting
If everything is going well until now, it is time to start the operation and to take advantages of .
Before starting operation, pre-check points are described in this chapter. Some comments about maintenance and how to do troubleshooting are presented.
Check List before Starting Operation
Turn off the power before changing wiring or handling product
CAUTION
• All switches having contacts for different poles should be wired
tightly according to regional or national legislation.
• Only qualified person can proceed wiring.
• Wiring and local-supplied electric parts should be complied with European and regional regulations.
• Wiring should be following the wiring diagram supplied with the
product.
• Install ELB (earth leakage breaker) with 30mA.
• ELB inside the control box of the indoor unit should be turned on before starting operation.
• Earth should be connected. Do not earth to gas or city water pipe,
metallic section of a building, surge absorber, etc.
• Use dedicated power line.
• Connections on the terminal block (inside the control box of the indoor unit) should be tightened.
• After water charging, the pressure gage (in front of the indoor unit)
should indicate 2.0~2.5 bar. Do not exceed 3.0 bar.
• During water charging, air should be taken out through the hole of
the air purge.
• If water does not splash out when the tip (at the top of the hole) is
pressed, then air purging is not completed yet. If well purged, the
water will splash out like fountain.
• Be careful when testing air purge. Splashed water may make your
dress wet.
• Two shut-off valves (located at the end of water inlet pipe and water
outlet pipe of the indoor unit) should be open.
• By-pass valve should be installed and adjusted to secure enough
water flow rate. If water flow rate is low, flow switch error (CH14) can
be occurred.
• As the indoor unit is hung on the wall, vibration or noise can be
heard if the indoor unit is not fixed tightly.
• If the indoor unit is not fixed tightly, it can fall down during operation.
• There should be no apparently damaged parts inside the indoor unit.
• Refrigerant leakage degrades the performance. If leakage found,
contact qualified LG air conditioning installation person.
• While cooling operation, condensed dew can drop down to the bottom of the indoor unit. In this case, prepare drainage treatment (for
example, vessel to contain condensed dew) to avoid water drop.
No Category Item Check Point
1
Electricity
Field wiring
Protective devices
Earth wiring
Power supply
Terminal block wiring
Charged water pressure
Air purge
Shut-off valve
By-pass valve
Hang to the wall
Parts inspection
Refrigerant leakage
Drainage treatment
Water
Product Installation
2
3
4
5
6
7
8
9
10
11
12
13
92 Air-to-Water Heat Pump
Check Points, Maintenance and Troubleshooting
To assure best performance of , it is required to perform periodical check and maintenance.
It is recommended to proceed following check list for once a year.
Maintenance
Turn off the power before proceeding maintenance
CAUTION
During test operation in winter, it will drive the heating operation focused.
Before cooling test operation, to concern freezing of the plate heat exchanger, performing
the cooling test operation after raising the water temperature up to 30℃ in the heating
mode.
CAUTION
• In normal state, the pressure gage (in front of the indoor unit) should
indicate 2.0~2.5 bar.
• If the pressure is less than 0.3 bar, please recharge the water.
• Close the shut-off valves and disassemble strainer. Then wash the
strainer to make it clean.
• While disassembling the strainer, be careful for water flood out.
• Open the switch of the safety valve and check if water is flood out
through the drain hose.
• After checking, close the safety valve.
• Look and inspect if there is loosen or defected connection on the
terminal block.
No Category Item Check Point
Water
Electricity
Water pressure
Strainer(Water filter)
Safety valve
Terminal block wiring
1
2
3
4
Installation Manual 93
ENGLISH
Test Run
1
Check to see whether there is any refrigerant leakage, and check whether the power or
transmission cable is connected properly.
2
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal
block and ground. Do not operate in the case of 2.0 MΩ or less.
NOTE: Never carry out mega ohm check over terminal control board.
Otherwise the control board may break.
Immediately after mounting the unit or after leaving it turned off for an extended
length of time, the resistance of the insulation between the power supply
terminal board and the ground may decrease to approx. 2.0 MΩ as a result of
refrigerant accumulation in the internal compressor.
If the insulation resistance is less than 2.0 MΩ, turn on the main power supply.
Check before Test run
Check Points, Maintenance and Troubleshooting
If operates not properly or it does not start operation, please check following list.
Troubleshooting
Turn off the power before proceeding troubleshooting
Troubleshooting for Problem while Operation
CAUTION
94 Air-to-Water Heat Pump
No Problem Reason Solution
Heating or cooling is not
satisfactory.
Although electric power
supply is OK (remote
controller displays
information), the unit does
not start working.
Water pump noise.
Water is flood out through
drain hose.
Sanitary water is not hot.
• Setting target temperature
is not proper.
• Charged water is not
enough.
• Water inlet temperature is
too high.
• Water inlet temperature is
too low.
• Air purging is not
completely finished.
• Water pressure is low.
• Too much water is
charged.
•
Expansion tank is
damaged.
•
Thermal protector of
water tank heater is
activated.
• Sanitary water heating
is disabled.
• Water flow rate is low.
1
2
3
4
5
• Set target temperature correctly.
• Check if temperature is water-based or air-based. See Function
code 03 and 05 in Chapter 6.
• Check pressure gage and charge more water until pressure gage
is indicating 200~250 kPa.
• Check if strainer gathers too much particles. If so, strainer should
be cleaned.
• Check if internal water pump speed is NOT set as ‘High’. It should
be set as ‘High.’
• Check if pressure gage indicates above 30 kPa.
• Check if water pipe is getting closed due to stacked particles or
lime.
• If water inlet temperature is above 55 °C, the unit does not
operated for the sake of system protection.
• If water inlet temperature is below 5 °C, the unit does not operated
for the sake of system protection. Wait while unit warms up the
water inlet temperature.
• Open the cap of air purge and charge more water until pressure
gage is indicating 200~250 kPa.
• If water does not splash out when the tip (at the top of the hole) is
pressed, then air purging is not completed yet. If well purged, the
water will splash out like fountain.
• Check if pressure gage indicates above 30 kPa.
• Check if the expansion tank and pressure gage operates well.
• Flood out the water by opening the switch of the safety valve until
pressure gage is indicating 200~250 kPa.
• Replace the expansion tank.
• Open the side panel of the sanitary water tank and push the reset
button of the thermal protector. (for more detail information, please
refer to installation manual of sanitary water tank.)
• Push button and identify if icon is displayed on the
remote controller.
Check Points, Maintenance and Troubleshooting
Installation Manual 95
ENGLISH
Troubleshooting for Error Code
Code
No.
DescriptionCauseNormal Condition
1Problem in remote room air sensor
• Incorrect connection between
sensor and PCB(Heater).
• PCB(Heater) fault
• Sensor fault
• Resistance: 10 kΩ at 25
centigrade (unplugged) → for
Remote room air sensor
• Resistance: 5 kΩ at 25 centigrade
(unplugged) → for all sensors
EXCEPT remote room air sensor
• Voltage: 2.5 V DC at 25 centigrade
(plugged) (for all sensors)
• Refer resistance-temperature table
to check in different temperature
2Problem in refrigerant (inlet side) sensor
6Problem in refrigerant (outlet side) sensor
8Problem in water tank sensor
16Problems in sensors
17Problem in water-inlet sensor
18Problem in water-outlet sensor
19Problem in water-interim sensor
3
Bad communication between remote
controller and unit.
• Incorrect connection between
sensor and PCB(Heater)
• PCB(Heater) fault
• Sensor fault
• Wire connection between remote
controller and Main PCB
assembly(Heater) should be tight
• Output voltage of PCB should be
12 V DC
5
Bad communication between Main PCB
assembly(Heater) and Main PCB
assembly(Inverter) of the unit.
• The connector for transmission is
disconnected
• The connecting wires are
misconnected
• The communication line is broken
• Main PCB assembly(Inverter) is
abnormal
• Main PCB assembly(Heater) is
abnormal
• Wire connection between remote
control panel and Main PCB
assembly(Heater) should be tight.
53
9PCB program (EEPROM) fault
• Electrical or mechanical damage a
the EEPROM
• This error can not be permitted
14Problem in flow switch
• Flow switch is open while internal
water pump is working
• Flow switch is closed while internal
water pump is not working
• Flow switch is open while DIP
switch No. 5 of Main PCB
assembly(Heater) is set as on
• Flow switch should be closed while
internal water pump is working or
DIP switch No. 5 of Main PCB
assembly(Heater) is set as on
• Flow switch should be open while
internal water pump is not working
15Water pipe overheated
• Abnormal operation of electric
heater
• Leaving water temperature is
above 57 ℃
• If there is no problem in electric
heater control, possible maximum
leaving water temperature is 57 ℃
20Thermal fuse is damaged
• Thermal fuse is cut off by
abnormal overheating of internal
electric heater
• Mechanical fault at thermal fuse
• Wire is damaged
• This error will not be happened if
temperature of electric heater tank
is below 80 ℃
n Calculate refrigerant concentration
Refrigerant concentration =
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
3
)
Limiting concentration: 0.44kg/m3(R410A)
Check Points, Maintenance and Troubleshooting
The A-weighted sound pressure emitted by this product is below 70 dB.
• The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a
correlation between the emission and exposure levels, this cannot be used reliably to determine
whether or not further precautions are required. Factor that influence the actual level of exposure of
the workforce include the characteristics of the work room and the other sources of noise, i.e. the
number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard
and risk.
Airborne Noise Emission
Limiting concentration is the limit of Freon gas concentration where immediate measures can be
taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall
be described in the unit of kg/m
3
(Freon gas weight per unit air volume) for facilitating calculation
Limiting concentration
96 Air-to-Water Heat Pump
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.