LG GJ176P User Manual

LG
SPECIFICATIONS for LG HERMETIC COMPRESSOR
R410A
G J 1 7 6 P 1PH, 220/240V – 50Hz
Application Range
Compressor Cooling Natural Eva. Temp. Range -10℃ ~ 12℃ 14℉ ~ 54℉ Condensing Temp. 65℃ max. 149℉ max. Return Gas Temp. 35℃ max. 95℉ max. Discharge gas Temp. 115℃ max. 239℉ max. Motor Wire Temp. 130℃ max. 266℉ max.
Rated Performance
Capacity 14,400/14,550 Btu/h 4,220/4,264 Watts Motor Input 1,485/1,532 W Current Not Fixed EER 9.7/9.5 Btu/W.h 2.84/2.78 W/W
Compressor Data
Design Rolling Piston Typed Rotary Displacement 17.6 cc/rev 1.07 in Oil / Oil Charge FVC 68D (PVE) / 440 cc Weight 14.7 Kg 32.3 lb
Motor Data
Motor Type 2 Pole Induction (PSC) Voltage Range 198 V to 264 V Locked Rotor Amps. Not Fixed
3
/rev
Standard Dimensions
33
10.0
±0.15
Φ127.7
0.5
113
±3
Φ75
2.3
DIS. I.D 9.7
42
±3
293.6
251.6
20
Detail of ⓐ Detail of ⓑ
SUC. I.D 12.8
±3
229
266.2
37.2
10.0
0.5
0.15
0
120
Φ176
S
R
C
90
Electrical Components
Running Capacitor 40 ㎌ 400 VAC (Not Fixed) Overload Protector Internal Type (Not Fixed)
Capacity Test Conditions
Evaporating Temp. 7.2℃ 45℉ Condensing Temp. 54.4℃ 130℉ Return Gas Temp. 35.0℃ 95℉ Liquid Temp. 46.1℃ 115℉ Ambient Temp. 35.0℃ 95℉
Specifications are subject to change without notice. Normal Performance value ±5%.
Compressor Mounting Wiring Diagram
Bolt, Stud
Nut, Hexagon
Comp. Tri-plate
Grommet
Unit Base
Washer, Plain
28 mm
(1.10 inch)
C
Line
Running Capacitor
C.S.R mark is embossed on a Cover Terminal
Air Conditioning Compressor Division
S
R
Compressor
O.L.P
Loading...