LG Código de Erros Ar Condicionado Schematic

Keyword

Response

00

Text the 1, 2 or 3 digit fault code number only. I.e. If you see fault code CH07 on your indoor unit or R/Controller, only type 7 or 07 in your text message.

 

 

01

Indoor unit return air sensor fault. Disconnect sensor from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace sensor

 

 

1

Indoor unit return air sensor fault. Disconnect sensor from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C if not replace sensor

 

 

02

Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5

kOhm at 25C. If not replace sensor.

 

2

Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5

kOhm at 25C. If not replace sensor.

 

03

Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power

3

Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power

04

RAC Product = Heat Sink Sensor Error, Open/Short Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check drain pan is empty,

check pump is working OK. If no pump check blue jumper plug is inserted in socket CN Float.

 

4

RAC Product = Heat Sink Sensor Error, Open/Short Cct or over 95C. Commercial Product = Condensate pump float switch risen. Check drain pan is empty,

check pump is working OK. If no pump check blue jumper plug is inserted in socket CN Float.

 

05

Comms Error, check your wiring, remove external pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

 

 

5

Comms Error, check your wiring, remove external pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

 

 

06

Indoor unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10C and 4 kOhm at 30C. if not replace sensor. Split = text 21

 

 

6

Indoor unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10C and 4 kOhm at 30C. if not replace sensor. Split = text 21

 

 

07

Multi Splits and Multi V = indoor unit is set to run in a different mode from the master indoor unit. Set ALL indoor units to cooling or ALL to heating to clear.

Splits = Compressor Over Current (CT2), also see Code 06.

 

7

Multi Splits and Multi V = indoor unit is set to run in a different mode from the master indoor unit. Set ALL indoor units to cooling or ALL to heating to clear.

Splits = Compressor Over Current (CT2), also see Code 06.

 

 

RAC Indoor unit BLDC Fan problem. This is caused by the Indoor fan being locked. Check fan motor is plugged in correctly, Electrically & Mechanically sound.

08

Check the fan motor turns freely, check the AC Voltage supplied to the fan motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If no

 

Voltage is present the the PCB is faulty, if Voltage is present the fan motor will be Faulty.

 

RAC Indoor unit BLDC Fan problem. This is caused by the Indoor fan being locked. Check fan motor is plugged in correctly, Electrically & Mechanically sound.

8

Check the fan motor turns freely, check the AC Voltage supplied to the fan motor, this will vary from 120 V ac at low speed to 170V AC at high speed. If no

 

Voltage is present the the PCB is faulty, if Voltage is present the fan motor will be Faulty.

09

Split = Outdoor unit fan problem. Check Outdoor fan motor is plugged in, Electrically & Mechanically sound, if not replace motor, otherwise replace PCB. Multi V

= Indoor unit EEPROM error - Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control.

 

 

 

9

Split = Outdoor unit fan problem. Check Outdoor fan motor is plugged in, Electrically & Mechanically sound, if not replace motor, otherwise replace PCB. Multi V

= Indoor unit EEPROM error - Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control.

 

 

 

10

RAC Product: Compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C, 168 kOhm at 30C. Multi Fdx & Multi V text 8

 

 

11

Multi V indoor unit not connected to an outdoor unit. Check comms wiring is correct, and check initialisation has been carried out correctly

12

RAC Product = EEPROM Sum Check Error, text 60 for help.

13

RAC Product = PSC (Reactor) Error, text 27 for help.

14

RAC Product = Compressor Phase Current Error

15

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

16

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

17

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

18

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

19

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

20

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

21

Inverter compressor run current high. Check compressor windings all equal 1 to 4 Ohms, Check to earth 50 MOhm minimum, check run current

 

 

22

Inverter compressor run current high. Check compressor windings all equal 1 to 4 Ohms . Check to earth 50 MOhm minimum, check run current

 

 

23

Inverter dc voltage low. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter PCB

24

Splits and Multi Splits = High or low pressure trip. Low at 1 bar High at 35 bar check pressures. Multi V = High pressure trip.

25

Check power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK, check fuses, if fuses are OK replace outdoor

main PCB

 

26

Inverter compressor seized. Check compressor windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum, check run current and Inverter

outputs

 

27

Inverter current irregularity. Check inverter PCB, check reactor connections and its resistance is less than 1 ohm.

28

Inverter dc voltage too high. Check dc voltage of capacitors 300 Vdc for 1Ph and 600 Vdc for 3Ph. If OK change outdoor inverter PCB

29

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

30

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

31

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

32

Inverter compressor discharge temperature too high. If over 105°C, check refrigerant charge

33

Excessive rise of standard compressor discharge temperature. If over 105°C check refrigerant charge

34

Excessive high pressure rise, over 35 bar at HP sensor. Check pressures, check coils, and filters are clean check for OFN in system pipework

35

Excessive low pressure drop under 1 Bar at LP sensor. Check pressures, and check service valves open

36

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

37

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

38

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

39

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

40

Inverter ac current abnormal. Check compressor windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum, check run current and inverter

outputs

 

41

Inverter compressor discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C.

42

Low pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar

43

High pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar

44

Outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at 30C and 13 kOhm at 20C. If OK replace PCB, if not replace sensor

 

 

45

Outdoor unit coil sensor fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

46

Outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

47

Compressor discharge sensor fault. Disconnect from PCB measure resistance. 237 kOhm at 20°C and 168 kOhm at 30°C. If OK replace PCB, if not replace

sensor

 

48

Split/Multi Split = Outdoor unit discharge and air sensor both unplugged. Multi V = Outdoor unit coil sensor. Text 45 for diagnostics

49

Check power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK check fuses, if fuses OK, replace outdoor main

PCB

 

50

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

51

Unit mismatch. Check model number of units do not exceed maximum. Multi V - also check Sub outdoor unit dipswitch settings

52

Communication error between inverter PCB and main outdoor unit PCB. Check wiring fuses and LEDs . If OK either inverter or main PCB defective

 

 

53

Comms error indoor to outdoor unit. Check your wiring . Split and Multi - check voltage from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4

 

 

54

Reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

 

 

55

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

56

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

57

Comms error between outdoor main PCB and inverter PCB. Check wiring fuses and LEDs are lit. If OK either inverter or main PCB defective

58

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

59

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

60

Outdoor unit PCB EEPROM failure, try removing EEPROM and refitting if removable (possible contact fault), otherwise replace PCB if the EEPROM is non-

removable.

 

61

Condenser coil over 65°C. Check coil and filters are clean and free from debris, and airflow is OK. Check system pressures for non-condesables

 

 

62

Inverter over 85°C. Check air flow across heat sink, check inverter tight to heatsink use thermal paste. Multi V - check inverter cooling fan

63

Multi F(DX) - "Cond. Pipe Sensor Temp. Low" (opposite to Error Code 61). Check Temperature/Resistance reading and replace sensor if found to be faulty. If

sensor okay, check for cause of low temperature and rectify.

 

64

no such fault code Text 1, 2 or 3 digit fault code number only. If you see fault code CH07 only type 7 in your text message

65

Outdoor unit inverter fin temperature sensor fault. Disconnect from PCB measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C

67

Outdoor Fan Motor siezed, or rotation sensing circuit failure. Check motor for mechanical and/or electrical failure, if okay replace pcb.

100

Excessive discharge temperature rise 105°C Sub condenser 1 standard compressor. Check refrigerant

101

Excessive discharge temperature rise 105°C Sub condenser 1 standard compressor. Check refrigerant

102

Excessive discharge temperature rise 105°C Sub condenser 2 standard compressor. Check refrigerant

103

Excessive discharge temperature rise 105°C Sub condenser 2 standard compressor. Check refrigerant

104

Communication error between Main and Sub outdoor units. Check comms wiring and power to all outdoor units

105

Communication error between outdoor main PCB and fan PCB. Check plug connections and LEDs. If OK, replace either main or fan PCB

106

Outdoor unit fan motor high current. Check fans rotate freely, and are connected correctly

107

Outdoor unit low voltage to fan PCB. Check 300 Vdc supply, check fuses and plug connections. If OK, replace fan PCB

108

Communication error between outdoor main PCB, and fan PCB. Check plug connections and LEDs. If OK replace either main or fan PCB

109

Sub 1 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

110

Sub 1 reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

 

 

111

Communication error between Main and Sub outdoor units. Check comms wiring and power to all outdoor units

113

Main outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

114

Main outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

115

Main outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

116

Sub 1 high pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar

117

Sub 1 low pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar

118

Sub 1 outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace

sensor

 

120

Sub 1 outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. if not replace sensor

 

 

121

Sub 1 compressor 1 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C. if not replace sensor

 

 

122

Sub 1 compressor 2 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168 kOhm at 30°C. if not replace sensor

 

 

123

Sub 1 outdoor unit coil sensor A fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

124

Sub 1 outdoor unit coil sensor B fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

125

Sub 1 outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

126

Sub 1 outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

127

Sub 1 outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

128

Sub 2 high pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar

129

Sub 2 low pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar

130

Sub 2 outdoor unit air sensor fault. Disconnect from PCB and measure resistance. 8 kOhm at 30°C and 13 kOhm at 20°C. If OK replace PCB, if not replace

sensor

 

132

Sub 2 outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C.if not replace sensor

 

 

133

Sub 2 compressor 1 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168kOhm at 30°C. if not replace sensor

 

 

134

Sub 2 compressor 2 discharge sensor fault. Disconnect from PCB measure resistance 237 kOhm at 20°C and 168kOhm at 30°C.if not replace sensor

 

 

135

Sub 2 outdoor unit coil sensor A fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

136

Sub 2 outdoor unit coil sensor B fault. Disconnect from PCB measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace sensor

 

 

137

Sub 2 outdoor unit liquid pipe sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

138

Sub 2 outdoor unit Subcool inlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

139

Sub 2 outdoor unit Subcool outlet sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C

140

Sub 2 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

141

Sub 2 reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

 

 

142

Communication error between Main and Sub outdoor units. Check comms wiring and power to all outdoor units

143

Sub 1 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

144

Sub 1 excessive drop of low pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

145

Sub 2 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

146

Sub 2 excessive drop of low pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

147

Sub 1 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%).check fuses, if fuses OK replace outdoor main PCB

 

 

148

Sub 1 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

 

 

149

Sub 2 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

 

 

150

Sub 2 check power supply voltage to the outdoor unit is correct (1ph 220 Vac ±10% or 3ph 380 Vac ±10%). check fuses, if fuses OK replace outdoor main PCB

 

 

151

Faulty 4 way valve. Check solenoid coil and output from PCB. If OK, mechanical failure.

152

Excessive discharge temperature rise 105°C Sub condenser 2 standard compressor. Check refrigerant

153

Excessive discharge temperature rise 105°C Sub condenser 2 standard compressor. Check refrigerant

154

Sub 3 excessive rise of high pressure. Check pressures, check for non condensables, check heat exchanger coil is free from debris

155

Sub 3 reverse or open phase. Check all 3 phases are present and correct. If correct voltage appears at all three phases, swap any two to cure the fault

 

 

156

Communication error between Main and Sub outdoor units. Check comms wiring and power to all outdoor units

157

Sub 3 high pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 8 bar up to 2.5 Vdc = 37 bar

158

Sub 3 low pressure sensor fault. Check dc voltage between white and black cable on plug. Multi V: 1 Vdc = 4 bar up to 5 Vdc = 32 bar