Lg B-mmh09fa-1, B-mmc12fa-1, B-mmc09fa-1, A-mmh36fa-1, A-mmc36fa-1 Service Manual

...
Wall Mounted
Multi-Split System
Air Conditioning/Heat Pump
Indoor Unit: B-MMC09FA-1
B-MMH09FA-1 B-MMC12FA-1 B-MMH12FA-1
Outdoor Unit : A-MMH18FA-1
A-MMC24FA-1 A-MMH24FA-1 A-MMC36FA-1 A-MMH36FA-1
Before servicing the unit, read the
“safety precautions” in this manual.
Only for authorized service personnel.
Multi type Air Conditioner Service Manual
TABLE OF CONTENTS
Combination table.......................................................................................................................................3
Safety Precautions......................................................................................................................................4
Installation guide at the seaside..............................................................................................................10
Dimensions................................................................................................................................................11
Indoor Unit..............................................................................................................................................11
Outdoor Unit...........................................................................................................................................12
Product Specifications .............................................................................................................................15
Indoor Unit..............................................................................................................................................15
Outdoor Unit...........................................................................................................................................16
Installation .................................................................................................................................................19
Installation Parts.....................................................................................................................................19
Installation Tools.....................................................................................................................................19
Select the best location .........................................................................................................................20
Piping length and elevation ....................................................................................................................21
Fixing Installation Plate(Standard Type).................................................................................................22
Drill a hole in the wall ...........................................................................................................................22
Flaring Work and Connection of Piping..................................................................................................23
Flaring work............................................................................................................................................24
Connecting the Piping ............................................................................................................................24
Connecting the Cable between Indoor Unit and Outdoor Unit .............................................................31
Connect the cable to the Indoor unit. .....................................................................................................31
Connect the cable to the Outdoor unit....................................................................................................32
Connection method of the connecting cable(Example)..........................................................................33
Connect the cable to the indoor unit.......................................................................................................34
Checking the Drainage, Forming the Pipings and Long Pipe Setting .................................................35
Checking the drainage............................................................................................................................35
Forming the piping..................................................................................................................................36
Air Purging and Evacuation.....................................................................................................................37
Checking method ...................................................................................................................................37
Evacuation..............................................................................................................................................38
Charging ....................................................................................................................................................39
Test Running .............................................................................................................................................40
Operation ...................................................................................................................................................41
Function of control..................................................................................................................................41
Function of Indoor Unit...........................................................................................................................46
Function of Outdoor Unit ........................................................................................................................47
Remote Control Operation .....................................................................................................................48
Disassembly ..............................................................................................................................................49
Indoor Unit..............................................................................................................................................49
Schematic Diagram...................................................................................................................................52
Electronic Control Device .......................................................................................................................52
Wiring Diagram.......................................................................................................................................55
Components Locations...........................................................................................................................57
Troubleshooting Guide .............................................................................................................................61
Refrigeration Cycle Diagram ..................................................................................................................61
Self-diagnosis Function..........................................................................................................................64
Cycle Troubleshooting Guide..................................................................................................................65
Electronic Parts Troubleshooting Guide .................................................................................................66
Error Code..............................................................................................................................................71
2-way, 3-way Valve ....................................................................................................................................75
Exploded View ..........................................................................................................................................79
Indoor Unit .............................................................................................................................................79
Outdoor Unit...........................................................................................................................................81
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 2 -
LGE Internal Use Only
NOTICE
Combination table
18 kBtu( 2 rooms)
1 UNIT 9 - 9 2 UNIT 9 9 18
24 kBtu( 2 rooms)
1 UNIT
2 UNIT 9 12 21
Combination table
Combination
Unit-A Unit-B Total
Combination
Unit-A Unit-B Total
9-9
12 - 12
9918
12 12 24
36 kBtu (3 rooms)
Combination
Unit-A Unit-B Unit-C Total
1 UNIT
2 UNIT 9 12 - 21
3 UNIT
Notes :
1.Cooling Capacity is based on : indoor temp. 26.7°C(80.1°F)DB, 19.4°C(66.9°F)WB; outdoor temp. 35°C(95°F)DB, 23.9°C(75°F)WB
2.Heating Capacity is based on : indoor temp. 21.1°C(70°F)DB, 15.6°C(60.1°F)WB; outdoor temp. 8.3°C(46.9°F)DB, 6.1°C(43°F)WB
9-- 9
12 - - 12
99-18
12 12 - 24
99927 9 9 12 30 9121233
12 12 12 36
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 3 -
LGE Internal Use Only
Safety Precautions
WARNING
CAUTION
WARNING
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use a defective or under­rated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center
• Do not disassemble or repair the product. There is risk of fire or electric shock.
.
Always install a dedicated cir­cuit and breaker.
• Improper wiring or installation may cause fire or electric shock
Always ground the product.
• There is risk of fire or electric shock.
Use the correctly rated break­er or fuse.
• There is risk of fire or electric shock.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 4 -
LGE Internal Use Only
Safety Precautions
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con­denser and evaporator.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condi­tioner could fall with it, causing property damage, product failure, and personal injury.
For installation, always con­tact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Do not allow water to run into electric parts.
Do not store or use flammable gas or combustibles near the product.
• It may cause There is risk of fire, failure of the product, or electric shock.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
• There is risk of fire or failure of product.
- 5 -
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
Gasolin
LGE Internal Use Only
Safety Precautions
When flammable gas leaks, turn off the gas and open a window for ventilation before
If strange sounds, or smoke comes from product. Turn the breaker off.
turn the product on.
• Do not use the telephone or turn switches on or off. There is risk of explosion or fire
Do not open the inlet grill of the product during operation. (Do not touch the elec­trostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
• There is risk of electric shock or fire.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Stop operation and close the window in storm or hurricane. If possible, remove the prod­uct from the window before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electric shock.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
Turn the main power off when cleaning or maintaining the product.
• There is risk of electric shock.
- 6 -
LGE Internal Use Only
Safety Precautions
CAUTION
When the product is not to be used for a long time, disconnect the power by turning off the breaker.
• There is risk of product damage or failure, or unintend­ed operation.
Installation
Always check for gas (refrigerant) leak­age after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product dam­age.
Keep level even when installing the product.
• Low refrigerant levels may cause failure of product.
Do not install the product where the noise or hot air from the outdoor unit could oftend neighbors.
• It may cause a problem for your neighbors.
• A bad connection may cause water leakage.
Use two or more people to lift and transport the product.
• Avoid personal injury.
• To avoid vibration or water leak­age.
90°
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 7 -
LGE Internal Use Only
Safety Precautions
Operational
Do not expose the skin direct­ly to cool air for long periods of time. (Don't sit in the draft.)
• This could harm to your health.
Use a soft cloth to clean. Do not use harsh detergents, sol­vents, etc.
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of personal injury.
Do not block the inlet or outlet of air flow.
• It may cause product failure.
Do not step on or put anyting on the product. (outdoor units)
• There is risk of personal injury and failure of product.
Thinner
Wax
Always insert the filter secure­ly. Clean the filter every two weeks or more often if neces­sary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
• There are sharp and moving parts that could cause personal injury.
- 8 -
Do not drink the water drained from the product.
• It is not sanitary and could cause serious health issues.
LGE Internal Use Only
Safety Precautions
Use a firm stool or ladder when cleaning or maintaining the product.
• Be careful and avoid personal injury.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
• They may burn or explode.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of bat­teries.
• There is risk of fire or explosion
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 9 -
LGE Internal Use Only
Installation guide at the seaside
Sea wind Sea wind
Installation guide at the seaside
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc­tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
3) Select a well-drained place.
1.
If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
It should be strong enough like concrete to prevent the sea wind from the sea.
The height and width should be more than 150% of the outdoor unit.
It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 10 -
LGE Internal Use Only
Dimensions
Installation plate
D
H
W
Indoor Unit
Split Type Indoor
Dimensions
Model
Dimension
W mm(in) 840(33) 895(35.2)
Split Type
S4
9 kBtu/h
SE
12 kBtu/h
H mm(in) 270(10.6) 282(11.1)
D mm(in) 153(6) 165(6.5)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 11 -
LGE Internal Use Only
W
D
L1
L2
L4
L3
H
L7L5L6
Dimensions
Outdoor Unit
MODEL
DIM
W mm(in) 870(34.3)
H mm(in) 655(25.8)
D mm(in) 320(12.6)
L1 mm(in) 370(14.6)
L2 mm(in) 25(1.0)
L3 mm(in) 775(30.5)
L4 mm(in) 25(1.0)
L5 mm(in) 546(21.5)
L6 mm(in) 160(6.3)
L7 mm(in) 160(6.3)
UE
18kBtu/h
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 12 -
LGE Internal Use Only
W
D
L1
L2
L4
L3
H
L7L5L6
MODEL
DIM
W mm(in) 870(34.3)
H mm(in) 808(31.8)
UE 1
24kBtu/h
D mm(in) 320(12.6)
L1 mm(in) 370(14.6)
L2 mm(in) 25(1.0)
L3 mm(in) 775(30.5)
L4 mm(in) 25(1.0)
L5 mm(in) 546(21.5)
L6 mm(in) 160(6.3)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
L7 mm(in) 160(6.3)
- 13 -
LGE Internal Use Only
Dimensions
L6L7 L8
L9
L4
H
L5
W
D
L1
L3
L2
L10 L11 L11 L11L11L11
Gas side 3-way valve
Liquid side 2-way valve
MODEL
DIM
W mm(in) 870(34.3)
H mm(in) 1038(40.7)
D mm(in) 320(12.6) L1 mm(in) 360(14.2) L2 mm(in) 340(13.4) L3 mm(in) 25(1.0) L4 mm(in) 1035(40.8) L5 mm(in) 25(1.0) L6 mm(in) 546(21.5) L7 mm(in) 160(6.3) L8 mm(in) 160(6.3) L9 mm(in) 44(11.7)
L10 mm(in) 64.5(2.5) L11 mm(in) 50(2.0)
UE2
36kBtu/h
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 14 -
LGE Internal Use Only
Product Specifications
Indoor Unit
Product Specifications
Indoor Unit Type
Model
Nominal Cooling Capacity kcal/h(W)
Nominal Heating Capacity kcal/h(W)
Air Circulation H/M/L CMM(CFM) Setting temperature range(cool/heat) °C Fan motor Output W
Fan Type
Noise Level (Sound Press,1m) Temperature controller Coil Tube Size (OD) inch(mm)
Dehumidification Rate l/h Dimensions (W*H*D) inch(mm) Net Weight kg(lbs) Piping Connection Liquid inch(mm)
Packing Dimension (W*H*D) inch(mm) Stuffing Quantity With(Without) S/Parts 20/40ft(hi-c)
Btu/h
Btu/h
Model Input V Running Current A
No. Used / Diameter EA/inch(mm)
H/M/L dBA
Fins per inch No. of Rows & Column
Gas inch(mm) Drain hose (ID Ø) mm
Wall Mounted
B-MMC09FA-1 B-MMH09FA-1 B-MMC12FA-1 B-MMH12FA-1
2,267(2,637) 2,267(2,637) 3,023(3,516) 3,023(3,516)
9,000 9,000 12,000 12,000
- 2,267(2,637) - 3,023(3,516)
- 9,000 - 12,000
8.2(289) 8.2(289) 9.4(332) 9.4(332) 18~30 18~30 18~30 18~30
15 15 15 15
DL-88430LGIF DL-88430LGIF DL-88430LGIF DL-88430LGIF
DC36 DC36 DC36 DC36
0.15 0.15 0.15 0.15
Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
1/3.74(95) 1/3.74(95) 1/3.74(95) 1/3.74(95)
31 / 29 / 22 31 / 29 / 22 36 / 32 / 29 36 / 32 / 29
Thermistor Thermistor Thermistor Thermistor
0.197(5.0) 0.197(5.0) 0.197(5.0) 0.197(5.0) 20 20 18 18
2R,15C 2R,15C 2R,15C 2R,15C
- 1.1 - 1.2
33.0*10.6*6.0(840*270*153) 33.0*10.6*6.0(840*270*153) 35.2*11.1*6.5(895*282*165) 35.2*11.1*6.5(895*282*165) 7(15.4) 7(15.4) 9.5(20.9) 9.5(20.9)
1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
20 20 20 20
35.7*13.1*8.8(906*332*223) 35.7*13.1*8.8(906*332*223) 38.3*9.1*14.6(973*231*372) 38.3*9.1*14.6(973*231*372)
440/910 (1091) 440/910 (1091) 353/719 (792) 353/719 (792)
Note : 1.★See the page "Combination Table"
2. Due to our policy of innovation some specifications may be changed without notification.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 15 -
LGE Internal Use Only
Product Specifications
Outdoor Unit - Multiple piping models
Model
Cooling Capacity Btu/hr
Heating Capacity Btu/hr
Input Cooling W
Running Current(208/230V)
Power Supply Ø,V,Hz Max. Number of Connectable Indoor Units Compressor Type (Constant) Model
Compressor Type (Constant) Model
Refrigerant charge Charge g(oz)
Coil Tube Size (OD) inch(mm)
Fan motor Model
Fan Type
Air Circulation Outdoor CMM(CFM) Noise Level(H/L) at 230V Defrosting SVC Valve Liquid inch(mm)
Dimensions W*H*D inch(mm) Net Weight Outdoor kg(lbs) Max. Interunit Piping Length
Max. Installation Indoor Unit~Outdoor Unit m Height Difference Indoor Unit~Indoor Unit m Packing Dimension W*H*D inch(mm) Testing Combinations Stuffing Quantity 20/40ft
Heating W Cooling A Heating A
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Type Control
Fins per inch No. of Rows & Column/No.
Output W Capacitor µF/Vac
No. Used / Diameter EA/inch(mm) Discharge Side / Top
Sound Press,1m dB(A) 1
Gas
Total of Each Room m For One Room m
W
kcal/hr
W
kcal/hr
A-MMH18FA-1
9,000~18,000
2637~5275 2267~4536
9,000~18,000
2637~5275 2267~4536 1070~1980 1040~1960
4.9~8.8
4.6~8.6
1,208/230,60
2
Rotary GK094K Hermetic
1
955
330±10 FVC68D 30 / 370
External Type(MRA98996-12026)
Rotary GK113K Hermetic
1
1,120
330±10 FVC68D 35 / 370
External Type(MRA12124-12026)
1400(49)
R410A
EEV
0.276(7.0) 18
2R,28C
IC-1640LG GE
90
6/370
Propeller
1 / 460
Side
50(1765.7)
51
Invertion Cycle 1/4 (6.35) * 2EA 3/8 (9.52) * 2EA
34.3*25.8*12.6 (870*655*320) 57(125.7)
30 15
7.5
7.5
40.2*28.2*17.2 (1020*716*437) S4 9k + S4 9k
81/171
Note:
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB
Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
2. Wiring cable size must comply with the applicable local and national code.
3. Capacities are Net Capacities.
4. : See the page "Combination Table"
5. The specification may be subject to change without prior notice for purpose of improvement.
- 16 -
LGE Internal Use Only
Product Specifications
Model
Cooling Capacity Btu/hr
Heating Capacity Btu/hr
Input Cooling W
Running Current(208/230V)
Power Supply Ø,V,Hz Max. Number of Connectable Indoor Units Compressor Type (Constant) Model
Compressor Type (Constant) Model
Refrigerant charge Charge g(oz)
Coil Tube Size (OD) inch(mm)
Fan motor Model
Fan Type
Air Circulation Outdoor CMM(CFM) Noise Level(H/L) at 230V Defrosting SVC Valve Liquid inch(mm)
Dimensions W*H*D inch(mm) Net Weight Outdoor kg(lbs) Max. Interunit Piping Length
Max. Installation Indoor Unit~Outdoor Unit m Height Difference Indoor Unit~Indoor Unit m Packing Dimension W*H*D inch(mm) Testing Combinations Stuffing Quantity 20/40ft
Heating W Cooling A Heating A
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Type Control
Fins per inch No. of Rows & Column/No.
Output W Capacitor µF/Vac
No. Used / Diameter EA/inch(mm) Discharge Side / Top
Sound Press,1m dB(A) 1
Gas
Total of Each Room m For One Room m
W
kcal/hr
W
kcal/hr
A-MMC24FA-1 A-MMH24FA-1
9,000~24,000 9,000~24,000
2637~7033 2637~7033 2267~6037 2267~6037
- 9,000~24,000
- 2637~7033
- 2267~6037
1170~2390 1170~2390
- 1220~2440
7.7~10.1 7.7~10.1
- 7.4~9.8
1,208/230,60 1,208/230,60
22
Rotary Rotary GK094K GK094K Hermetic Hermetic
11
955 955
330±10 330±10
FVC68D FVC68D
30 / 370 30 / 370
External Type(MRA98996-12026) External Type(MRA98996-12026)
Rotary Rotary GK141K GK141K Hermetic Hermetic
11
1430 1,430
350±10 350±10
FVE FVE
35 / 370 35 / 370
External Type(MRA12105-12026) External Type(MRA12105-12026)
1600 1600
R410A R410A
EEV EEV
0.276(7.0) 0.276(7.0) 18 18
2R,36C 2R,36C
IC-1640LG GE IC-1640LG GE
90 90
6/370 6/370
Propeller Propeller
1 / 460 1 / 460
Side Side
53(1872) 53(1872)
54 54
- Invertion Cycle 1/4 (6.35) * 2EA 1/4 (6.35) * 2EA 3/8 (9.52) * 2EA 3/8 (9.52) * 2EA
34.3*31.8*12.6 (870*808*320) 34.3*31.8*12.6 (870*808*320) 64(141.1) 64(141.1)
30 30 15 15
7.5 7.5
7.5 7.5
40.2*34.3*17.2 (1022*870*437) 40.2*34.3*17.2 (1022*870*437) SE 12K +SE 12K SE 12K +SE 12K
54/114 54/114
Note:
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB
Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
2. Wiring cable size must comply with the applicable local and national code.
3. Capacities are Net Capacities.
4. : See the page "Combination Table"
5. The specification may be subject to change without prior notice for purpose of improvement.
- 17 -
LGE Internal Use Only
Product Specifications
Model
Cooling Capacity Btu/hr
Heating Capacity Btu/hr
Input Cooling W
Running Current(208/230V)
Power Supply Ø,V,Hz Max. Number of Connectable Indoor Units Compressor Type (Constant) Model
Compressor Type (Constant) Model
Refrigerant charge Charge g(oz)
Coil Tube Size (OD) inch(mm)
Fan motor Model
Fan Type
Air Circulation Outdoor CMM(CFM) Noise Level(H/L) at 230V SVC Valve Liquid inch(mm)
Dimensions W*H*D inch(mm) Net Weight Outdoor kg(lbs) Max. Interunit Piping Length
Max. Installation Indoor Unit~Outdoor Unit m Height Difference Indoor Unit~Indoor Unit m Packing Dimension W*H*D inch(mm) Stuffing Quantity 20/40ft
Heating W Cooling A Heating A
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Motor Type Quantity Ea Motor Input W Oil Charge cc Oil Type Capacitor µF/Vac O.L.P Type(model name)
Type Control
Fins per inch No. of Rows & Column/No.
Output W Capacitor µF/Vac
No. Used / Diameter EA/inch(mm) Discharge Side / Top
Sound Press,1m dB(A) 1
Gas
Total of Each Room m For One Room m
W
kcal/hr
W
kcal/hr
A-MMC36FA-1 A-MMH36FA-1
9,000~36,000 9,000~36,000
2637~10,550 2637~10,550
2267~9071 2267~9071
- 9,000~36,000
- 2637~10,550
- 2267~9071
1320~3680 1320~3680
- 1410~3340
5.9~16.6 5.9~16.6
- 6.3~15.0
1,208/230,60 1,208/230,60
33
Rotary Rotary
GK141K GK141K
2 Pole Induction(PSC) 2 Pole Induction(PSC)
11
1430 1430 350Å}10 350Å}10 FVC68D FVC68D 35 / 370 35 / 370
External Type External Type
Rotary Rotary
GJ230K GJ230K
2 Pole Induction(PSC) 2 Pole Induction(PSC)
11
2370 2370
700±10 7000±10 FVC68D FVC68D 50 / 400 50 / 400
Internal Type Internal Type
2400 2400
R410A R410A
EEV EEV
0.276(7.0) 0.276(7.0) 18 18
2R,48C 2R,48C
ARC286B01 * 2 ARC286B01 * 2
102 102
2/370 2/370
Propeller Propeller
2 / 15.7(400) 2 / 15.7(400)
Side Side
63(2225) 63(2225)
51 51
1/4 (6..35) * 3EA 1/4 (6..35) * 3EA 3/8 (9.52) * 3EA 3/8 (9.52) * 3EA
34.3*40.7*12.6 (870*1038*320) 34.3*40.7*12.6 (870*1038*320) 84(185.2) 84(185.2)
45 45 15 15
7.5 7.5
7.5 7.5
41.3*44.9*17.3 (1048*1140*439) 41.3*44.9*17.3 (1048*1140*439) 53/111 53/111
Note:
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB
Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
2. Wiring cable size must comply with the applicable local and national code.
3. Capacities are Net Capacities.
4. : See the page "Combination Table"
5. The specification may be subject to change without prior notice for purpose of improvement.
- 18 -
LGE Internal Use Only
Installation
Type "A" screw and plastic anchor
Type "B" screw
Remote Control Holder
Installation plate
Figure FigureName
Screw driver
Electric Drill
Measuring Tape, Knife
Hole Core Drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Gas Leak Detector
Thermometer,
Level
Flaring Tool Set
Name
Read carefully, and then follow step by step.
Installation Parts
Installation
Installation Tools
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 19 -
LGE Internal Use Only
Installation
More than 20 cm
(7.9 inch)
More than 10 cm
(3.9 inch)
More than 10 cm
(3.9 inch)
More than 2.4m
(8 ft)
Select the best location
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conve­niently routed away.
4. Do not install near a doorway.
5. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
6. Use a Metal Detector or Metal Scanner to locate studs to prevent unnecessary damage to the wall.
CAUTION: Install the indoor unit on the wall where the height from the floors more than 2.4 m (8 ft).
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radia­tion from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows around front, back and side of the unit.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and sound from
5. the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
18 / 24 kBtu
more than 30 cm
(11.8 inch)
more than 70 cm
(27.6 inch)
36 kBtu
more than 30 cm
(11.8 inch)
more than 30 cm
(11.8 inch)
more than 60 cm
(23.6 inch)
more than 30 cm
(11.8 inch)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 20 -
more than 70 cm
(27.6 inch)
more than 60 cm
(23.6 inch)
LGE Internal Use Only
Piping length and elevation
h2
h2
h1
A
B
B
C
h2
h1
A
B
h1
h1
h1
Multi Piping Type
Installation
Capacity
Max total length
of all pipes
(A+B/A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
18 kBtu 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft) 24 kBtu 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft) 36 kBtu 45 m (150 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft)
Pipe Size
Indoor Capacity
Gas Liquid Standard Length
Additional
Refrigerant
9 kBtu 9.52 mm (3/8") 6.35 mm (1/4") 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
12 kBtu 9.52 mm (3/8") 6.35 mm (1/4") 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
18 / 24 kBtu
36 kBtu
CAUTION: Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 21 -
LGE Internal Use Only
Installation
Installation Plate
Type "A" screw
Chassis
Hook
5-7 mm
(0.2"~0.3")
Indoor
WALL
Outdoor
Fixing Installation Plate(Standard Type)
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
• Mount the installation plate horizontally by aligning the
centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
CHASSIS
(Grade)
S4 50 105 59 105 SE 65 110 85 110
ABCD
Distance (mm)
D
C
Ø70mm
Left rear piping Right rear piping
Installation plate
B
A
Ø70mm
Drill a hole in the wall
• Drill the piping hole with a Ø 70 mm (Ø 2.75 inch) hole core drill. Drill the piping hole at either the right or the left
with the hole slightly slanted to the outdoor side.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 22 -
LGE Internal Use Only
Flaring Work and Connection of Piping
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Flaring Work and Connection of Piping
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m (5.0ft) longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Pipe
Reamer
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
• Carry out flaring work using flaring tool as shown below.
• Firmly hold copper pipe in a Bar in the dimension shown in the
table Below.
Outside diameter A
mm inch mm Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5
Point down
Flare nut
Copper tube
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 23 -
LGE Internal Use Only
Flaring Work and Connection of Piping
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Check
1. Compare the flared work with the figure by.
2. If a flared section is defective, cut it off and do flaring work again.
Connecting the Piping
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by) and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction of rear right.
2.
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
• Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the Upper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweat­ing"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
Drain hose
Tape
Connecting pipe
Drain hose
Connecting cable
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 24 -
LGE Internal Use Only
4. Indoor unit installation
Drain hose
Connecting
cable
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting the piping to the indoor unit and drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
Flaring Work and Connection of Piping
Indoor unit tubing Flare nut Pipes
Outside diameter Torque
mm inch kg.m lbf.in Ø6.35 1/4 1.8 156.2 Ø9.52 3/8 4.2 364.5
3. When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the connecting por­tion.
1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Wrench
Indoor unit tubing
Drain pipe
Connection pipe
Vinyl tape (wide)
Connecting cable
Open-end wrench (fixed)
Flare nut
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
Plastic bands
Insulation material
Wrap with vinyl tape
Vinyl tape(narrow)
Connection pipe
Indoor unit pipe
Pipe
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 25 -
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
LGE Internal Use Only
Flaring Work and Connection of Piping
For left rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
3.
Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection
later.
4. Tape the drain hose and the connecting cables.
5. Indoor unit installation
• Hang the indoor unit from the hooks at the top of the
installation plate.
• Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the indoor unit from the wall.
Connecting the piping to the indoor unit and the drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
Connecting
cable
Drain pipe
Indoor unit
Spacer
Installation plate
8cm
2. Tighten the flare nut with a wrench.
Outside diameter Torque
mm inch kg.m lbf.in Ø6.35 1/4 1.8 156.2 Ø9.52 3/8 4.2 364.5
3. When extending the drain hose at the indoor unit, install the drain pipe.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 26 -
Indoor unit tubing Flare nut Pipes
Open-end wrench (fixed)
Flare nut
Wrench
Indoor unit tubing
Drain hose
Indoor unit drain hose
Adhesive
Vinyl tape
LGE Internal Use Only
Connection pipe
(narrow)
Wrap the insulation material around the connecting por-
Plastic bands
Insulation material
tion.
1. Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Flaring Work and Connection of Piping
Connection pipe
Vinyl tape (wide)
Connecting cable
Drain hose
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape(wide)
Indoor unit piping
Indoor unit installation
1. Remove the spacer.
2. Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
3. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 27 -
Piping for passage through piping hole
Connecting
cable
Drain hose
LGE Internal Use Only
Flaring Work and Connection of Piping
Installation Information. For left piping. Follow the instruction below.
Good case
• Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
• Following bending type from right to left may cause damage to the tubing.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 28 -
LGE Internal Use Only
REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
HOW TO INSERT BATTERIES
Remove the battery cover from the remote con­troller.
• Slide the cover according to the arrow direction.
Insert the two batteries.
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
Flaring Work and Connection of Piping
• Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and per­formance.
• Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 29 -
LGE Internal Use Only
Flaring Work and Connection of Piping
Liquid side piping
Torque wrench
B-UNIT
A-UNIT
Gas side piping
Outdoor unit
Outdoor
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Ø6.35 1/4 1.8 156.2 Ø9.52 3/8 4.2 364.5
Outside diameter Torque
mm inch kg.m lbf.in
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 30 -
LGE Internal Use Only
Air
Conditioner
Main power source
Circuit Breaker Use a circuit breaker or time delay fuse.
Connecting the Cable between Indoor Unit and Outdoor Unit
GN/YL
20 mm
(0.79 inch)
Line voltage (208~230V)
18 / 24 kBtu 36 kBtu
GN/YL
20 mm
(0.79 inch)
Line voltage (208~230V)
AWG14
AWG12 (Allowable temperature to the wire rated at least 90C˚)
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are
the same as those of the indoor unit.)
The earth wire should be longer than the common wires. The circuit diagram is not subject to change without notice. When installing, refer to the electrical diagram behind the front panel of Indoor Unit. The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.
WARNING:
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring to the wiring diagram.
WARNING: Provide a circuit breaker between power source and the outdoor unit as shown below.
WARNING:
The power cord connected to the outdoor unit should be complied with the following speci-
fications (ETL recognized and CSA certified).
The power connecting cable connected to the indoor and outdoor unit should be complied with the fol­lowing specifications
WARNING:
trol box panel by using tie wrap as the fixture.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
(ETL recognized and CSA certified).
AWG18
Low voltage (below 40V)
When using the separate wire as the power cord, please fix the separate wire into the con-
GN/YL
20mm
- 31 -
LGE Internal Use Only
Connecting the Cable between Indoor Unit and Outdoor Unit
NOTICE
Outdoor unit
Over 5mm
Holder for
power supply
cord
Connecting
cable
Cover control
Terminal block
Power supply
cable
Connect the cable to the Outdoor unit.
1. Remove the cover control from the unit by loosening the
screw. Connect the wires to the terminals on the control board individually as the following.
2. Secure the cable onto the control board with the holder
(clamper).
3. Refix the cover control to the original position with the
screw.
18 kBtu
Power Source
208/230V AC
(High voltage)
Teminal on the Outdoor Unit
Power Source
208/230V AC
(High voltage)
Teminal on the Outdoor Unit
Power Source
208/230V AC
(High voltage)
Teminal on the Indoor Unit
A-UNIT
43
432121
Teminal on the Outdoor Unit Teminal on the Outdoor Unit
A Indoor B Indoor
Teminal on the Indoor Unit
Connecting cable(Low voltage)
4321L1 L2
24 kBtu
Teminal on the Indoor Unit
A-UNIT
L2L1
Teminal on the Outdoor Unit
432121
Teminal on the Indoor Unit
43
Teminal on the Outdoor Unit
B IndoorA Indoor
36 kBtu
Teminal on the Indoor Unit
A-UNIT
L2L1
Teminal on the Outdoor Unit
432121
Teminal on the Indoor Unit
43
Teminal on the Outdoor Unit
B IndoorA Indoor
B-UNIT
B-UNIT
B-UNIT
4321
4321
Connecting cable(Low voltage)
4321
Teminal on the Indoor Unit
4321
4321
C-UNIT
Teminal on the Outdoor Unit
C Indoor
4321
Connecting cable(Low voltage)
4321
:
1. Separately wire the high and low voltage line.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit.
(For example, Type SJOW)
WARNING:
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 32 -
LGE Internal Use Only
High voltage
Low voltage
Strip 10mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
G
Terminal block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Cord clamp
Hole (for low voltage line)
Cap(Remove) Taping
(for sealing)
Low voltage line (connecting cable)
Connecting the Cable between Indoor Unit and Outdoor Unit
Connection method of the connecting cable(Example)
(1) Remove two-caps on the conduit panel.
(for low voltage line) (2) Pull out connection cable through conduit. (3) After conduit to the panel, fix nut to the opposite
side of panel. (4) Pass the connection cabel through the hole. (5) Properly connect the cable on the terminal block. (6) Fix the connection cable with cord clamp provided
on the unit not to have strain at the terminal when
the connection cable is pulled outside up to a 35
pound weight
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
󱇲 For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the strand wiring about 10mm(3/8").
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a round terminal fastener or pliers, securely clamp
each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
WARNING: Loose wiring may cause the termi-
nal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure
all wiring is tightly connected.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 33 -
LGE Internal Use Only
Connecting the Cable between Indoor Unit and Outdoor Unit
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Main power source
Model Power source
Fuse or breaker
Capacity
1Ø, 230 / 208V
20 A
1Ø, 230 / 208V
25 A
1Ø, 230 / 208V
40 A
18 kBtu 24 kBtu 36 kBtu
Connecting cable
CAUTION: Provide a circuit breaker between power source and the unit as shown below.
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec­tively.
2. Attach the Grille onto the cabinet.
• Grasp the lower left and right side of the Grille and
engage four tabs on the top inside edge of the chassis.
• Press the Grille toward the chassis until it will be back into
place.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 34 -
LGE Internal Use Only
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Checking the drainage
To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Drain piping
1. The drain hose should point downward for easy drain flow.
2. Do not make drain piping.
Accumulated drain water
Air
Waving
Water leakage
Do not raise
Water leakage
Water leakage
Tip of drain hose dipped in water
Ditch
Downward slope
Less than 50mm gap
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 35 -
LGE Internal Use Only
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Seal a small opening around the pipings with gum type sealant.
Trap
Trap
Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings
Connecting cable
Power supply cord
Seal a small opening around the pipings with gum type sealant.
Forming the piping
Form the piping by wrapping the con­necting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
• If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1. Tape the piping, drain hose and connecting cable from
down to up.
2. Secure the tapped piping along the exterior wall using
saddle or equivalent.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1. Tape the piping and connecting cable from down to up.
2. Secure the taped piping along the exterior wall. Form a
trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 36 -
LGE Internal Use Only
NOTICE
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Pressure gauge
Air Purging and Evacuation
Air Purging and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensi­ble gas and moisture in the system.
Checking method
Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the ser­vice valve caps from both the gas and the liquid side on the out­door unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges) and dry nitro­gen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a manifold
valve for leak testing. The high side manifold valve must always be kept closed.
• Pressurize the system to no more than 150 P.S.I.G. with dry
nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION:
refrigerant system in a liquid state, the top
To avoid nitrogen entering the
of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
:
Leakage test shoud be done for each indoor
unit connection set, separately.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 37 -
LGE Internal Use Only
Air Purging and Evacuation
NOTICE
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
Required time for evacuation when 4 CFM vacuum
If tubing length is less
than 10m (33 ft) 10 min. or more 15 min. or more
pump is used
If tubing length is longer
than 10m (33 ft)
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side ser­vice port and fasten the flare nut securely with an adjustable wrench. This process is very important to pre­vent leakage from the system.
5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready for test running.
: Repeat evacuation procedure for each indoor
unit.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 38 -
LGE Internal Use Only
Charging
Charging
Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted.
Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).
Max total length
Capacity (Btu/h)
18k 30m(100ft) 15m(50ft) 5m(16ft) 7.5m(25ft) 7.5m(25ft) 20g/m(0.22oz/ft)
24k 30m(100ft) 15m(50ft) 3m(10ft) 7.5m(25ft) 7.5m(25ft) 20g/m(0.22oz/ft)
Capacity (Btu/h)
36k 45m(150ft) 15m(50ft) 3m(10ft) 7.5m(25ft) 7.5m(25ft) 20g/m(0.22oz/ft)
of all pipes
(A+B)
Max total length
of all pipes
(A+B+C)
Max length of
each pipe (A/B)
Max length of
each pipe
(A/B/C)
Min length of
each pipe (A/B)
Min length of
each pipe
(A/B/C)
Max Elevation
between each indoor
unit and outdoor unit
(h1)
Max Elevation
between each indoor
unit and outdoor unit
(h1)
Max elevation
between indoor
units (h2)
Max elevation
between indoor
units (h2)
Additional
Refrigerant
Additional
Refrigerant
Example: A 80ft line set is used for tril - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. Unit is critically charged.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 39 -
LGE Internal Use Only
Test Running
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
Test Running
Split Type
1. Check that all tubing and wiring have been properly con­nected.
2. Check that the gas and liquid side service valves are fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to the arrow direction.
Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
Reattach the cover by pushing it back into position.
4) Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(14.4°F) (Cooling) or reversely (Heating).
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
• Remove the batteries from the remote controller if the sys­tem is not going to be used for a long time.
2) Precautions in test run
3) Settlement of outdoor unit
The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compres­sor. Then attention must be paid.
Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later auto­matically)
The test run is started by pressing timer cancel button five times continuously. (Room type)
To cancel the test run, press any button.
Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.
Refrigerant
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
The pressure of the gas side
service valve.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 40 -
LGE Internal Use Only
Operation
Function of control
1. MAIN UNIT FUNCTION
DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
Operation
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(0.9 fan stop.
°F)
• When it reaches 0.5°C(0.9
Compressor ON Temp Setting Temp+0.5°C(0.9 Compressor OFF Temp Setting Temp-0.5°C(0.9
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is off fan operates at low speed regardless of the setting.
above the setting temp, they start to operate again.
°F)
below the setting temp, the compressor and the outdoor
°F)
°F)
Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8 24°C(75.2 18°C(64.4 Intake Air Temp<18°C(64.4
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C(0.9 Compressor OFF Temp. Setting Temp-0.5°C(0.9
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
°F)
Intake Air Temp ➲ 25°C(77
°F)
Intake Intake Air Temp<26°C(78.8
°F)
Intake Intake Air Temp<24°C(75.2
°F)
°F) °F)
°F)
°F)
Intake Air Temp-1°C(30.2Intake Air Temp-0.5°C(31.118°C(64.4
°F)
°F)
°F)
°F)
Heating Mode Operation
• When the intake air temp reaches +3°(37.4 below the setting temp, the compressor is turned on.
Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C(37.4
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68 27°C(80.6
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
°F)
, it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68
°F)
…above the setting temp, the compressor is turned off. When
°F)
- 41 -
°F)
, when above
°F)
LGE Internal Use Only
and
Operation
27°C(80.6
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4
35°C(95
• While in defrost control, the indoor is outdoor fans are turned off.
°F)
, it operates with Super-Low(while in sleep mode, with the medium airflow speed).
°F)
, it operates with the low airflow speed.
°F)
, when above
Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2 passed from starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature rises over 15°C(59
• The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2 passed from ending of the first defrost and more than 4 minutes operation of compressor.
°F)
even before 12 minutes.
°F)
after 35 minutes
°F)
after 35 minutes
Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C(75.2 21°C(69.8 Intake Air Temp<21°C(69.8
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
°F)
Intake Air Temp ➲ Fuzzy Operation for Cooling
°F)
Intake Air Temp<24°C(75.2
°F)
°F)
Fuzzy Operation for DehumidificationFuzzy Operation for Heating
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9
°F)
below the setting temp, the compressor is turned off. When 0.5°C(0.9 compressor is turned on.
Compressor ON Temp Setting Temp +0.5°C(0.9 Compressor OFF Temp Setting Temp + 0.5°C(0.9
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C(78.8 24°C(75.2 22°C(71.6 18°C(64.4 Intake Air Temp<18°C(64.4
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper­ature.
°F)
Intake Air Temp ➲ 25°C(77
°F)
Intake Air Temp<26°C(78.8
°F)
Intake Air Temp<24°C(75.2
°F)
Intake Air Temp<22°C(71.6
°F)
°F) °F) °F)
Intake Air Temp + 1°C(1.8Intake Air Temp + 0.5°C(0.9Intake Air Temp18°C(64.4
°F)
°F)
°F)
°F)
or more above the setting temp, the
°F)
°F)
°F)
or more
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 42 -
LGE Internal Use Only
Operation
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9 °F)
below the setting temp, the compressor is turned off. When 0.5°C(0.9 compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C(0.9 Compressor OFF Temp Setting Temp+0.5°C(0.9
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8 24°C(75.2 22°C(71.6 18°C(64.4 Intake Air Temp<18°C(64.4
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
°F)
Intake Air Temp ➲ 25°C(77
°F)
Intake Air Temp<26°C(78.8
°F)
Intake Air Temp<24°C(75.2
°F)
Intake Air Temp<22°C(71.6
°F)
°F) °F) °F)
Intake Air Temp+1°C(1.8Intake Air Temp+0.5°C(0.9Intake Air Temp18°C(64.4
°F)
°F)
°F)
°F)
or more above the setting temp, the
°F)
°F)
°F)
or more
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37.4
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp + 3°C(5.4
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C(68 Intake Air Temp<20°C(68
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
°F)
Intake Air Temp ➲ Intake Air Temp + 0.5°C(0.9
°F)
20°C(68
°F)
°F)
°F)
°F)
or more
Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow
speed selection key on the remote control.
On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 43 -
LGE Internal Use Only
Operation
• If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C(33.8
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
°F)
. After another 30 min elapse, it increases by 1°C(1.8
°F)
again.
Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64.4
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.
Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
°F)
.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 44 -
LGE Internal Use Only
Operation
Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control position to the forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera­tion condition is set according to the intake air temperature as follows.
24°C(43.2 21°C(37.8 Intake Air Temp<21°C(37.8
°F)
Intake Air Temp ➲ Cooling Mode Operation, 22°C(39.6
°F)
Intake Air Temp<24°C(43.2
°F)
°F)
Dehumidification Operation, 23°C(41.4Heating Mode Operation, 24°C(43.2
°F)
, High Speed
°F)
, High Speed
°F)
, High Speed
Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 45 -
LGE Internal Use Only
Operation
On/Off : Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode
Outdoor unit operation
: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)
: Lights up during outdoor unit operation.(Cooling model only)
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature indicator Cooling : 18°C~30°C(64°F~86°F) AI : Auto Operation
Dehumidification : 18°C~30°C(64°F~86°F) Po : Jet Cool
Heating : 16~30°C(60°F~86°F) Lo : Test Mode
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 seconds at the starting.
Restarting is delayed for approx. 3 minutes.
High, Med, Low, Chaos, Jet Cool
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.(Model base)
Split Type
Indoor Unit
Operation ON/OFF by Remote controlle
r
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops during deicing.
Hot start after deice ends.
The indoor fan stops until the
evaporator piping temperature will be reached at 27°C(80.6°F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
* Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Function of Indoor Unit
"Wall Mounted Type is standard" * Functions is dependent on model type.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 46 -
LGE Internal Use Only
Function of Outdoor Unit
Outdoor Unit
Operating Step
LEV Control
Out door Fan Control
Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on.
LEV pulse is modulated to keep constant superheat or subcooling.
Outdoor fan operates at High or Off to respond to the load condition.
R/Valve Control(Heating Model Only)
Convert R/Valve to change cooling to heating, heating to cooling.
Defrost Function
After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -
5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode.
To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to cooling mode.
Oil Return System
In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.
Comp Overload Protection
To protect comp from being overload, protector will turn off the comp.
High Pressure Protction
If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A
Operation
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 47 -
LGE Internal Use Only
Operation
ON
OFF
CANCEL
AUTO CLEAN
SET
1
3
5
4
9
10
12
14
16
7
2
8
13
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
15
Operation Mode
(Heat Pump)
(Cooling Only)
Remote Control Operation
The Remote Controller transmits the signals to the system.
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
JET COOL
5.
Used to start or stop the speed cooling/heating. (speed cooling/heating operates super high fan speed.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. RESET BUTTON
Used prior to resetting time.
14. 2nd F Button
Used prior to using modes printed in blue at the bottom of buttons.
15. AUTO CLEAN
Used to set Auto Clean mode.
16. ˚C TO ˚F SWITCHING BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
- 48 -
LGE Internal Use Only
Disassembly
Earth Conductor
Indoor Unit
Split Type Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.
Disassembly
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 49 -
LGE Internal Use Only
Disassembly
Screw
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis carefully.
3. To remove the Discharge Grille.
• Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
• Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
• When repair, do not damage the Caution label.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 50 -
LGE Internal Use Only
• Unhook the tab on the right inside of the chassis
Motor cover
Bearing
Cross-flow fan
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
• Remove 2 securing screw.
• Pull the motor cover out from the chassis carefully.
Disassembly
6. To remove the Cross-Flow Fan
• Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
• Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
• Remove the left end of the cross-flow fan from the self-aligning bearing.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 51 -
LGE Internal Use Only
Disassembly
Schematic Diagram
Electronic Control Device
1. Indoor Unit
1) Split Type
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 52 -
LGE Internal Use Only
2. Outdoor Unit
P07
SW01F
OR2H,OR7H,OR10H:91K,OR3H-4H,OR8H-9H,OR11H-12H:15K(ETC:20K)
R03T
11
DC 5V
56K
R04T
1K
1
2
7036P
IC01A
CN-JIG
3
4
3
4
22
JIG_RX
JIG_TX
DC 5V
10K
R01T
1K
R02T
C01H-C04H : 103
P21
21
JIG_RX
26
OSC01B
CST-8.00MGW
JIG_TX
+
3
C02A
10
R03A,100
50V
25V
0.01
C01A
R02A,4.7K
R01A,1K
Xin
Vss
Xout
R01B,1M
25
24
P22
RESET
23
22
P20
19
R01F,1K
R02F,10K
R02G,10K
R01G,10K
R04G,10K
R03G,10K
P32
29
30
P33
28
27
P31
P30
L4(C)
L3(C)
L1(A)
L2(B)
PWM(A)
PWM(C)
PWM(B)
P53
P54
46
47
P52
45
51
P60
50
P62
P63
P61
52
53
31
P37
343536
P41
P40
33
32
P36
P35
RX(C)
RX(B)
TX(C)
RX(A)
TX(B)
14
13
P13
P12
P34
111012
P10
P11
TX(A)
CN-LEV(C)
CN-LEV(B)
DC 5V
+
C52M
220
50V
231
231
5
4
5
4
IC03M
44
220
50V
+
C51M
1 132
3
2
50V
55
1
+
220
C50M
1
22
11
OUT_PIPE
OUT_TH
22
33
44
CN-TH2
SUCTION
33
44
DC 5V
R05H-R20H
(ETC: 12.1K 1%)
(R05H,R06H,R07H:6.2K 1%)
DISCHARGE
CN-TH1
11
41
R01H,1K
60
P71
P66
P65
P64
555654
P70
P67
59
57
63
P73
P72
R04H,1K
62
61
P76
P74
P75
R02H,1K
R03H,1K
1
64
7 8 9
P05
P06
5
6
P02
P04
P03
P51
44 4 3
P00
P01
42
43
P47
P50
MICOM
TMP87CM41F
58
TEST
P77
20
2
VSS
AVDD
49
48
VDD
Q01Z
KRA107M
39
40
P44
P46
P45
38
37
P42
P43
DC 5V
CN-LEV(A)
IC02M
423
423
5 5
RY-COMP(A)
RY-FAN(H)
RY-COMP(B)
IC01M
R01Z-R07Z : 4.7K
RY-LIQ
RY-FAN(L)
RY-GAS
RY-4WAY
DC 15V
Schematic Diagram
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 53 -
LGE Internal Use Only
Schematic Diagram
23.2K
8.06K
8.06K
23.2K
23.2K
8.06K
1%
1%
51.1K
102
100V
C25M
1%
9.1k
R27M
100uf
C24M
+
2
5
4
6
100uF
25V
C26M
R28M
13K
1%
1
5
+
R29M,2K,1%
4
22
51.1K
10K
1
2.94K
6
7
4.7K
PWM(C)
35.7K
4.3K
R26M
10.2K
3
2
1
21.5K
6.04K
KRA101M
Q07M
DC 5V
7
3K 5.23K39.2K 13K
20 20
9
8
R04S
20K
14
51.1K
102
C14M
100V
R15MC13M+1%
100uf 9.1k
2
5
4
6
C15M
25V
100uF
R16M
1
5
+
1%
13K
R17M,2K,1%
4
22 10K
1
51.1K
2.94K
6
7
4.7K
PWM(B)
35.7K
4.3K
10.2K
R14M
2
3
1
21.5K
6.04K
Q04M
KRA101M
DC 5V
7
3K 5.23K39.2K 13K
20
8
20
9
R04S
14
20K
51.1K
102
100V
C02M
R02M
9.1k
1%
100uf
C01M
+
2
5
4
6
100uF
25V
C03M
1
5
R03M
13K
1%
+
R04M,2K,1%
4
22 10K
1
51.1K
6
7
2.94K
PWM(A)
4.7K
35.7K
4.3K
R01M
10.2K
1%
2
3
1
21.5K
6.04K
KRA101M
Q01M
7
DC 5V
3K 5.23K39.2K 13K
R04S
8
20 20
9
14
20K
51.1K
RY-COMP(B)
RY-COMP(A)
51.1K
2SD2220
Q08M
51.1K
R31M
220
3
34K
100K
R33M
1.5K103K
100V
R34MC31M
Vm(C)
MT 15V
94
S/W TRANS6
2
3 7
Q09M
30,1W
R37M
ZD03M
12V
200
R36M
472/250V
C30M
100V
473K
C27M
2
8
10K
R32M
IC06M
63V
680uF
C28M
+
821K
C29M
1KV
L10M
L09M
FMX12S
D05M
Q05M
2SD2220
R19M
51.1K
220
3
34K
R21M
100K
1.5K103K
100V
R22MC21M
Vm(B)
ERB-44-08
D06M
8 4
6
S/W TRANS5
L12M
L11M
11 2
1KV
222K
C33M
3W
68K
R35M
C32M
MT 15V
94
S/W TRANS4
2
3 7
Q06M
R25M
30,1W
12V
200
R24M
ZD02M
u-POWER MODULE
NF02J
C09J~C10J
1uF
C08J
222*2
25V
ZNR01J~ZNR02J
uRM1515-2B
302
D01J
C04J
1M
C06J~C07J
C05J
9mH
472*3
R01J
1mH
NF01J
1uF
1uF
C03J
35V
C10D
102M
561*2
C04D
35V
470UF
12uH
L01D
1000UF
35V
220uF
C05D
10V
220uF
C03D
DC 5V
DC 15V
IC04D
C06D
50V
103
7805
C07D
50V
+
+
103
C02D
470uF
+
2K
R02D
1/2W
MT 15V
C08D
103
50V
L02D
12uH
D101
FB
12
OUT
R202
9
7
+
C01D
GND
PC201
D201
R201
D202
268
C102
BP
TNY
S
D
13
+
C101
R102
OUT
GND
3
NC
DC 0V
6
5
PC201
GND
NC
DC 310V
1
IN
R101
D01D
1N4937
RY-FAN(L)
RY-FAN(H)
RY-GAS
LIVE1
3 3
CN-POWER
NEUTRAL
1
FUSE
ZNR01J
250V/T5A
INR14D471K
SVC561D-14A
1
COMP B
COMP A
43
LIVE2
43
NF01M
HOT GAS
FAN LOW
FAN HI
1
1
NF02M
1
1
1
NF04M
NF03M
1
CN-FAN
COM(A)
COM(B)
COM(C)
DKS-10D-22
1/2W
560K
R11M
51.1K
472/250V
C19M
C16M
100V
473K
8
2
10K
R20M
IC05M
63V
C17M
680uF
+
C18M
821K
1KV
L06M
L05M
FMX12S
D03M
Q02M
2SD2220
51.1K
R06M
220
3
34K
R08M
100K
1.5K103K
100V
R09MC09M
Vm(A)
ERB-44-08
D04M
8 4
6
S/W TRANS3
L08M
L07M
11 2
C23M
1KV
222K
R23M3W68K
C22M
MT 15V
94
S/W TRANS2
3
2
7
Q03M
30,1W
R13M
ZD01M
12V
200
R12M
472/250V
C07M
C04M
473K
100V
8
2
R07M
10K
IC04M
C05M+63V
680uF
C06M
821K
1KV
L02M
L01M
D01M
FMX12S
ERB-44-08
D02M
8 4
6
S/W TRANS1
L03M
L04M
11 2
1KV
C11M
222K
3W
68K
R10M
C10M
+
NTC
450V
330UF
C12M
COM(B)
3
20TX(B)
1K
R14K
102
C03K
TX(C)
RX(C)
RX(B)
RY-LIQ
RY-4WAY
R15K
10K
R12K
10K
R16K
3
2
1
8
4
20
8
4
7
5
6
R10K
1K
C02K
102
2
1
4
IC03K
4
7
5
6
8
COM(C)
DC 15V
Vm(C)
Vm(B)
DC 15V
DC 0V
BD01M
D15XB60
DC 310V
RX(A)
DC 15V
TX(A)
DC 5V
R13K
1K1K
R01K
1K
R09K
10K
R07K
R05K
R11K
10K
C01K
1K
102
8
4
7
5
6
10K
R06K
IC02K
10K
R08K
8
R02K
R04K
10K
R03K
IC01K
2
3
1
8
4
20
COM(A)
Vm(A)
DC 15V
LIQUID
1
NF05M
1
1
1
4WAY
324
324
314
3
1
CN-COM3
4
412
412
CN-COM2
231
CN-COM1
231
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
- 54 -
Wiring Diagram
1. Indoor Unit
Schematic Diagram
2. Outdoor Unit
1)A-MMH18FA-1 2) A-MMC24FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 55 -
LGE Internal Use Only
Schematic Diagram
3) A-MMH24FA-1 4) A-MMC36FA-1
5) A-MMH36FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 56 -
LGE Internal Use Only
Components Locations
PCB :6870A90409B ASSY:6871A20771
6871A20782
1. Indoor Unit
MAIN P.C.B ASM
1) Split Type
• TOP VIEW
Schematic Diagram
• BOTTOM VIEW
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 57 -
LGE Internal Use Only
Schematic Diagram
2. Display ASSEMBLY
1) Split Type (6871A20680)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 58 -
LGE Internal Use Only
3. Outdoor Unit
1) Component side
Schematic Diagram
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 59 -
LGE Internal Use Only
Schematic Diagram
2) Solder side
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 60 -
LGE Internal Use Only
Troubleshooting Guide
Refrigerant Flow
Cooling
Heating
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor Th4: Defrost thermistor
Field Piping Gas
Field Piping Liquid
Room A
EEV-B
EEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø9.52
Th2
High pressure S/W
Th3
Th4
Th1
Constant
Compressor
Constant
Compressor
Accumulator
Strainer
Field Piping Gas
Field Piping Liquid
Refrigerant Flow
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor
Room A
Cooling
EEV-B
EEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø9.52
Th2
High pressure S/W
Th3
Th4
Th1
Constant
Compressor
Constant
Compressor
Accumulator
Strainer
Strainer
Refrigeration Cycle Diagram
1. A-MMH18FA-1
Troubleshooting Guide
2. A-MMC24FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 61 -
LGE Internal Use Only
Troubleshooting Guide
Refrigerant Flow
Cooling
Heating
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor Th4: Defrost thermistor
Field Piping Gas
Field Piping Liquid
Room A
EEV-B
EEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø9.52
Th2
High pressure S/W
Th3
Th4
Th1
Constant
Compressor
Constant
Compressor
Accumulator
Strainer
Strainer
Field Piping Gas
Field Piping Liquid
Refrigerant Flow
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor
Room A
Cooling
EEV-B
EEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø6.35
Ø9.52
Room C
Ø9.52
Th2
High pressure S/W
Th3
Th1
EEV-C
Room C
Constant
Compressor
Constant
Compressor
Accumulator
3. A-MMH24FA-1
4. A-MMC36FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 62 -
LGE Internal Use Only
Refrigerant Flow
Cooling
Heating
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor Th4: Defrost thermistor
Field Piping Gas
Field Piping Liquid
Room A
EEV-B
EEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø9.52
Room C
Ø9.52
Th2
High pressure S/W
Th3
Th4
Th1
EEV-C
Room C
Ø6.35
Constant
Compressor
Constant
Compressor
Accumulator
5. A-MMH36FA-1
Troubleshooting Guide
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 63 -
LGE Internal Use Only
Troubleshooting Guide
LED1
LED2
Self-diagnosis Function
Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
Error code Description MPS Variable LED1 LED2 Indoor Status
00 No Error ON
01 Indoor Room Thermistor Error 1 time OFF
02 Indoor In-Piping Error 2 times OFF
05 Communication Error between In and Out 5 times OFF
06 Indoor Out-Piping Error 6 times OFF
07 Differnt mode operation 7 times OFF
10 Indoor fan motor locked error 1 times OFF
Outdoor Error
Error code Description MPS Variable LED1(Red) LED2(Green) Indoor Status
33 D-Pipe High(Normal) 3 times 3 times OFF
44 Outdoor Air Thermistor Error(Open/Short) 4 times 4 times OFF
45 Cond Pipe Thermistor Error(Open/Short) 4 times 5 times OFF
47
51 Capcity Error(High/Low)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
Const. D-Pipe Thermistor Error(Open/Short)
- 64 -
4 times 7 times OFF
5 times 1 times OFF
LGE Internal Use Only
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
Troubleshooting Guide
Temp. difference : approx. 0°C(0°F) Current : less than 80% of
rated current
Temp. Difference
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Operating Current
Temp. difference : less than 8°C Current : near the rated cur-
rent
Temp. difference : over 8°C
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
(14.4°F)
(14.4°F)
(14.4°F)
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
2. Check temperature and pressure of refrigeration cycle.
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)
High Defective compressor Current is low.
Higher
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation.
Insufficient amount of Current is low.
Lower Higher refrigerant(Leakage)
Clogging
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 65 -
LGE Internal Use Only
Troubleshooting Guide
Electronic Parts Troubleshooting Guide
Refer to electronic contorol device drawing & schematic diagram.
Trouble 1
Check the voltage of power(AC208V/AC230V, 60Hz).
• The voltage of main power.
• The voltage applied to the unit.
• The connecting method of Indoor/Outdoor connecting cable (each color)
• The P.W.B. Ass'y (Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)
The Product doesnt operate at all.
Turn off the main power and wait until LED on outdoor PCB is off.
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
NO
YES
• Primarily, the operating condi­tion of Micom is O.K.
• Check CN-DISP1
The operation check of the P.C.B. Ass'y
Procedure
1) The input voltage of power trans­former.
2) The output voltage of power transformer.
3) IC01D(7812)
4) IC02D(7805)
5) IC01A(KIA7036)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
1) AC230V ± 30V : Check the rated voltage
2) 15V ± 1.5V
3) DC12V
4) DC5V
5) The voltage of micom pin 29 : DC4.5V
Specification
- 66 -
Remedy
1) Replace power transfomer.
2) Replace power transfomer.
3) Replace IC01D.
4) Replace IC02D.
5) Replace IC01A.
LGE Internal Use Only
Troubleshooting Guide
Trouble 2
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
Caused by the remote controller.
Product doesn't operate with the remote controller.
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
Caused by other parts except
the remote controller
When the mark ( ) is displayed in LCD
screen, replace battery.
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(▲ / ▼) and wind
speed selecting.
Check the Display PWB Ass'y • Check receiver ass'y
Check the contact of CN-DISP 1 connector
Check DISP PWB Ass'y
-Voltage between CN1 ➀ - ➆ : DC +5V
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 67 -
LGE Internal Use Only
Troubleshooting Guide
Trouble 3
Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least.
Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped.
The Compressor/Outdoor Fan are don't operate
Turn on the main power.
When in air circulation mode, compressor/outdoor fan is stopped.
• Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 ,
75 , 76 , 77 ).
• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).
Check the Relay(RY-PWR, RY-START) for driving Compressor.
• Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC208V / 230V).
• Check the related circuit of relay in Outdoor PCB Ass'y.
Check Point
Between Micom(No. 50,51) and GND
Between IC01M(No. 10) and GND
Comp. ON Comp. OFF
DC 5V DC 0V
DC 12VDC 1V
Turn off main power.
Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 68 -
LGE Internal Use Only
Troubleshooting Guide
Trouble 4
When indoor Fan does not operate.
When indoor Fan does not operate.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in Indoor unit corresponds to values in the Table of page 69
Does the voltage of terminal of CN-DC/DC CONNECTOR in Indoor unit corresponds to the values in the table of page 56
Do the voltage of terminal of CN-DC/DC CONNECTOR in Outdoor unit corresponds to the values in the table of page 56
NO
Check the patterns and the conditions of outdoor unit PWB Assy's.
Check the pattern and the condition of Indoor unit PWB Ass'y.
YES
Check the connecting condi­tion and disconnection of connecting wires between Indoor and Outdoor unit.
Check connecting condition of the CN-MOTOR CON­NECTOR
Check the interference of Indoor Fan.
Check the motor of Indoor Fan
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode). Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F. (At that times, Defrost indicator is turned on)
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 69 -
LGE Internal Use Only
Troubleshooting Guide
Trouble 5
When the louver does not operate.
When Vertical Louver does not operate.
• Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with hands Normal
• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin (RED) of CN-UP/DOWN and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 60 , 61 , 62 and 63 of MICOM
- Between
- Between 12 , 13 ,
- Between
2 , 3 , 4 and 5 of IC01M
14 , 15
of IC01M
1 , 2 , 3 , 4 and 5 of CN-UP/DOWN
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 70 -
LGE Internal Use Only
Error Code
Trouble Shooting
Troubleshooting Guide
Error code
01 Indoor air sensor
02 Indoor inlet pipe sensor
06 Indoor outlet pipe sensor
Title Cause of error Check point & Normal condition
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
10K
Normal resistor : 10K/ at 25°C(77°F) (Unplugged) Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5KΩ/ at 25°C(77°F) (Unplugged) Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5KΩ/ at 25°C(77°F) (Unplugged) Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
2.5Vdc
V
Check the resistance / voltage
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor
3. If the resistance of the sensor is 10KΩ/5KΩ at 25°C(77°F), then sensor is normal
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc / at 25°C(77°F), then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 71 -
LGE Internal Use Only
Troubleshooting Guide
Error
code
05 / 53
Communication (Indoor ➔ Outdoor)
Title Cause of error Check point & Normal condition
• Power input AC 230V.(Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• Communication poorly
• The GND 1,2 is not connected at main GND.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Check Point
1. Check the input power AC 230V.(Outdoor, Indoor)
2. Check the communication wires are correctly connected.
Adjust the connection of wireConfirm the wire of "Live", "Neutral".
3. Check the resistance between communication line and GND.(Normal : Over 2MΩ)
4. Check the connector for communication is correctly connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no problem. Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 72 -
LGE Internal Use Only
Troubleshooting Guide
Error code
33 D-Pipe Temp. High
Title Cause of error Check point & Normal condition
115°C(239°F)
100°C(212°F)
95°C(203°F)
Check Point
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerent.
4. Check the constant compressor.
• Discharge sensor temp. high
COMP OFF
LEV OPEN(16PULSE/MIN)
LEV OPEN(10PULSE/MIN)
NORMAL
• Check the discharge pipe sensor.
• Check the install condition for over load.
• Check the leakage of refrigerent.
• Check the SVC V/V open.
Error code
51 Capacitor error
Title Cause of error Check point & Normal condition
Check Point
1. Check the indoor unit capacity.
2. Check the combination table.
In the tropical model case single cycle has no error for over capacity.
• Over Capacitor com­bination
• Check the indoor unit capacity.
• Check the combination table
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 73 -
LGE Internal Use Only
Troubleshooting Guide
Error
code
44 Outdoor air sensor
45 Condensor pipe sensor
47 D-Pipe sensor
Title Cause of error Check point & Normal condition
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 10K/ at 25°C(77°F) (Unplugged) Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5K/ at 25°C Normal voltage : 2.5Vdc / at 25°C
Normal resistor : 200K/ at 25°C Normal voltage : 4.5Vdc / at 25°C
(77°F)
(77°F)
(77°F)
(77°F)
(Unplugged)
(plugged)
(Unplugged)
(plugged)
Check the resistance
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance is 0V or 5Vdc, then sensor is abnormal
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 74 -
LGE Internal Use Only
2-way, 3-way Valve
Flare nut
To piping connection
Open position Closed position
Flare nut
Valve cap
To piping connection
Open position Closed position
Hexagonal wrench (4mm)
To outdoor unit
Pin
Service port
Service port cap
To outdoor unit
2-way Valve (Liguid Side) 3-way Valve (Gas Side)
2-way, 3-way Valve
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Air purging Open Closed Open
(Installation) (counter-clockwise) (clockwise) (push-pin or with
1. vacuum pump)
Operation Open Open Closed
(with valve cap) (with valve cap) (with cap)
Pumping down Closed Open Open
2.
(Transfering) (clockwise) (counter-clockwise) (connected
Evacuation Open Open Open
3.
4.
(Servicing) (with charging
cylinder)
Gas charging Open Open Open
(Servicing) (with charging
cylinder)
manifold gauge)
Pressure check Open Open Open
5.
6.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
(Servicing) (with charging
Gas releasing Open Open Open
(Servicing) (with charging
- 75 -
cylinder)
cylinder)
LGE Internal Use Only
2-way, 3-way Valve
Indoor unit
Outdoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
Hi- handle (CLOSE)
Low­handle (CLOSE)
(1) Pumping down
Procedure
1. Confirm that both the gas side and liquid side valves are set to the open position.
- Remove the valve stem caps and confirm that the valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con­nect the manifold gauge to the service port of the gas side valve.
- Connect the hose of the gauge with the push pin to the service port.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge slightly to air purge from the hose.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.
7. Immediately set the gas side valve to the closed position.
- Do this quickly so that the gauge ends up indicat-
ing 1kg/ g.
8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.
- Use torque wrench to tighten the service port nut to
a torque of 1.8kg.m.(156.2 lbf·in) [4.2kg.m (364.5
lbf·in)/5.5kg.m (477.4 lbf·in)]
- Be sure to check for gas leakage.
5. Set the liquid side valve to the closed position.
• Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 76 -
LGE Internal Use Only
(2) Evacuation
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Vacuum pump
Hi- handle (OPEN)
Low­handle (OPEN)
(All amount of refrigerant leaked)
2-way, 3-way Valve
Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of the manifold gauge.
3. Connect the service port of the gas side valve to the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump).
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
6. Disconnect the charge hose from the vacuum pump.
- Vacuum pump oil. If the vacuum pump oil becomes dirty or deplet­ed,replenish as needed.
7. Mount the valve caps and the service port caps.
- 77 -
LGE Internal Use Only
2-way, 3-way Valve
manifold gauge
Charging
cylinder
Hi- handle (OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
(3) Gas Charging
(After Evacuation)
Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect­ed from the vacuum pump to the valve at the bottom of the cylinder.
- If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid.
2. Purge the air from the charge hose.
-
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge the system with liquid refrigerant.
- If the system can not be charged with the speci­fied amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure(pumping down-pin).
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
4. Immediately disconnect the charge hose from the gas side valve's service port.
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
5. Mount the valve stem nuts and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
- 78 -
LGE Internal Use Only
135301
152302B
152302A
342800
567480B
Air inlet +
Eva in
Eva out
567480A
359011
131410 733010
135312
135311
147581
268711A
146811
147582
346810
135516
35211B
354210
249951
352150
268711B
268711C
267110
135500
152313
Exploded View
Indoor Unit
Model : B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1
Exploded View
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 79 -
LGE Internal Use Only
Exploded View
435512
435301
349480
437211
430411
559010
447910
546810
349600
554030
137213B
137213A
435300
567480C
552112
552113A
548490
435511A
552203A
552203B
552203A
552203B
554160A
554160B
661400B
552200
566000
H/P switch
552113B
552114
552201
661400B
649950
W0CZZB
W0CZZA
268711F
561410
567480D
Discharge
552116
435511B
268711H
552202
Outdoor Unit
Model : A-MMH18FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 80 -
LGE Internal Use Only
552113B
552202
561410
Heat pump type
Heat pump type
Heat pump type
649950
268711F
268711H
435511
552203A
552203B
552203A
552203B
554160A
554160B
Internal
OLP Type
Internal
OLP Type
661400A
552200
552200
567480C
Inlet air + pipe
567480D
Discharge
W0CZZA
349600
W0CZZB
554030
435512
559010
435301
349480
546810
447910
437210
430410
437211
552201
137213A137213B
435300
566000
L/P switch
552114
552116
552113A
552112
661400B
Model : A-MMC24FA-1, A-MMH24FA-1
Exploded View
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 81 -
LGE Internal Use Only
546810
546810
349600
552113B
559010
559010
552116
Heat pump type
552203A
552203B
554160B
Internal
OLP type
554160A
567502
554030
447910
430410
435512
435301
349480
435301
349480
437211
137213A137213B
435300
548490
552112
552113
552114
567480C
Air inlet+Pipe
W6640
567480D
Discharge
649950
268711F
268711H
W0CZZA
W0CZZB
435511
561410
552201
552202
661400A
552200
552200
552200
661400B
661400C
Exploded View
Model : A-MMC36FA-1, A-MMH36FA-1
Copyright ©2008 LG Electronics. Inc. All right reserved. Only for training and service purposes
- 82 -
LGE Internal Use Only
Specifications and performance data subject to change without notice.
HEAT CONTROLLER, INC.
1900 WELLWORTH AVENUE • JACKSON, MICHIGAN 49203
THE QUALITY LEADER IN CONDITIONING AIR
P/No.:3828A20390X
Loading...