LG AVNQ18GM1A1 installation guide [en,th]

P/NO : MFL67889012
INSTALLATION MANUAL
AIR CONDITIONER
www.lg.com
Please read this installation manual completely before install­ing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ceiling suspended air conditioner
ENGLISH
Copyright © 2017 LG Electronics Inc. All Rights Reserved.
2
TIPS FOR SAVING ENERGY
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition­er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty pur­poses. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air con­ditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
!
!
WARNING
• Install or repair by unqualified persons can result in hazards to you and others.
• Installation MUST comply with local building codes. If there is no local codes, comply with the Nation Electrical Code NFPA 70/ANSI C1-1003, Canadian Electrical Code Part1 CSA C.22.1. or current edition.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury or death.
This appliance is not intended for use by persons (including children) with reduced physical, senso­ry or mental capabilities, or lack of experience and knowledge, unless they have been given super­vision or instruction concerning use of the appliance by a person responsible for their safety.
Installation
• Do not install duct through disassemble or repare the product yourself.
- This product can not install duct.
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a win-
dow is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con­denser and evaporator.
• For installation, always contact the dealer or an authorized service center.
- There is risk of fire, electric shock, explosion, or injury.
!
ENGLISHENGLISH
4
ENGLISH
ENGLISH
Operation
IMPORTANT SAFETY INSTRUCTIONS
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it may cause fire, electric shock, explosion or death.
• Take care to ensure that power cable could not be pulled out or damaged during operation. There is risk of fire or electric shock.
• Do not place anything on the power cable. There is risk of fire or electric shock.
• Do not touch(operate) the product with wet hands. There is risk of fire or electrical shock.
• Do not place a heater or other appliances near the power cable. There is risk of fire and elec­tric shock.
• Do not allow water to run into electric parts. There is risk of fire, failure of the product, or elec­tric shock.
• Do not store or use flammable gas or combustibles near the product. There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time. Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on. Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
• If strange sound, smell or smoke comes from product, turn the breaker off or disconnect the power supply cable. There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives. There is risk of property damage, failure of product or electric shock.
• Do not open the inlet grill of the product during operation.(Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure.
• When the product is soaked (flooded or submerged), contact an authorized service center. There is risk of fire or electric shock.
• Be cautious that water could not enter the product. There is risk of fire, electric shock, or product damage.
• Ventilate the product from time to time when operating it together with a stove, etc. There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product. There is risk of electric shock.
• When the product is not be used for a long time or the product use first time after test run­ning, turn on main power switch before 6hours ago.
• Take care to ensure that nobody could step on or fall onto the outdoor unit. This could result in personal injury and product damage.
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
CAUTION
Installation
Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant lev-
els may cause failure of product.
Install the drain hose to ensure that water is drained away properly. A bad connection may cause
water leakage.
Keep level even when installing the product. To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neigh-
borhoods. It may cause a problem for your neighbors.
Use two or more people to lift and transport the product. Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause cor-
rosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operation
Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.) This could
harm to your health.
Do not use the product for special purposes such as preserving foods, works of art, etc. It is a con-
sumer air conditioner, not a precision refrigeration system. There is risk of damage or loss of proper­ty.
Do not block the inlet or outlet of air flow. It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc. There is risk of fire, electric
shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp! There
is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units) There is risk of personal injury and fail-
ure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary. A dirty
filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product. It is not sanitary and could cause serious health
issues.
Use a firm stool or ladder when cleaning or maintaining the product. Be careful and avoid personal
injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and
new batteries or different types of batteries. There is risk of fire or explosion
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire. They may burn or
explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not
use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
!
ENGLISHENGLISH
TABLE OF CONTENTS
6
ENGLISH
ENGLISH
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY
3 IMPORTANT SAFETY INSTRUCTIONS
7 INSTALLATION PLACES
8 THE INDOOR UNIT INSTALLATION
9 Open side-cover
10 Mounting the anchor nut and bolt
12 Indoor unit drain piping
12 Drain piping
12 Drain test
13 Heat insulation
13 Connecting cables to the indoor unit
13 Wiring connection
15 TEST RUNNING
15 Precautions in test running
15 Check the following items when installation is complete
15 Connection of power supply
15 Evaluation of the performance
16 Hand over
17 INSTALLATION INSTRUCTIONS
17 Installer setting - setting address of central control
17 Installer setting - checking address of central control
INSTALLATION PLACES
7
INSTALLATION PLACES
Indoor unit
Ceiling suspended type
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
700(27 – 9/16) or more 700(27 – 9/16) or more
2500 (98 – 3/7) or more
Floor
10 (13/32) or more
300 (11 – 13/16) or more
Unit: mm(inch)
ENGLISHENGLISH
8
THE INDOOR UNIT INSTALLATION
ENGLISH
THE INDOOR UNIT INSTALLATION
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
Cooking table
Air conditioner
Take enough distance
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
-liec eht no tlob rohcna rof eloh eht llirD •
ing.
CAUTION
!
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange effi­ciency reduction, or water drops, drain pump mal-function. In these cases, take the following ac­tions;
• Make sure that ventilation fan is enough
to cover all noxious gases from this place.
• Ensure enough distance from the cook-
ing room to install the air conditioner in such a place where it may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron pow­der is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is gen­erated.
5. Avoid places near high frequency gen­erators.
ENGLISH
THE INDOOR UNIT INSTALLATION
9
Open side-cover
Step 1
Backside
Right side cover
Backside
Left side cover
Step 2
Step 5
- Remove two screws from side-cover.
Step 3
Step 4
- Remove bracket from side-panel.
- Remove paper bracket from side-cover.
- Unlock side-cover from side-panel slightly (Tap the side-cover with your palm on the backside)
- Knock out the pipe hole from the left side­cover with nipper/plier.
Hold the side-cover with other hand while tapping to prevent it to fall down.
CAUTION
!
ENGLISHENGLISH
10
ENGLISH
ENGLISH
THE INDOOR UNIT INSTALLATION
Mounting the anchor nut and bolt
- Prepare 4 suspension bolts. (Each bolts length should be same.)
- Measure and mark the position for the Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the suspen­sion bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the anchor­nuts firmly.
- Secure the hangers onto the Suspension bolts (adjust level roughly.) using nuts, wash­ers and spring washers.
- Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
- Adjust a level on the direction of top-bottom by adjusting supension bolts. Then the unit will be declined to the bottomside so as to drain well.
(Unit : mm)
Model
VM1
VM2
Dimension
AVNQ18GM1A1 AVNQ24GM1A1 AVNQ30GM1A1
AVNQ36GM2A1 AVNQ36LM2A1 AVNQ48LM2A1
A B
1018
355
1418
Hanging bolt (W3/8 or M10)
Nut (W3/8 or M10)
Spring washer (M10)
Flat washer for M10 (accessory)
Flat washer for M10 (accessory)
Nut (W3/8 or M10)
- The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10
CAUTION
!
Tighten the nut and bolt to prevent unit from falling
• Drill the piping hole on the wall slightly
tilted to the outdoor side by using a Ø 70 hole-core drill.
Ceiling
Nut
Suspension
Suspension
bolts
bolts
Anchor nut
WasherWasher
A
Suspension bolt
Suspension
bolts
Spring
washer
Hangen
Max.
12mm
B
Nut
Washer
THE INDOOR UNIT INSTALLATION
11
Installation information for declination
- Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10 mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be de­clined to the bottomside.
CAUTION
!
Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1° or in between 10 to 20 mm inclined in drain direction as shown in fig.
Ceiling
10~20 mm
Side of view
- The unit must be inclined to the bottomside of the unit when finished installation.
Ceiling
5~10 mm
ENGLISHENGLISH