Test Running .............................................................................................................................................40
Function of control..................................................................................................................................41
Function of Indoor Unit...........................................................................................................................46
Function of Outdoor Unit ........................................................................................................................47
Remote Control Operation .....................................................................................................................48
Indoor Unit .............................................................................................................................................79
Turn the main power off when cleaning or
maintaining the product.
• There is risk of electric shock.
- 6 -
LGE Internal Use Only
Safety Precautions
CAUTION
When the product is not to be used for a long time,
disconnect the power by turning off the breaker.
• There is risk of product damage or failure, or unintended operation.
■ Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that
water is drained away properly.
Take care to ensure that nobody could step on
or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Keep level even when
installing the product.
• Low refrigerant levels may cause
failure of product.
Do not install the product
where the noise or hot air
from the outdoor unit could
oftend neighbors.
• It may cause a problem for your
neighbors.
• A bad connection may cause water
leakage.
Use two or more people to lift
and transport the product.
• Avoid personal injury.
• To avoid vibration or water leakage.
90°
Do not install the product
where it will be exposed to
sea wind (salt spray) directly.
• It may cause corrosion on the
product. Corrosion, particularly on
the condenser and evaporator fins,
could cause product malfunction or
inefficient operation.
Do not expose the skin directly to cool air for long periods
of time.
(Don't sit in the draft.)
• This could harm to your health.
Use a soft cloth to clean. Do
not use harsh detergents, solvents, etc.
• There is risk of fire, electric shock,
or damage to the plastic parts of
the product.
Do not use the product for
special purposes, such as
preserving foods, works of
art, etc. It is a consumer air
conditioner, not a precision
refrigeration system.
• There is risk of damage or loss of
property.
Do not touch the metal parts of
the product when removing the
air filter. They are very sharp!
• There is risk of personal injury.
Do not block the inlet or outlet
of air flow.
• It may cause product failure.
Do not step on or put anyting
on the product. (outdoor
units)
• There is risk of personal injury and
failure of product.
Thinner
Wax
Always insert the filter securely. Clean the filter every two
weeks or more often if necessary.
•
A dirty filter reduces the efficiency of
the air conditioner and could cause
product malfunction or damage.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
3) Select a well-drained place.
1.
If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
• It should be strong enough like concrete to prevent
the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
• It should be keep more than 70 cm of space
between outdoor unit and the windbreak for easy
air flow.
2. Select a place where there are no obstacles in front
of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
6. Use a Metal Detector or Metal Scanner to locate
studs to prevent unnecessary damage to the wall.
CAUTION: Install the indoor unit
on the wall where the height from
the floors more than 2.4 m (8 ft).
Outdoor unit
1. If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows around
front, back and side of the unit.
3. Do not place animals and plants in the path of the
warm air.
4. Take the air conditioner weight into account and
select a place where noise and vibration are minimum.
Select a place so that the warm air and sound from
5.
the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be
sure to level the unit. Ensure the roof structure and
anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
18 kBtu30 m (100 ft)15 m (50 ft)3 m (10 ft)7.5 m (25 ft)7.5 m (25 ft)
24 kBtu30 m (100 ft)15 m (50 ft)3 m (10 ft)7.5 m (25 ft)7.5 m (25 ft)
36 kBtu45 m (150 ft)15 m (50 ft)3 m (10 ft)7.5 m (25 ft)7.5 m (25 ft)
Pipe Size
Indoor Capacity
GasLiquidStandard Length
Additional
Refrigerant
9 kBtu9.52 mm (3/8")6.35 mm (1/4")7.5 m (25 ft)20 g/m (0.22 oz/ft)
12 kBtu9.52 mm (3/8")6.35 mm (1/4")7.5 m (25 ft)20 g/m (0.22 oz/ft)
18 / 24 kBtu
36 kBtu
CAUTION: Capacity is based on standard length and maximum allowance length is on the
The wall you select should be strong and solid enough to
prevent vibration
1. Mount the installation plate on the wall with
type "A" screws. If mounting the unit on a concrete wall,
use anchor bolts.
• Mount the installation plate horizontally by aligning the
centerline using a level.
2. Measure the wall and mark the centerline. It is also
important to use caution concerning the location of the
installation plate-routing of the wiring to power outlets is
through the walls typically. Drilling the hole through the
wall for piping connections must be done safely.
CHASSIS
(Grade)
S45010559105
SE6511085110
ABCD
Distance (mm)
D
C
Ø70mm
Left rear pipingRight rear piping
Installation plate
B
A
Ø70mm
Drill a hole in the wall
• Drill the piping hole with a Ø 70 mm (Ø 2.75 inch) hole core drill. Drill the piping hole at either the right or the left
with the hole slightly slanted to the outdoor side.
2. If a flared section is defective, cut it off and do flaring work
again.
Connecting the Piping
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by)
and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in
the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction
of rear right.
2.
Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
•
Make a small loop with the cable for easy connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be
sure that the drain hose is located at the lowest side of the
bundle. Locating at the Upper side can cause drain pan to
overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose
with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the
indoor unit with the upper edge of the installation plate.)
Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
Connecting the piping to the indoor unit and drain hose
to drain pipe.
1. Align the center of the pipes and sufficiently tighten the
flare nut by hand.
3. When extending the drain hose at the indoor unit, install
the drain pipe.
Wrap the insulation material around the connecting portion.
1. Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together
with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping
them with vinyl tape for enough to cover where they fit into
the rear piping housing section.
Wrap the insulation material around the connecting por-
Plastic bands
Insulation material
tion.
1. Overlap the connection pipe heat insulation and the indoor
unit pipe heat insulation material. Bind them together with
vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping
them with cloth tape over the range within which they fit
into the rear piping housing section.
Reroute the pipings and the drain hose across the back
of the chassis.
Flaring Work and Connection of Piping
Connection
pipe
Vinyl tape
(wide)
Connecting cable
Drain hose
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Pipe
Vinyl tape(narrow)
Wrap with
vinyl tape(wide)
Indoor
unit piping
Indoor unit installation
1. Remove the spacer.
2. Ensure that the hooks are properly seated on the installation plate by moving it left and right.
3. Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
Circuit Breaker
Use a circuit breaker
or time delay fuse.
Connecting the Cable between Indoor Unit and Outdoor Unit
GN/YL
20 mm
(0.79 inch)
Line voltage (208~230V)
18 / 24 kBtu36 kBtu
GN/YL
20 mm
(0.79 inch)
Line voltage (208~230V)
AWG14
AWG12 (Allowable temperature
to the wire rated at least 90C˚)
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are
the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the electrical diagram behind the front panel of Indoor Unit.
The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.
WARNING:
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring to the wiring diagram.
WARNING: Provide a circuit breaker
between power source and the outdoor
unit as shown below.
WARNING:
The power cord connected to the outdoor unit should be complied with the following speci-
fications (ETL recognized and CSA certified).
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications
Connecting the Cable between Indoor Unit and Outdoor Unit
Connection method of the connecting cable(Example)
(1) Remove two-caps on the conduit panel.
(for low voltage line)
(2) Pull out connection cable through conduit.
(3) After conduit to the panel, fix nut to the opposite
side of panel.
(4) Pass the connection cabel through the hole.
(5) Properly connect the cable on the terminal block.
(6) Fix the connection cable with cord clamp provided
on the unit not to have strain at the terminal when
the connection cable is pulled outside up to a 35
pound weight
When connecting each power wire to the corresponding terminal,
follow instructions "How to connect wiring to the terminals" and
fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the strand wiring about
10mm(3/8").
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a round terminal fastener or pliers, securely clamp
each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
WARNING: Loose wiring may cause the termi-
nal to overheat or result in unit malfunction. A
fire hazard may also exist. Therefore, be sure
Nitrogen gas
cylinder(in vertical
standing position)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Pressure
gauge
Air Purging and Evacuation
Air Purging and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Checking method
Preparation
• Check that each tube(both liquid and gas side tubes) between
the indoor and outdoor units have been properly connected and
all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service
valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a manifold
valve for leak testing.
The high side manifold valve must always
be kept closed.
• Pressurize the system to no more than 150 P.S.I.G. with dry
nitrogen gas and close the cylinder valve when the gauge
reading reached 150 P.S.I.G. Next, test for leaks with liquid
soap.
CAUTION:
refrigerant system in a liquid state, the top
To avoid nitrogen entering the
of the cylinder must be higher than its bottom
when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
1. Do a leakage test of all joints of the tubing(both indoor and
outdoor) and both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off the soap with a
clean cloth.
2. After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is
reduced to normal, disconnect the hose from the cylinder.
1. Connect the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit.
Confirm the "Lo" knob of the manifold valve is open. Then,
run the vacuum pump.
The operation time for evacuation varies with tubing length
and capacity of the pump. The following table shows the
time required for evacuation.
Required time for evacuation when 4 CFM vacuum
If tubing length is less
than 10m (33 ft)
10 min. or more15 min. or more
pump is used
If tubing length is longer
than 10m (33 ft)
2. When the desired vacuum is reached, close the "Lo" knob
of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid
side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise to
fully open the valve.
3. Loosen the charge hose connected to the gas side service
port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side service
valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready for test running.
■ Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor
line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant
charge has to be adjusted.
■ Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added
or removed based on 20g(0.22oz) of R-410A per meter(foot).
Example: A 80ft line set is used for tril - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge
adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. Unit is critically charged.
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are
fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to
the arrow direction.
Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
Reattach the cover by pushing it back into position.
4) Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of
air.
3. Ensure the difference between the intake temperature
and the discharge is more than 8°C(14.4°F) (Cooling) or
reversely (Heating).
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the system is not going to be used for a long time.
2) Precautions in test run
3) Settlement of outdoor unit
■ The initial power supply must provide at least 90% of
the rated voltage.
Otherwise, the air conditioner should not be operated.
■ For test run, carry out the cooling operation firstly
even during heating season. If heating operation is
carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
■ Carry out the test run more than 5 minutes without
fail. (Test run will be cancelled 18 minutes later automatically)
■ The test run is started by pressing timer cancel button
five times continuously. (Room type)
■ To cancel the test run, press any button.
■ Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
■ When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
■ In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
Operation
■ Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(0.9
fan stop.
°F)
• When it reaches 0.5°C(0.9
Compressor ON Temp ➲ Setting Temp+0.5°C(0.9
Compressor OFF Temp➲ Setting Temp-0.5°C(0.9
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
above the setting temp, they start to operate again.
°F)
below the setting temp, the compressor and the outdoor
°F)
°F)
■ Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8
24°C(75.2
18°C(64.4
Intake Air Temp<18°C(64.4
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.➲ Setting Temp+0.5°C(0.9
Compressor OFF Temp.➲ Setting Temp-0.5°C(0.9
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
°F)
≤ Intake Air Temp ➲ 25°C(77
°F)
≤ Intake Intake Air Temp<26°C(78.8
°F)
≤ Intake Intake Air Temp<24°C(75.2
°F)
°F)
°F)
°F)
°F)
➲ Intake Air Temp-1°C(30.2
➲ Intake Air Temp-0.5°C(31.1
➲ 18°C(64.4
°F)
°F)
°F)
°F)
■ Heating Mode Operation
• When the intake air temp reaches +3°(37.4
below the setting temp, the compressor is turned on.
Compressor ON Temp.➲ Setting Temp.
Compressor OFF Temp.➲ Setting Temp.+3°C(37.4
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68
27°C(80.6
, it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68
°F)
…above the setting temp, the compressor is turned off. When
°F)
- 41 -
°F)
, when above
°F)
LGE Internal Use Only
and
Operation
27°C(80.6
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4
35°C(95
• While in defrost control, the indoor is outdoor fans are turned off.
°F)
, it operates with Super-Low(while in sleep mode, with the medium airflow speed).
°F)
, it operates with the low airflow speed.
°F)
, when above
■ Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2
passed from starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C(59
• The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2
passed from ending of the first defrost and more than 4 minutes operation of compressor.
°F)
even before 12 minutes.
°F)
after 35 minutes
°F)
after 35 minutes
■ Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(75.2
21°C(69.8
Intake Air Temp<21°C(69.8
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
°F)
≤ Intake Air Temp ➲ Fuzzy Operation for Cooling
°F)
≤ Intake Air Temp<24°C(75.2
°F)
°F)
➲ Fuzzy Operation for Dehumidification
➲ Fuzzy Operation for Heating
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9
°F)
below the setting temp, the compressor is turned off. When 0.5°C(0.9
compressor is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C(0.9
Compressor OFF Temp ➲ Setting Temp + 0.5°C(0.9
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8
24°C(75.2
22°C(71.6
18°C(64.4
Intake Air Temp<18°C(64.4
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
°F)
≤ Intake Air Temp ➲ 25°C(77
°F)
≤ Intake Air Temp<26°C(78.8
°F)
≤ Intake Air Temp<24°C(75.2
°F)
≤ Intake Air Temp<22°C(71.6
°F)
°F)
°F)
°F)
➲ Intake Air Temp + 1°C(1.8
➲ Intake Air Temp + 0.5°C(0.9
➲ Intake Air Temp
➲ 18°C(64.4
• If the appliance is on pause at the time set by the timer, the pause continues.
■ Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.
■ Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C(33.8
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
°F)
. After another 30 min elapse, it increases by 1°C(1.8
°F)
again.
■ Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
■ Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
■ Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64.4
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
■ Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched to the Auto Restarting (or test operation) position or switched from the remote control
position to the forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows.
24°C(43.2
21°C(37.8
Intake Air Temp<21°C(37.8
°F)
≤Intake Air Temp ➲ Cooling Mode Operation, 22°C(39.6
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer: Lights up during Timer operation.
Defrost Mode
Outdoor unit
operation
: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)
: Lights up during outdoor unit operation.(Cooling model only)
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature
indicator• Cooling: 18°C~30°C(64°F~86°F)• AI : Auto Operation
• Dehumidification : 18°C~30°C(64°F~86°F)• Po : Jet Cool
• Heating: 16~30°C(60°F~86°F)• Lo : Test Mode
• Room temperature sensor. (THERMISTOR)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is delayed for approx. 3 minutes.
• High, Med, Low, Chaos, Jet Cool
• Intermittent operation of fan at low speed.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
•
The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing
up and down automatically.(Model base)
Split Type
Indoor Unit
Operation ON/OFF by Remote controlle
r
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
• Both the indoor and outdoor fan
stops during deicing.
• Hot start after deice ends.
• The indoor fan stops until the
evaporator piping temperature will
be reached at 27°C(80.6°F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
* Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Function of Indoor Unit
"Wall Mounted Type is standard"
* Functions is dependent on model type.
• Compressor step varies considering condition such as room temp,outdoor temp, operating room
number,Temp gap between room temp and set temp and so on.
• LEV pulse is modulated to keep constant superheat or subcooling.
• Outdoor fan operates at High or Off to respond to the load condition.
R/Valve Control(Heating Model Only)
• Convert R/Valve to change cooling to heating, heating to cooling.
Defrost Function
• After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -
5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min
cooing mode.
•
To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to cooling mode.
Oil Return System
• In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.
Comp Overload Protection
• To protect comp from being overload, protector will turn off the comp.
High Pressure Protction
• If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A
1. Check temperature difference between intake and discharge air, and operating current.
Troubleshooting Guide
Temp. difference : approx. 0°C(0°F)
Current: less than 80% of
rated current
Temp. Difference
Temp. difference : approx. 8°C
Current: less than 80% of
rated current
Operating Current
Temp. difference : less than 8°C
Current: near the rated cur-
rent
Temp. difference : over 8°C
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
(14.4°F)
(14.4°F)
(14.4°F)
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
2. Check temperature and pressure of refrigeration cycle.
Suction pressureTemperature
(Compared with(Compared withCause of TroubleDescription
the normal value)the normal value)
HighDefective compressorCurrent is low.
Higher
NormalExcessive amount of High pressure does not quickly
refrigerantrise at the beginning of operation.
Insufficient amount ofCurrent is low.
LowerHigherrefrigerant(Leakage)
Clogging
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in
Indoor unit corresponds to values in the Table of page 69
Does the voltage of terminal of CN-DC/DC CONNECTOR in
Indoor unit corresponds to the values in the table of page 56
Do the voltage of terminal of
CN-DC/DC CONNECTOR in
Outdoor unit corresponds to the
values in the table of page 56
NO
Check the patterns and the
conditions of outdoor unit
PWB Assy's.
Check the pattern and the
condition of Indoor unit PWB
Ass'y.
YES
Check the connecting condition and disconnection of
connecting wires between
Indoor and Outdoor unit.
Check connecting condition of the CN-MOTOR CONNECTOR
Check the interference of Indoor Fan.
Check the motor of Indoor Fan
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F.
(At that times, Defrost indicator is turned on)
1. Confirm that both the liguid side valve and gas
side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of
the manifold gauge.
3. Connect the service port of the gas side valve to
the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge needle
does not move(approximately 5 minutes after
turning off the vacuum pump).
6. Disconnect the charge hose from the vacuum
pump.
- Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted,replenish as needed.
7. Mount the valve caps and the service port caps.
- 77 -
LGE Internal Use Only
2-way, 3-way Valve
manifold gauge
Charging
cylinder
Hi- handle
(OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
(3) Gas Charging
(After Evacuation)
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnected from the vacuum pump to the valve at the
bottom of the cylinder.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
-
Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air. (Be careful of the liquid refrigerant). The
procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the specified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from
the gas side valve's service port.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
- 78 -
LGE Internal Use Only
135301
152302B
152302A
342800
567480B
Air inlet +
Eva in
Eva out
567480A
359011
131410733010
135312
135311
147581
268711A
146811
147582
346810
135516
35211B
354210
249951
352150
268711B
268711C
267110
135500
152313
Exploded View
Indoor Unit
Model : B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1