LG DK-H1208C00 INSTALLATION MANUAL

LG Single Packege-Type Air Conditioner
INSTALLATION MANUAL
LG
IMPORTANT
• Please read this installation manual completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
ENGLISH ITALIANO FRANÇAIS DEUTSCH
кмллдав ьбхд
ESPAÑOL
2 Single Package Type Air Conditioner
Single Package Type Air Conditioner Installation Manual
TABLE OF CONTENTS
Safety Precautions .................................................................................................3
Introduction.............................................................................................................8
Symbols Used in this Manual ...............................................................................8
Features................................................................................................................8
Dimensional Data ...................................................................................................9
Installation of Unit................................................................................................12
Inspection............................................................................................................12
Location and Recommendations ........................................................................12
Ductwork .............................................................................................................13
Information ..........................................................................................................13
Condensate Drain Piping....................................................................................14
Filter Installation .................................................................................................14
Installation of remote controller...........................................................................15
Electrical Wiring ..................................................................................................17
Control Wiring .....................................................................................................18
Start-Up Pre-Start Quick Check List...................................................................20
Test Mode Procedure..........................................................................................21
Trial Run Mode....................................................................................................23
Group Control .....................................................................................................23
Evaporator Fan Adjustment ................................................................................24
Starting the Unit ..................................................................................................25
Final Installation Checklist and Maintenance......................................................26
Installation guide at the seaside .........................................................................28
Safety Precautions
Installation Manual 3
ENGLISH
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Be sure to read before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified
by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Installation
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
4 Single Package Type Air Conditioner
Safety Precautions
Operation
Use the specified wires to connect the unit.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
• There is risk of fire or electric shock.
Do not place anything on the power cable.
• There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during operation.
• There is risk of fire or electric shock.
Do not touch(operate) the product with wet hands.
• There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.
Safety Precautions
Installation Manual 5
ENGLISH
Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
• There is risk of electric shock.
Do not allow water to run into electric parts.
• It may cause There is risk of fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off.
There
is risk of explosion or fire
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
• There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.
Do not open the panel of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Gasolin
6 Single Package Type Air Conditioner
Safety Precautions
Installation
Always check for gas (refrigerant) pressure after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Don't use people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the unit.
• This could result in personal injury and product damage.
Having perfect vacuum process in the factory, our units don't have drier but have filter in the refrigerant circuit.
In case of recharging gas in the field,
"DRIER" must be installed on the liquid line which is connected from discharge part of
condenser to intake part of evaporator. Because the refrigerant circuit is capable of containing water with imperfect vacuum.
90°
Safety Precautions
Installation Manual 7
ENGLISH
Operation
Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter.They are very sharp!
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every four weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Thinner
Wax
8 Single Package Type Air Conditioner
Introduction
Return
Control access panel
Refresh air
hood
Air intake vents
Supply
Air outlet vents
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Introduction
Symbols Used in this Manual
Features
Front View
Rear View
Installation Manual 9
ENGLISH
Dimensional Data
Dimensional Data
Single packaged cooling unit are designed for outdoor mounting with vertical condenser discharge. They can be located either at ground level or on roof. Each unit contains an operating charge of Refrigerant as shipped.
Unit Dimensions(Figure 1A)
E
G
F
Center line of hole
A
B
CLEARANCE 36"
CLEARANCE
18"
(HORIZONTAL)
CLEARANCE
32"
(DOWN FLOW)
CLEARANCE
34"
1" Dia. hole control wires
1
1
/2" Dia. hole power wires
1
1
/2" Dia. hole other purpose
CLEARANCE 48"
D
C
A 42 19/32(1082) B 43 11/16(1109) C 64 3/16(1630) D 42 17/32(1080) E7
5
/16(185)
F2
3
/8(60)
G2
15
/16(70)
6.25RT/7.5RT
Unit : Inch(mm)
Horizontal Application Unit(Figure 1B)
Rear view showing duct opening for horizontal air flow.
A
G
H
BCD
E
SUPPLY
RETURN
F
Figure 1B
Figure 1A
Unit : Inch(mm)
Down flow application unit (Figure 1C)
10
15
/16
(278)
9
3
/16
(233)
14
9
/16
(370)
6
13
/32
(163)
3
29
/32(99)
B
3
29
/32
(99)
A24 1/4(616)
SUPPLY
RETURN
1" Condensate Location
Top view
Unit : Inch(mm)
Figure 1C
UNITS
A 14 13/16(377) B9
4
/16(235) C 10 15/16(278) D2
7
/16(62)
E9
6
/16(136) F 22 9/16(700) G 18 5/16(465) H4
11
/32(110)
6.25RT/7.5RT
UNITS
A 27 9/16(700) B 18
5
/16(465)
6.25RT/7.5RT
UNITS
Unit : Inch(mm)