LG GR-282MF Owner’s Manual

SERVICING PRECAUTIONS
Air Recharging in Compressor
Test the refrigeration by connecting itelectrically before refilling operation. It is necessary to ascertain the function
of the motor*compressor and identify the defects immediately. If the defects have been found, empty the old
system of eventual R-12 residue by breaking off the end of the extension piece at its narrow point. (Figure 1)
POINTTO BE BROKEN
SERVICE TUBE EXTENSION
Figure 1
It is necessary to execute the soldering operation with valve open so that the fumes caused by oil residue can come out freely without blowholes between two tubes during heating the point to be soldered. The extension fitted with the male Hansen is connected to
the female fitting of the vacuum pump tube. (Figure 3)
CHARGE TUBE EXTENSION
MALE HANSEN
SOLDERING POINT
Figure 2
vacuum operation is over, add the quantity in grams of
R-12 to the refrigerant system. Remember that every system has an exact quantity of R-12 with a tolerance of +5 grams that can be added. (Figure 4)
TO THE R-12CYLINDER
_= J_ TOsTTHEEMREgRIGERATION
Figure 4
Before performing this operation (if the vacuum pump and
refilling cylinder are connected), make sure that the valve
placed between the vacuum pump and refilling tube are closed to keep the Freon for adding to the system. (Figure 5)
FILLING OR VALVE TQ BE OPENED CHARGE TUBE WHEN REFILLING
TO THE REFRIGERATION TO THE CHARGE SYSTEM CYLINDER
puOMT_ cUUM
PRESSURE
GAUGE
Figure 3
Air evacuating from the system begins so soon as the pump starts. The refrigeration system must be kept under
vacuum until the reading on the low-pressure gauge indicates vacuum (0 absolute, -1 atm., -760 mm hg) in any case it is advisable to keep the pump running for about 60 minutes. (Figure 3)
In case that a considerable leakage occurs and to stop the vacuum pump will be necessary and add a small quantity of Freon to the system, if vacuum should not be obtained (pressure gauge can't fall to 1 atmosphere), start the refrigeration unit and find the leakage with the special leak- finder. When the defective soldering point is visible, re-do it after opening the extension tube valve and reestablishing the normal outside pressure inside the group.
Because the melted alloy is sucked into the tubes and block them, the pressure must be rebalanced when vacuum is in the system in soldering. As soon as the
VALVE TO BE CLOSED AFTER VACUUM
TO THE VACUUM PUMP
In addition, check the graduated scale on the cylinder for the quantity of R-12 to be added, for example, if we have
750 grams of Freon in the cylinder and must add 165 grams to the group, this amount will be reached when
R-12 has dropped to 585 grams, remembering that the
indicator shows a lower limit of meniscus. Do this after choosing the scale corresponding to the gas pressure
different scales reported as the same gas pressure
indicated by the pressure gauge on the top of the column. To make R-12 flow into the system, open the valve placed
at the base of the cylinder and connected to the filling tube. The amount of Freon cannot be added to the system all at once because it may cause a blocking of
motor-compressor. Therefore, proceed by adding original quantity of about 20-30 grams and close the valve
immediately. The pressure rises and the motor-compressor must start,
sucking the gas and making the pressure go down again.
Regulate the valve again, maintaining the same manner
until reaching to the quantity of R-12 established for the system being charged. When the system is running, the suction pressure must be stabilized between 0.10 to 0.4 atmosphere.
Figure 5
-3-
Air Recharging in Compressor
Test the refrigeration by connecting it electrically before refilling operation. It is necessary to ascertain the function
of the motor*compressor and identify the defects immediately, If the defects have been found, empty the old
system of eventual R-134a residue by breaking off the end of the extension piece at its narrow point. (Figure 1)
vacuum operation is over, add the quantity in grams of
R-134a to the refrigerant system. Remember that every system has an exact quantity of R-134a with a tolerance of +5 grams that can be added. (Figure 4)
POINTTO BE BROKEN
CHARGE TUBE EXTENSION
MALE HANSEN
SERVICE TUBE EXTENSION
Figure 1
SOLDERING POINT
Figure 2
It is necessary to execute the soldering operation with valve open so that the fumes caused by oil residue can come out freely without blowholes between two tubes during heating the point to be soldered. The extension fitted with the male Hansen is connected to
the female fitting of the vacuum pump tube. (Figure 3)
UM
_i TO TiE R-134a CYLINDER
__ TyOsTTHEEMREFRIGERATiON
Figure 4
Before performing this operation (if the vacuum pump and
refilling cylinder are connected), make sure that the valve
placed between the vacuum pump and refilling tube are closed to keep the Freon for adding to the system. (Figure 5)
FILLING OR VALVE TO BE OPENED
CHARGE TUBE WHEN REFILLING
TO THE REFRIGERATION TO THE CHARGE
SYSTEM CYLINDER
VALVE TO BE CLOSED AFTER VACUUM
TO THE VACUUM PUMP
Figure 5
PRESSURE
GAUGE
Figure 3
Air evacuating from the system begins so soon as the pump starts. The refrigeration system must be kept under
vacuum until the reading on the low-pressure gauge indicates vacuum (0 absolute, -1 atm., -760 mm hg) in any case it is advisable to keep the pump running for about 60 minutes. (Figure 3)
In case that a considerable leakage occurs and to stop the vacuum pump will be necessary and add a small quantity of Freon to the system, if vacuum should not be obtained (pressure gauge can't fall to 1 atmosphere), start the refrigeration unit and find the leakage with the special leak- finder. When the defective soldering point is visible, re-do it after opening the extension tube valve and reestablishing the normal outside pressure inside the group.
Because the melted alloy is sucked into the tubes and block them, the pressure must be rebalanced when vacuum is in the system in soldering. As soon as the
In addition, check the graduated scale on the cylinder for the quantity of R-134a to be added, for example, if we have
750 grams of Freon in the cylinder and must add 165 grams to the group, this amount will be reached when
R-134a has dropped to 585 grams, remembering that the
indicator shows a lower limit of meniscus. Do this after choosing the scale corresponding to the gas pressure
different scales reported as the same gas pressure
indicated by the pressure gauge on the top of the column. To make R-134a flow into the system, open the valve
placed at the base of the cylinder and connected to the filling tube. The amount of Freon cannot be added to the system all at once because it may cause a blocking of
motor-compressor. Therefore, proceed by adding original quantity of about 20-30 grams and close the valve
immediately. The pressure rises and the motor-compressor must start,
sucking the gas and making the pressure go down again.
Regulate the valve again, maintaining the same manner
until reaching to the quantity of R-134a established for the system being charged. When the system is running, the suction pressure must be stabilized between 0.10 to 0.4 atmosphere.
-4-
1. SPECIFICATIONS
1-1 GR-242M / MV/S/SV
ITEMS
FREEZER
NETCAPACITY
(§/)
DIMENSIONS (mm) NET WEIGHT (kg)
COOLING SYSTEM TEMPERATURE CONTROL
DEFROSTING
OUT CASE
INNER CASE INSULATION
REFRIGERATOR
TOTAL
SPECIFICATIONS
60_ 140_
200_
540(W)x607(D)x1407(H)
46
FanCooling Knob Dial
Full Automatic Heater Defrost
With a Timer
Coated SteeI Sheet
ABS
Polyurethane Foam
ITEMS
FREEZER
SHELF
REFRIGERATOR VEGETABLETRAY EGG TRAY
ICETRAY ICE BANK COMPRESSOR
EVAPORATOR CONDENSER
REFRIGERANT LUBRICATING OIL
SPECIFICATIONS
1 EA
2 EA 1 EA 1 EA
1 Pieces(PLASTIC) 1 Piece
RT.C Starting Type Fin Tube Type
Pipe on Sheet Type R-12 (140g)
HTS-95 (210cc)
1-2 GR-282M I MV I SI SV
ITEMS
FREEZER
NETCAPACITY
DIMENSIONS (mm)
NET WEIGHT (kg)
COOLING SYSTEM TEMPERATURE CONTROL
DEFROSTING
OUT CASE
INNER CASE INSULATION
REFRIGERATOR
TOTAL
SPECIFICATIONS
60.12
170_ 230_
540(W)x607(D)x1553(H)
48
FanCooling Knob Dial
Full Automatic Heater Defrost
With a Timer
Coated SteeI Sheet
ABS
Polyurethane Foam
ITEMS
FREEZER SHELF
REFRIGERATOR
VEGETABLETRAY EGG TRAY
ICE TRAY
ICE BANK
COMPRESSOR
EVAPORATOR CONDENSER
REFRIGERANT LUBRICATING OIL
SPECIFICATIONS
1 EA 3 EA
1 EA 1 EA
1 Pieces(PLASTIC) 1 Piece
RT.C Starting Type Fin Tube Type
Pipe on Sheet Type R-12 (140g)
HTS-95 (210cc)
-5-
1-3 GR-242MF / MVF / SF / SVF
ITEMS
FREEZER
NETCAPACITY
(§/)
DIMENSIONS (mm) NET WEIGHT (kg)
COOLING SYSTEM TEMPERATURE CONTROL
DEFROSTING
OUT CASE
INNER CASE INSULATION
REFRIGERATOR
TOTAL
SPECIFICATIONS
60_ 140_
200_
540(W)x607(D)x1407(H)
46
FanCooling Knob Dial
Full Automatic Heater Defrost
With a Timer
Coated SteeI Sheet
ABS
Polyurethane Foam
ITEMS
FREEZER SHELF
REFRIGERATOR VEGETABLETRAY EGG TRAY
ICETRAY ICE BANK COMPRESSOR
EVAPORATOR CONDENSER
REFRIGERANT LUBRICATING OIL
SPECIFICATIONS
1 EA
2 EA 1 EA 1 EA
1 Pieces(PLASTIC) 1 Piece
RT.C Starting Type Fin Tube Type
Pipe on Sheet Type Rq34a (120g) FREOL ¥_2G (210cc)
1-4 GR-282MF / MVF / SF / SVF
ITEMS
FREEZER
NETCAPACITY
DIMENSIONS (mm)
NET WEIGHT (kg)
COOLING SYSTEM TEMPERATURE CONTROL
DEFROSTING
OUT CASE
INNER CASE INSULATION
REFRIGERATOR
TOTAL
SPECIFICATIONS
60.12
170_ 230_
540(W)x607(D)x1553(H)
48
FanCooling Knob Dial
Full Automatic Heater Defrost
With a Timer
Coated SteeI Sheet
ABS
Polyurethane Foam
ITEMS
FREEZER SHELF
REFRIGERATOR
VEGETABLETRAY EGG TRAY
ICE TRAY
ICE BANK
COMPRESSOR
EVAPORATOR CONDENSER
REFRIGERANT LUBRICATING OIL
SPECIFICATIONS
1 EA 3 EA
1 EA 1 EA
1 Pieces(PLASTIC) 1 Piece
RT.C Starting Type Fin Tube Type
Pipe on Sheet Type R-134a (120g)
FREOL ¥_2G (210cc)
-6-
2. PARTS IDENTIFICATION
FREEZER
COMPARTMENT
Freezer Temperature
Control Dial
Freezer Shelf -
Ice Tray
Ice Cube Box
REFRIGERATOR
COMPARTMENT
Freezer Door Rack
-- Egg Storage Rack
Refrigerator Temperature --
Control Dial
Lamp --
Shelves --
Vegetable Drawer --
Used to keep fruits
and vegetables, etc.
fresh and crisp.
Refrigerator Door Rack
Leveling Screws
NOTE : This is a basic model. The shape of refrigerator is subject to change.
-7-
3. DISASSEMBLY
3-1 HOW TO REPLACE THE DOOR OPENING TYPE (when converting from the left-opening type to right opening type)
1,Separate the Cap Oand Hinge Upper 2. Separating the Freezer Door _,
@
3, Separating the Hinge-C Oand the Refrigerator
Door
5, Move the Position of Adjustable Screw
Assembly O:
4. Separating the Hinge Lower
6, Assemble the Hinge Lower _.
-8-
Loading...
+ 11 hidden pages