Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the
national wiring standards by authorized personnel only.
Please retain this installation manual for future reference
after reading it thoroughly.
Ceiling suspended air conditioner
MFL67791202
P/NO : MFL67791202
www.lg.com
TIPS FOR SAVING ENERGY
2
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
ENGLISH
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
!
It can result in serious injury or death when the directions are ignored
CAUTION
!
It can result in minor injury or product damage when the directions are ignored
WARNING
!
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service
Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or
a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
3
ENGLISH
4
Batteries :
ENGLISH
Operation
Installation
IMPORTANT SAFETY INSTRUCTIONS
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product
failure, and personal injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
CAUTION
!
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neigh-
borhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation
ENGLISH
Do not burn, do not try to open it, do not dispose in ordinary trash. Preserve
environment and your health.
After use, batteries must be delivered to the merchant or service authorized
network (Conama number 401 dated 11/2008).
ENGLISH
TABLE OF CONTENTS
TABLE OF CONTENTS
5
ENGLISH
2TIPS FOR SAVING ENER-
GY
3IMPORTANT SAFETY
INSTRUCTIONS
6INSTALLATION PLACES
7THE INDOOR UNIT
INSTALLATION
8Open side-cover
9Mounting the anchor nut and bolt
11Indoor unit drain piping
11Drain piping
11Drain test
12Heat insulation
12Connecting cables to the indoor unit
12Wiring connection
14 TEST RUNNING
14Precautions in test running
14Check the following items when installa-
tion is complete
14Connection of power supply
14Evaluation of the performance
15Hand over
16 INSTALLATION INSTRUC-
TIONS
16Installer setting - how to enter installer
setting mode
17Installer setting - installer setting code
table
17Installer setting code table
18Installer setting - setting address of cen-
tral control
18Installer setting - checking address of
central control
INSTALLATION PLACES
6
ENGLISH
INSTALLATION PLACES
Indoor unit
Ceiling suspended type
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
Unit: mm(inch)
10 (13/32)
or more
300 (11 – 13/16)
or more
ENGLISH
2500 (98 – 3/7)
or more
Floor
700(27 – 9/16) or more700(27 – 9/16) or more
THE INDOOR UNIT INSTALLATION
ENGLISH
THE INDOOR UNIT INSTALLATION
Air conditioner
Take enough
distance
Cooking table
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
7
ENGLISH
CAUTION
!
• Install the unit horizontally using a level
gauge.
• During the installation, care should be
taken not to damage electric wires.
• Select and mark the position for fixing
bolts and piping hole.
• Decide the position for fixing bolts
slightly tilted to the drain direction after
considering the direction of drain hose.
• Drill the hole for anchor bolt on the ceiling.
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen
where considerable amount of oil
steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain
pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough
to cover all noxious gases from this
place.
• Ensure enough distance from the cook-
ing room to install the air conditioner in
such a place where it may not suck oily
steam.
2. Avoid installng air conditioner in such
places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is
generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
8
Step 1
Backside
Right side cover
Backside
Left side
cover
Step 2
Step 5
Step 3
Step 4
ENGLISH
THE INDOOR UNIT INSTALLATION
ENGLISH
Open side-cover
- Remove two screws from side-cover.
- Unlock side-cover from side-panel slightly
(Tap the side-cover with your palm on the
backside)
S
- Remove paper bracket from side-cover.
- Knock out the pipe hole from the left sidecover with nipper/plier.
CAUTION
!
Hold the side-cover with other hand while
tapping to prevent it to fall down.
- Remove bracket from side-panel.
Washer
Suspension
bolts
ENGLISH
THE INDOOR UNIT INSTALLATION
9
ENGLISH
Mounting the anchor nut and bolt
- Prepare 4 suspension bolts. (Each bolts
length should be same.)
- Measure and mark the position for the
Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on
the ceiling.
- Mount the suspension bolts to the anchornuts firmly.
- Secure the hangers onto the Suspension
bolts (adjust level roughly.) using nuts, washers and spring washers.
- Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
- Adjust a level on the direction of top-bottom
by adjusting supension bolts. Then the unit
will be declined to the bottomside so as to
drain well.
(Unit : mm)
AB
VM1
VM2
1018
355
1418
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Flat washer
for M10
(accessory)
Flat washer
for M10
(accessory)
Nut
(W3/8 or M10)
- The following parts is option.
Hanging Bolt - W 3/8 or M10
Nut- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
CAUTION
!
Tighten the nut and bolt to prevent unit
from falling
• Drill the piping hole on the wall slightly
tilted to the outdoor side by using a
Ø 70 hole-core drill.
Anchor nut
Ceiling
Nut
Suspension
Suspension
bolts
bolts
Washer
Washer
A
Suspension bolt
Suspension
bolts
Spring
washer
Hanger
Max.
12mm
B
Nut
Washer
Indoor
Wall
Outdoor
Slope gradient for
drain Should be
1/50 ~ 1/100
THE INDOOR UNIT INSTALLATION
Ceiling
10~20 mm
Ceiling
5~10 mm
10
ENGLISH
CAUTION
!
Installation information for declination
- Install declination of the indoor unit is very important for the drain of the convertible type air
conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10 mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1° or in between 10 to 20 mm inclined in drain
direction as shown in fig.
ENGLISH
Side of view
- The unit must be inclined to the bottomside of the unit when finished installation.
Drain hoseDrain hoseDrain hose
Bracket
ENGLISH
THE INDOOR UNIT INSTALLATION
11
ENGLISH
Indoor unit drain piping
- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- Remove the rubber stopple before connecting drain hose.
- Hook on the bracket after connecting the
drain hose as below.
Drain piping
- The drain hose should point downward for
easy drain flow.
- Do not make drain piping like the following.
Do not raise
Water
leakage
Tip of drain
hose dipped
in water
Water
leakage
- Be sure to execute heat insulation on the
drain piping.
Heat insulation material: Polyethylene foam
with thickness more than 8 mm.
Water
leakage
Ditch
Accumulated
drain water
Air
Waving
Less than
50 mm gap
Drain test
Use the following procedure to test the drain
pump operation:
Downward
slope
- Set the air direction louvers up-and-down to
the position(horizontally) by hand.
- Pour a glass of water on the evaporator
using a kettle.
- Ensure the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
12
Control box cover
ENGLISH
THE INDOOR UNIT INSTALLATION
ENGLISH
Heat insulation
Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120 °C).
Precautions in high humidity circumstance:
This air conditioner has been tested according
to the "KS Standard Conditions with Mist" and
confirmed that there is not any default.
However, if it is operated for a long time in
high humid atmosphere (dew point temperature: more than 23 °C), water drops are liable
to fall. In this case, add heat insulation material according to the following procedure:
Fastening band
Refrigerant piping
Indoor unit
Thermal insulator
- Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to 20
mm.
- Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Connecting cables to the indoor unit
Wiring connection
Connect the wires to the terminals on the
control board individually according to the outdoor unit connection.
1(L) 2(N) 3
1(L) 2(N) 3
C
!
The connecting cable
NORMAL CROSS-SECTIONAL AREA
ModelPhase(Ø) Area(mm2)
/YL
AVNW36GM1S0
AVNW60LM2S0
10.75
31.00
- Remove the control box cover for electrical
connection between the indoor and out door
unit
- Use the cord clamper to fix the cord.
Loading...
+ 25 hidden pages