LG B30AWYN7G6 Installation Manual

<![if ! IE]>

<![endif]>ENGLISH

INSTALLATION MANUAL

AIR

CONDITIONER

Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Please retain this installation manual for future reference after reading it thoroughly.

CEILING CONCEALED DUCT

Original instruction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.lg.com

 

MFL41755821

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rev.00_081618

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2018 LG Electronics Inc. All Rights Reserved.

<![if ! IE]>

<![endif]>ENGLISH

2 TABLE OF CONTENTS

TABLE OF CONTENTS

3

INTRODUCTION

27

LEAKAGE TEST AND

3

Tips for saving energy

 

 

EVACUATION

4

Important safety instructions

 

 

 

27

Preparation

7

Installation process

27

Leakage test

8

Features

28

Evacuation

 

 

9Environment-friendly alternative

 

refrigerant R-410A

29

TEST RUNNING

10 INSTALLATION PLACE

 

 

 

31

FORMING THE PIPING

11

Indoor unit installation place

 

 

 

32

 

12

Outdoor unit installation place

REMOTE CONTROLLER

14

Installation guide at the seaside

 

 

INSTALLATION

15 THE INDOOR UNIT

 

 

32

Wired remote controller installation

 

INSTALLATION

33

Location of remote controller

 

 

34

 

15

Install the unit above the ceiling

SETTING & TEST

 

correctly.

17

36

Installer Setting - E.S.P Function

Insulation, others

38

Self-diagnosis function

17

Checking the Drainage

38

Indoor Unit Error

19 CONNECTING PIPES

39

Error Indicator (Outdoor)

 

 

40

Dip switch setting

19

Preparation of Piping

20

Connecting the pipings to the indoor

 

41

FUNCTION

 

unit and drain hose to drain pipe

20

Connecting the pipes to the Outdoor

41

Dip S/W Setting

 

unit

 

42

ACCESSORY GUIDE

22 PIPING LENGTH AND THE

42

Dry Contact(Only AC 24 V)

 

ELEVATION

43

Connecting the DRED to the outdoor

 

 

 

 

unit

 

 

 

 

23 WIRING CONNECTION

23Electrical Wiring

24Connecting cables to the Indoor Unit

24 Clamping of cables

26Connecting the cable to the Outdoor Unit

44INSTALLATION PI485

45Damper Controller

46Remote Temperature Sensor

47Two wired remote controller

48WLAN module installation

INTRODUCTION 3

INTRODUCTION

Tips for saving energy

Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:

Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.

Block sunlight with blinds or curtains while you are operating the air conditioner.

Keep doors or windows closed tightly while you are operating the air conditioner.

Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

Speed up the fan to cool or warm indoor air quickly, in a short period of time.

Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.

Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.

<![if ! IE]>

<![endif]>ENGLISH

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

<![if ! IE]>

<![endif]>ENGLISH

4 INTRODUCTION

Important safety instructions

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.

Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product

! WARNING

It can result in serious injury or death when the directions are ignored

! CAUTION

It can result in minor injury or product damage when the directions are ignored

! WARNING

Installation or repairs made by unqualified persons can result in hazards to you and others.

Installation of all field wiring and components MUST conform with local building codes.

The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.

Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

- Children should be supervised to ensure that they do not play with the appliance.

Installation

Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.

-There is risk of fire or electric shock.

For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.

-Do not disassemble or repair the product. There is risk of fire or electric shock.

Always ground the product.

-There is risk of fire or electric shock.

Install the panel and the cover of control box securely.

-There is risk of fire or electric shock.

Always install a dedicated circuit and breaker.

-Improper wiring or installation may cause fire or electric shock.

Use the correctly rated breaker or fuse.

-There is risk of fire or electric shock.

Do not modify or extend the power cable.

-There is risk of fire or electric shock.

Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.

-Moisture may condense and wet or damage furniture.

Be cautious when unpacking and installing the product.

-Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.

For installation, always contact the dealer or an Authorized Service Center.

-There is risk of fire, electric shock, explosion, or injury.

Do not install the product on a defective installation stand.

-It may cause injury, accident, or damage to the product.

Be sure the installation area does not deteriorate with age.

INTRODUCTION

 

5

• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress

<![if ! IE]>

<![endif]>ENGLISH

- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.

air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion. - There is the risk of death, injury, fire or explosion.

• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it may cause fire, electric chock, explosion or death.

• The appliance shall be installed in accordance with national wiring regulations.

• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules

Operation

Take care to ensure that power cable could not be pulled out or damaged during operation. There is risk of fire or electric shock.

Do not place anything on the power cable. There is risk of fire or electric shock.

Do not plug or unplug the power supply plug during operation. There is risk of fire or electric shock.

Do not touch(operate) the product with wet hands. There is risk of fire or electrical shock.

Do not place a heater or other appliances near the power cable. There is risk of fire and electric shock.

Do not allow water to run into electric parts. There is risk of fire, failure of the product, or electric shock.

Do not store or use flammable gas or combustibles near the product. There is risk of fire or failure of product.

Do not use the product in a tightly closed space for a long time. Oxygen deficiency could occur.

When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on. Do not use the telephone or turn switches on or off. There is risk of explosion or fire

If strange sounds, or smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable. There is risk of electric shock or fire.

Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives. There is risk of property damage, failure of product, or electric shock.

Do not open the inlet grill of the product during operation.(Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure.

When the product is soaked (flooded or submerged), contact an Authorized Service Center. There is risk of fire or electric shock.

Be cautious that water could not enter the product. There is risk of fire, electric shock, or product damage.

Ventilate the product from time to time when operating it together with a stove, etc. There is risk of fire or electric shock.

Turn the main power off when cleaning or maintaining the product. There is risk of electric shock.

When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker. There is risk of product damage or failure, or unintended operation.

Take care to ensure that nobody could step on or fall onto the outdoor unit. This could result in personal injury and product damage.

! CAUTION

Installation

Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant levels may cause failure of product.

 

6

INTRODUCTION

 

 

<![if ! IE]>

<![endif]>ENGLISH

Install the drain hose to ensure that water is drained away properly. A bad connection may cause

 

 

water leakage.

 

Keep level even when installing the product. To avoid vibration or water leakage.

 

Do not install the product where the noise or hot air from the outdoor unit could damage the

 

neighborhoods. It may cause a problem for your neighbors.

 

Use two or more people to lift and transport the product. Avoid personal injury.

 

Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause

 

corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause

 

product malfunction or inefficient operation.

Operation

Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.) This could harm to your health.

Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system. There is risk of damage or loss of property.

Do not block the inlet or outlet of air flow. It may cause product failure.

Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. There is risk of fire, electric shock, or damage to the plastic parts of the product.

Do not touch the metal parts of the product when removing the air filter. They are very sharp! There is risk of personal injury.

Do not step on or put anyting on the product. (outdoor units) There is risk of personal injury and failure of product.

Always insert the filter securely. Clean the filter every two weeks or more often if necessary. A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.

Do not insert hands or other objects through the air inlet or outlet while the product is operated. There are sharp and moving parts that could cause personal injury.

Do not drink the water drained from the product. It is not sanitary and could cause serious health issues.

Use a firm stool or ladder when cleaning or maintaining the product. Be careful and avoid personal injury.

Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries. There is risk of fire or explosion

Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire. They may burn or explode.

If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.

If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.

The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.

The sound pressure of this product is below 70 dB.

The noise level can vary depending on the site.

INTRODUCTION 7

Installation process

Determination of division work

Indicate clearly who will be responsible for switch setting.

Preparation of contract drawings

Make connection clearly between outdoor, indoor, remote controller and option.

 

 

 

 

 

 

 

Sleeve and insert work

Take account of gradient

Outdoor unit foundation work

The foundation must be level even

of drainage pipe

 

 

 

 

 

 

Installation of indoor unit

Check model name to make

Installation of outdoor unit

Avoid short circuits and ensure

sure the fitting is made correctly

sufficient space is allowed for service

 

 

 

 

 

Refrigerant pipe work

Special attention to dryness,

 

 

 

 

cleanness and tightness

 

 

 

 

 

 

 

 

 

 

Drainage pipe work

Adjust to downward gradient

 

 

 

 

Duct work

Make sure airflow is sufficient

 

 

 

 

Heat insulation work

Make sure no gaps are left where

 

 

the insulating materials are joined

 

 

 

 

 

 

 

Electrical work

Multiple core cable must not be used.

 

 

(connection circuits and drive circuits)

(suitable cable should be selected)

 

 

 

 

 

 

 

 

 

Airtight test

Vacuum drying

Additional charge of refrigerant

Fit facing panels

Test run adjustment

Transfer to customer with explanation

In the final check for 24 hours at 3.8 MPa(38.7 kgf/cm2) there must be no drop in pressure.

The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour

Recharge correctly as calculated in this manual. and record the amount of added refrigerant

Make sure there are no gaps left between the facing materials used on the ceiling

Run each indoor unit in turn to make sure the pipe work has been fitted correctly

Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order

!CAUTION

The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.

The wall thickness of the pipe should comply with the relevant local and national regulations for the designed pressure 3.8 MPa.

Since R-410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

8 INTRODUCTION

Features

Top view

Control box

Air intake vents

Front view

Air outlet vents

 

Remote Controller

Air Intake

 

Vents Side

Rear

 

Connecting

Wires

Drain Hose

Air Outlet Vents

Base Plate

Air outlet vents

Air intake vents

*Picture may differ depending on the model.

INTRODUCTION 9

Environment-friendly alternative refrigerant R-410A

-The refrigerant R-410A has the property of higher operating pressure in comparison with R22.

Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation. R-410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R-410A is 0. These days the developed countries have approved it as the environment-friendly refrigerant and encouraged to use it widely to prevent environment pollution.

!CAUTION

The wall thickness of the pipe should comply with the relevant local and national regulations for the designed pressure 3.8 MPa

Since R-410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.

If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.

Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.

For high-pressure refrigerant, any unapproved pipe must not be used.

Do not heat pipes more than necessary to prevent them from softening.

Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

10 INSTALLATION PLACE

INSTALLATION PLACE

Select space for installing outdoor unit, which will meet the following conditions:

-No direct thermal radiation from other heat sources

-No possibility of annoying neighbors by noise from unit

-No exposition to strong wind

-With strength which bears weight of unit

-Note that drain flows out of unit when heating

-With space for air passage and service work shown next

-Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and

leakage of combustible gas is expected.

-Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.

-Do not use unit under any special environment where oil, steam and sulfuric gas exist.

-It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit.

-If installation site is area of heavy snowfall, then the following directions should be observed.

Make the foundation as high as possible.

Fit a snow protection hood.

-Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.

Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the product at a place With a high humidity in winter (near beach, coast, lake, etc. )

(Ex : Rooftop where there is always sunshine.)

INSTALLATION PLACE 11

Indoor unit installation place

-The place shall easily bear a load exceeding four times the indoor unit’s weight.

-The place shall be able to inspect the unit.

-The place where the unit shall be leveled.

-The place shall allow easy water drainage.

-The place shall easily connect with the outdoor unit.

-The place where the unit is not affected by an electrical noise.

-The place where air circulation in the room will be good .

-There should not be any heat source or steam near the unit

Top view

Front view

(unit: mm)

Inspection hole

(unit: mm)

(600 x 600)

 

Control box

 

Air Intake

 

 

H=200 or more

<![if ! IE]>

<![endif]>0001

 

Air Outlet

 

Front

 

* Suitable dimension “H” is necessary to get a slope to drain.

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

12 INSTALLATION PLACE

Outdoor unit installation place

-If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.

-Ensure that the spaces indicated by arrows around front, back and side of the unit.

-Do not place animals and plants in the path of the warm air.

-Take the air conditioner weight into account and select a place where noise and vibration are minimum.

-Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

 

Sunroof

 

More than

 

 

300 mm

 

 

 

 

More than

Fence

 

300 mm

 

 

obstacles

 

 

or

 

 

More than 600 m

 

More than 700 mm

* Picture may differ depending

Unit : mm

on the model.

 

-Place that can sufficiently endure the weight and vibration of the outdoor unit and where even installation is possible.

-Place that has no direct influence of snow or rain

-Place with no danger of snowfall or icicle drop

-Place without weak floor or base such as decrepit part of the building or with a lot of snow accumulation

-Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flooded area.

INSTALLATION PLACE 13

Obstacle height of discharge side is lower than the unit 1. Stand alone installation

L ≤ H

 

 

 

 

<![if ! IE]>

<![endif]>H

<![if ! IE]>

<![endif]>L

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

350

 

 

 

or

more

000

 

1

more

 

 

 

[Unit:mm]

L ≤ H

 

 

 

 

 

 

 

 

less

 

 

500

 

or

 

 

 

 

 

 

<![if ! IE]>

<![endif]>000 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>1

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>L

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

350

 

 

 

 

 

 

 

 

or

 

more

1000

 

 

 

 

 

 

 

 

 

 

 

more

 

 

2. Collective installation L ≤ H

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>L

 

 

 

 

 

 

 

 

 

 

 

 

 

100

or

more

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

350

 

 

 

 

 

 

 

 

or

more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

 

more

 

 

L ≤ H

 

 

 

 

 

less

 

 

 

 

<![if ! IE]>

<![endif]>000or more

 

 

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

or

more

 

 

 

 

 

350

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

more

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

more

 

 

 

* Picture may differ depending on the model.

<![if ! IE]>

<![endif]>ENGLISH

<![if ! IE]>

<![endif]>ENGLISH

14 INSTALLATION PLACE

Installation guide at the seaside

!CAUTION

Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.

Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.

If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.

Selecting the location(Outdoor Unit)

If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.

In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak

Sea wind

-It should be strong enough like concrete to prevent the sea wind from the sea.

-The height and width should be more than 150 % of the outdoor unit.

-It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.

Place with fluent water draining

-Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flooded area.

Sea wind

• If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.

• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water

Sea wind

LG B30AWYN7G6 Installation Manual

THE INDOOR UNIT INSTALLATION 15

THE INDOOR UNIT INSTALLATION

Install the unit above the ceiling correctly.

Case1

Position of suspension Bolt

-Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.

-Apply a filter Accessory at air return hole.

Dimension

 

 

 

Capacity

A B C D E F G H I J K

L

 

 

 

(Btu/h)

 

 

 

8.8/10.5/

1 352 1 320 840 287

400 441 563 1 172 1 365 317 360

40

12.5/15 kW

 

I

K

L

 

H

 

 

J

 

GF

 

 

 

E D

C

B

A

Case2

Position of Console Bolt

-A place where the unit will be leveled and that can support the weight of the unit.

-A place where the unit can withstand its vibration.

-A place where service can be easily performed.

M10 Nut

X 4

(Local

M10 SP. washer

X 4

supply)

M10 washer

X 4

 

M10 washer

X 4

(Local

M10 SP. washer

X 4

supply)

M10 Nut

X 4

 

-Select and mark the position for fixing bolts.

-Drill the hole for set anchor on the face of ceiling.

<![if ! IE]>

<![endif]>ENGLISH

 

16

THE INDOOR UNIT INSTALLATION

 

 

 

 

 

 

<![if ! IE]>

<![endif]>ENGLISH

- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on

 

 

the ceiling.

 

 

 

- Mount the suspension bolts to the set anchor firmly.

 

 

 

- Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts,

 

washers and spring washers.

 

 

 

 

 

Old building

New building

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Set anchor

2 Plate washer

3 Spring washer

4 Nut

5Suspension bolts

Local supplySet anchor

Plate washer - M10Spring washer - M10Nut - W3/8 or M10

Suspension bolt - W3/8 or M10

! CAUTION

Tighten the nut and bolt to prevent unit falling.

!CAUTION

1 Install declination of the indoor unit is very important for the drain of the duct type air conditioner.

2 Minimum thickness of the insulation for the connecting pipe shall be 10 mm.

Ceiling

<![if ! IE]>

<![endif]>1~3 mm

Drainage hole

Drainage hole

Safety drain hole Main drain hole

 

 

 

CORRECT

INCORRECT

 

 

 

Loading...
+ 36 hidden pages