LG AVNQ54GM2T1 Installation Manual

INSTALLATION MANUAL
Ceiling Suspended Air conditioner
AIR CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
MFL70699801
Rev.00_051018
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
ENGLISH
FRANÇAIS
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 1
2
TIPS FOR SAVING ENERGY
ENGLISH
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 2
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Don’t use a power cable, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
!
!
!
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 3
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
!
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 4
TABLE OF CONTENTS
5
ENGLISH
2 TIPS FOR SAVING ENERGY
3 IMPORTANT SAFETY INSTRUCTIONS
6 PRODUCT PARTS
6 INSTALLATION TOOLS
7 INSTALLATION
7 Indoor unit
8 THE INDOOR UNIT INSTALLATION
9 Open side-cover 10 Mounting the anchor nut and bolt 12 Indoor unit drain piping 12 Drain piping 12 Drain test 13 Heat insulation 13 Flaring Work 16 Wiring Connection
17 TEST RUNNING
19 INSTALLATION INSTRUCTIONS
19 Installer Setting - How to enter installer setting mode 20 Installer Setting - Installer Setting Code Table 21 Installer Setting - Setting Address of Central Control 21 Installer Setting - Checking Address of Central Control
TABLE OF CONTENTS
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 5
6
PRODUCT PARTS
ENGLISH
PRODUCT PARTS
INSTALLATION TOOLS
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 6
Right side cover
Air filters (behind inlet grille)
Air inlet vent (inlet grille)
Louver
Figure FigureName
Screw driver
Air outlet vent
Left side cover
Name
Multi-meter
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Level
Flaring tool set
INSTALLATION
7
ENGLISH
INSTALLATION
Indoor unit
Ceiling suspended type
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
Unit: mm(inch)
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 7
10 (13/32) or more
300 (11 – 13/16) or more
2500 (98 – 3/7) or more
Floor
700(27 – 9/16) or more 700(27 – 9/16) or more
8
THE INDOOR UNIT INSTALLATION
ENGLISH
THE INDOOR UNIT INSTALLATION
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the ceiling.
CAUTION
!
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough
to cover all noxious gases from this place.
• Ensure enough distance from the
cooking room to install the air conditioner in such a place where it may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
1,MFL70699801,영어 2018. 6. 27. 오후 4:06 페이지 8
Air conditioner
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Loading...
+ 16 hidden pages